Plan Review Details - Project Z16080008
Plan Review Stops For Project Z16080008
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-13-2016 Cont ID  
Sent By rbrown Date 09-13-2016 Time 20:12 Rev Time 0.00
Received By rbrown Date 09-13-2016 Time 20:12 Sent To  
Notes
2016-09-13 20:16:04DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE PERMIT APPLICATION FOR THE BUILDING ADDITION AND
 REMODEL SHALL STATE THAT THIS IS A CHANGE OF OCCUPANCY.
 A NEW CERTIFICIATE OF OCCUPANCY WILL BE REQUIRED FOR
 THE PROPOSED USE.
  
 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 4. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. THIS PROJECT MAY BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 10-27-2016 Cont ID  
Sent By pleduc Date 10-27-2016 Time   Rev Time 0.00
Received By pleduc Date 10-27-2016 Time 13:47 Sent To  
Notes
2016-10-27 13:51:552ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE MEMO AND
 ATTACHMENTS DATED OCTOBER 26, 2016, FROM PAUL GREILICH,
 SENIOR PLANNER, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS WERE NOT SPECIFICALLY
 ADDRESSED; HOWEVER, THE BUREAU HAS PREVIOUSLY PASSED
 THIS PROJECT'S REVIEW.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 09-09-2016 Cont ID  
Sent By pleduc Date 09-09-2016 Time   Rev Time 0.00
Received By pleduc Date 09-09-2016 Time 11:35 Sent To  
Notes
2016-09-09 16:10:21THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES,
 INCLUDING NFPA 101, CHAPTER 32 NEW RESIDENTIAL BOARD
 AND CARE OCCUPANCIES.
  
 SHOULD THERE BE ANOTHER OCCUPANCY CLASSIFICATION THAT
 BETTER SERVES THE PROPOSED PROJECT, PLEASE PROVIDE IT
 AND ANY SPECIFIC SUPPORTING DETAILS.
  
 6. THIS PROPOSED PROJECT REPRESENTS AN OCCUPANCY
 CLASSIFICATION CHANGE AND SHALL BE SUBMITTED FOR
 OCCUPANCY CHANGE AT THE TIME OF PERMIT APPLICATION.
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS OCCUPANCY. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S, FIRE HYDRANTS) FOR THE PROJECT SHALL BE
 IDENTIFIED AND COORDINATED WITH THE BUREAU OF FIRE
 PREVENTION.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 8. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 9. A KITCHEN IS INDICATED. ALL KITCHEN EQUIPMENT AND
 OPERATIONS SHALL COMPLY WITH NFPA 96, STANDARD FOR
 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL
 COOKING OPERATIONS. EXTINGUISHMENT AND VENTILATION
 SYSTEM SHOP DRAWINGS SHALL BE SUBMITTED SEPARATELY FOR
 APPROVAL.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXITS AND EXIT ACCESS AND/OR EGRESS CONTROLS,
 SHALL COMPLY WITH NFPA 101, CHAPTER 7 MEANS OF EGRESS
 REQUIREMENTS.
  
 12. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 13. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 10-21-2016 Cont ID  
Sent By rcaranci Date 10-21-2016 Time 09:31 Rev Time 0.00
Received By rcaranci Date 10-21-2016 Time 09:31 Sent To  
Notes
2016-10-21 09:31:42FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2521 METROCENTRE Z16080008
 OCTOBER 21, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A SITE DATA CHART ON THE
 LANDSCAPE PLAN TO REFLECT THE REQUIRED, APPROVED, AND
 PROVIDED OPEN SPACE AND LANDSCAPE AREA IN SQUARE
 FOOTAGE.
  
 2. SATISFIED. PLEASE PROVIDE A SITE DATA CHART ON THE
 LANDSCAPE PLAN TO REFLECT THE REQUIRED, APPROVED, AND
 PROVIDED NUMBER OF TREES, FLOWERING TREES AND SHRUBS
 BASED ON THE REQUIRED OPEN SPACE.
  
 3. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 4. CONDITIONALLY SATISFIED. PLEASE SHOW LOCATIONS OF
 WATER AND SEWER LINES THAT SERVICE THE BUILDING,
 LOCATIONS OF ABOVE GROUND VALVES, AND LOCATION OF
 DRAINAGE STRUCTURES ON THE LANDSCAPE PLAN AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
  
 5. CONDITIONALLY SATISFIED. PLEASE PROVIDE SCREENING
 FOR ALL GROUND MOUNTED EQUIPMENT AND UTILITIES.
  
 6. SATISFIED. PLEASE PROVIDE A ROOT BARRIER DETAIL AND
 SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 7. SATISFIED. PLEASE REVISE THE FLORIDA FRIENDLY
 LANDSCAPE CHART PER SECTION 94-446 (G) AND PROVIDE
 DOCUMENTATION FOR THE TYPE OF LANDSCAPE IRRIGATION
 MOISTURE SENSOR OTHER THAN A RAIN SWITCH TO BE
 PROVIDED.
  
 8. CONDITIONALLY SATISFIED. THERE ARE 3 OAK TREES IN
 LOCATIONS THAT ARE NOT LIKELY TO SURVIVE THE
 CONSTRUCTION OF BUILDING WALLS AND FOUNDATION FOOTERS.
 PLEASE PROVIDE AN ACCOUNTING OF THE NUMBER OF TREES
 APPROVED FOR THE SITE, AND INDICATE IF ADDITIONAL
 MITIGATION TREES CAN BE PLANTED, OR PAYMENT IN LIEU MAY
 BE THE ONLY OPTION.
  
 9. CONDITIONALLY SATISFIED. ALL INVASIVE EXOTIC PLANTS
 MUST BE REMOVED FROM THE SITE INCLUDING THE CARROTWOOD
 TREES ALONG THE WEST BUFFER.
  
 10. CONDITIONALLY SATISFIED. ALL HEDGES THAT ARE DEAD
 OR DISEASED, AND ALL MISSING TREES MUST BE REPLACED,
 ALTERNATE SPECIES MAY BE CHOSEN AT THIS TIME.
  
 11. SATISFIED. THE TERMINAL ISLAND ON THE EAST SIDE OF
 THE WEST PARKING LOT ENTRANCE MUST CONTAIN A TREE AS
 REQUIRED.
  
 12. SATISFIED. PLEASE PROVIDE THE REQUIRED HEDGE ON ALL
 THREE SIDES OF THE DUMPSTER ENCLOSURE.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT, THE
 LANDSCAPE PLAN SHALL BE REVISED TO SHOW LOCATIONS OF
 WATER AND SEWER LINES THAT SERVICE THE BUILDING,
 LOCATIONS OF ABOVE GROUND VALVES, AND LOCATION OF
 DRAINAGE STRUCTURES ON THE LANDSCAPE PLAN AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
  
 3. PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY OR COMPLETION, ALL GROUND MOUNTED EQUIPMENT
 SHALL BE SCREENED, ALL INVASIVE EXOTIC PLANTS REMOVED
 FROM THE SITE, AND ALL MISSING OR DEAD PLANT MATERIAL
 WILL BE REPLACED.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 09-12-2016 Cont ID  
Sent By rcaranci Date 09-12-2016 Time 17:08 Rev Time 0.00
Received By rcaranci Date 09-12-2016 Time 17:08 Sent To  
Notes
2016-09-12 17:08:57FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2521 METROCENTRE Z16080008
 SEPTEMBER 12, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A SITE DATA CHART ON THE LANDSCAPE
 PLAN TO REFLECT THE REQUIRED, APPROVED, AND PROVIDED
 OPEN SPACE AND LANDSCAPE AREA IN SQUARE FOOTAGE.
  
 2. PLEASE PROVIDE A SITE DATA CHART ON THE LANDSCAPE
 PLAN TO REFLECT THE REQUIRED, APPROVED, AND PROVIDED
 NUMBER OF TREES, FLOWERING TREES AND SHRUBS BASED ON
 THE REQUIRED OPEN SPACE.
  
 3. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 4. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES THAT
 SERVICE THE BUILDING, LOCATIONS OF ABOVE GROUND VALVES,
 AND LOCATION OF DRAINAGE STRUCTURES ON THE LANDSCAPE
 PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
  
 5. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
 6. PLEASE PROVIDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 7. PLEASE REVISE THE FLORIDA FRIENDLY LANDSCAPE CHART
 PER SECTION 94-446 (G) AND PROVIDE DOCUMENTATION FOR
 THE TYPE OF LANDSCAPE IRRIGATION MOISTURE SENSOR OTHER
 THAN A RAIN SWITCH TO BE PROVIDED.
  
 8. THERE ARE 3 OAK TREES IN LOCATIONS THAT ARE NOT
 LIKELY TO SURVIVE THE CONSTRUCTION OF BUILDING WALLS
 AND FOUNDATION FOOTERS. PLEASE PROVIDE AN ACCOUNTING OF
 THE NUMBER OF TREES APPROVED FOR THE SITE, AND INDICATE
 IF ADDITIONAL MITIGATION TREES CAN BE PLANTED, OR
 PAYMENT IN LIEU MAY BE THE ONLY OPTION.
  
 9. ALL INVASIVE EXOTIC PLANTS MUST BE REMOVED FROM THE
 SITE INCLUDING THE CARROTWOOD TREES ALONG THE WEST
 BUFFER.
  
 10. ALL HEDGES THAT ARE DEAD OR DISEASED, AND ALL
 MISSING TREES MUST BE REPLACED, ALTERNATE SPECIES MAY
 BE CHOSEN AT THIS TIME.
  
 11. THE TERMINAL ISLAND ON THE EAST SIDE OF THE WEST
 PARKING LOT ENTRANCE MUST CONTAIN A TREE AS REQUIRED.
  
 12. PLEASE PROVIDE THE REQUIRED HEDGE ON ALL THREE
 SIDES OF THE DUMPSTER ENCLOSURE.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 3 Status F Date 10-28-2016 Cont ID  
Sent By tward Date 10-28-2016 Time 17:13 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-10-28 17:12:48REVIEW OF 10/24/2016 SUBMITTAL:
 1. NO ENGINEERING PLANS SUBMITED.
  
 2. SAME COMMENTS FROM FIRST TWO STORMWATER REVIEWS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEER SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 2 Status F Date 10-20-2016 Cont ID  
Sent By tward Date 10-20-2016 Time 15:58 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-10-20 16:06:56REVIEW OF 10/3/2016 SUBMITTAL:
 1. NO ENGINEERING PLANS SUBMITED.
  
 2. SAME COMMENTS FROM INITIAL STORMWATER REVIEW.
  
 3. IT APPEARS THERE IS A DRAINAGE SWALE ALONG THE BACK
 OF SIDEWALK ALONG METROCENTRE BLVD. WEST. THE LANDSCAPE
 PLANTINGS SHOULD NOT ALTER THE STORAGE OR CONVEYANCE
 CAPACITY OF THE SWALE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEER SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status F Date 09-14-2016 Cont ID  
Sent By tward Date 09-14-2016 Time 08:09 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2016-09-14 08:10:48THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION
 INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD
 HAZARD AREA.
  
 3. NO ENGINEERING PLANS WERE SUBMITTED.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER
 INDICATING THE CHANGES TO THE ONSITE PEAK FLOOD STAGES
 WILL NOT EXCEED THE SFWMD PERMITTED FLOOD STAGES AND
 STORMWATER PRE-TREATMENT VOLUMES ARE BEING PROVIDED PER
 SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP OR MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 10-25-2016 Cont ID  
Sent By   Date 10-25-2016 Time   Rev Time 0.00
Received By   Date 10-24-2016 Time   Sent To  
Notes
2016-10-25 12:39:251.) PRIOR TO THE REMOVAL OR REMOVAL OF ANY TREES ON THE
 PROPERTY, A TREE ALTERATION PERMIT MUST BE SUBMITTED,
 REVIEWED, AND APPROVED BY THE DEVELOPMENT SERVICES,
 PLANNING DIVISION.
 2.) PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT, THE
 LANDSCAPE PLAN SHALL BE REVISED TO SHOW THE LOCATIONS
 OF ABOVE GROUND VALVES, AND LOCATIONS OF DRAINAGE
 STRUCTURES ON THE LANDSCAPE PLAN AND RESOLVE ANY
 CONFLICTS WITH LANDSCAPING.
 3.) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY OR COMPLETION, ALL GROUND MOUNTED EQUIPMENT
 SHALL BE SCREENED, ALL INVASIVE EXOTIC PLANTS REMOVED
 FROM THE SITE, AND ALL MISSING OR DEAD PLANT MATERIAL
 SHALL BE REPLACED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 10-21-2016 Cont ID  
Sent By   Date 10-21-2016 Time   Rev Time 0.00
Received By   Date 10-21-2016 Time   Sent To  
Notes
2016-10-21 13:36:27PROJECT: 2521 METROCENTRE (Z1608008)
 OCTOBER 21, 2016
  
  
 1. HANDICAP SPACES SHOWN ON PLAN DO NOT MATCH HANDICAP
 PARKING AND RAMP DETAIL PROVIDED. PLEASE ADDRESS
  
 PAUL GREILICH, SENIOR PLANNER
 (561)-822-1443
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 09-09-2016 Cont ID  
Sent By pgreilic Date 09-09-2016 Time 12:02 Rev Time 0.00
Received By pgreilic Date 09-12-2016 Time 08:36 Sent To  
Notes
2016-09-12 08:37:33SITE PLAN
  
 1. SHOW EXISTING BUILDING FOOTPRINT ON SITE PLAN AND
 INDICATE LIMITS OF PROPOSED BUILDING EXPANSION
  
 2. CORRECT FUTURE LAND USE TO SHOW ?SPECIAL IMPACT
 ZONE/COMMERCIAL (SIZ/C)? IN SITE DATA
  
 3. HANDICAP SPACES SHOWN ON PLAN (10.5? X 3? LOADING)
 DO NOT MATCH HANDICAP PARKING AND RAMP DETAIL PROVIDED
 (SEC. 94-485).
  
 4. LOADING ZONE SHOWN AS 20?X12?, REQUIRED TO BE
 25?X10? (SEC. 94-485).
  
 5. LOADING SPACE CANNOT BE INCLUDED AS A PARKING SPACE
 IN PARKING CALUCULATIONS
  
 6. LABEL DIMENSIONS OF DUMPSTER
  
 7. DUMPSTER DETAIL DOES NOT MEET REQUIREMENTS (SEC.
 94-444).
  
 8. DIMENSION THE SIDEWALK TO THE SOUTH OF THE BUILDING
  
 9. SHOW LOCATION OF ALL FIRE HYDRANTS
  
 10. REVISE PLAN TO SHOW WHEEL STOPS FOR PARKING SPACES
 IN FRONT AND SIDE OF THE BUILDING TO PREVENT DRIVERS
 FROM PARKING ACROSS THE SIDEWALK
  
  
  
 LANDSCAPE PLAN
  
 11. LIVE OAK LIKELY TOO CLOSE TO LIMITS OF PROPOSED
 EXPANSION AND MAY NEED TO BE MITIAGATED
  
 12. PROVIDE SCREENING FOR DUMPSTER (SEC. 94-444).
  
  
 13. THE PROPOSED EXPANSION WILL REQUIRE THE REMOVAL OF
 EXISTING TREES ON SITE. PLEASE NOTE THAT ANY EXISTING
 TREES AND/OR PALMS CANNOT BE REMOVED FROM THE PROPERTY
 WITHOUT FIRST OBTAINING A TREE ALTERATION PERMIT FROM
 THE DEVELOPMENT SERVICES DEPARTMENT PLANNING DIVISION.
  
 ADDITIONAL COMMENTS ON THE LANDSCAPE PLAN TO BE
 PROVIDED BY THE CITY?S LANDSCAPE PLANNER, RAY CARANCI.
  
  
  
 FLOOR PLANS AND ELEVATIONS
  
 NO COMMENTS
  
  
 INSTRUCTIONS FOR RESUBMITTAL
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT
  
 WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE (5)
 PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFFICIENTLY ADDRESSED,
 THE APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH
 FEE WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY 11/14/16), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
  
 CONTACT PAUL GREILICH @ (561) 822-1443 IF THERE ARE ANY
 QUESTIONS
  
  