Plan Review Details - Project Z16070034
Plan Review Stops For Project Z16070034
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-10-2016 Cont ID  
Sent By rbrown Date 08-10-2016 Time 10:56 Rev Time 0.00
Received By rbrown Date 08-10-2016 Time 10:56 Sent To  
Notes
2016-08-10 11:01:12DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBLE PARKING. THE INCREASE IN THE TOTAL NUMBER
 OF PARKING SPACES MAY TRIGGER A REQUIREMENT FOR
 ADDITIONAL ACCESSIBLE PARKING SPACES. NO NEW OVERALL
 PARKING DATA TABLE WWAS PROVIDED. EITHER PROVIDE
 ACCESSIBLE PARKING SPACES IN HIS LOT, OR PROVIDE A NEW
 OVERALL PARKING DATA TABLE TO SHOW THAT NO ADDITIONAL
 ACCESSIBLE PARKING SPACES ARE REQUIRED BY FLORIDA
 ACESSIBILTY CODE. THE MINIMUM NUMBER OF ACCESSIBLE
 PARKING SPACES PROVIDED SHALL BE IN ACCORDANCE WITH
 SECTION 208.2 OF FLORIDA ACCESSIBILITY CODE.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-08-2016 Cont ID  
Sent By pleduc Date 08-08-2016 Time   Rev Time 0.00
Received By pleduc Date 08-08-2016 Time 09:08 Sent To  
Notes
2016-08-08 09:16:17THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. DEMOLITION OF THE EXISTING STRUCTURES SHALL COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF ANY TEMPORARY CONSTRUCTION
 TRAILERS. A PERMIT IS REQUIRED FOR ANY CONSTRUCTION
 TRAILER RELATED TO THIS PROJECT THAT IS PLACED ON SITE.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION/DEMOLITION ACTIVITIES.
  
 3. EXISTING FIRE HYDRANT LOCATIONS IN THE AREA SHALL BE
 MAINTAINED CLEAR OF ANY OBSTRUCTIONS AND SHALL BE
 ACCESSIBLE AT ALL TIMES.
  
 4. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 5. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By rcaranci Date 08-09-2016 Time 13:59 Rev Time 0.00
Received By rcaranci Date 08-09-2016 Time 13:59 Sent To  
Notes
2016-08-09 14:01:15FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RYBOVICH 40TH STREET PARKING, CLASS B
 Z16070034
 AUGUST 9, 2016
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
  
 1. PLEASE PROVIDE A MITIGATION CHART TO SHOW HOW TREES
 PROPOSED TO BE REMOVED WOULD BE MITIGATED. EACH SITE
 WOULD REQUIRE A SEPARATE REMOVAL AND MITIGATION PLAN,
 INCLUDING THE CITY OWNED PARK.
  
 2. PLEASE EXPLAIN THE NEED TO REMOVE TREE #35 THAT IS
 LOCATED ON THE ADJACENT PROPERTY.
  
 3. PLEASE PROVIDE THE CALCULATIONS FOR REQUIRED SHADE
 TREES, FLOWERING TREES AND SHRUBS USING THE REQUIRED
 40% OPEN SPACE OF THE ENTIRE SITE.
  
 4. PLEASE PROVIDE CALCULATIONS FOR ALL BUFFERS FOR
 REQUIRED SHADE TREES PER 94-443(B) (4) AND (5), AND
 PROVIDE ON THE LANDSCAPE PLAN.
  
 5. PLEASE ADD TREES AND PROVIDE LANDSCAPE AREAS AT
 LEAST 5 FEET IN WIDTH AT THE END OF EACH ROW OF PARKING
 PER SECTION 94-443 (C) (3) A.
  
 6. PLEASE PROVIDE CALCULATIONS TO SHOW COMPLIANCE WITH
 SECTION 94-443 (C)(3) AND (4) FOR THE LANDSCAPE AREAS
 WITHIN THE PARKING AND PAVED AREAS, INCLUDING REQUIRED
 NUMBER OF SHADE TREES.
  
 7. PLEASE PROVIDE THE WATER NEEDS CATEGORY FOR EACH
 SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE
 GUIDE TO SHOW COMPLIANCE WITH FLORIDA FRIENDLY
 LANDSCAPING PER 94-442 (G).
  
 8. PLEASE REVISE THE LANDSCAPE AND ENGINEERING PLANS TO
 AVOID CONFLICTS BETWEEN LANDSCAPING AND WATER, SEWER,
 DRAINAGE, LIGHTING AND FPL EQUIPMENT. PLEASE SHOW
 LOCATIONS OF ALL UTILITIES AND EASEMENTS CLEARLY LABEL
 THEM ON THE LANDSCAPE PLAN.
  
 9. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 10. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH
 AS A/C COMPRESSORS FOR THE GUARD SHACK, ETC., AND
 PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND
 UTILITIES.
  
 11. PLEASE ADDRESS WHAT WILL BE DONE WITH THE OVERHEAD
 POWER LINES AND POLES THAT CURRENTLY RUN ALONG THE REAR
 OF THE EXISTING PROPERTIES, AS THIS MAY AFFECT THE
 SPECIES OF TREES THAT ARE PROPOSED FOR THE BUFFER.
  
 12. JATROPHA INTERRIGMA DOES NOT QUALIFY AS A TREE.
 PLEASE PROVIDE A SPECIES THAT QUALIFIES AS A TREE
 GROWING AT LEAST 15 FEET TALL BY 15 FEET WIDE.
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By lle Date 08-09-2016 Time 23:16 Rev Time 0.00
Received By lle Date   Time   Sent To  
Notes
2016-08-09 23:15:30FROM: LAURA LE, PUBLIC UTILITIES ENGINEER
 AUGUST 9, 2016
  
 THIS IS A CONCEPTUAL LEVEL REVIEW.THE FOLLOWING MUST BE
 ADDRESSED PRIOR TO ISSUANCE OF CONSTRUCTION
 AUTHORIZATION INCLUDING BUILDING
 PERMITS AND ENGINEERING DEVELOPMENTAL APPROVAL:
  
 1. ADD EXISTING UTILITIES ON 41TH STREET AND
 N.FLAGLER/POINSETTIA STREET. LABEL PIPE INFORMATION -
 TYPE, MATERIAL, AND SIZE FOR PIPES AND SERVICES.
 2. CITY'S RECORD INFORMATION INDICATES EXISTING
 UTILITIES ON 41ST STREET INCLUDE A 6-INCH WATER MAIN,
 8-INCH SANITARY SEWER, AND 72-INCH STORMWATER PIPE
 3. CITY'S RECORD INFORMATION INDICATES EXISTING
 UTILITIES ON N FLAGLER/POINSETTIA STREET INCLUDE AN
 8-INCH WATER MAIN, 24-INCH SANITARY SEWER, AND 36-INCH
 STORMWATER PIPE
 4. EXISTING UTILITY SERVICE LINES, IF NOT USED BY THE
 SITE REDEVELOPMENT, ARE TO BE CUT AND CAPPED AT THE
 MAIN AND REMOVED (IF LARGER THAN 2 INCHES IN DIAMETER).
 RESTORE THE TRENCH CUT PER THE CITY'S STANDARD DETAILS

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By tward Date 08-09-2016 Time 15:02 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2016-08-09 15:04:09THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. IS NOTE #12 ON SHEET C-200 APPLICABLE?
  
 2. IDENTIFY THE CONTROL STRUCTURE FOR EXFILTRATION
 TRENCH ZONE 1 AND HOW THE TRENCH WILL BE SURCHARGED TO
 THE TOP OF THE TRENCH.
  
 3. IT APPEARS THE PROPOSED PARKING LOT WILL BE 1 FOOT
 TO 2.5 FEET BELOW THE 40TH STREET SIDEWALK AND THE
 PROPERTY TO THE NORTH. ARE THE PARKING LOT GRADES
 HIGHER THAN THE HYDRAULIC GRADE LINE OF THE 66? STORM
 PIPE?
  
 4. SHOW THE EXISTING DRAINAGE PIPE RUNNING NORTH UNDER
 THE PUBLIC PARKING LOT FROM THE EXISTING DRAINAGE
 MANHOLE WHERE THE ONSITE DRAINAGE SYSTEM IS BEING
 CONNECTED.
  
 5. SHOW EXISTING AND PROPOSED UTILITIES ON THE
 LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER
 INDICATING THE CHANGES TO THE ONSITE PEAK FLOOD STAGES
 WILL NOT EXCEED THE SFWMD PERMITTED FLOOD STAGES AND
 STORMWATER TREATMENT IS BEING PROVIDED PER SFWMD
 CRITERIA. THE UNSATURATED DEPTH ?DU? VALUE IN THE
 EXFILTRATION TRENCH EQUATION SHOULD BE DEPTH OF THE
 EXFILTRATION TRENCH ABOVE THE MEAN HIGH TIDE ELEVATION.
 THE HEAD ?H? VALUE IN THE EXFILTRATION TRENCH EQUATION
 SHOULD BE THE DIFFERENCE BETWEEN THE TRENCH CONTROL
 (WEIR) ELEVATION AND THE MEAN HIGH TIDE ELEVATION
  
 3. PROVIDE A COPY OF THE SFWMD ERP FOR THIS PROJECT.
  
 4. DETAILS SHEETS WILL NEED TO UTILIZE CITY OF WEST
 PALM BEACH STANDARD DETAILS, WHICH MAY BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 08-10-2016 Cont ID  
Sent By jroach Date 08-10-2016 Time 15:20 Rev Time 0.00
Received By jroach Date 08-10-2016 Time 15:20 Sent To  
Notes
2016-08-10 15:20:18PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.10.2016
 PROJECT NO.: Z16070034, Z16070035, Z16070036, Z16070037
 AND Z16070033
 CASE NO.: ZBA CASE NOS. 3340, 3341, 3342 AND 3343, AND
 PB CASE NO. 1716
 ADDRESS: NORTHWEST CORNER OF NORTH FLAGLER DRIVE AND
 40TH STREET
 APPLICANT/CONTACT: BRIAN M. SEYMOUR, ESQ. AND JOSH I.
 LONG, AICP, OF GUNSTER, ON BEHALF OF FLAMINGO
 PROPERTIES 4105 LLC AND JAD 416 LLC
 TELEPHONE NO.: 561.650.0717
 SCOPE OF REVIEW: CONSTRUCTION OF A 104-SPACE OFF-SITE
 PARKING LOT.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-342(E)(3) AND ARTICLE XVI,
 INCLUDING SECTION 94-513(A)(1), OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, LOTS OR PORTIONS OF
 LOTS CANNOT BE SUBDIVIDED SO AS TO CREATE A
 NONCONFORMITY, OR INCREASE AN EXISTING NONCONFORMITY.
  
 2. THE IMPROVEMENTS SHOWN WITHIN THE PARK / NORTH
 FLAGLER DRIVE RIGHT-OF-WAY SHALL BE REMOVED FROM THE
 PLANS OR NOTED ACCORDINGLY AS THEY ARE NOT A PART OF
 THIS APPLICATION.
  
 3. PURSUANT TO SECTION 94-313(1), THE SITE SHALL BE
 LIMITED TO ONE (1) ACCESS POINT.
  
 4. ALL LANDSCAPE BUFFERS SHALL BE DIMENSIONED AND SHALL
 BE A MINIMUM OF FIVE (5) FEET IN WIDTH (AREAS OF
 CONCERN ARE IN THE SOUTHEAST CORNER ALONG THE RADIUS,
 AND ALONG THE EAST PROPERTY LINE).
  
 5. PURSUANT TO SECTION 94-443(B)(2), THE LANDSCAPE
 BUFFER MAY NOT BE INTERRUPTED BY MORE THAN 25 PERCENT
 OF ITS REQUIRED LENGTH FOR VEHICULAR INGRESS/EGRESS.
  
 6. PLEASE CONFIRM THAT NO LIGHTING WILL BE PROVIDED.
  
 7. WITH THE PROPOSED LOCATION OF THE FENCE, AND
 LANDSCAPING BEING LOCATED ON THE OUTSIDE OF THE FENCE,
 ALONG THE ADJACENT RESIDENTIAL HOMES, HOW IS IT
 ANTICIPATED THAT THIS LANDSCAPE BUFFER WILL BE
 MAINTAINED? WILL THERE BE AN EASEMENT FROM THE ADJACENT
 PROPERTY OWNER?
  
 8. IT IS SUGGESTED THAT THE FENCE IN THE SOUTHWEST
 CORNER RECESS IN (PARALLEL TO THE CURB LINE) TO ALLOW
 MOST OF THE LANDSCAPING IN THIS AREA TO BE LOCATED ON
 THE OUTSIDE OF THE FENCE.
  
 9. IT IS ENCOURAGED THAT THE WHEEL STOPS ON THE
 PERIMETER PARKING SPACES BE REMOVED AND CURBING BE
 UTILIZED, ALLOWING EXPANSION OF THE PLANTING AREA.
 VEHICLES CAN OVERHANG INTO THE ADDITIONAL LANDSCAPING
 SO LONG AS THE LANDSCAPE MATERIAL IS LIMITED TO SOD OR
 GROUNDCOVER. THIS PROVIDES FOR A LARGER PLANTING AREA
 FOR PROPOSED TREES, ETC.
  
 10. CURBING SHALL BE PROVIDED IN THE NORTHWEST CORNER
 OF THE LOT, SEPARATING THE PLANTING AREA FROM THE
 VEHICULAR CIRCULATION.
  
 11. SETBACKS SHALL BE PROVIDED FOR THE GUARD HOUSE AND
 SHALL CONFORM TO THE REQUIREMENTS OF THE ZLDRS.
  
 12. PLEASE PROVIDE ELEVATIONS OF THE PROPOSED GUARD
 HOUSE. THE STYLE SHALL BE COMPATIBLE WITH THE
 SURROUNDING ARCHITECTURE.
  
 13. ALL EXISTING CURB CUTS THAT WILL NO LONGER BE
 UTILIZED SHALL BE REMOVED AND REPLACED WITH APPROPRIATE
 CURBING.
  
 14. STRIPING DETAIL SHALL BE PROVIDED.
  
 15. A PEDESTRIAN CONNECTION SHALL BE PROVIDED TO THE
 40TH STREET / NORTH FLAGLER DRIVE INTERSECTION.
 PEDESTRIANS SHALL NOT BE REQUIRED TO CROSS THE STREET
 MID-BLOCK, NOR WALK ACROSS THE GRASS.
  
 16. THE CORPORATION LISTED AS THE OWNER OF 435 40TH
 STREET DIFFERS BETWEEN THE PROPERTY APPRAISER?S
 WEBSITE, THE DEED, AND THE AFFIDAVIT PROVIDED FOR
 WAIVER OF THE REQUIRED WALL.
  
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved