Plan Review Details - Project Z16070018
Plan Review Stops For Project Z16070018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-10-2016 Cont ID  
Sent By rbrown Date 08-10-2016 Time 10:38 Rev Time 0.00
Received By rbrown Date 08-10-2016 Time 10:38 Sent To  
Notes
2016-08-10 10:45:23DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. MEANS OF EGRESS. OVERHEAD/VEHICULAR ACCESS DOORS
 CANNOT BE COUNTED TOWARD THE MEANS OF EGRESS. WHEN
 SUBMITTED FOR PERMIT, SHEETS A1.0 AND A1.1 SHALL SHOW A
 PEDESTRIAN EGRESS DOOR LEADING FROM THE "OPEN STORAGE"
 SPACE VIA WALKWAY TO A PLACE OF SAFETY.
  
 3. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 07-11-2018 Cont ID  
Sent By mgonzale Date 07-11-2018 Time   Rev Time 1.00
Received By mgonzale Date 07-11-2018 Time   Sent To Z
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 12-27-2017 Cont ID  
Sent By squinone Date 12-27-2017 Time   Rev Time 0.00
Received By squinone Date 12-20-2017 Time   Sent To  
Notes
2017-12-27 11:03:14CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 DATE: 12/27/2017
 PROJECT: GANDER AND WHITE SITE PLAN REVIEW
 ADDRESS: 2206 MERCER AVE.
 STATUS: PASSED
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. AFTER THE SITE PLAN IS APPROVED,
 IN THE NEXT PHASE:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 07-12-2018 Cont ID  
Sent By pleduc Date 07-12-2018 Time   Rev Time 0.00
Received By pleduc Date 07-12-2018 Time 08:54 Sent To  
Notes
2018-07-12 08:56:00AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM PAUL
 GREILICH, SENIOR PLANNER, WITH ATTACHMENTS DATED JUNE
 26, 2018, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-05-2016 Cont ID  
Sent By pleduc Date 08-05-2016 Time   Rev Time 0.00
Received By pleduc Date 08-05-2016 Time 13:24 Sent To  
Notes
2016-08-05 13:59:56THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. THESE
 COMMENTS ARE GENERAL IN NATURE AND ADDITIONAL, MORE
 SPECIFIC, COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVEIW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPACY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADAQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SSPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS
 AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 06-29-2018 Cont ID  
Sent By rcaranci Date 06-29-2018 Time 16:56 Rev Time 0.00
Received By rcaranci Date 06-29-2018 Time 16:56 Sent To  
Notes
2018-06-29 16:56:46FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GANDER AND WHITE Z16070018
 JUNE 29, 2018
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED.
 2. SATISFIED.
 3. SATISFIED.
  
 4. SATISFIED.
 5. SATISFIED.
  
 6. WITHDRAWN.
 7. SATISFIED.
  
 ADDITIONAL COMMENTS 12/2/16:
 8. SATISFIED.
 9. SATISFIED.
 10. SATISFIED.
 11. SATISFIED. SHOW LOCATIONS OF LIGHTS ON THE
 LANDSCAPE PLAN MATCHING THE PHOTOMETRIC PLAN, AND
 RESOLVE ANY CONFLICTS WITH TREES.
 12. SATISFIED.
 ADDITIONAL COMMENTS 1/3/18:
 13. NOT SATISFIED. THE SITE AND LANDSCAPE PLANS WERE
 CHANGED AND REVERT TO EXISTING CONDITIONS WHICH CONTAIN
 MANY NONCONFORMITIES. SITE LANDSCAPE MUST BE BROUGHT TO
 CURRENT CODE REQUIREMENTS FOR THE BUFFERS AND PARKING
 AREAS ALONG WHITNEY ST.
 LANDSCAPE BUFFER DOES NOT MEET CODE REQUIREMENTS WEST
 OF THE MODIFIED ENTRANCE.
  
 14. NOT SATISFIED. PLEASE CONTINUE LANDSCAPE BUFFER
 TREES AND HEDGES AS APPLICABLE WHEN ACCESS DRIVE IS
 MODIFIED AS REQUIRED BY ENGINEERING.
 LANDSCAPE BUFFER DOES NOT MEET CODE REQUIREMENTS WEST
 OF THE MODIFIED ENTRANCE.
  
 15. CONDITIONALLY SATISFIED. MODIFICATIONS TO THE
 BUILDING REQUIRE ALL LANDSCAPE IMPROVEMENTS TO BE
 APPROVED WITH THIS PETITION TO BE COMPLETED AT THE TIME
 OF THE FIRST EXPANSION.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. ALL LANDSCAPE IMPROVEMENTS APPROVED WITH THIS
 PETITION SHALL BE PERMITTED AND COMPLETED PRIOR TO THE
 ISSUANCE OF THE CERTIFICATE OF OCCUPANCY FOR THE FIRST
 EXPANSION.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 01-26-2018 Cont ID  
Sent By rcaranci Date 01-26-2018 Time 15:16 Rev Time 0.00
Received By rcaranci Date 01-26-2018 Time 15:16 Sent To  
Notes
2018-01-26 15:17:56FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GANDER AND WHITE Z16070018
 JANUARY 26, 2018
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE CORRECT CALCULATIONS TO SHOW
 COMPLIANCE WITH SECTION 94-443 (C)(3) AND (4) FOR THE
 LANDSCAPE AREAS REQUIREMENTS WITHIN THE PARKING AND
 PAVED AREAS, INCLUDING REQUIRED NUMBER OF SHADE TREES,
 THEN CALCULATE THE MAXIMUM NUMBER OF PALMS SUBSTITUTED
 FOR THE REQUIRED PARKING LOT TREES.
 CALCULATIONS FOR PAVED AREAS NEED TO BE INCLUDED IN
 CALCULATIONS, AND PROVIDE A GRAPHIC FOR THE PROVIDED
 AREAS.
  
 2. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL
 EQUIPMENT SUCH AS A/C COMPRESSORS, ETC., AND PROVIDE
 SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND
 UTILITIES.
 PLEASE SHOW HOW SCREENING FOR THE GENERATOR WILL BE
 PROVIDED.
  
 3. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER
 LINES THAT SERVICE THE BUILDING, AND LOCATIONS OF ABOVE
 GROUND VALVES.
  
 4. SATISFIED. PLEASE REVISE TO ASSURE THE 10 FOOT
 BUFFER STRIPS ADJACENT TO THE LOADING AREA MEET ALL
 LANDSCAPE BUFFER REQUIREMENTS INCLUDING MINIMUM WIDTH
 NOT INCLUDING CURBS, TREE OR PALM SPACING AND HEDGES.
 AREA NORTH OF DRIVE CAN BE 10 FEET WIDE.
  
 5. SATISFIED. PLEASE ADD IN A WHEEL STOP IN THE PARKING
 SPACE ALONG THE NORTH SIDE OF PARKING AREA ADJACENT TO
 THE LANDSCAPE ISLAND CONTAINING ILEX CASSINE.
  
 6. WITHDRAWN. THE LIVE OAK TREE TO BE PRESERVED
 ADJACENT TO THE LANDSCAPE ISLAND ALONG THE NORTH SIDE
 OF PARKING AREA CAN ONLY BE COUNTED FOR THE BUFFER
 REQUIREMENT OR THE LANDSCAPE ISLAND REQUIREMENT, NOT
 BOTH. PLEASE ADD ANOTHER TREE TO SATISFY BOTH
 REQUIREMENTS.
 PLAN WAS CHANGED.
  
 7. SATISFIED. PLEASE PROVIDE THE REQUIRED HEDGE AROUND
 THE DUMPSTER ENCLOSURE WALL.
  
 ADDITIONAL COMMENTS 12/2/16:
 8. SATISFIED. ADD REQUIRED TERMINAL ISLAND TREE AT THE
 END OF THE LINE OF PARKING TERMINATING AT THE WEST SIDE
 OF THE DRIVEWAY.
 9. SATISFIED. TREE #14 WILL NOT BE POSSIBLE TO PRESERVE
 AS SHOWN WITH THE WALL PLACEMENT.
 10. SATISFIED. CORRECT THE CAD LAYER ON THE LANDSCAPE
 PLAN SHOWING DIFFERENT ISLANDS AND CURB TO MATCH THE
 SITE PLAN.
 11. NOT SATISFIED. SHOW LOCATIONS OF LIGHTS ON THE
 LANDSCAPE PLAN MATCHING THE PHOTOMETRIC PLAN, AND
 RESOLVE ANY CONFLICTS WITH TREES.
 12. SATISFIED. ADD REQUIRED TREES IN TERMINAL ISLANDS
 AS REQUIRED IN PLANTER AREA, AND SWITCHBOX ISLAND.
 ADDITIONAL COMMENTS 1/26/18:
 13. THE SITE AND LANDSCAPE PLANS WERE CHANGED AND
 REVERT TO EXISTING CONDITIONS WHICH CONTAIN MANY
 NONCONFORMITIES. SITE LANDSCAPE MUST BE BROUGHT TO
 CURRENT CODE REQUIREMENTS FOR THE BUFFERS AND PARKING
 AREAS ALONG WHITNEY ST.
  
 14. PLEASE CONTINUE LANDSCAPE BUFFER TREES AND HEDGES
 AS APPLICABLE WHEN ACCESS DRIVE IS MODIFIED AS REQUIRED
 BY ENGINEERING.
  
 15. MODIFICATIONS TO THE BUILDING REQUIRE ALL LANDSCAPE
 IMPROVEMENTS APPROVED WITH THIS PETITION TO BE
 COMPLETED AT THE TIME OF THE FIRST EXPANSION.
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-02-2016 Cont ID  
Sent By rcaranci Date 12-02-2016 Time 17:15 Rev Time 0.00
Received By rcaranci Date 12-02-2016 Time 17:15 Sent To  
Notes
2016-12-02 17:15:34FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GANDER AND WHITE Z16070018
 DECEMBER 2, 2016
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
  
 1. NOT SATISFIED. PLEASE CORRECT CALCULATIONS TO SHOW
 COMPLIANCE WITH SECTION 94-443 (C)(3) AND (4) FOR THE
 LANDSCAPE AREAS REQUIREMENTS WITHIN THE PARKING AND
 PAVED AREAS, INCLUDING REQUIRED NUMBER OF SHADE TREES,
 THEN CALCULATE THE MAXIMUM NUMBER OF PALMS SUBSTITUTED
 FOR THE REQUIRED PARKING LOT TREES.
 CALCULATIONS FOR PAVED AREAS NEED TO BE INCLUDED IN
 CALCULATIONS, AND PROVIDE A GRAPHIC FOR THE PROVIDED
 AREAS.
  
 2. NOT SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL
 EQUIPMENT SUCH AS A/C COMPRESSORS, ETC., AND PROVIDE
 SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND
 UTILITIES.
 PLEASE SHOW HOW SCREENING FOR THE GENERATOR WILL BE
 PROVIDED.
  
 3. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER
 LINES THAT SERVICE THE BUILDING, AND LOCATIONS OF ABOVE
 GROUND VALVES.
  
 4. NOT SATISFIED. PLEASE REVISE TO ASSURE THE 10 FOOT
 BUFFER STRIPS ADJACENT TO THE LOADING AREA MEET ALL
 LANDSCAPE BUFFER REQUIREMENTS INCLUDING MINIMUM WIDTH
 NOT INCLUDING CURBS, TREE OR PALM SPACING AND HEDGES.
 AREA NORTH OF DRIVE CAN BE 10 FEET WIDE.
  
 5. SATISFIED. PLEASE ADD IN A WHEEL STOP IN THE PARKING
 SPACE ALONG THE NORTH SIDE OF PARKING AREA ADJACENT TO
 THE LANDSCAPE ISLAND CONTAINING ILEX CASSINE.
  
 6. WITHDRAWN. THE LIVE OAK TREE TO BE PRESERVED
 ADJACENT TO THE LANDSCAPE ISLAND ALONG THE NORTH SIDE
 OF PARKING AREA CAN ONLY BE COUNTED FOR THE BUFFER
 REQUIREMENT OR THE LANDSCAPE ISLAND REQUIREMENT, NOT
 BOTH. PLEASE ADD ANOTHER TREE TO SATISFY BOTH
 REQUIREMENTS.
 PLAN WAS CHANGED.
  
 7. SATISFIED. PLEASE PROVIDE THE REQUIRED HEDGE AROUND
 THE DUMPSTER ENCLOSURE WALL.
  
 ADDITIONAL COMMENTS 12/2/16:
  
 8. ADD REQUIRED TERMINAL ISLAND TREE AT THE END OF THE
 LINE OF PARKING TERMINATING AT THE WEST SIDE OF THE
 DRIVEWAY.
 9. TREE #14 WILL NOT BE POSSIBLE TO PRESERVE AS SHOWN
 WITH THE WALL PLACEMENT.
 10. CORRECT THE CAD LAYER ON THE LANDSCAPE PLAN SHOWING
 DIFFERENT ISLANDS AND CURB TO MATCH THE SITE PLAN.
 11. SHOW LOCATIONS OF LIGHTS ON THE LANDSCAPE PLAN
 MATCHING THE PHOTOMETRIC PLAN, AND RESOLVE ANY
 CONFLICTS WITH TREES.
 12. ADD REQUIRED TREES IN TERMINAL ISLANDS AS REQUIRED
 IN PLANTER AREA, AND SWITCHBOX ISLAND.
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By rcaranci Date 08-09-2016 Time 15:39 Rev Time 0.00
Received By rcaranci Date 08-09-2016 Time 15:39 Sent To  
Notes
2016-08-09 15:40:20FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GANDER AND WHITE Z16070018
 AUGUST 9, 2016
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
  
 1. PLEASE CORRECT CALCULATIONS TO SHOW COMPLIANCE WITH
 SECTION 94-443 (C)(3) AND (4) FOR THE LANDSCAPE AREAS
 REQUIREMENTS WITHIN THE PARKING AND PAVED AREAS,
 INCLUDING REQUIRED NUMBER OF SHADE TREES, THEN
 CALCULATE THE MAXIMUM NUMBER OF PALMS SUBSTITUTED FOR
 THE REQUIRED PARKING LOT TREES.
  
 2. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH
 AS A/C COMPRESSORS, ETC., AND PROVIDE SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT AND UTILITIES.
  
 3. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES THAT
 SERVICE THE BUILDING, AND LOCATIONS OF ABOVE GROUND
 VALVES.
  
 4. PLEASE REVISE TO ASSURE THE 10 FOOT BUFFER STRIPS
 ADJACENT TO THE LOADING AREA MEET ALL LANDSCAPE BUFFER
 REQUIREMENTS INCLUDING MINIMUM WIDTH NOT INCLUDING
 CURBS, TREE OR PALM SPACING AND HEDGES.
  
 5. PLEASE ADD IN A WHEEL STOP IN THE PARKING SPACE
 ALONG THE NORTH SIDE OF PARKING AREA ADJACENT TO THE
 LANDSCAPE ISLAND CONTAINING ILEX CASSINE.
  
 6. THE LIVE OAK TREE TO BE PRESERVED ADJACENT TO THE
 LANDSCAPE ISLAND ALONG THE NORTH SIDE OF PARKING AREA
 CAN ONLY BE COUNTED FOR THE BUFFER REQUIREMENT OR THE
 LANDSCAPE ISLAND REQUIREMENT, NOT BOTH. PLEASE ADD
 ANOTHER TREE TO SATISFY BOTH REQUIREMENTS.
  
 7. PLEASE PROVIDE THE REQUIRED HEDGE AROUND THE
 DUMPSTER ENCLOSURE WALL.
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By lle Date 08-09-2016 Time 18:04 Rev Time 0.00
Received By lle Date   Time   Sent To  
Notes
2016-08-09 18:19:40FROM: LAURA LE, PUBLIC UTILITIES ENGINEER
 AUGUST 9, 2016
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. THE FOLLOWING
 COMMENTS MUST BE ADDRESSED PRIOR TO SITE PLAN APPROVAL:
  
 1. INCLUDE REVIEW FOR PB CASE NOS. 1714 & 1715
 2. THE LANDSCAPE PLAN SHOWS TREES BEING PLANTED OVER OR
 NEAR THE EXISTING 8-INCH WATER AND 10-INCH SANITARY
 SEWER PIPES
 3. CALL OUT THE EXISTING WATER AND SEWER MAINS AND
 SERVICES, PIPE SIZE, MATERIAL, VALVES, MANHOLES, ETC
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 4 Status P Date 07-10-2018 Cont ID  
Sent By tward Date 07-10-2018 Time 13:43 Rev Time 0.00
Received By tward Date 07-10-2018 Time 13:43 Sent To  
Notes
2018-07-10 13:43:19THE 6/26/18 SUBMITTAL PACKAGE ADDRESS PREVIOUS
 STORMWATER STOP SITE PLAN APPROVAL COMMENTS.
  
 THE PROPOSED CURBS FOR CREATING BULBOUTS ON THE FORMER
 BOYD STREET ARE NOT TO RESULT IN STANDING WATER ON
 WHITNEY STREET. PROVIDE SUFFICIENT SPOT GRADES THAT
 DEMONSTRATE THIS ON THE PLANS TO BE SUBMITTED FOR
 ENGINEERING PERMIT.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 3 Status F Date 01-26-2018 Cont ID  
Sent By tward Date 01-26-2018 Time 14:09 Rev Time 0.00
Received By tward Date 01-26-2018 Time 14:32 Sent To  
Notes
2018-01-26 14:32:27THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/19/17 REVIEW SUBMITTAL:
  
 1. THE TREE ROOT DETAIL IN THE LANDSCAPE PLANS MAKE
 REFERENCE TO PBCWUD UTILITIES. ADD A REFERENCE TO CWPB
 UTILTIES (WATER, SEWER, STORM). [REPEAT COMMENT].
  
 2. SHOW ROOT BARRIER ON THE LANDSCAPE PLANS FOR THE
 STORM PIPE BETWEEN THE EXISTING CB (BEING CONVERTED TO
 MH COVER) AND STRUCTURE S-105.
  
 3. THE ENGINEERING PLAN DOES NOT MATCH THE SITE PLAN
 AND LANDSCAPE PLANS. THE ENGINEERING PLAN DOES NOT SHOW
 THE LANDSCAPE ISLAND ON THE SOUTHWEST SIDE OF THE
 HANDICAP PARKING SPACES.
  
 4. DRAINAGE STRUCTURE S-101 IS TO HAVE TWO PRBS BECAUSE
 IT IS CONNECTED TO TWO EXFILTRATION TRENCHES. VERIFY
 THE PRBS WILL FIT IN A TYPE 'C' DITCH BOTTOM INLET.
  
 5. VERIFY THE EXISTING CB NORTH OF STRUCTURE S-101 WILL
 HAVE A TWO FOOT SUMP IN ORDER FOR A PRB TO BE INSTALLED
 ON THE SOUTH WALL.
  
 6. EXTEND THE SIDEWALK WITH CURB RAMPS TO THE EDGE OF
 PAVEMENT ON EACH SIDE OF BOYD STREET.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 2 Status F Date 12-05-2016 Cont ID  
Sent By tward Date 12-05-2016 Time 11:02 Rev Time 0.00
Received By tward Date 12-05-2016 Time 11:05 Sent To  
Notes
2016-12-05 11:05:44COMMENTS FROM THE REVIEW OF THE 11/18/2016 RESUBMITTAL.
  
 1. EXISTING PARKING LOT IS BEING MODFIED / EXPANDED.
 ADD WATER QUALITY TREATMENT FOR THIS PARKING LOT
 2. REVIEW GRADING PLAN AND PROVIDE FLOW ARROWS
 INDICATING DIRECTION OF FLOW OF SURFACE RUNOFF. IT IS
 NOT CLEAR WHERE THE RUNOFF FROM THE PARKING SPACES NEXT
 TO THE BUILDING WILL END UP.
 3. SIDEWALK AND CURBING IN RIGHT-OF-WAY TO BE
 CONSTRUCTED PER CITY STANDARD DETAILS. TYPE ?F? CURB TO
 BE CONSTRUCTED IN THE RIGHT-OF-WAY. DROP CURB ALONG THE
 DRIVEWAY IF NEEDED.
 4. DRIVEWAY APRON TO BE CONSTRUCTED PER CITY STANDARD
 DETAILS.
 5. SHOW CONCRETE SIDEWALK ACROSS DRIVEWAY.
 6. EXISTING INLET AT NORTH CORNER OF THE EXISTING
 BUILDING TO BE CONVERTED TO MANHOLE TOP.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-09-2016 Cont ID  
Sent By tward Date 08-09-2016 Time 14:57 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2016-08-09 14:59:36THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE LANDSCAPE PLAN SHOWS TREES BEING PLANTED OVER OR
 NEAR EXISTING AND PROPOSED STORMWATER PIPES.
  
 2. ONSITE STORMWATER SYSTEM TO PROVIDE REQUIRED
 PRE-TREATMENT PER SFWMD REGULATIONS.
  
 3. MODIFY ROOT BARRIER DETAIL TO INCLUDE CITY?S
 UTILITIES.
  
 4. EASEMENT WILL BE NEEDED FOR THE PORTION OF
 STORMWATER SYSTEM BETWEEN THE BOYD STREET RIGHT-OF-WAY
 AND OUTFALL INTO THE STUB CANAL.
  
 5. ELIMINATE THE PIPE BETWEEN STRUCTURES S-103 AND
 S-104. THE ONSITE DRAINAGE SYSTEM CAN USE THE 18? RCP
 OUTFALL FROM S-103.
  
 6. A CONTROL STRUCTURE WILL BE NEEDED FOR THE
 EXFILTRATION TRENCH SYSTEM.
  
 7. REVIEW THE LOCATION OF THE EXFILTRATION TRENCH NEXT
 TO THE PROPOSED EXPANSION. THE EFFICIENCY OF
 EXFILTRATION TRENCH SYSTEMS DECREASE OVER TIME AND THE
 TRENCH WILL HAVE TO BE REPLACED IN ORDER TO BECOME
 FUNCTIONAL AGAIN.
  
 8. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 9. APPLICANT SHOULD MEET WITH FERDINAND RIVERA
 (822-2076) OF PUBLIC WORKS TO REVIEW SERVICEABILITY OF
 DUMPSTER IN NEW PROPOSED LOCATION. PROVIDE AN AUTOTURN
 ANALYSIS SHOWING ACCESS TO AND FROM THE DUMPSTER FROM
 BOTH DIRECTIONS ON MERCER AVE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER
 INDICATING THE CHANGES TO THE ONSITE PEAK FLOOD STAGES
 WILL NOT EXCEED THE SFWMD PERMITTED FLOOD STAGES.
  
 3. DETAILS SHEETS WILL NEED TO UTILIZE CITY OF WEST
 PALM BEACH STANDARD DETAILS, WHICH MAY BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-07-11 10:13:23PASSED BUT REQUIRE EASEMENTS PER NEWLY RECORDED PLAT BE
 SHOWN ON ALL PLANS.

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 12-06-2016 Cont ID  
Sent By vnoel Date 12-06-2016 Time 10:09 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2016-12-06 10:09:21PASSED WITH CONDITIONS:
  
 1. INCLUDES REVIEW FOR PB CASE NOS. 1714 & 1715
 2. SEPARATE PLAT REVIEW SUBMITTAL TO ENGINEERING WILL
 BE REQUIRED. FEE WILL BE $1501.
 3. EASEMENTS WILL BE REQUIRED FOR ALL EXISTING
 UTITLITIES AND DRAINAGE. THESE CAN BE DEDICATED BY
 PLAT.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-08-2016 Cont ID  
Sent By vnoel Date 08-08-2016 Time 07:26 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2016-08-08 07:42:031. INCLUDES REVIEW FOR PB CASE NOS. 1714 & 1715
 2. SEPARATE PLAT REVIEW SUBMITTAL TO ENGINEERING WILL
 BE REQUIRED. FEE WILL BE $1501.
 3. APPRAISAL WILL BE REQUIRED FOR ABANDONMENT.
 APPRAISAL FEE OF $1800 MADE OUT TO ANDERSON & CARR WILL
 BE REQUIRED.
 4. ADDITIONAL EASEMENTS WILL BE REQUIRED FOR EXISTING
 SANITARY OVER PARKING LOT AND EXISTING DRAINAGE AT STUB
 CANAL.
 5. ADD EXISTING UTILITIES TO SITE PLAN.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 07-09-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-07-09 18:22:10- RESPONSE TO PREVIOUS COMMENT WAS NOT INCLUDED IN JUNE
 21, 2018 RESPONSE LETTER.
 -THE EAST CURB RADIUS AT INTERSECTION OF FORMER BOYD
 STREET AND WHITNEY STREET NEEDS TO BE REDUCED AS IT
 ONLY ACCOMODATES PASSENGER CARS.
 - SHOW AUTOTURN PATH SHOWING TRUCK ACCESS TO THE TWO
 LOADING BAYS.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 01-30-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-01-30 08:44:12DRIVEWAY (FORMERLY BOYD STREET) NEEDS TO BE SQUARED OFF
 AT INTERSECTION WITH WHITNEY STREET.
  
 ERIK FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 01-30-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-01-30 08:41:52DRIVEWAY (FORMERLY BOYD STREET) NEEDS TO BE SQUARED OFF
 AT INTERSECTION WITH WHITNEY STREET.
  
 ERIK FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-10-2016 Cont ID  
Sent By KUDANG Date 08-10-2016 Time   Rev Time 0.50
Received By   Date 08-10-2016 Time   Sent To I
Notes
2016-08-10 12:09:08PLANNING BOARD CASE NO. 1715
 LEVEL II SITE PLAN
 2206 MERCER AVE.
  
 - CONTACT UYEN DANG @ (561) 494-1087
  
 PROVIDE CHANELIZE ISLAND AT THE INTERSECTION OF MERCER
 AVE AND WITNEY STREET

Review Stop Z ZONING
Rev No 5 Status P Date 09-11-2018 Cont ID  
Sent By pgreilic Date 09-11-2018 Time 09:46 Rev Time 0.00
Received By pgreilic Date 09-11-2018 Time 09:46 Sent To  
Notes
2018-09-11 09:47:161.) ALL SITE IMPROVEMENTS MUST BE COMPLETED PRIOR TO
 ISSUANCE OF FINAL C.O. FOR FIRST PHASE OF WAREHOUSE
 EXPANSION
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 07-09-2018 Time   Rev Time 0.00
Received By pgreilic Date 07-09-2018 Time 10:48 Sent To  
Notes
2018-07-09 10:49:21FAILED
  
 1.) SHIFT HANDICAP SPACES EAST TO ALIGN HC RAMP WITH
 EXISTING WALKWAY. SHOW CROSSWALK ACCROSS DRIVE AISLE
 2.) ALL SITE IMPROVEMENTS MUST BE COMPLETED PRIOR TO
 ISSUANCE OF FINAL C.O. FOR FIRST PHASE OF WAREHOUSE
 EXPANSION
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 01-31-2018 Cont ID  
Sent By   Date 01-31-2018 Time   Rev Time 0.00
Received By pgreilic Date 01-31-2018 Time 10:33 Sent To  
Notes
2018-01-31 10:36:04FAILED
  
 1.) REDUCE NONCONFORMITIES ON SITE WHERE POSSIBLE IE
 DRIVEWAY WIDTH/ALIGNMENT, DRIVE AISLE WIDTH, LANDSCAPE
 BUFFERS, TERMINAL ISLANDS ETC.
 2.) ALL SITE IMPROVEMENTS MUST BE COMPLETED PRIOR TO
 ISSUANCE OF FINAL C.O. FOR FIRST PHASE OF WAREHOUSE
 EXPANSION
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 04-25-2017 Cont ID  
Sent By   Date 04-25-2017 Time   Rev Time 0.00
Received By pgreilic Date 11-18-2016 Time 12:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 08-05-2016 Cont ID  
Sent By llouie Date 08-05-2016 Time   Rev Time  
Received By llouie Date 08-05-2016 Time   Sent To  
Notes
2016-08-05 16:41:55GENERAL COMMMENTS:
  
 1.) THE SITE PLAN IS CONTINGENT UPON THE APPROVAL OF
 APPLICATIONS PB CASE NO. 1715 (ROW ABANDONMENT OF BOYD
 STREET) AND PB CASE NO. 1714 (MAJOR SUBDIVISION).
 PLEASE NOTE THAT THE SITE PLAN WILL NOT BE CONSIDERED
 FOR APPROVAL UNTIL THE APPLICANT HAS OBTAINED APPROVALS
 FOR PB 1715 AND PB 1714.
  
 2.) PLEASE NOTE THAT STAFF HAS SOME CONCERNS WITH THE
 REQUEST TO ABANDON BOYD STREET, BETWEEN WHITNEY STREET
 AND THE CSX (PB CASE NO. 1715). ALTHOUGH THIS SECTION
 OF BOYD STREET IS CURRENTLY CLOSED OFF, IT IS STILL
 FREQUENTLY UTILIZED BY PEDESTRIANS TO CROSS OVER THE
 CSX TRACKS TO THE NORTH/SOUTH SIDES OF THE STREET.
 FURTHER DISCUSSION ON THE PROPOSED ABANDONMENT AND THE
 POSSIBILITY OF PROVIDING A PEDESTRIAN CROSSING IS
 REQUIRED BETWEEN THE APPLICANT, AND STAFF FROM THE
 PLANNING DIVISION AND THE ENGINEERING SERVICES
 DEPARTMENT.
  
 3.) A TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY TRAFFIC DIVISION, VERIFYING
 THAT THE PROJECT MEETS THE TPS STANDARDS OF THE COUNTY
 WILL BE REQUIRED PRIOR TO THE APPROVAL OF THIS
 APPLICATION.
  
  
 SITE PLAN:
  
 1.) THE PROPOSED 6 FT. HIGH CHAIN LINK FENCE ALONG
 WHITNEY STREET, WHICH LIES ADJACENT TO A RESIDENTIAL
 ZONING DISTRICT, IS NOT PERMITTED PURSUANT TO ZLDR S.
 94-443(A). PLEASE REPLACE THE CHAIN LINK FENCE WITH A
 PROTECTIVE SCREEN WALL THAT IS CONSTRUCTED OUT OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE AND AESTHETIC WOOD OR METAL.
  
 2.) THE CURRENT PROPOSED LOCATION OF THE DUMPSTER
 ENCLOSURE AT THE REAR OF THE BUILDING DOES NOT SEEM TO
 BE AN APPROPRIATE LOCATION FOR SANITATION TRUCKS TO
 EASILY ACCESS. PLEASE RELOCATE THE DUMPSTER ENCLOSURE
 TO A MORE FEASIBLE LOCATION.
  
 3.) THE AREA OF THE EXISTING LOADING ZONE AND THE
 CAPABILITY OF TRUCKS TO MANEUVER WITHIN THE LOADING
 AREA HAVE BEEN MODIFIED TO ACCOMMODATE THE PROPOSED
 EXPANSION. PLEASE NOTE THAT THE CONFIGURATION OF
 LOADING INGRESS AND EGRESS, WHICH REQUIRES BACKING
 DIRECTLY ONTO A STREET FROM A LOADING SPACE IS
 PROHIBITED. DEMONSTRATE HOW THE PROPOSED LOADING AREA
 CONFIGURATION WILL NOT BACK OUT DIRECTLY ON MERCER
 AVENUE OR RECONFIGURE THE LOADING AREA FOR
 LOADING/UNLOADING SO THAT THIS REQUIREMENT IS
 ADDRESSED. [ZLDR S.94-485(J)(1)]
  
 4.) PURSUANT TO ZLDR S.94-485(Q), ONE (1) BICYCLE
 PARKING SHALL BE PROVIDED FOR EVERY 20 AUTOMOBILE
 PARKING SPACE. PLEASE IDENTIFY THE BICYCLE RACK
 LOCATION AND INCLUDE A DETAIL OF THE RACK IN THE SITE
 PLAN. ALSO INCLUDE THE BICYCLE PARKING CALCULATIONS IN
 THE SITE DATA TABULAR.
  
 5.) THE EXISTING USE ON THE PROPERTY IS CLASSIFIED AS
 "WAREHOUSING HAVING MODERATE EXTERNAL IMPACTS." PLEASE
 MAKE ALL THE NECESSARY CORRECTIONS IN THE SITE DATA
 TABULAR (INCLUDING THE PARKING CALCULATIONS) TO REFLECT
 THIS USE CLASSIFICATION IN ACCORDANCE WITH S.94-486 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 6.) ARE THERE ANY MECHANICAL EQUIPMENT (I.E. A/C UNITS,
 ETC.) PROPOSED FOR THE EXPANSION? IF SO, PROVIDE
 INFORMATION TO WHERE THE EQUIPMENT WILL BE LOCATED.
  
 7.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE SITE
 DATA TABULAR: APPLICATION NUMBER: FSPR 16-07; TOTAL
 SITE AREA: 79,715 SQ. FT. (NOT 79,775 SQ. FT.);
 PROPOSED PARKING: 65 SPACES (NOT 67 SPACES); LOADING
 REQUIRED: 2 (NOT 1); BUILDING HEIGHT: 24' (MAX. 50');
 "LOADING REQUIRED (10' X 50')" IS NOTATED BY AN
 ASTERISK (*) - CLARIFY WHAT THE ASTERISK IS SUPPOSED TO
 MEAN.
  
 8.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE
 DEVELOPMENT REGULATIONS TABULAR: MAXIMUM BUILDING
 HEIGHT IS 50'
  
 9.) PLEASE NOTATE IN THE SITE AND LANDSCAPING PLANS
 THAT THE EXISTING AND PROPOSED BUILDING IS A WAREHOUSE
 USE. "EXISTING BUILDING" AND "PROPOSED BUILDING" SEEMS
 INSUFFICIENT.
  
  
 LANDSCAPE PLAN:
  
 1.) THE PROPOSED EXPANSION WILL REQUIRE THE REMOVAL OF
 EXISTING TREES ON SITE. PLEASE NOTE THAT ANY EXISTING
 TREES AND/OR PALMS CANNOT BE REMOVED FROM THE PROPERTY
 WITHOUT FIRST OBTAINING A TREE ALTERATION PERMIT FROM
 THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING
 DIVISION.
  
 2.) ADDITIONAL COMMENTS ON THE LANDSCAPE PLAN TO BE
 PROVIDED BY THE CITY'S LANDSCAPE PLANNER, RAY CARANCI.
  
  
 FLOOR PLANS AND ELEVATIONS:
  
 1.) CONSIDER ADDING ARCHITECTURAL FEATURES AND
 FENESTRATION TO THE PROPOSED BUILDING EXPANSION,
 PARTICULARLY ALONG THE ELEVATIONS THAT ARE MOST VISIBLE
 FROM THE RIGHT-OF-WAYS (I.E. ALONG MERCER AVENUE AND
 ALONG THE CSX RAILROAD TRACKS).
  
 2.) PLEASE CHECK THE BUILDING ELEVATIONS IN SHEET EL
 AND MAKE CORRECTIONS WHERE NECESSARY. THERE SEEMS TO BE
 SOME INCONSISTENCIES WITH THE BUILDING ELEVATIONS
 PROVIDED.
  
 3.) FINAL PLANS SHALL BE SIGNED, DATED AND SEALED BY A
 FLORIDA REGISTERED ARCHITECT.
  
  
 LIGHTING:
  
 1.) WILL THERE BE ANY SITE LIGHTING FOR THE PROPOSED
 PROJECT? IF SO, PLEASE PROVIDE LOCATION OF THE LIGHT
 FIXTURES IN A PHOTOMETRIC PLAN.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX
 (6) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND
 AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT
 CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($300.00).
  
 * CONTACT PAUL GREILICH @ (561) 822-1443 IF THERE ARE
 QUESTIONS.