Plan Review Details - Project Z16070016
Plan Review Stops For Project Z16070016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 09-22-2016 Cont ID  
Sent By eschneid Date 09-22-2016 Time 10:58 Rev Time 0.00
Received By eschneid Date 09-22-2016 Time 10:58 Sent To  
Notes
2016-09-22 10:59:32PROVISO - ALL ADA CROSS WALKS NEED TO BE SHOWN ON THE
 PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-10-2016 Cont ID  
Sent By rbrown Date 08-10-2016 Time 11:07 Rev Time 0.00
Received By rbrown Date 08-10-2016 Time 11:07 Sent To  
Notes
2016-08-10 11:13:49DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBILITY. PROPOSED FLOOR PLAN, SHEET 5, AND
 PROPOSED LAYOUT, SHEET 6, SHOW ACCESS TO THE WOOD DECKS
 VIA STEPS ONLY. THOSE PLAN SHEETS TO NOT ALIGN WITH
 SITE PLAN, SHEET SP-1, WHICH DOES NOT SHOW STEPS ON THE
 SIDE OF THE DECK THAT IS CLOSEST TO THE RESTAURANT
 BUILDING. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL
 SHOW AT LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH
 SECTIONS 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE,
 CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES
 WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE
 BUILDING OR FACILITY
  
 3. WHEN ADDRESSING THE COMMENT ABOVE, PLEASE NOTE THAT
 ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER
 THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY
 WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-08-2016 Cont ID  
Sent By pleduc Date 08-08-2016 Time   Rev Time 0.00
Received By pleduc Date 08-08-2016 Time 09:18 Sent To  
Notes
2016-08-08 09:57:10THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 THIS APPEARS TO BE AN ASSEMBLY OCCUPANCY SPACE AND
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS. A REVIEW
 OF THE PROPOSED EXIT STAIRS WIDTH MAY BE NECESSARY TO
 ENSURE IT MEETS THE OCCUPANCY EXIT REQUIREMENTS.
  
 6. BASED ON SOME OF THE DESIGN PICTURES AND VARYING
 OVERHEAD ROOFING/CANOPIES AND A POTENTIAL OCCUPANCY
 OVER 300 A FIRE SPRINKLER AND FIRE ALARM MAY BE
 REQUIRED.
  
 ANY EXISITNG ENGINEERED FIRE AND LIFE SAFETY SYSTEM(S)
 IN THE MAIN STRUCTURE(S) SHALL BE EXTENDED INTO THE
 PROPOSED PROJECT TO PROVIDE THE SAME OR EQUAL LEVEL OF
 FIRE AND LIFE SAFETY.
  
 7. ANY PROPOSED CANOPY CONFIGURATION SHALL BE OF A
 LISTED FIRE RETARDANT/PROOF CONSTRUCTION MATERIAL.
  
 8. OPEN FLAME(S) EFFECTS/DEVICES ARE PROHIBITED UNLESS
 SPECIFACCALY APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL.
  
 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 09-22-2016 Cont ID  
Sent By rcaranci Date 09-22-2016 Time 16:35 Rev Time 0.00
Received By rcaranci Date 09-22-2016 Time 16:35 Sent To  
Notes
2016-09-22 16:35:42PROJECT: VILLAGE COMMONS OUTDOOR SEATING Z16070016
 SEPTEMBER 22, 2016
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE REVISE THE LANDSCAPE AND
 ENGINEERING PLANS TO AVOID CONFLICTS BETWEEN
 LANDSCAPING AND WATER, SEWER, DRAINAGE, LIGHTING AND
 FPL EQUIPMENT. PLEASE SHOW LOCATIONS OF ALL UTILITIES
 AND EASEMENTS ON THE LANDSCAPE PLAN.
  
 2. SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL AND
 SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 3. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL
 EQUIPMENT SUCH AS A/C COMPRESSORS, ETC., AND PROVIDE
 SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND
 UTILITIES.
  
 4. NOT SATISFIED. PLEASE PROVIDE A TREE DISPOSITION AND
 MITIGATION CHART TO SHOW COMPLIANCE WITH SECTION 94-448
 FOR THE FOUR EXISTING ROYAL PALMS THAT WILL BE
 AFFECTED.
  
 THE ROYAL PALMS SHOULD STAY IN THE SAME AREA IF
 POSSIBLE, MOVING THEM TO OTHER AREAS IN THE PARKING LOT
 IS SUBJECT TO REVIEW OF THE APPROVED LANDSCAPE PLANS TO
 ASSURE TREES ARE NOT MISSING IN THOSE LOCATIONS, AND
 NEED TO BE REPLACED.
  
 5. SATISFIED. PLEASE INDICATE EXISTING LANDSCAPING THAT
 WILL STAY IN PLACE ON THE LANDSCAPE PLAN.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-08-2016 Cont ID  
Sent By rcaranci Date 08-08-2016 Time 16:00 Rev Time 0.00
Received By rcaranci Date 08-08-2016 Time 16:00 Sent To  
Notes
2016-08-08 16:01:38FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: VILLAGE COMMONS OUTDOOR SEATING Z16070016
 AUGUST 8, 2016
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. PLEASE REVISE THE LANDSCAPE AND ENGINEERING PLANS TO
 AVOID CONFLICTS BETWEEN LANDSCAPING AND WATER, SEWER,
 DRAINAGE, LIGHTING AND FPL EQUIPMENT. PLEASE SHOW
 LOCATIONS OF ALL UTILITIES AND EASEMENTS ON THE
 LANDSCAPE PLAN.
  
 2. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 3. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH
 AS A/C COMPRESSORS, ETC., AND PROVIDE SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT AND UTILITIES.
  
 4. PLEASE PROVIDE A TREE DISPOSITION AND MITIGATION
 CHART TO SHOW COMPLIANCE WITH SECTION 94-448 FOR THE
 FOUR EXISTING ROYAL PALMS THAT WILL BE AFFECTED.
  
 5. PLEASE INDICATE EXISTING LANDSCAPING THAT WILL STAY
 IN PLACE ON THE LANDSCAPE PLAN.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 08-09-2016 Cont ID  
Sent By lle Date 08-09-2016 Time 15:27 Rev Time 0.00
Received By lle Date   Time   Sent To  
Notes
2016-08-09 15:30:01NO UTILITY IMPACTS.

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 08-09-2016 Cont ID  
Sent By tward Date 08-09-2016 Time 15:11 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2016-08-09 15:14:351. INDICATE IF THERE ARE ANY UTILITIES IN THE PROJECT
 AREA.
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 08-08-2016 Cont ID  
Sent By vnoel Date 08-08-2016 Time 07:57 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2016-08-08 07:57:39NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 09-22-2016 Cont ID  
Sent By eschneid Date 09-22-2016 Time 15:05 Rev Time 3.00
Received By eschneid Date 09-22-2016 Time 11:03 Sent To  
Notes
2016-09-22 15:01:19CASE NO. PB812N - RESUBMITAL 8/26/16
 VILLAGE COMMONS OUTDOOR SEATING MAJOR AMENDMENT
 831 VILLAGE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 SEPTEMBER 30, 2016, TO BE ELIGIBLE FOR THE NOVEMBER 15,
 2016 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE COMMENTS BEING ISSUED (BY NOVEMBER
 22, 2016), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) REPEAT COMMENT: PROVIDE A COPY OF THE PALM BEACH
 COUNTY TRAFFIC APPROVAL LETTER.
  
 2) REPEAT COMMENT: PROVIDE COPIES OF THE FPL, COMCAST,
 AND CITY SERVICE LETTERS.
  
 3) REPEAT COMMENT: THE PROPOSED SITE PLAN HAS REMOVED
 SOME OF THE ADA CROSS WALKS ACROSS THE DRIVE AISLES
 THAT ARE ON THE CURRENT APPROVED PLAN AND EXIST ON THE
 SITE. SHOW ALL CROSS-WALKS FOR THE ENTIRE SITE (STAFF
 COUNTS SIX MISSING WHEN COMPARED TO THE EXISTING
 CONDITIONS). PLEASE REMEMBER THAT THIS WILL BE THE SITE
 PLAN OF RECORD ONCE APPROVED BY THE CITY COMMISSION.
 STAFF HAS SENT THE SITE PLANNER A LINK TO THE PALM
 BEACH COUNTY PICTOMETRY WHICH SHOWS THE SITE WITH ALL
 THE CROSSWALKS.
  
 4) REVISED COMMENT: PLEASE REVIEW THE BICYCLE PARKING
 PROVIDED. THE SUBMITTED SITE PLAN ONLY SHOWS 42 PARKING
 SPACES PROVIDED, NOT 44 AS STATED ON THE DATA CHART.
 STAFF REVIEWED APPROVAL WITH THE PUBLIX EXPANSION AND
 THERE ARE 48 BICYCLE PARKING SPACES PROVIDED. STAFF HAS
 SENT THE SITE PLANNER A COPY OF THE APPROVED BUILDING
 PERMIT (16010722) SHOWING THE LOCATIONS OF THE 24
 BICYCLE RACKS (48 BICYCLE PARKING SPACES). THE MAJOR
 AMENDMENT SITE PLAN AND DATA TABLE SHALL BE AMENDED TO
 REFLECT THE ACCURATE NUMBER AND LOCATIONS OF THE
 BICYCLE PARKING.
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-05-2016 Cont ID  
Sent By eschneid Date 08-05-2016 Time 17:17 Rev Time 2.00
Received By eschneid Date 08-05-2016 Time 17:17 Sent To  
Notes
2016-08-05 17:17:29CASE NO. PB812N
 VILLAGE COMMONS OUTDOOR SEATING MAJOR AMENDMENT
 831 VILLAGE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 AUGUST 26, 2016, TO BE ELIGIBLE FOR THE OCTOBER 18,
 2016 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY OCTOBER 10,
 2016), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) PROVIDE A COPY OF THE PALM BEACH COUNTY TRAFFIC
 APPROVAL LETTER.
  
 2) PROVIDE COPIES OF THE PUBLIC UTILITY AND CITY
 SERVICE LETTERS.
  
 3) HOW IS ADA ACCESS BEING PROVIDED TO THE NEW RAISED
 OUTDOOR SEATING DECKS?
  
 4) PLEASE PROVIDE DETAILS FOR THE HEIGHT OF THE SEATING
 AREA WALLS AND THE MATERIALS OF WHICH THEY WILL BE
 CONSTRUCTED. SOME OF THE DRAWINGS INCLUDE SOLID ROOFS,
 SOME ARE OF TRELLIS COVERINGS AND SOME HAVE NO COVER.
 WHAT IS THE ULTIMATE PLAN FOR COVER? THIS SHALL BE LAID
 OUT IN THE CPD DESIGN GUIDELINES, EVEN IF IT HAS
 MULTIPLE OPTIONS.
  
 5) THE PICTURES PROVIDED WITH THE APPLICATION SHOW TWO
 LARGE ROYAL PALMS WITHIN THE LIMITS OF WORK. PLEASE
 REVIEW THE POSSIBILITY TO RELOCATE THESE PALMS
 ELSEWHERE ON SITE. THERE ARE SOME TERMINAL ISLANDS IN
 THE NORTH PORTION OF THE PLAZA THAT DO NOT HAVE TREES.
  
 6) THE PROPOSED SITE PLAN HAS REMOVED SOME OF THE ADA
 CROSS WALKS ACROSS THE DRIVE AISLES THAT ARE ON THE
 CURRENT APPROVED PLAN AND EXIST ON THE SITE.
  
 7) SITE DATA TABLE ITEMS
 A. THE NEW OUTDOOR RESTAURANT SEATING SHALL BE ADDED
 ADJACENT TO THE LINE ITEM FOR BUILDING 6 UNDER TOTAL
 GROSS FLOOR AREA.
 B. WHY DOES BUILDING 2 SHOW ONLY 762 SF OF OUTDOOR
 SEATING WHEN THERE IS 1,076 SF SHOWN ON THE PLAN?
 C. PLEASE REVIEW THE BICYCLE PARKING PROVIDED. ALEX
 HANSEN, CITY COMPREHENSIVE PLANNER, BELIEVES THAT
 VILLAGE COMMONS HAS INSTALLED ADDITIONAL BICYCLE
 PARKING. PLEASE NOTE THAT THE ADDITIONAL OUTDOOR
 SEATING SQUARE FOOTAGE REQUIRES AN ADDITIONAL TWO
 BICYCLE PARKING SPACES UNLESS THE ENTIRE PLAZA HAS AT
 LEAST 51 BICYCLE PARKING SPACES (OVERALL REQUIRED
 1,029/20).
 D. HOW DID THE BUILDING LOT COVERAGE (AND USES) REDUCE
 WITH THE ADDITIONAL OUTDOOR SEATING AREA? NOTE: THE
 GROSS FLOOR AREA VALUE DOESN?T MATCH THE BUILDING LOT
 COVERAGE VALUE.
  