Plan Review Details - Project Z16060060
Plan Review Stops For Project Z16060060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 07-13-2016 Cont ID  
Sent By rbrown Date 07-13-2016 Time 15:37 Rev Time 0.00
Received By rbrown Date 07-13-2016 Time 15:37 Sent To  
Notes
2016-07-13 15:37:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBLE PARKING SPACE DISTRIBUTION. SHEET A-G,
 GARAGE PLAN, SHOWS ONLY ONE ACCESSIBLE PARKING SPACE
 ADJACENT TO THE ELEVATORS SERVING THE SOUTH RESIDENTIAL
 BUILDING, AND IT SHOW NO ACCESSIBLE SPACES NEAR THE
 ELEVATORS SERVING THE RESIDENTIAL UNITS AT THE EAST END
 OF THE MAIN BUILDING. PER SECTION 208.3 OF FLORIDA
 ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES ARE TO BE
 LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH
 BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 3. VAN ACCESSIBLE PARKING SPACES. NONE OF THE PROPOSED
 ACCESSIBLE PARKING SPACES ARE NOTED AS VAN ACCESSIBLE.
 PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE
 IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A
 PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. CONSTRUCTION TYPE. WHEN SUBMITTED FOR BUILDING
 PERMIT, THE PLANS SHALL SHOW THAT THE TYPE OF
 CONSTRUCTION FOR THE BUILDINGS WILL BE IN ACCORDANCE
 WITH THE HEIGHT, AREA AND OCCUPANCY LIMITATIONS IN
 CHAPTER 5 OF THE FLORIDA BUILDING CODE
  
 5. HORIZONTAL SEPARATION. WHEN SUBMITTED FOR BUILDING
 PERMIT, COMPLIANCE WITH ALL BUILDING SEPARATION,
 PERCENTAGE OF OPENINGS AND OPENING PROTECTIVE
 REQUIREMENTS OF CHAPTERS 6 AND 7 OF THE FLORIDA
 BUILDING CODE SHALL BE VERIFIED.
  
 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. BUILDING ADDRESSES. EACH SEPARATE BUILDING SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 10. THE PROPERTY LINE THAT SEPARATES THE PROPOSED EL
 FLAMINGO PROJECT FROM THE SINGLE FAMILY RESIDENCE LOT
 TO THE EAST SHALL EITHER BE MOVED, SO THAT THE EL
 FLAMINGO PARKING GARAGE ACCESS RAMP DOE NOT CROSS THE
 PROPERTY LINE, OR A UNITY OF TITLE OTHER LEGAL
 INSTRUMENT SHALL BE PROVIDED TO DEMONSTRATE CONTROL
 OVER FUTURE DEVELOPMENT AND USE OF THE SINGLE FAMILY
 RESIDENCE LOT.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By llouie Date   Time   Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-07-13 12:07:52PLAN REVIEW STARTED BY ANOTHER REVIEWER IN ERROR UNDER
 THE WRONG DISCIPLINE. SEE REVIEW # 2 FOR BUILDING
 DIVISION COMMENTS.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 07-12-2016 Cont ID  
Sent By pleduc Date 07-12-2016 Time   Rev Time 0.00
Received By pleduc Date 07-12-2016 Time 15:30 Sent To  
Notes
2016-07-12 15:33:50THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 BOTH BUILDINGS:
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 WHAT TYPE OF OCCUPANCY WILL THIS PROPOSED PROJECT BE,
 MIXED USE, SEPARATED, NON-SPEPARATED? PLEASE PROVIDE
 DETAILS.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
  
  
 EL FLAMINGO:
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 HIGH RISES SHALL HAVE TWO SEPARATE SOURCES OF WATER
 SUPPLY.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION.
  
 THE APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION
 18.4. PER NFPA 14 SECTION 7.12.2, HIGH-RISE BUILDINGS
 SHALL HAVE AT LEAST TWO REMOTELY LOCATED FIRE
 DEPARTMENT CONNECTIONS FOR EACH ZONE.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 8. A CLASS "A" NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 THE PROPOSED EXIT STAIRWAY SEPARATION OF THE NORTH-EAST
 APARTMENTS MAY NOT MEET THE MINIMUM SEPARATION
 REQUIREMENT; NO DIMENSIONS ARE PROVIDED.
  
 THE PROPOSED 5TH FLOOR POOL DECK EXITS MAY NOT MEET THE
 OCCUPANCY LOAD EXIT REQUIREMENT; NO DIMENSIONS OR
 OCCUPANCY LOADS PROVIDED AND/OR DOOR SWING NOT OPENING
 IN THE PATH OF TRAVEL.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. COMMAND ROOM
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 13. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM
 FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE
 RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
  
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
  
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
  
  
  
 EL CORDOVA:
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 8. A CLASS "A" NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 THE PROPOSED POOL DECK EXITS MAY NOT MEET THE OCCUPANCY
 LOAD EXIT REQUIREMENT; NO DIMENSIONS OR OCCUPANCY LOADS
 PROVIDED AND/OR DOOR SWING NOT OPENING IN THE PATH OF
 TRAVEL.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC'S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM
 FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE
 RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 13. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 07-12-2016 Cont ID  
Sent By rcaranci Date 07-12-2016 Time 14:07 Rev Time 0.00
Received By rcaranci Date 07-12-2016 Time 14:07 Sent To  
Notes
2016-07-12 14:08:07FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2000 S DIXIE CAREFREE Z16060060
 JULY 12, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. TREE INVENTORY ON SHEET TS-1 DOES NOT MATCH THE TREE
 SURVEY PROVIDED. PLEASE ADDRESS THE FOLLOWING:
 ? UNKNOWN TREES NEED TO BE IDENTIFIED ON ALL SHEETS
 ? TREES ON PARCEL 3 NEED TO BE INCLUDED ON THE SURVEY
 AND INVENTORY
 ? TREES 65, 66, AND 67 ARE NOT LOCATED ON THE SUBJECT
 PROPERTY, AND ARE NOT SHOWN ON THE SURVEY
 ? TREES LOCATED ON THE SUBJECT PROPERTY NEED TO BE
 SEPARATED FROM THE TREES LOCATED OFF PROPERTY IN THE
 RIGHT OF WAYS IN THE MITIGATION CHART. REPLACEMENT
 CANOPY SHOULD ALSO BE SEPARATED.
  
 2. PLEASE PROVIDE A LANDSCAPE PLAN FOR LOT 3 MEETING
 THE MINIMUM REQUIREMENTS FOR RESIDENTIAL LANDSCAPING
 PER SECTION 94-442(B)(2)A.
  
 3. PLEASE PROVIDE AN OPEN SPACE DIAGRAM TO DEMONSTRATE
 THE AREAS PROVIDED AS OPEN SPACE AND LANDSCAPE AREAS ON
 SITE WITHIN THE PROPERTY LINES TO PROVIDE REFERENCE FOR
 THE WAIVER REQUESTS.
  
 4. PLEASE PROVIDE MEASUREMENTS AND CALCULATIONS FOR THE
 BUFFER TREES REQUIRED FOR ALL BUFFER LENGTHS PER
 SECTION 94-443 B. AND INDICATE HOW MANY WILL BE
 ELIMINATED THROUGH THE WAIVER REQUESTS.
  
 5. PLEASE CALCULATE THE SHADE TREES FLOWERING TREES AND
 SHRUBS REQUIRED USING 40 PERCENT OPEN SPACE AND SHOW
 WHAT WILL BE PROVIDED WITH THE WAIVER REQUEST.
  
 6. PLEASE PROVIDE THE DROUGHT TOLERANCE LEVEL FOR EACH
 PLANT SPECIES ON THE PLANT LIST CHARTS TO VERIFY
 PERCENTAGES CLAIMED WITH THE FLORIDA FRIENDLY LANDSCAPE
 REQUIREMENTS OF SECTION 94-442 (G).
  
 7. PLEASE SEPARATE MATERIAL IN THE PLANT LIST FOR THE
 ONSITE AND OFFSITE LANDSCAPING, AND FOR THE ROOFTOP
 POOL DECK.
  
  
  
 8. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 9. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 10. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED
 EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC.,
 AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT
 AND UTILITIES.
  
 11. PLEASE INDICATE THE WIDTH OF ALL LANDSCAPE BUFFERS
 PROVIDED ON THE LANDSCAPE PLAN.
  
 12. PLEASE INDICATE THE WIDTH OF THE SIDEWALK ALONG S
 DIXIE. IF WIDE ENOUGH, PLEASE ADD STREET TREES WITH
 TREE GRATES. STREET TREES LOCATED IN A SIDEWALK SHALL
 HAVE STRUCTURAL SOIL EXTENDING 5 FEET IN ALL DIRECTIONS
 UP TO THE CURB. INDICATE STRUCTURAL SOIL LOCATIONS AND
 PROVIDE A TYPICAL STRUCTURAL SOIL DETAIL ON THE
 LANDSCAPE DETAIL PAGE.
  
 13. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 14. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 15. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED
 EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC.,
 AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT
 AND UTILITIES.
  
 16. PLEASE PROVIDE CALCULATIONS FOR LANDSCAPING AROUND
 EACH STRUCTURE TO MEET THE 30% REQUIREMENT FOR TREES,
 SHRUBS OR HEDGES PER SECTION 94-443 (E)(1).
  
 17. THE ELEVATIONS SHOW GREEN PLANTS ON BALCONY
 RAILINGS ON THE UPPER FLOORS, AND SOME WALL AREAS
 COVERED WITH PLANTS OR VINES. PLEASE PROVIDE MORE
 DETAIL.
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status F Date 07-13-2016 Cont ID  
Sent By ssamuels Date 07-13-2016 Time 12:37 Rev Time 0.00
Received By ssamuels Date 07-13-2016 Time 12:37 Sent To  
Notes
2016-07-13 12:41:21SEAN SAMUELS CPP
 PARKING FACILITY SUPERVISOR
 561-822-1507
 [email protected]
  
 PLEASE PROVIDE DETAIL SPECIFICATION OF ADA AND REGULAR
 PARKING SPACES.
 HANDICAP SYMBOL AND SIGNS PER THE CITY ZONING CODE.

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lle Date 07-12-2016 Time 18:33 Sent To  
Notes
2016-07-12 18:31:41THIS IS A PRELIMINARY REVIEW OF THE CONCEPTUAL PAVING,
 DRAINANGE, WATER AND WASTEWATER PLAN. ADDITIONAL
 COMMENTS ARE EXPECTED WHEN FULL DRAWINGS ARE SUBMITTED
 FOR ENGINEERING DEVELOPMENT APPROVAL APPLICATION:
  
 1. PLEASE PROVIDE THE ESTIMATED WATER AND SEWER DEMANDS
 (AVERAGE AND PEAK) AND FIRE FLOW DEMAND;
 2. CITY'S RECORD INFORMATION INDICATES THAT THE
 EXISTING WM ON BARCELONA ROAD IS 20-INCH TRANSITE/AC AT
 THE PROPOSED FIRE SERVICE LINE CONNECTION. CONSIDER
 EXTENDING A 12-INCH WM FROM S. DIXIE HWY FROM A 12-INCH
 WM STUB OUT TO THE PROPOSED CONNECTION. PLEASE PROVIDE
 PROFILE OF THE PROPOSED WM WITHIN THE ROADWAY R/W FROM
 THE POINT OF CONNECTION TO THE POINT OF SERVICE;
 3. CITY'S RECORD INFORMATION INDICATES THAT THERE IS AN
 EXISTING 3-INCH TRANSITE/AC WM RUNNING EAST-WEST FROM
 S. DIXIE TO OLIVE AVENUE BETWEEN BARCELONA ROAD AND
 CORDOVA ROAD. THIS WM WILL BE UNDER THE PROPOSED
 BUILDING (RETAIL/RESIDENTIAL/GARAGE) BETWEEN BARCELONA
 AND CORDOVA. PLEASE ADDRESS.
 4. THE CITY WILL VERIFY THAT THE EXISTING 8-INCH
 SANITARY SEWER IN THE EAST-WEST CORRIDOR BETWEEN
 FLAMINGO DRIVE AND BARCELONA ROAD ON THE DEVELOPMENT
 SITE IS PRIVATE.
 5. EXISTING UTILITY SERVICE LINES (WATER AND SEWER), IF
 NOT USED BY THE SITE REDEVELOPMENT, ARE TO BE CUT AND
 CAPPED AT THE MAIN AND REMOVED IF LARGER THAN 2 INCHES
 IN DIAMETER. PLEASE ADD THE APPROPRIATE NOTES ON THE
 WATER & WASTEWATER PLAN;
 6 PLEASE PROVIDE CCTV RECORD (VIDEO AND TV LOG) OF THE
 EXISTING SAN SEWER MAIN ON S. DIXIE HWY TO DETERMINE
 THE LOCATION OF EXISTING SANITARY SEWER LATERALS;
 7. PLEASE PROVIDE THE FIRE HYDRANT FLOW TEST DATA FROM
 EXISTING FIRE HYDRANT USED FOR DESIGN;
 8. PLEASE SHOW EXISTING WATER AND SEWER SYSTEM
 INCLUDING PIPE SIZE, MATERIAL, CONNECTIVITY, AND
 VALVING. CONTACT ENGINEERING DEPARTMENT @ 561-494-1040
 FOR SYSTEM INFORMATION. ALL INFORMATION IS TO BE FIELD
 VERIFIED BY THE DESIGN ENGINEER.
 9. PLEASE INCLUDE APPLICABLE CITY OF WEST PALM BEACH
 STANDARD WATER AND SEWER DETAILS TO THE DETAILS SHEET.
 CONTACT THE ENGINEERING SERVICES DEPARTMENT (561)
 494-1040 FOR THE LATEST REVISED DETAILS.
  
 LAURA LE, P.E.
 PUBLIC UTILITIES ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 561-494-1040
 [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 07-12-2016 Cont ID  
Sent By tward Date 07-12-2016 Time 18:41 Rev Time 0.00
Received By tward Date 07-12-2016 Time 18:42 Sent To  
Notes
2016-07-13 12:52:13THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS ARE MUST BE ADDRESSED PRIOR TO
 SITE PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. PROPOSED STORMWATER OVERFLOW CONTROL STRUCTURES ARE
 TO BE LOCATED ONSITE AND NOT IN THE RIGHT-OF-WAY.
  
 3. IT APPEARS THE STORMWATER MANAGEMENT (SWM) SYSTEM
 CONSISTS OF BUBBLE-UP INLETS OUT INTO THE ROAD. THE SWM
 SYSTEM SHOULD CONNECT INTO THE NEAREST DRAINAGE SYSTEM
 (CORDOVA ROAD AND/OR S. DIXIE HIGHWAY.
  
 4. S. DIXIE HIGHWAY IS MAINTAINED BY THE FLORIDA
 DEPARTMENT OF TRANSPORTATION. PERMITS WILL BE NEEDED
 FROM FDOT.
  
 5. THE GATEWAY STRUCTURE OVER BARCELONA ROAD WILL NEED
 APPROVAL FROM THE TRAFFIC ENGINEER.
  
 6. APPLICATION(S) WILL NEED TO BE SUBMITTED TO THE
 TRAFFIC CALMING COMMITTEE FOR THE PROPOSED SPEED TABLES
 ON THE CITY STREETS.
  
 7. WHAT IS THE SEASONAL HIGH WATER TABLE ELEVATION FOR
 THE SITE AND HOW WILL GROUNDWATER TO BE CONTROLLED
 AROUND THE UNDERGROUND PARKING STRUCTURE.
  
 8. DRAINAGE CALCULATIONS SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER WILL NEED TO BE
 SUBMITTED DEMONSTRATING WATER QUALITY TREATMENT AND
 PEAK DISCHARGE ATTENUATION. RUNOFF VELOCITIES AND
 VOLUMES SHOULD NOT EXCEED EXISTING CONDITIONS.
  
 9. INDICATE MILLING AND RESURFACING LIMITS AROUND
 TRENCH CUTS ON CITY STREETS.
  
 10. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS
 OF ALL EXISTING AND PROPOSED UTILITIES INCLUDING BUT
 NOT LIMITED TO WATER METERS, VALVES, CLEAN-OUTS, LIGHT
 POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE
 PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR
 POTABLE WATER LINES.
  
 11. HOW WILL THE UNDERGROUND PARKING GARAGES DRAIN? HOW
 WILL WATER QUALITY TREATMENT BE OBTAINED?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. DETAILS SHEETS WILL NEED TO UTILIZE STANDARD CITY OF
 WEST PALM BEACH DETAILS, WHICH MAY BE DOWNLOADED AT HTT
 P://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,
 -PERMITS-APPLICATIONS
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2016-07-11 13:32:421. REPLAT WILL BE REQUIRED.
 2. UNDERGROUND PARKING WILL NEED DISCUSSION. NEED A
 BETTER UNDERSTANDING OF LIMITS AND DEPTH.
 3. A FDOT MMOA WILL NEED TO BE PROVIDED FOR
 IMPROVEMENTS ALONG DIXIE HWY. A DEVELOPER'S AGREEMENT
 FOR THE MMOA AND SIDE STREET IMPROVEMENTS WILL BE
 REQUIRED.
 4. 309 BARCELONA RD NEEDS TO BE ADDED TO PROJECT
 LIMITS.
 5. HOW IS GARBAGE COLLECTION TO BE HANDLED?
 6. SITE CIVIL PERMIT WILL BE REQUIRED THROUGH
 ENGINEERING SERVICES.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 07-13-2016 Time 09:02 Sent To  
Notes
2016-07-13 09:03:17PROVIDE A TRAFFIC STUDY TO SHOW EXISTING CONDITIONS AND
 PROPOSED LANE ELIMINATION PROJECT. PROPOSED LANE
 ELIMINATION IS A 3 LANE SECTION.
  
 COMMENTS FROM UYEN DANG

Review Stop Z ZONING
Rev No 1 Status F Date 07-12-2016 Cont ID  
Sent By   Date 07-12-2016 Time   Rev Time 0.00
Received By llouie Date 07-12-2016 Time 16:55 Sent To  
Notes
2016-07-12 16:59:34GENERAL COMMENTS:
  
 1.) THE PROPOSED FLOOR AREA RATIO (FAR) OF 2.43 AND
 DENSITY OF 53.77 DWELLING UNITS/GROSS ACRE EXCEEDS THE
 MAXIMUM ALLOWABLE FAR OF 1.5 AND DENSITY OF 32.27
 DWELLING UNIT/GROSS ACRE ALLOWED BY COMPREHENSIVE PLAN,
 FUTURE LAND USE ELEMENT (FLUE) POLICY 1.1.3. [ZLDR
 S.94-207(A)(1)B., S.94-207(D)(5), S.94-243, TABLE
 VIII-3]
  
 2.) THE SCALE OF THE PROPOSED PROJECT IS SIGNIFICANTLY
 OUT OF PROPORTION WITH THE ONE AND TWO STORY
 SINGLE-FAMILY RESIDENTIAL DWELLINGS IMMEDIATELY EAST OF
 THE SUBJECT PROPERTY (EL CID HISTORIC DISTRICT). STAFF
 ADVISES THE APPLICANT TO SCALE THE PROJECT BACK (I.E.
 MASSING, DENSITY, FAR, HEIGHT) IN ORDER TO BE MORE
 COMPATIBLE WITH THE SCALE OF THE ADJACENT RESIDENTIAL
 NEIGHBORHOOD.
  
 3.) THE APPLICANT IS SEEKING A TOTAL OF FOURTEEN (14)
 WAIVERS FOR THE PROJECT, WHICH SEEMS EXCESSIVE. THE
 APPLICANT NEEDS TO PROVIDE MORE INFORMATION TO JUSTIFY
 THE NEED FOR EACH WAIVER (I.E. ARE THERE SITE/DESIGN
 CONSTRAINTS? WHAT ARE THE BENEFITS FOR WAIVING EACH
 REQUIREMENT AND HOW WILL IT BENEFIT THE COMMUNITY/CITY?
 WHAT ARE THE IMPACTS AND HOW ARE THE IMPACTS BEING
 MITIGATED IN THE SITE DESIGN? HAVE OTHER ALTERNATIVES
 BEEN EXPLORED? ). THE ADDITIONAL INFORMATION FOR EACH
 WAIVER IS NEEDED IN ORDER TO DETERMINE THE VALIDITY OF
 EACH WAIVER REQUEST.
  
 4.) A TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY TRAFFIC DIVISION VERIFYING
 THAT THE PROJECT MEETS THE TPS STANDARDS OF THE COUNTY
 IS REQUIRED.
  
 5.) A LETTER FROM THE SCHOOL DISTRICT OF PALM BEACH
 COUNTY CONFIRMING THAT THE PROJECT MEETS CONCURRENCY
 FOR SCHOOLS IS REQUIRED.
  
 6.) PURSUANT TO ZLDR S.94-207(B)(1), THE PLANNED
 DEVELOPMENT SHALL COMPLY WITH SUBSECTION 94-35(C) (SITE
 DESIGN QUALITATIVE DEVELOPMENT STANDARDS). PLEASE
 PROVIDE WRITTEN STATEMENTS TO HOW EACH STANDARD OF ZLDR
 S.94-35(C) IS ADDRESSED FOR THE PROJECT.
  
  
 SITE PLAN COMMENTS:
  
 1.) PURSUANT TO ZLDR S.94-207(D)(8), ANY SOURCE OF
 ILLUMINATION LOCATED WITHIN A COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL NOT EXCEED ONE (1) FOOT CANDLE
 AT OR BEYOND THE BOUNDARIES OF SUCH DEVELOPMENT AND IN
 EXCESS OF 0.5 FOOT CANDLES WHEN MEASURED IN A
 RESIDENTIAL ZONING DISTRICT. THE APPLICANT MUST
 DEMONSTRATE HOW THIS REQUIREMENT WILL BE MET.
  
 2.) LOADING INGRESS AND EGRESS CONFIGURATIONS WHICH
 REQUIRE BACKING DIRECTLY ONTO A STREET FROM A LOADING
 SPACE IS PROHIBITED. THE PROPOSED LOADING AREAS DO NOT
 SEEM ADEQUATE FOR LARGER TRUCKS TO MANEUVER ON SITE.
 [ZLDR S.94-485(J)(1)]
  
 3.) DIMENSIONS AND DETAILS TO BE PROVIDED IN THE PLANS
 (I.E. PARKING STALL DETAIL, STALL/AISLE WIDTH
 DIMENSIONS, ETC.)
  
  
 HISTORIC PRESERVATION COMMENTS:
  
 1.) HPB CASE NO. 16-58 (Z16060056): CERTIFICATE OF
 APPROPRIATENESS (COA) FOR THE DEMOLITION OF ACCESSORY
 STRUCTURE AND PLACEMENT OF GARAGE RAMP ON THE WEST SIDE
 OF THE LOT:
  
 - PROVIDE ACCURATE SCOPE OF WORK DESCRIPTION.
 CURRENTLY, THE APPLICATION IS REQUESTING OFF-SITE
 PARKING LOT.
  
 - PROVIDE PICTURES OF THE GARAGE/SITE IN QUESTION.
  
 - PROVIDE STRUCTURAL ENGINEERING REPORTS TO WHY THE
 GARAGE NEEDS TO BE DEMOLISHED.
  
 - REQUIREMENTS FOR DEMOLITION ARE NOT COMPLETE. SEE
 REQUIREMENT STANDARDS IN THE COA APPLICATION (LINK: HTT
 P://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/HISTORIC-P
 RESERVATION/APPLICATIONS?PAGE=2)
  
 - SHOW ELEVATIONS OF NEW SITE WITHOUT GARAGE.
  
 - DEMONSTRATE WHY THE GARAGE CANNOT REMAIN IN PLACE.
 FROM THE SUBMITTED PLANS, IT APPEARS TO HAVE ROOM.
  
 2.) HPB CASE NO. 16-57 (Z16060057): CLASS B SPECIAL USE
 PERMIT TO ALLOW AN OFF-SITE ACCESSORY PARKING LOT:
 WAIVER #1 ? TO ALLOW RELIEF FROM THE 5 FT. WIDE BUFFER
 ALONG ALL PROPERTY LINES; WAIVER #2 ? TO ALLOW RELIEF
 FROM THE OPAQUE WALL ALONG THE SIDE PROPERTY LINES:
  
 - PROVIDE ACCURATE SCOPE OF WORK DESCRIPTION. PAGE 2 OF
 THE JUSTIFICATION STATEMENT INCLUDES AN OFF-SITE
 PARKING LOT AS WELL AS SUBTERRANEAN PARKING. SURFACE
 PARKING WILL NOT BE SUPPORTED BY STAFF.
  
 - WAIVER #1 DOES NOT HAVE ENOUGH JUSTIFICATION, NOR
 DOES THE LANDSCAPE PLAN REFLECT A SINGLE-FAMILY
 RESIDENCE STYLE OF LANDSCAPING AS INDICATED IN THE
 NARRATIVE. ROOM EXISTS FOR ADDITIONAL BUFFERING AND A
 MORE RESIDENTIAL PLAN.
  
 - WAIVER #2 DOES NOT HAVE ENOUGH JUSTIFICATION TO
 ELIMINATE THE 5 FT. HIGH WALL AT THE REAR (NORTH)
 PROPERTY LINE, EAST OR WEST PROPERTY LINE FROM RAMP
 OPENING TO THE FRONT PROPERTY LINE.
  
 * ONCE THESE ITEMS HAVE BEEN ADDRESSED AND ITEMS
 SUBMITTED, CASES WILL BE SCHEDULED FOR A HEARING.
  
 * CONTACT FRIEDERIKE MITTNER, HISTORIC PRESERVATION
 PLANNER, @ (561) 822-1457 IF THERE ARE QUESTIONS.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TEN
 (10) COPIES, ONE (1) REDUCED COPY (8.5 BY 11), AND AN
 ELECTRONIC COPY IN .PNG FORMAT OF ALL PLANS. PLEASE
 NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% ($600) OF THE ORIGINAL APPLICATION FEE.
  
 *CONTACT LINDA LOUIE @ (561) 855-1458 IF THERE ARE
 QUESTIONS.
  