Plan Review Details - Project Z16020012
Plan Review Stops For Project Z16020012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-08-2016 Cont ID  
Sent By rbrown Date 03-08-2016 Time 01:26 Rev Time 0.00
Received By rbrown Date 03-08-2016 Time 01:26 Sent To  
Notes
2016-03-08 01:29:22DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 3. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED. THE
 EQUIVALENT REQUIREMENTS FOR ONE AND TWO FAMILY
 DWELLINGS, AND TOWNHOUSES ARE IN SECTION R302 OF
 FLORIDA BUILDING CODE (RESIDENTIAL).
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 5. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 15:04 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 15:03 Sent To  
Notes
2016-03-08 15:04:10CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. PLEASE SUBMIT A COPY OF THE SURVEY.
  
 2. PLEASE REVISE THE COVER SHEET TO REFLECT THE CORRECT
 DEPARTMENT. (DEPARTMENT OF ENGINEERING SERVICES DOES
 NOT EXIST.)
  
 3. PLEASE SPECIFY THE VERTICAL DATUM ON THE CIVIL
 PLANS.
  
 4. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT HTTP://WWW.CO.PALM-BEACH.FL.US/NEWSROOM/08
 14/08-26-14-FLOOD_MAPS.HTM. PLEASE REVIEW THE MAPS AND
 VERIFY THAT THE NEW MAPS WILL NOT IMPACT THE PROPOSED
 PROJECT.
  
 5. DETAILS SHEETS WILL NEED TO UTILIZE STANDARD CITY OF
 WEST PALM BEACH DETAILS, WHICH MAY BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 6. WHAT IS BEING DISCHARGED FROM THE SUMP DRAIN INTO
 THE DRAINAGE SYSTEM?
  
 7. PLEASE REVIEW THE PROPOSED CATCH BASIN INLET FOR
 CONSTRUCTABILITY AND SEPARATION REQUIREMENTS. THE
 PROPOSED CATCH BASIN INLET IS LESS THAN 3 FEET FROM 60?
 PIPE LINE AND LESS THAN 5 FEET FROM 30? RAW WATER LINE.
 PLEASE ALSO REVIEW THE LOCATION OF THE PROPOSED
 EXFILTRATION TRENCH, WHICH IS LESS THAN 5 FEET FROM 30?
 RAW WATER LINE.
  
 8. HOW MUCH COVER WILL REMAIN OVER THE EXISTING
 DRAINAGE SYSTEM IN THE DRY RETENTION POND?
  
 9. DRY RETENTION POND APPEARS TO HAVE 1:1 SIDE SLOPES.
 HOW WILL THIS BE MAINTAINED?
  
 10. PLEASE REVISE THE PLANS TO COMPLY WITH CODE SECTION
 94-485 FOR PARKING LOT STRIPING (DOUBLE LINES CONNECTED
 AT END).
  
 11. ARE PAVERS PROPOSED AS PART OF THE PROJECT?
 STRIPING DETAIL CALLS OUT MATERIAL FOR PAVER SYSTEMS.
  
 12. NO DIRECT STORMWATER RUNOFF FROM ROADWAY AND
 PARKING LOTS SHOULD ENTER INTO EAST LAKE. RUNOFF SHOULD
 BE COLLECTED IN INLETS, SWALES OR DRY RETENTION AREAS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 2. PLEASE PROVIDE A COPY OF THE MODIFICATION OF SFWMD
 PERMIT.
  
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 561-494-1120
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-24-2016 Cont ID  
Sent By pleduc Date 02-24-2016 Time   Rev Time 0.00
Received By pleduc Date 02-24-2016 Time 12:36 Sent To  
Notes
2016-02-24 12:42:58THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 11. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 06-07-2016 Cont ID  
Sent By rcaranci Date 06-07-2016 Time 12:39 Rev Time 0.00
Received By rcaranci Date 06-07-2016 Time 12:39 Sent To  
Notes
2016-06-07 12:40:58FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: WPB WATER TREATMENT PLANT Z16020012
 JUNE 6, 2016
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE TWO SABAL PALMS IN THE
 TERMINAL ISLAND SOUTH OF THE ROW OF PARKING EAST OF THE
 PROPOSED BUILDING.
  
 2. SATISFIED. PER SECTION 94-448, PLEASE RELOCATE
 EXISTING HEALTHY SABAL PALMS RATHER THAN REMOVE THEM.
  
 3. SATISFIED. PLEASE PROVIDE A TREE PROTECTION DETAIL,
 AND SHOW LOCATIONS OF TREE PROTECTION TO BE MAINTAINED
 DURING CONSTRUCTION.
  
 4. SATISFIED. PLEASE PROVIDE THE DROUGHT TOLERANCE
 LEVEL FOR EACH PLANT SPECIES ON THE PLANT LIST, AND
 SHOW COMPLIANCE WITH SECTION 94-442(G) FLORIDA FRIENDLY
 LANDSCAPING REQUIREMENTS IN A CHART LABELED AS SUCH ON
 THE LANDSCAPE PLAN.
  
 ADDITIONAL COMMENTS 6/6/16:
 5. PLEASE PROVIDE LANDSCAPING ADJACENT TO THE GENERATOR
 SCREEN WALL.
  
 6. PARKING AREA SHOWN ON SITE PLAN SHEET C-2 IN AREA B
 IS NOT SHOWN ON THE LANDSCAPE PLAN. PLEASE REVISE TO
 INCLUDE THIS AREA.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-07-2016 Cont ID  
Sent By rcaranci Date 03-07-2016 Time 15:09 Rev Time 0.00
Received By rcaranci Date 03-07-2016 Time 15:09 Sent To  
Notes
2016-03-07 15:10:50FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: WPB WATER TREATMENT PLANT Z16020012
 MARCH 7, 2016
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE TWO SABAL PALMS IN THE TERMINAL
 ISLAND SOUTH OF THE ROW OF PARKING EAST OF THE PROPOSED
 BUILDING.
  
 2. PER SECTION 94-448, PLEASE RELOCATE EXISTING HEALTHY
 SABAL PALMS RATHER THAN REMOVE THEM.
  
 3. PLEASE PROVIDE A TREE PROTECTION DETAIL, AND SHOW
 LOCATIONS OF TREE PROTECTION TO BE MAINTAINED DURING
 CONSTRUCTION.
  
 4. PLEASE PROVIDE THE DROUGHT TOLERANCE LEVEL FOR EACH
 PLANT SPECIES ON THE PLANT LIST, AND SHOW COMPLIANCE
 WITH SECTION 94-442(G) FLORIDA FRIENDLY LANDSCAPING
 REQUIREMENTS IN A CHART LABELED AS SUCH ON THE
 LANDSCAPE PLAN.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 15:05 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 15:05 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 15:05 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 15:04 Sent To  
Notes
2016-03-08 15:05:04SEE COMMENTS UNDER ENG PPRC

Review Stop SURVEY SURVEYING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 15:04 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 15:04 Sent To  
Notes
2016-03-08 15:04:47SEE COMMENTS UNDER ENG PPRC

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 15:04 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 15:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 06-06-2016 Cont ID  
Sent By jroach Date 06-06-2016 Time 13:40 Rev Time 0.00
Received By jroach Date 06-06-2016 Time 13:40 Sent To  
Notes
2016-06-06 13:41:14PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2016
 PROJECT NO.: Z16020012
 CASE NO.: ISPR 16-02
 ADDRESS: 1009 BANYAN BOULEVARD
 APPLICANT/CONTACT: HEATH WINTZ
 TELEPHONE NO.: 561.222.8763
 SCOPE OF REVIEW: NEW UV BUILDING @ CITY OF WPB WATER
 TREATMENT PLANT.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. WHAT IS THE ?OWNER?S FIELD OFFICE?? IS THIS
 TEMPORARY? PLEASE PROVIDE INFORMATION REGARDING THIS.
  
 2. YOU MAY WANT TO PROVIDE MORE CLARITY IN THE PARKING
 STRIPING DETAIL (I.E. 12 INCHES BETWEEN STRIPES, COLOR,
 ETC.). I WILL EMAIL YOU A COPY OF THE CITY DETAIL THAT
 YOU CAN INCLUDE IN YOUR DRAWINGS.
  
 3. DRIVE AISLES BETWEEN PARKING SPACES NEED TO BE A
 MINIMUM OF 24 FEET, AS REQUIRED BY SECTION 94-485(N)(2)
 AND FIGURE XV-2 OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 4. THE LANDSCAPE PLAN DOES NOT MATCH THE SITE PLAN
 (SPECIFICIALLY WITH REGARD TO PARKING LAYOUT).
  
 5. SITE PLANS ARE STILL UNCLEAR BETWEEN EXTERIOR WALL
 OF THE BUILDING AND THE CONCRETE APRON ON THE NORTH
 SIDE. DELINEATE THE EXTERIOR WALLS OF THE BUILDING
 SEPARATE FROM CONCRETE APRONS, PADS, ETC.
  
 6. THE SCREEN WALL FOR THE DIESEL STORAGE TANKS IS TO
 BE LANDSCAPED IN ACCORDANCE WITH SEC. 94-444(B) OF THE
 CITY?S CODE OF ORDINANCES.
  
 7. SHEET 17A-3 MENTIONS A DECORATIVE FENCE AROUND HVAC
 EQUIPMENT, AND THE STRUCTURAL PLANS REFER TO DETAIL
 S-190, BUT I COULD NOT FIND THIS DETAIL. PLEASE
 IDENTIFY THE SHEETS IN WHICH THE FENCING IS IDENTIFIED
 IN PLAN VIEW AS WELL AS ELEVATION AND/OR DETAILED
 SECTIONS.
  
 8. TWO (2) OF THE HVAC EQUIPMENT BOXES LOCATED ON THE
 EAST SIDE OF THE BUILDING NEED TO HAVE LANDSCAPING
 INSTALLED AS SCREENING. IF FENCING IS PROPOSED INSTEAD,
 PLEASE SEE COMMENT PROVIDED ABOVE.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 03-09-2016 Cont ID  
Sent By jroach Date 03-09-2016 Time 11:50 Rev Time 0.00
Received By jroach Date 03-09-2016 Time 11:50 Sent To  
Notes
2016-03-09 11:51:05PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.09.2016
 PROJECT NO.: Z16020012
 CASE NO.: ISPR 16-02
 ADDRESS: 1009 BANYAN BOULEVARD
 APPLICANT/CONTACT: HEATH WINTZ
 TELEPHONE NO.: 561.222.8763
 SCOPE OF REVIEW: NEW UV BUILDING @ CITY OF WPB WATER
 TREATMENT PLANT.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. UTILITY LETTERS SHALL BE PROVIDED.
  
 2. THE PARKING DETAIL SHALL CONFORM TO THE MINIMUM CITY
 STANDARDS, INCLUDING DOUBLE-STRIPING.
  
 3. THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  A. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY,
 EXISTING/PROPOSED EASEMENTS, ETC.
  B. STREETS, DRIVEWAYS, INTERSECTIONS, CURB CUTS AND
 TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT
 PROPERTY.
  
 4. PLEASE VERIFY THE LOCATION OF THE ACCESSIBLE PARKING
 IS ACCEPTABLE TO ADA REQUIREMENTS. WHERE IS THE
 ACCESSIBLE ENTRANCE INTO THE BUILDING? IS THERE
 REQUIRED TO BE ONE? USERS OF THE ACCESSIBLE PARKING
 SPACE CANNOT BE DIRECTED BEHIND OTHER PARKED VEHICLES.
  
 5. DIMENSIONS SHALL BE PROVIDED FOR THE FOLLOWING:
  A. SETBACKS FROM THE PROPOSED BUILDING TO NEARBY
 PROPERTY LINES.
  B. PARKING SPACES AND DRIVE AISLES.
  
 6. IT IS MY UNDERSTANDING THAT THE SCREENING OF THE
 DIESEL STORAGE TANKS IS BEING INCLUDED IN THIS SCOPE OF
 WORK, HOWEVER, NO DETAILS HAVE BEEN PROVIDED AND SUCH
 WORK HAS NOT BEEN INDICATED ON THE PLANS.
  
 7. THE LANDSCAPE PLAN CONFLICTS WITH THE
 SITE/ARCHITECTURAL PLANS BY SHOWING LANDSCAPING IN
 FRONT OF AND ACROSS TH DOORWAY ON THE WEST SIDE OF THE
 BUILDING. ENSURE THAT ALL PLANS MATCH.
  
 8. LANDSCAPE SCREENING SHALL BE PROVIDED AROUND THE
 CONDENSING UNITS.
  
 9. THE RENDERINGS PROVIDED DO NOT MATCH THE SITE PLAN,
 SPECIFICALLY WITH REGARD TO THE EAST FA?ADE AND
 ADJACENT CURBING.
  
 10. IT APPEARS THAT THE SIZE OF THE BUILDING ON THE
 SITE PLAN DOES NOT MATCH THE FLOOR PLAN. ON THE FLOOR
 PLAN THE NORTH SIDE OF THE BUILDING APPEARS TO HAVE A
 CONCRETE PAD OUTSIDE OF THE EXTERIOR WALLS OF THE
 STRUCTURE, BUT THE SITE PLAN DEPICTS THIS AS BEING A
 PART OF THE BUILDING. PLEASE CLARIFY AND ENSURE THAT
 ALL PLANS ARE CONSISTENT.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved