Plan Review Details - Project Z16020008
Plan Review Stops For Project Z16020008
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 04-13-2016 Cont ID  
Sent By rbrown Date 04-13-2016 Time 20:54 Rev Time 0.00
Received By rbrown Date 04-13-2016 Time 20:54 Sent To  
Notes
2016-04-13 20:59:55DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE
 PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES.
  
 3. THE PARKING REQUIREMEMNTS TABLE ON SITE PLAN SHEET
 SP-1 NOW SHOWS THAT 150 PARKING SPACES ARE PROPOSED,
 AND STATES THAT 7 ACCESSIBLE SPACES ARE PROPOSED.
 HOWEVER, THE PLAN ONLY SHOWS WHERE 4 OF THE ACCESSIBLE
 PARKING SPACES ARE LOCATED. WHEN SUBMITTED FOR PERMIT,
 AT LEAST 5 ACCESSIBLE PARKING SPACES MUST BE SHOWN ON
 THE PLAN TO DEMONSTRATE THAT THE MINIMUM NUMBER OF
 ACCESSIBLE PARKING SPACES WILL BE PROVIDED IN
 ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY
 CODE.
  
 4. WHE SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 8. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By rbrown Date 03-08-2016 Time 00:52 Rev Time 0.00
Received By rbrown Date 03-08-2016 Time 00:52 Sent To  
Notes
2016-03-08 01:03:28DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE
 PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES.
  
 3. SITE PLAN SHEET SP-1 SHOWS THAT 148 PARKING SPACES
 ARE PROPOSED, AND JUST 4 ACCESSIBLE PARKING SPACES ARE
 PROPOSED. 5 ACCESSIBLE PARKING SPACES ARE REQUIRES
 BECAUSE THE MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES
 PROVIDED SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF
 FLORIDA ACCESSIBILITY CODE.
  
 4. WHE SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 8. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 05-06-2016 Cont ID  
Sent By dkittred Date 05-06-2016 Time 10:54 Rev Time 0.00
Received By dkittred Date   Time   Sent To  
Notes
2016-05-06 10:55:555/5/16 D. KITTREDGE SPOKE WITH K. CRANFORD AND PROJECT
 IS OKAY TO MOVE FORWARD WITH 'PASS' STATUS.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 14:19 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 14:18 Sent To  
Notes
2016-03-08 14:19:15CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. REQUIREMENTS LISTED UNDER ORIGINAL APPROVAL STILL
 APPLY.
  
 2. POTABLE WATER SYSTEM MAY REQUIRE A MASTER METER.
  
 3. CAN PHASE 2 BE SOLD TO A SEPARATE OWNER?
  
 4. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES.
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 561-494-1120
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-24-2016 Cont ID  
Sent By pleduc Date 02-24-2016 Time   Rev Time 0.00
Received By pleduc Date 02-24-2016 Time 11:47 Sent To  
Notes
2016-02-24 11:53:53THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. PROVIDE FOR THE APPROPRIATE FIRE LANE DIMENSIONS
 AND/OR TURN-AROUND CONFIGURATIONS, INCLUDING AUTO-TURN,
 FOR SITE EMERGENCY VEHICLES ACCESS AND EGRESS.
  
 7. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 8. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 05-06-2016 Cont ID  
Sent By rcaranci Date 05-06-2016 Time 10:48 Rev Time 0.00
Received By rcaranci Date 05-06-2016 Time 10:47 Sent To  
Notes
2016-05-06 10:49:26FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: NOVUS MEDICAL Z16020008
 MAY 6, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. PLEASE PROVIDE A TREE SURVEY FOR THE
 SITE. THERE IS ONE BLACK OLIVE ON SITE THAT IS NOT
 SHOWN ON THE TREE DISPOSITION PLAN.
 PLEASE SUBMIT A TREE SURVEY.
  
 2. SATISFIED. THE PINES EXISTING ON THE SITE ARE PINUS
 CLAUSA. PLEASE VERIFY AND CORRECT THE TREE DISPOSITION
 PLAN.
  
 3. SATISFIED. PLEASE PROVIDE A TREE MITIGATION CHART
 SHOWING THE TREE CATEGORIES REMOVED AND REPLACED WITH
 THE PROPOSED PLAN.
  
 THERE ARE MANY CORRECTIONS NECESSARY ON THE TREE
 DISPOSITION PLAN. A MEETING TO REVIEW THE CORRECTIONS
 WOULD BE THE MOST EFFICIENT WAY TO COMMUNICATE THE
 CORRECTIONS NEEDED.
  
 4. SATISFIED. THERE ARE MANY HEALTHY MATURE SABAL PALMS
 ON SITE THAT CAN BE RELOCATED RATHER THAN DESTROYED.
 PLEASE INDICATE PRESERVATION OF THE SABAL PALMS ON THE
 TREE DISPOSITION PLAN.
  
 5. SATISFIED. PLEASE CORRECT THE NOTE ON THE TREE
 DISPOSITION PLAN REGARDING TREE MITIGATION. ALL TREES
 LESS THAN 35 FEET OF CANOPY SPREAD MUST BE MITIGATED
 ONE FOR ONE. THE LISTED INVASIVE EXOTIC SPECIES ARE THE
 ONLY ONES EXEMPT FROM MITIGATION.
  
 6. SATISFIED. PLEASE CORRECT THE OPEN SPACE PERCENTAGE
 ON SHEET SP-1TO REFLECT THE CORRECT OPEN SPACE AS
 DEFINED BY CODE.
  
 7. SATISFIED. THE NUMBER OF TREES, FLOWERING TREES AND
 SHRUBS REQUIRED PER SECTION 94-442 MUST BE CALCULATED
 ON 50 PERCENT OPEN SPACE REQUIRED PER SECTION 94-203.
 PLEASE REVISE THE DATA TABLE TO REFLECT THE CORRECT
 QUANTITIES.
  
 8. SATISFIED. PLEASE REVISE THE REQUIRED TREE COUNTS
 FOR THE NORTH AND SOUTH BUFFERS TO 23 EACH, AND ADD THE
 TREES TO THE LANDSCAPE PLAN.
  
 9. SATISFIED. PLEASE REVISE TO SHOW TREES AT THE
 REQUIRED SPACING ALONG THE NORTH BUFFER. THE ADJACENT
 PROPERTY OWNER CAN BE CONTACTED TO REMOVE THE
 AUSTRALIAN PINES WITHIN THEIR BUFFER.
  
 10. SATISFIED. PLEASE PROVIDE THE HEDGE IN ALL
 LANDSCAPE BUFFERS AS ORIGINALLY APPROVED, AND PER
 SECTION 94-443.
  
 11. SATISFIED. PLEASE PROVIDE THE TREE CATEGORIES FOR
 TREES AND PALMS TO BE REMOVED AND MITIGATION TREES
 PROVIDED ON THE TREE ALTERATION PLAN SHEET TAP-1.
  
 THERE ARE MANY CORRECTIONS NECESSARY ON THE TREE
 DISPOSITION PLAN. A MEETING TO REVIEW THE CORRECTIONS
 WOULD BE THE MOST EFFICIENT WAY TO COMMUNICATE THE
 CORRECTIONS NEEDED.
  
 12. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 INDIVIDUAL LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN TO
 CORRESPOND TO THE WIDTHS AS LISTED ON SHEET SP-1.
  
 13. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS
 TO PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS.
 THIS INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND
 CURBS, AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED
 BY TREE ROOTS.
  
 14. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. PLEASE SHOW ALL
 EASEMENTS.
  
 LIFT STATION NEEDS SCREENING.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. A SEPARATE TREE ALTERATION PERMIT SHALL BE SUBMITTED
 FOR EACH PHASE OF THE PROJECT. ALL TREES EXISTING
 WITHIN THE PHASE AREA SHALL BE ACCOUNTED FOR AND
 MITIGATED AT TIME OF PERMITTING.
  
 3. PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY FOR EACH PHASE, ALL INVASIVE EXOTIC PLANTS
 SHALL BE REMOVED WITHIN THE PHASE AREA.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-19-2016 Cont ID  
Sent By rcaranci Date 04-19-2016 Time 14:40 Rev Time 0.00
Received By rcaranci Date 04-11-2016 Time 14:40 Sent To  
Notes
2016-04-19 14:42:25FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: NOVUS MEDICAL Z16020008
 APRIL 18, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. NOT SATISFIED. PLEASE PROVIDE A TREE SURVEY FOR THE
 SITE. THERE IS ONE BLACK OLIVE ON SITE THAT IS NOT
 SHOWN ON THE TREE DISPOSITION PLAN.
 PLEASE SUBMIT A TREE SURVEY.
  
 2. SATISFIED. THE PINES EXISTING ON THE SITE ARE PINUS
 CLAUSA. PLEASE VERIFY AND CORRECT THE TREE DISPOSITION
 PLAN.
  
 3. NOT SATISFIED. PLEASE PROVIDE A TREE MITIGATION
 CHART SHOWING THE TREE CATEGORIES REMOVED AND REPLACED
 WITH THE PROPOSED PLAN.
  
 THERE ARE MANY CORRECTIONS NECESSARY ON THE TREE
 DISPOSITION PLAN. A MEETING TO REVIEW THE CORRECTIONS
 WOULD BE THE MOST EFFICIENT WAY TO COMMUNICATE THE
 CORRECTIONS NEEDED.
  
 4. SATISFIED. THERE ARE MANY HEALTHY MATURE SABAL PALMS
 ON SITE THAT CAN BE RELOCATED RATHER THAN DESTROYED.
 PLEASE INDICATE PRESERVATION OF THE SABAL PALMS ON THE
 TREE DISPOSITION PLAN.
  
 5. SATISFIED. PLEASE CORRECT THE NOTE ON THE TREE
 DISPOSITION PLAN REGARDING TREE MITIGATION. ALL TREES
 LESS THAN 35 FEET OF CANOPY SPREAD MUST BE MITIGATED
 ONE FOR ONE. THE LISTED INVASIVE EXOTIC SPECIES ARE THE
 ONLY ONES EXEMPT FROM MITIGATION.
  
 6. SATISFIED. PLEASE CORRECT THE OPEN SPACE PERCENTAGE
 ON SHEET SP-1TO REFLECT THE CORRECT OPEN SPACE AS
 DEFINED BY CODE.
  
 7. SATISFIED. THE NUMBER OF TREES, FLOWERING TREES AND
 SHRUBS REQUIRED PER SECTION 94-442 MUST BE CALCULATED
 ON 50 PERCENT OPEN SPACE REQUIRED PER SECTION 94-203.
 PLEASE REVISE THE DATA TABLE TO REFLECT THE CORRECT
 QUANTITIES.
  
 8. SATISFIED. PLEASE REVISE THE REQUIRED TREE COUNTS
 FOR THE NORTH AND SOUTH BUFFERS TO 23 EACH, AND ADD THE
 TREES TO THE LANDSCAPE PLAN.
  
 9. SATISFIED. PLEASE REVISE TO SHOW TREES AT THE
 REQUIRED SPACING ALONG THE NORTH BUFFER. THE ADJACENT
 PROPERTY OWNER CAN BE CONTACTED TO REMOVE THE
 AUSTRALIAN PINES WITHIN THEIR BUFFER.
  
 10. SATISFIED. PLEASE PROVIDE THE HEDGE IN ALL
 LANDSCAPE BUFFERS AS ORIGINALLY APPROVED, AND PER
 SECTION 94-443.
  
 11. NOT SATISFIED. PLEASE PROVIDE THE TREE CATEGORIES
 FOR TREES AND PALMS TO BE REMOVED AND MITIGATION TREES
 PROVIDED ON THE TREE ALTERATION PLAN SHEET TAP-1.
  
 THERE ARE MANY CORRECTIONS NECESSARY ON THE TREE
 DISPOSITION PLAN. A MEETING TO REVIEW THE CORRECTIONS
 WOULD BE THE MOST EFFICIENT WAY TO COMMUNICATE THE
 CORRECTIONS NEEDED.
  
 12. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 INDIVIDUAL LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN TO
 CORRESPOND TO THE WIDTHS AS LISTED ON SHEET SP-1.
  
 13. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS
 TO PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS.
 THIS INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND
 CURBS, AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED
 BY TREE ROOTS.
  
 14. NOT SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. PLEASE SHOW ALL
 EASEMENTS.
  
 LIFT STATION NEEDS SCREENING.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. A SEPARATE TREE ALTERATION PERMIT SHALL BE PERMITTED
 SEPARATELY FOR EACH PHASE OF THE PROJECT.
  
 3. PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY, ALL INVASIVE EXOTIC PLANTS SHALL BE REMOVED
 FROM THE ENTIRE SITE.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-03-2016 Cont ID  
Sent By rcaranci Date 03-03-2016 Time 16:54 Rev Time 0.00
Received By rcaranci Date 03-03-2016 Time 16:54 Sent To  
Notes
2016-03-03 16:54:39FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: NOVUS MEDICAL Z16020008
 MARCH 3, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE PROVIDE A TREE SURVEY FOR THE SITE. THERE IS
 ONE BLACK OLIVE ON SITE THAT IS NOT SHOWN ON THE TREE
 DISPOSITION PLAN.
  
 2. THE PINES EXISTING ON THE SITE ARE PINUS CLAUSA.
 PLEASE VERIFY AND CORRECT THE TREE DISPOSITION PLAN.
  
 3. PLEASE PROVIDE A TREE MITIGATION CHART SHOWING THE
 TREE CATEGORIES REMOVED AND REPLACED WITH THE PROPOSED
 PLAN.
  
 4. THERE ARE MANY HEALTHY MATURE SABAL PALMS ON SITE
 THAT CAN BE RELOCATED RATHER THAN DESTROYED. PLEASE
 INDICATE PRESERVATION OF THE SABAL PALMS ON THE TREE
 DISPOSITION PLAN.
  
 5. PLEASE CORRECT THE NOTE ON THE TREE DISPOSITION PLAN
 REGARDING TREE MITIGATION. ALL TREES LESS THAN 35 FEET
 OF CANOPY SPREAD MUST BE MITIGATED ONE FOR ONE. THE
 LISTED INVASIVE EXOTIC SPECIES ARE THE ONLY ONES EXEMPT
 FROM MITIGATION.
  
 6. PLEASE CORRECT THE OPEN SPACE PERCENTAGE ON SHEET
 SP-1TO REFLECT THE CORRECT OPEN SPACE AS DEFINED BY
 CODE.
  
 7. THE NUMBER OF TREES, FLOWERING TREES AND SHRUBS
 REQUIRED PER SECTION 94-442 MUST BE CALCULATED ON 50
 PERCENT OPEN SPACE REQUIRED PER SECTION 94-203. PLEASE
 REVISE THE DATA TABLE TO REFLECT THE CORRECT
 QUANTITIES.
  
 8. PLEASE REVISE THE REQUIRED TREE COUNTS FOR THE NORTH
 AND SOUTH BUFFERS TO 23 EACH, AND ADD THE TREES TO THE
 LANDSCAPE PLAN.
  
 9. PLEASE REVISE TO SHOW TREES AT THE REQUIRED SPACING
 ALONG THE NORTH BUFFER. THE ADJACENT PROPERTY OWNER CAN
 BE CONTACTED TO REMOVE THE AUSTRALIAN PINES WITHIN
 THEIR BUFFER.
  
 10. PLEASE PROVIDE THE HEDGE IN ALL LANDSCAPE BUFFERS
 AS ORIGINALLY APPROVED, AND PER SECTION 94-443.
  
 11. PLEASE PROVIDE THE TREE CATEGORIES FOR TREES AND
 PALMS TO BE REMOVED AND MITIGATION TREES PROVIDED ON
 THE TREE ALTERATION PLAN SHEET TAP-1.
  
 12. PLEASE INDICATE THE WIDTH OF ALL INDIVIDUAL
 LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN TO CORRESPOND
 TO THE WIDTHS AS LISTED ON SHEET SP-1.
  
 13. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 14. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED
 EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC.,
 AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT
 AND UTILITIES. PLEASE SHOW ALL EASEMENTS.
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 04-28-2016 Cont ID  
Sent By tward Date 04-28-2016 Time 16:40 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-04-28 16:48:21THE SITE PLAN IS APPROVED SUBJECT TO THE FOLLOWING
 CONDITIONS:
  
 1.THE ONSITE WATER MAIN WILL BE A PRIVATE MAIN AND
 WATER USAGE WILL BE MEASURED WITH A MASTER METER FOR
 THE DEVELOPMENT.
  
 2. THE WATER MAIN IS NOT TO BE LOCATED WITHIN THE
 STORMWATER RETENTION AREA.
  
 3. THE GRADING PLAN FOR THE PARKING LOTS ON THE NORTH
 SIDE OF THE SITE ARE TO BE DESIGNED TO DRAIN TOWARD THE
 DRAINAGE SYSTEM OF CATCH BASINS.
  
 4. GRADING OF PHASE 2 ROADWAY ALONG SOUTH PROPERTY LINE
 NOT INCLUDED IN THE SITE PLAN.
  
 5. GRADING PLAN FOR ENGINEERING PERMIT WILL NEED
 ADDITIONAL PROPOSED GRADES FOR THE CORNERS OF THE
 PARKING LOTS.
  
 6. REQUIREMENTS LISTED UNDER THE ORIGINAL APPROVAL
 STILL APPLY.
  
 TRACY L. WARD, P.E.
 PUBLIC WORKS DEPARTMENT
 [email protected]
 (561) 494-1120

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 04-25-2016 Cont ID  
Sent By tward Date 04-25-2016 Time 12:19 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-04-25 12:19:30THE FOLLOWING COMMENTS ARE BASED ON THE REVIEW OF THE
 APRIL 8, 2016 PLAN SUBMITTAL TO PPRC:
 1. SHEET C-1 SHOWS WHAT APPEARS TO BE AN EASEMENT OVER
 THE WATER MAIN. THIS IS INCONSISTENT WITH THE
 ACKNOWLEDGEMENT OF THE ENGINEER THAT THE WATER SYSTEM
 WILL BE MASTER METERED.
  
 2. REVISE THE PROPOSED RETENTION AREA OR WATER MAIN
 ROUTE SO THAT THE WATER MAIN DOES NOT CROSS THE STORM
 RETENTION AREA. PERHAPS THE STORM RETENTION AREA CAN
 INCLUDE INLET D-13 INSTEAD OF D-14, THEREBY ELIMINATING
 THE 90 LF OF 36" RCP THAT WOULD BE REMOVED IN PHASE 2.
  
 3. ENGINEER HAS ACKNOWLEDGED THE NORTH PARKING LOTS
 NEED TO BE RE-GRADED TO DRAIN TO THE STORM INLETS
 INSTEAD OF THE BACK OF THE PARKING SPACES.
  
 4. GRADING OF PHASE 2 ROADWAY ALONG SOUTH PROPERTY LINE
 NOT INCLUDED IN THIS SUBMITTAL.
  
 5. GRADING PLAN FOR ENGINEERING PERMIT WILL NEED
 ADDITIONAL PROPOSED GRADES FOR THE CORNERS OF THE
 PARKING LOTS.
  
 6. ENGINEER EMAILED AN AUTOTURN ANALYSIS DEMONSTRATING
 THE DUMPSTER LOCATION CAN BE READILY SERVICED.
  
 7. REQUIREMENTS LISTED UNDER THE ORIGINAL APPROVAL
 STILL APPLY.
  
 TRACY L. WARD, P.E.
 PUBLIC WORKS DEPARTMENT
 [email protected]
 (561) 494-1120

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 14:19 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 14:19 Sent To  
Notes
2016-03-08 14:20:03SEE COMMENTS UNDER ENG PPRC

Review Stop STORM STORMWATER
Rev No 2 Status F Date 04-25-2016 Cont ID  
Sent By tward Date 04-25-2016 Time 12:20 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-04-25 12:21:37SEE COMMENTS UNDER PUBLIC WORKS #2.
  
 TRACY L. WARD, P.E.
 PUBLIC WORKS DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-08-2016 Cont ID  
Sent By Ward Date 03-08-2016 Time 14:19 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 14:19 Sent To  
Notes
2016-03-09 12:10:591. STEEP BACK OF CURB SLOPE ALONG SOUTH PROPERTY LINE.
  
 2. PROPOSED PERIMETER SPOT GRADE OF 20.25 BELOW MINIMUM
 PERIMETER GRADE OF 20.56.
  
 3. PARKING SPACES ALONG NORTH PROPERTY LINE SLOPE
 TOWARD PROPERTY LINE INSTEAD OF TO CENTERLINE OF DRIVE
 WHERE THE DRAINAGE INLETS ARE LOCATED.
  
 4. ?14? CONTOUR MISLABELED FOR RETENTION AREA AROUND
 STRUCTURE D-2.
  
 5. SHOW ALL UTILITIES ON LANDSCAPE PLANS (STORM NOT
 SHOWN; WATER AND SEWER DO NOT MATCH CIVIL PLANS).
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 561-494-1120
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 14:20 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 14:20 Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 03-08-2016 Cont ID  
Sent By cranford Date 03-08-2016 Time 14:20 Rev Time 0.00
Received By cranford Date 03-08-2016 Time 14:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 05-06-2016 Cont ID  
Sent By dkittred Date 05-06-2016 Time 20:31 Rev Time 0.00
Received By dkittred Date   Time   Sent To  
Notes
2016-05-06 20:33:18PLANNING AND ZONING COMMENTS:
  
 5/6/16
  
 1. TRAFFIC CONCURRENCY APPROVAL LETTER REQUIRED PRIOR
 TO ISSUANCE OF SITE PLAN APPROVAL.
  
 CONDITIONS OF APPROVAL:
  
 A. A PLAT SHALL BE RECORDED FOR THE SUBJECT PROPERTY
 PRIOR TO C.O., AS LISTED IN THE CONDITIONS OF APPROVAL
 OF THE LAST SITE PLAN APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 04-19-2016 Cont ID  
Sent By dkittred Date 04-19-2016 Time 16:15 Rev Time 0.00
Received By dkittred Date 04-11-2016 Time 14:08 Sent To  
Notes
2016-04-19 16:15:21PLANNING AND ZONING COMMENTS: ***FAILED***
  
 4/19/2016
  
 1. [PREVIOUS COMMENT #1] PLEASE PROVIDE DOCUMENTATION
 AS TO ANDREW ROTNERMEL'S (OR BRYN WESCH'S) RELATIONSHIP
 TO THE PROPERTY OWNER - ORIGINS BEHAVIORAL HEALTHCARE
 OF FLORIDA, LLC, AND AUTHORIZATION TO SIGN THE
 APPLICATION.
  
 2. [PREVIOUS COMMENT #3] TRAFFIC CONCURRENCY LETTER WAS
 NOT PROVIDED. PLEASE PROVIDE. THE PREVIOUSLY ISSUED
 TRAFFIC CONCURRENCY LETTER FOR THIS SITE HAS EXPIRED.
  
 3. [PREVIOUS COMMENT #4] GRAPHIC DEPICTING CHANGE IN
 BUILDING FOOTPRINT NEEDS TO INCLUDE A CALCULATION
 DEMONSTRATING THAT THERE IS NOT GREATER THAN A 5%
 CHANGE IN THE BUILDING FOOTPRINT TO STAY WITHIN THE
 MINOR PD AMENDMENT CATEGORY.
  
 4. [PREVIOUS COMMENT #5] REVISE THE DETAIL ON THE
 BICYCLE PAD SHOWING DIMENSIONS. THE WIDTH IS BASED ON
 THE MINIMUM REQUIRED SPACING SHOWN BETWEEN THE RACK AND
 DEPTH IS A MINIMUM OF 6 FEET. IF TWO ROWS OF PARKING
 ARE PROVIDED, THEN 4 FEET OF ADDITIONAL SPACE IS
 REQUIRED BETWEEN THE ROWS OF BICYCLE PARKING. IT IS
 RECOMMENDED THE DETAIL IS REVISED TO PROVIDE 4 BICYCLE
 PARKING SPACES (TWO 'U'-SHAPED RACKS) REQUIRED FOR THIS
 PHASE OF DEVELOPMENT AND ADDITIONAL BICYCLE PARKING
 PROVIDED PROPORTIONAL TO PHASE II THAT WILL BE ADDED TO
 THE SITE WHEN PHASE II IS CONSTRUCTED. ADJUST BICYCLE
 PARKING CALCULATION TO SHOW HOW THE MINIMUM BICYCLE
 PARKING WAS CALCULATED AND WHAT IS REQUIRED AND BEING
 INSTALLED FOR PHASE I AND PHASE II - FINAL BUILD-OUT.
  
 5. STALL DEPTH FOR 60 DEGREE ANGLE PARKING NEEDS TO BE
 A MINIMUM OF 19'-10". PLEASE DIMENSION ON PLAN. GRAPHIC
 IN ZLDR SEC. 94-485(J) SHOWS HOW THE STALL DEPTH
 DIMENSION IS CALCULATED.
  
 6. [PREVIOUS COMMENT #14] INFORMATION ON HEIGHT OF
 PROPOSED FENCE WAS REQUESTED. RESPONSE LETTER DID NOT
 INDICATE A HEIGHT OF THE FENCE. PLEASE PROVIDE HEIGHT
 OF FENCE TO DEMONSTRATE COMPLIANCE WITH ZLDR SEC.
 94-302.
  
 7. PARKING WAS BROKEN DOWN INTO PHASES, BUT ADA SPACES
 ALSO NEED TO BE BROKEN DOWN INTO PHASES TO DEMONSTRATE
 THAT ADA PARKING SPACES MEETS MINIMUM REQUIRED FOR
 PHASE I AND PHASE II - FINAL BUILD-OUT.
  
 8. IT IS UNCLEAR IF THE PROPOSED SITE DATA IS
 REPRESENTATIVE OF THE PHASE I CONSTRUCTION OR FINAL
 BUILD-OUT. PLEASE CLARIFY.
  
 9. [PREVIOUS COMMENT #17(F)] MAXIMUM LOT COVERAGE BY
 IMPERVIOUS AREA IS 75 PERCENT [ZLDR SEC.
 94-203(B)(2(B)], PLEASE INCLUDE THE CALCULATED
 PERCENTAGE ON THE PLAN INDICATING COMPLIANCE WITH THIS
 REQUIREMENT.
  
 10. SHEET SP-1 SITE DATA SHOWS THE LANDSCAPE AREA
 PERCENTAGE AS 43%, HOWEVER, BASED ON THE SQUARE FOOTAGE
 OF LANDSCAPE AREA PROVIDED, THE PERCENTAGE WOULD BE
 36%. PLEASE REVIEW AND REVISE ACCORDINGLY.
  
 11. INDICATE THE HEIGHT OF THE PROPOSED LIGHT POLES.
 LIGHT POLES SHALL NOT EXCEED THE MAXIMUM BUILDING
 HEIGHT FOR THE DISTRICT - 80 FEET [ZLDR SEC.
 94-203(B)(6)].
  
 CONDITION(S):
  
 A. A PLAT SHALL BE RECORDED FOR THE SUBJECT PROPERTY
 PRIOR TO C.O., AS LISTED IN THE CONDITIONS OF APPROVAL
 OF THE LAST SITE PLAN APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 03-02-2016 Cont ID  
Sent By dkittred Date 03-02-2016 Time 17:37 Rev Time 0.00
Received By dkittred Date 02-12-2016 Time 09:57 Sent To  
Notes
2016-03-02 17:36:22PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/2/16
  
 1. ANDREW ROTNERMEL HAS SIGNED THE OWNER'S CONSENT
 FORM. PLEASE PROVIDE DOCUMENTATION AS TO ANDREW
 ROTNERMEL?S RELATIONSHIP TO THE PROPERTY OWNER -
 ORIGINS BEHAVIORAL HEALTHCARE OF FLORIDA, LLC, AND
 AUTHORIZATION TO SIGN THE APPLICATION.
  
 2. OWNER'S CONSENT AUTHORIZES MARK RICKARDS TO SUBMIT
 THE APPLICATION ON BEHALF OF NOVUS PROPERTIES, LLC,
 HOWEVER, THE APPLICATION LISTS KYLE CARR AS THE
 AGENT/APPLICANT. PLEASE PROVIDE CLARIFICATION AS TO THE
 VARIOUS PARTIES/INDIVIDUALS INVOLVED WITH THE
 APPLICATION SUBMITTAL.
  
 3. TRAFFIC CONCURRENCY LETTER WAS NOT PROVIDED. PLEASE
 PROVIDE. THE PREVIOUSLY ISSUED TRAFFIC CONCURRENCY
 LETTER FOR THIS SITE HAS EXPIRED.
  
 4. SUBMITTAL APPEARS TO BE A MAJOR PD AMENDMENT RATHER
 THAN A MINOR PD AMENDMENT. PLEASE PROVIDE A GRAPHIC AND
 CALCULATION DEPICTING CHANGE IN ORIGINAL APPROVED
 BUILDING FOOTPRINT. RELOCATION OF MORE THAN FIVE
 PERCENT OF THE TOTAL SQUARE FOOTAGE INDICATED AS BEING
 COVERED BY STRUCTURES REQUIRES A MAJOR PD AMENDMENT
 [ZLDR SEC. 94-207(E)(1)(E)] AND ADDITIONAL FEES
 ASSOCIATED WITH PROCESSING A MAJOR PD AMENDMENT
 APPLICATION.
  
 5. PROVIDE BICYCLE PARKING IN ACCORDANCE WITH ZLDR SEC.
 94-485(Q). INCLUDE A CALCULATION, RACK STYLE (NOTE:
 WAVE AND COMB STYLES NOT PERMITTED), AND PAD DETAIL
 INCLUDING PAD DIMENSIONS AND BICYCLE RACK SPACING.
  
 6. PROVIDE SIDEWALK FROM PARKING LOT TO ENTRANCE(S).
  
 7. PROVIDE A SIDEWALK FROM THE LOADING AREA TO THE
 LOADING AREA ENTRANCE.
  
 8. THERE IS A PHASE 2 ALONG THE SOUTH SIDE OF THE
 PROPERTY WHICH CUTS THROUGH A ONE-WAY DRIVE. IT IS
 UNCLEAR HOW MUCH OF THE ONE WAY DRIVE WILL BE
 CONSTRUCTED DURING PHASE 1 AND IF IT WILL DEAD-END AT
 THE PHASE 2. IT IS RECOMMENDED THAT THE ENTIRE ONE-WAY
 DRIVE BE PUT IN AT A FUTURE DATE (UNLESS REQUIRED FOR
 EMERGENCY ACCESS) SINCE NO ONE WILL BE ABLE TO USE IT
 UNTIL THE REAR PARKING IS CONSTRUCTED.
  
 9. IT APPEARS ON THE SITE PLAN THAT THE NORTHERN
 STORMWATER RETENTION AREA WILL BE UTILIZED IN PHASE 1
 CONSTRUCTION, BUT NOT INCLUDED WITHIN PHASE 1 LIMITS.
 IT IS ALSO NOT CLEAR WHAT UTILITY WORK WILL BE
 CONSTRUCTED IN PHASE 1 VERSUS PHASE 2 AS THE LINES
 CROSS THE PHASING. PLEASE CLARIFY AND EXPAND PHASE 1
 BOUNDARY AS NECESSARY.
  
 10. DIMENSION LENGTH OF LOADING SPACE TO DEMONSTRATE
 COMPLIANCE WITH LOADING SPACE REQUIREMENTS [ZLDR SEC.
 94-485(P)].
  
 11. DIMENSION DRIVE AISLE ON THE SOUTH SIDE OF THE MAIN
 PARKING AREA AND INCLUDE A DIMENSION OF THE DRIVE AISLE
 ADJACENT TO THE LOADING AREA.
  
 12. WHAT IS THE ANGLE OF THE ANGLED PARKING SPACES?
 PLEASE INDICATE ON PLAN AND CORRECT ANGLED STRIPING
 DETAIL TO SHOW ANGLE AND DOUBLE LINES CONNECTED AT THE
 BOTTOM [ZLDR SEC. 94-485(J)].
  
 13. THERE IS A PROPOSED FENCE THAT GOES AROUND THE
 SOUTH AND WEST SIDE OF THE PARKING AREA. WHAT IS THE
 HEIGHT OF THIS FENCE AND DOES IT INTERFERE WITH THE
 PROPOSED STORMWATER RETENTION AREA TO THE EAST OF THE
 PARKING AREA?
  
 14. THERE IS A FENCE PROPOSED ALONG THE SOUTH SIDE OF
 THE ADA PARKING SPACES. HOW HIGH WILL THIS FENCE BE AND
 WILL THERE BE GATE ACCESS TO THE SIDEWALK THAT GOES
 AROUND THE SIDE OF THE BUILDING?
  
 15. THERE ARE SEVERAL STOP BARS SHOWN ON THE SITE PLAN.
 PLEASE INCLUDE STOP SIGNS WITH THE STOP BARS.
  
 16. DIMENSION SETBACKS OF DUMPSTER ENCLOSURE AND
 DEMONSTRATE COMPLIANCE WITH THE ZONING DISTRICT
 SETBACKS [ZLDR SEC. 94-203(B)(2)].
  
 17. THE FOLLOWING COMMENTS RELATE TO SHEET SP-1, SITE
 DATA CHART:
  
 A. 'PROPOSED USE' OF THE PROPERTY IS INDICATED AS
 'MEDICAL OFFICE BUILDING'. IT IS MY UNDERSTANDING A
 GROUP HOME, TYPE V IS PROPOSED FOR THIS LOCATION FOR
 PHASE I AND PHASE 2 WILL BE A MEDICAL OFFICE BUILDING.
 PLEASE UPDATE THE USE ACCORDINGLY.
  
 B. UPDATE THE SITE DATA CALCULATIONS TO CLARIFY WHAT IS
 HAPPENING IN PHASE 1 VERSUS SITE CALCULATIONS FOR
 BUILDING-OUT. FOR EXAMPLE, THE CHART SAYS 148 SPACES
 ARE BEING PROVIDED, HOWEVER, THIS REPRESENTS TOTAL
 BUILD-OUT AND ONLY 54 SPACES ARE REALLY BEING PROVIDED
 AS PART OF PHASE 1. CHART SHOULD DIFFERENTIATE BETWEEN
 PHASE 1 AND COMPLETE BUILD-OUT.
  
 C. THE SITE DATA CHART INDICATES THE EXISTING FAR AS
 0.16, BUILDING COVERAGE AS 16%, AND BUILDING HEIGHT AS
 19 FEET, HOWEVER, THE SITE IS VACANT. PLEASE REVISE.
  
 D. THE LAND USE FOR THE PROPERTY IS COMMUNITY SERVICES
 (CS) NOT COMMUNITY. PLEASE CORRECT.
  
 E. THE SIDE (SOUTH) SETBACK IS REQUIRED TO BE A MINIMUM
 OF 15 FEET, NOT 25 FEET [ZLDR SEC. 94-203(B)(2)(B)].
 PLEASE CORRECT.
  
 F. MAXIMUM LOT COVERAGE BY IMPERVIOUS AREA IS 75
 PERCENT [ZLDR SEC. 94-203(B)(5)]. PLEASE INCLUDE
 PERCENT ON PLAN DEMONSTRATING COMPLIANCE.
  
 G. PLEASE REVIEW THE OPEN SPACE CALCULATION, IT APPEARS
 TOO LOW. OPEN SPACE MEANS "AN OPEN, UNENCLOSED AREA
 CONSISTING OF SETBACKS, LANDSCAPING, BUFFERS, VEHICULAR
 AND PEDESTRIAN CIRCULATION FEATURES, AND SURFACE
 PARKING." [ZLDR SEC. 94-611].
  
 H. THE PARKING CALCULATION PROVIDED FOR THE TYPE V
 GROUP HOME ONLY INCLUDES PARKING SPACES BASED ON 1
 PARKING SPACE PER 6 BEDS AND DOES NOT PROVIDE GUEST
 PARKING OR PARKING FOR OFFICE SPACE. THE USE REQUIRES
 THE FOLLOWING PARKING REQUIREMENT '1 PER 6 BEDS
 (RESIDENTS), 1 PER 10 BEDS (GUESTS), 1 PER 300 SQ. FT.
 OF OFFICE, 50 PERCENT RESERVE PARKING ALLOWED.' [ZLDR
 SEC. 94-486, TABLEXV-6]. PLEASE REVISE CALCULATION TO
 DEMONSTRATE COMPLIANCE.
  
 I. PROVIDE A CALCULATION THAT SHOWS THE MINIMUM NUMBER
 OF REQUIRED ADA SPACES REQUIRED FOR THE PROJECT [ZLDR
 SEC. 94-485(O)].
  
 18. LOCATION OF UTILITIES BETWEEN THE PRELIMINARY
 ENGINEERING SHEET AND WHAT IS SHOWN ON THE LANDSCAPE
 SHEET ARE NOT THE SAME. PLEASE REVIEW AND CORRECT.
  
 19. LANDSCAPE BUFFER WILL BE REQUIRED ALONG THE SOUTH
 SIDE OF THE PROPERTY.
  
 20. WILL THERE BE ANY SITE LIGHTING? IF SO INDICATE
 LOCATIONS OF POLES (MUST COMPLY WITH SETBACKS) AND
 PROVIDE A PHOTOMETRIC PLAN DEMONSTRATING COMPLIANCE
 WITH ZLDR SEC. 94-207(D)(8), 94-309(A), AND 94-310(D).
  
 GENERAL COMMENTS:
 21. IF THERE WILL BE ANY FREESTANDING SIGNS PROPOSED
 FOR THIS PROJECT, PLEASE INCLUDE LOCATION ON SITE PLAN.
 ADDITIONALLY, IF THERE WILL BE ANY WALL SIGNAGE PLEASE
 ALSO INCLUDE ON THE PLAN TO AVOID HAVING TO COME BACK
 FOR A MINOR PD AMENDMENT WHEN SIGNAGE IS PROPOSED.
  
 22. A PLAT SHALL BE RECORDED FOR THE SUBJECT PROPERTY
 PRIOR TO C.O., AS LISTED IN THE CONDITIONS OF APPROVAL
 OF THE LAST SITE PLAN APPROVAL.
  
 23. NOTE THAT ALL NEW PRIVATE DEVELOPMENT, NEW
 CONSTRUCTION, RENOVATION OR REMODELING, WHERE TOTAL
 VERTICAL CONSTRUCTION COSTS OF ALL BUILDINGS ON A
 PROJECT SITE ARE EQUAL TO OR GREATER THAN $500,000.00,
 IS SUBJECT TO THE ART IN PUBLIC PLACES REQUIREMENTS
 OUTLINED IN CHAPTER 78, ARTICLE V OF THE CITY'S CODE OF
 ORDINANCES.
  
 WHEN RESUBMITTING:
 1. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 DEPARTMENTS IN A WRITTEN FORMAT WHEN RESUBMITTING.
  
 2. PROVIDE 15 SETS OF REVISED PLANS AND/OR DOCUMENTS
 ALONG WITH ONE REDUCED COPY AND ELECTRONIC COPY OF ALL
 PLANS.
  
 3. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 4. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2016-02-12 10:03:03SUFFICIENCY REVIEW
  
 2/12/16
  
 1. ANDREW ROTNERMEL HAS SIGNED THE OWNER'S CONSENT
 FORM. PLEASE PROVIDE DOCUMENTATION AS TO ANDREW
 ROTNERMEL'S RELATIONSHIP TO THE PROPERTY OWNER -
 ORIGINS BEHAVIORAL HEALTHCARE OF FLORIDA, LLC, AND
 AUTHORIZATION TO SIGN THE APPLICATION.
  
 2. OWNER'S CONSENT AUTHORIZES MARK RICKARDS TO SUBMIT
 THE APPLICATION ON BEHALF OF NOVUS PROPERTIES, LLC,
 HOWEVER, THE APPLICATION LISTS KYLE CARR AS THE
 AGENT/APPLICANT. PLEASE PROVIDE CLARIFICATION AS TO THE
 VARIOUS PARTIES/INDIVIDUALS INVOLVED WITH THE
 APPLICATION SUBMITTAL.
  
 3. TRAFFIC CONCURRENCY LETTER WAS NOT PROVIDED. PLEASE
 PROVIDE. THE PREVIOUSLY ISSUED TRAFFIC CONCURRENCY
 LETTER FOR THIS SITE HAS EXPIRED.
  
 4. ONLY 6 SETS OF PLANS WERE SUBMITTED. PLEASE SUBMIT 9
 ADDITIONAL SETS FOR A TOTAL OF 15 SETS OF PLAN AS THIS
 PROJECT REQUIRES PPRC REVIEW. ADDITIONAL PLANS MUST BE
 RECEIVED BY THURSDAY, FEBRUARY 18 OR ELSE THE PROJECT
 WILL NOT BE ABLE TO BE SCHEDULED FOR THE MARCH PPRC
 MEETING.
  
 5. SUBMITTAL APPEARS TO BE A MAJOR PD AMENDMENT RATHER
 THAN A MINOR PD AMENDMENT. PLEASE PROVIDE A GRAPHIC AND
 CALCULATION DEPICTING CHANGE IN ORIGINAL APPROVED
 BUILDING FOOTPRINT. RELOCATION OF MORE THAN FIVE
 PERCENT OF THE TOTAL SQUARE FOOTAGE INDICATED AS BEING
 COVERED BY STRUCTURES REQUIRES A MAJOR PD AMENDMENT
 [ZLDR SEC. 94-207(E)(1)(E)].
  