Plan Review Details - Project Z16010023
| Plan Review Stops For Project Z16010023 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
02-10-2016 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
02-10-2016 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
02-10-2016 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2016-02-10 10:50:54 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT | | | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS | | | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE | | | PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR | | | FACILITY ENTRANCES. | | | | | | 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT | | | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS | | | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, | | | CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES | | | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE | | | BUILDING OR FACILITY | | | | | | 4. THE CHANGE OF OCCUPANCY CLASSIFICATION FOR THE | | | EXISTING BUILDING IS COVERED BY CHAPTER 10 OF THE | | | FLORIDA EXISTING BUILDING CODE. EDUCATIONAL OCCUPANCY | | | IS A HIGHER RISK OCCUPANCY THAN THE PREVIOUS BUSINESS | | | OCCUPANCY. WHEN SUBMITTED FOR PERMIT THE PLANS SHALL BE | | | SUCH THAT THE BUILDING ALTERATIONS AND NEW SYSTEMS | | | DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF THE | | | FLORIDA EXISTING BUILDING CODE AS THEY PERTAIN TO THE | | | CHANGE OF OCCUPANCY AND THE CLASSIFICATION OF WORK | | | (ALTERATION LEVEL 3) FOR THE PROPOSED/REQUIRED | | | ATERATIONS. | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
02-08-2016 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
02-08-2016 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2016-02-11 16:25:47 | AS DISCUSSED AT THE PPRC MEETING ON 2/10/2016, COMMENT | | | NO. 10 IS BEING REVISED TO: | | | 10. REMOVE THE CURB CUTS ON FLAMINGO AND RESTORE THE | | | CURB LINE AND SIDEWALK. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | 561-494-1120 | | 2016-02-08 14:06:21 | CITY OF WEST PALM BEACH | | | PUBLIC WORKS DEPARTMENT | | | | | | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL. | | | | | | 1. PLEASE SHOW THE ALLEY (DB 259 PGS 353 AND 355 ON | | | LOTS 7 - 9 OF BLOCK 11) ON BOTH THE SITE PLAN AND | | | ENGINEERING PLANS. | | | | | | 2. A LICENSE AGREEMENT WILL BE REQUIRED FOR USE OF THE | | | ALLEY. | | | | | | 3. NO PERMANENT STRUCTURES WILL BE ALLOWED IN ALLEY. | | | PLAY EQUIPMENT MAY NEED TO BE SHIFTED. | | | | | | 4. SURVEY SHOULD LESS OUT THE WEST 15 FEET OF LOTS 10 | | | AND 11 PER DB 260/514 AND DB265/237. | | | | | | 5. A TRAFFIC STUDY WILL BE REQUIRED FOR THIS PROJECT | | | SHOWING HOW THE PROPOSED DEVELOPMENT WILL AFFECT THE | | | TRAFFIC VOLUME AND SURROUNDING LOCAL ROADWAYS. INCLUDE | | | TRAFFIC ACCIDENT DATA FOR AFFECTED STREET CORRIDORS. | | | ESTIMATE INCREASED OR DECREASED POTENTIAL. SAFETY | | | IMPROVEMENTS SHALL BE RECOMMENDED WHERE NECESSARY. | | | PLEASE SCHEDULE A MEETING WITH THE CITY TRAFFIC | | | ENGINEER (BRIAN COLLINS) TO DETERMINE THE SCOPE OF THE | | | REQUIRED STUDY. | | | | | | 6. PLEASE RELOCATED PROPOSED DRAINAGE STRUCTURE S-103 | | | OUT OF THE ALLEY. | | | | | | 7. POLLUTANT REDUCTION BAFFLES SHOULD BE INSTALLED IN | | | THE DRAINAGE STRUCTURES ON EITHER SIDE OF THE | | | EXFILTRATION TRENCH. | | | | | | 8. INDICATE VERTICAL DATUM ON ENGINEERING PLANS. | | | | | | 9. SHOW LIMITS OF ROAD MILLING AND RESURFACING ON | | | BISCAYNE FOR WATER MAIN CONNECTION. | | | | | | 10. REMOVE THE CURB CUT ON FLAMINGO IN FRONT OF THE | | | BUILDING AND RESTORE THE CURB LINE AND SIDEWALK. | | | | | | 11. FDOT PERMIT WILL BE NEEDED FOR ANY WORK IN DIXIE | | | HIGHWAY R/W. | | | | | | 12. PER SECTION 2.21.2 OF THE CITY RIGHT OF WAY | | | STANDARDS MANUAL, PROJECTS WHICH DISTURB 40% OR MORE OF | | | A ROADWAY (LINEAR FOOTAGE) PER BLOCK WILL BE REQUIRED | | | TO MILL AND RESURFACE THE ENTIRE BLOCK. THE ALLEY | | | BETWEEN PARCELS 3 & 4 WILL ALSO NEED TO BE REPAVED. | | | PLEASE SCHEDULE A MEETING WITH THE CITY?S TRAFFIC | | | ENGINEER TO FINALIZE THE DESIGN OF THE ALLEY, BICSAYNE | | | DRIVE, AND FLAMINGO DRIVE. DESIGN SHOULD INCLUDE | | | REPLACEMENT OF SIDEWALKS AND CURBS ADJACENT TO THE | | | SCHOOL SITE. SIDEWALK ON NORTH SIDE OF BISCAYNE SHOULD | | | EXTEND TO WEST PROPERTY LINE OF APPLICANT. | | | | | | 13. THE EXISTING CMP STORM PIPE IN LOT 11 OF BLOCK 11 | | | SHALL BE REPLACED BETWEEN INLET IN ALLEY AND MANHOLE IN | | | BISCAYNE DRIVE. | | | | | | 14. WHY IS THERE A GATE ACROSS THE WEST END OF BISCAYNE | | | DRIVE? | | | | | | 15. WHAT ARE THE LIMITS OF THE CANOPY SHOWN ON SITE | | | PLAN? | | | | | | 16. LABEL THE STREETS ON ENGINEERING PLANS. | | | | | | 17. ACCESS TO EXISTING WATER MAIN WILL NEED TO BE | | | ADDRESSED. PLEASE CONTACT LAURA LE, PE (561-494-1093 OR | | | [email protected]) IF YOU HAVE QUESTIONS REGARDING THE | | | CONNECTIONS TO THE CITY?S UTILITY SYSTEM. | | | | | | KELLY CRANFORD, P.E. | | | CAPITAL IMPROVEMENT PLAN MANAGER | | | [email protected] | | | 561-494-1098 (OFFICE) | | | | | | VINCE NOEL, PSM | | | CITY SURVEYOR / REAL ESTATE SUPERVISOR | | | [email protected] | | | 561-494-1096 | | | | | | BRIAN COLLINS, PE | | | CITY TRAFFIC ENGINEER | | | [email protected] | | | 561-494-1040 | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
02-04-2016 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
02-04-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
02-04-2016 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2016-02-04 14:22:39 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES | | | INCLUDING, BUT NOT LIMITED TO, NFPA 1, CHAPTER 20, | | | OCCUPANCY FIRE SAFETY, 20.2 EDUCATIONAL OCCUPANCIES AND | | | NFPA 101, CHAPTER 14, NEW EDICATIONAL OCCUPANCIES. | | | | | | 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | HAS A FIRE LOAD CALCUALTION BEEN COMPLETED FOR THIS | | | STRUCTURE AND COMPARED TO THE AVAILABLE WATER SUPPLY? | | | | | | IS A FIRE PUMP PROPOSED ? | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | 7. A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM | | | SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP | | | DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND | | | APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY | | | INSTALLATIO | | | | | | IS THERE A PROPOSED EMERGENCY POWER SUPPLY ? | | | | | | 8. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | IS THERE A PROPOSED EMERGENCY POWER SUPPLY ? | | | | | | 9. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 10. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY | | | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS | | | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. | | | | | | 11. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | 12. ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH | | | OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM | | | TERMINAL LANDING AND THE TOP TERMINAL LANDING EXCEEDS | | | 25 FEET MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE | | | PASSENGER ELEVATOR THAT IS OPERATIONAL AND WILL | | | ACCOMMODATE AN AMBULANCE STRETCHER 76 INCHES LONG AND | | | 24 INCHES WIDE IN THE HORIZONTAL POSITION. | | | | | | 13. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | PROJECT SHALL BE CLEARLY INDICATED AND IDENTIFIED ON | | | THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | 14. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS | | | (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND | | | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. | | | | | | THE FDC SHALL BE LOCATED WITHIN 150" OF A FIRE HYDRANT. | | | | | | 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE | | | ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED | | | ON THE PLAN. | | | | | | 16. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED | | | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY | | | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE | | | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES | | | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED | | | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED | | | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. | | | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | | MARKED WITH THE LETTER "R". | | | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | | SHALL BE MARKED WITH THE LETTER "F". | | | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | | | 17. THE WIDTH OF THE DROP-OFF ENRTY AND EGRESS LANES | | | INDICATES 12'; FOR USE OF FIRE APPARATUS/RESCUE | | | VEHICLES 20' IS REQUIRED. | | | | | | PROVIDE 30' RADUIS CURB AT EACH CORNER FOR FD APPARATUS | | | CLEARANCE. | | | | | | 18. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 19. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
06-01-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-01-2016 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-01-2016 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2016-06-01 17:09:07 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16010023 | | | JUNE 1, 2016 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE PROVIDE A TREE INVENTORY, TREE | | | DISPOSITION PLAN AND MITIGATION TABLE TO MEET THE | | | REQUIREMENTS OF SECTION 94-448. | | | | | | 2. SATISFIED. PLEASE PROVIDE MEASUREMENTS AND | | | CALCULATIONS FOR THE BUFFER TREES REQUIRED FOR ALL | | | BUFFER LENGTHS PER SECTION 94-443 B. | | | | | | 3. SATISFIED. EXISTING CANOPIES SHOULD BE REMOVED AND | | | BUFFER TREES PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS | | | AS REQUIRED, AND PROVIDE REQUIRED TREES IN THE TERMINAL | | | ISLANDS AT THE END OF ROWS OF PARKING. | | | | | | 4. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL | | | LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN. | | | | | | 5. WITHDRAWN. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL | | | OF FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST. | | | | | | 6. CONDITIONALLY SATISFIED. PLEASE INDICATE THE WIDTH | | | OF THE SIDEWALK ALONG S DIXIE. IF WIDE ENOUGH, PLEASE | | | ADD STREET TREES WITH TREE GRATES. STREET TREES LOCATED | | | IN A SIDEWALK SHALL HAVE STRUCTURAL SOIL EXTENDING 5 | | | FEET IN ALL DIRECTIONS UP TO THE CURB. INDICATE | | | STRUCTURAL SOIL LOCATIONS AND PROVIDE A TYPICAL | | | STRUCTURAL SOIL DETAIL ON THE LANDSCAPE DETAIL PAGE. | | | | | | FURTHER INVESTIGATION IS REQUIRED, THE MODIFICATIONS TO | | | SOUTH DIXIE ARE SEVERAL YEARS IN THE FUTURE, AND THIS | | | SECTION MAY NOT HAVE ANY MODIFICATION TO THE CURB | | | LOCATION. | | | | | | 7. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | LIGHTING PLAN MUST BE SUPPLIED FOR ZONING REVIEW, SO | | | COORDINATION WITH LANDSCAPE PLAN CAN BE ACCOMPLISHED | | | PRIOR TO APPROVAL. | | | | | | 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 9. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND | | | MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C | | | UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED EQUIPMENT AND UTILITIES. | | | | | | 10. SATISFIED. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE | | | AROUND THE WEST SIDE AND REAR OF THE DUMPSTER | | | ENCLOSURE. | | | | | | 11. SATISFIED. PLEASE PROVIDE ADDITIONAL LANDSCAPING | | | AROUND THE STRUCTURE TO MEET THE 30% REQUIREMENT FOR | | | TREES, SHRUBS OR HEDGES PER SECTION 94-443 (E)(1). | | | | | | THERE ARE LOCATIONS ALONG THE BUILDING WHERE | | | LANDSCAPING CAN BE ADDED TO COMPLY. | | | | | | | | | ADDITIONAL COMMENTS 5/9/16: | | | 12. WITHDRAWN. PLEASE CHANGE THE ROYAL PALMS ADJACENT | | | TO THE SPORTS FIELD OR PLAYGROUND TO A DIFFERENT | | | SPECIES TO AVOID THE POSSIBILITY OF FRONDS DROPPING ON | | | PEOPLE BELOW. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | FOR THE SCHOOL BUILDING, THE APPLICANT SHALL APPLY FOR | | | AN FDOT PERMIT FOR IMPROVEMENTS INCLUDING STREET TREES | | | AT THIRTY FOOT SPACING, STRUCTURAL SOIL, TREE GRATES | | | AND IRRIGATION IN THE SOUTH DIXIE RIGHT OF WAY ADJACENT | | | TO THE PROPERTY FROM FLAMINGO DRIVE TO BISCAYNE DRIVE. | | | TREE SPECIES AND DETAILS WILL BE AS APPROVED AND | | | PERMITTED BY FDOT. THE IMPROVEMENTS PERMITTED BY FDOT | | | SHALL BE INSTALLED WITHIN SIX MONTHS OF THE ISSUANCE OF | | | THE CERTIFICATE OF OCCUPANCY. THE PLANNING AND ZONING | | | ADMINISTRATOR MAY GRANT A ONE-TIME EXTENSION FOR | | | INSTALLATION AT THE REQUEST OF THE APPLICANT WITH GOOD | | | CAUSE. | | | | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE LANDSCAPING AND IRRIGATION | | | MAINTENANCE INCLUDING STREET TREES AT THIRTY FOOT | | | SPACING, STRUCTURAL SOIL, TREE GRATES AND IRRIGATION IN | | | THE SOUTH DIXIE RIGHT OF WAY ADJACENT TO THE PROPERTY | | | FROM FLAMINGO DRIVE TO BISCAYNE DRIVE. A SEPARATE | | | MAINTENANCE AGREEMENT WITH THE CITY SHALL BE REQUIRED. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
05-09-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-09-2016 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-09-2016 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2016-05-09 12:11:04 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16010023 | | | MAY 9, 2016 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE PROVIDE A TREE INVENTORY, TREE | | | DISPOSITION PLAN AND MITIGATION TABLE TO MEET THE | | | REQUIREMENTS OF SECTION 94-448. | | | | | | 2. SATISFIED. PLEASE PROVIDE MEASUREMENTS AND | | | CALCULATIONS FOR THE BUFFER TREES REQUIRED FOR ALL | | | BUFFER LENGTHS PER SECTION 94-443 B. | | | | | | 3. SATISFIED. EXISTING CANOPIES SHOULD BE REMOVED AND | | | BUFFER TREES PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS | | | AS REQUIRED, AND PROVIDE REQUIRED TREES IN THE TERMINAL | | | ISLANDS AT THE END OF ROWS OF PARKING. | | | | | | 4. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL | | | LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN. | | | | | | 5. WITHDRAWN. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL | | | OF FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST. | | | | | | 6. NOT SATISFIED. PLEASE INDICATE THE WIDTH OF THE | | | SIDEWALK ALONG S DIXIE. IF WIDE ENOUGH, PLEASE ADD | | | STREET TREES WITH TREE GRATES. STREET TREES LOCATED IN | | | A SIDEWALK SHALL HAVE STRUCTURAL SOIL EXTENDING 5 FEET | | | IN ALL DIRECTIONS UP TO THE CURB. INDICATE STRUCTURAL | | | SOIL LOCATIONS AND PROVIDE A TYPICAL STRUCTURAL SOIL | | | DETAIL ON THE LANDSCAPE DETAIL PAGE. | | | | | | FURTHER INVESTIGATION IS REQUIRED, THE MODIFICATIONS TO | | | SOUTH DIXIE ARE SEVERAL YEARS IN THE FUTURE, AND THIS | | | SECTION MAY NOT HAVE ANY MODIFICATION TO THE CURB | | | LOCATION. | | | | | | 7. NOT SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING | | | ON THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH | | | LANDSCAPING. | | | LIGHTING PLAN MUST BE SUPPLIED FOR ZONING REVIEW, SO | | | COORDINATION WITH LANDSCAPE PLAN CAN BE ACCOMPLISHED | | | PRIOR TO APPROVAL. | | | | | | 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 9. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND | | | MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C | | | UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED EQUIPMENT AND UTILITIES. | | | | | | 10. SATISFIED. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE | | | AROUND THE WEST SIDE AND REAR OF THE DUMPSTER | | | ENCLOSURE. | | | | | | 11. NOT SATISFIED. PLEASE PROVIDE ADDITIONAL | | | LANDSCAPING AROUND THE STRUCTURE TO MEET THE 30% | | | REQUIREMENT FOR TREES, SHRUBS OR HEDGES PER SECTION | | | 94-443 (E)(1). | | | | | | THERE ARE LOCATIONS ALONG THE BUILDING WHERE | | | LANDSCAPING CAN BE ADDED TO COMPLY. | | | | | | | | | ADDITIONAL COMMENTS 5/9/16: | | | 12. PLEASE CHANGE THE ROYAL PALMS ADJACENT TO THE | | | SPORTS FIELD OR PLAYGROUND TO A DIFFERENT SPECIES TO | | | AVOID THE POSSIBILITY OF FRONDS DROPPING ON PEOPLE | | | BELOW. | | | | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
02-08-2016 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
02-08-2016 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2016-02-08 16:39:27 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16010023 | | | FEBRUARY 8, 2016 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE PROVIDE A TREE INVENTORY, TREE DISPOSITION | | | PLAN AND MITIGATION TABLE TO MEET THE REQUIREMENTS OF | | | SECTION 94-448. | | | | | | 2. PLEASE PROVIDE MEASUREMENTS AND CALCULATIONS FOR THE | | | BUFFER TREES REQUIRED FOR ALL BUFFER LENGTHS PER | | | SECTION 94-443 B. | | | | | | 3. EXISTING CANOPIES SHOULD BE REMOVED AND BUFFER TREES | | | PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS AS REQUIRED, | | | AND PROVIDE REQUIRED TREES IN THE TERMINAL ISLANDS AT | | | THE END OF ROWS OF PARKING. | | | | | | 4. PLEASE INDICATE THE WIDTH OF ALL LANDSCAPE BUFFERS | | | ON THE LANDSCAPE PLAN. | | | | | | 5. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL OF | | | FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST. | | | | | | 6. PLEASE INDICATE THE WIDTH OF THE SIDEWALK ALONG S | | | DIXIE. IF WIDE ENOUGH, PLEASE ADD STREET TREES WITH | | | TREE GRATES. STREET TREES LOCATED IN A SIDEWALK SHALL | | | HAVE STRUCTURAL SOIL EXTENDING 5 FEET IN ALL DIRECTIONS | | | UP TO THE CURB. INDICATE STRUCTURAL SOIL LOCATIONS AND | | | PROVIDE A TYPICAL STRUCTURAL SOIL DETAIL ON THE | | | LANDSCAPE DETAIL PAGE. | | | | | | 7. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 8. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT | | | INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES | | | WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY | | | FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS. | | | | | | 9. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED | | | EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC., | | | AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT | | | AND UTILITIES. | | | | | | 10. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE AROUND THE | | | WEST SIDE AND REAR OF THE DUMPSTER ENCLOSURE. | | | | | | 11. PLEASE PROVIDE ADDITIONAL LANDSCAPING AROUND THE | | | STRUCTURE TO MEET THE 30% REQUIREMENT FOR TREES, SHRUBS | | | OR HEDGES PER SECTION 94-443 (E)(1). | | | | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
02-08-2016 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
02-08-2016 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
06-01-2016 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-01-2016 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-06-01 10:56:47 | REVISED COMMENT NO. 10 OF THE 2/10/16 ENGINEERING PPRC | | | COMMENTS HAS BEEN ADDRESSED. THERE IS THE FOLLOWING | | | CALLOUT TO A FLAMINGO DRIVE DRIVEWAY APRON ON SHEET 8 | | | OF 8 (SIGNED AND SEALED 3/16/16 BY RICHARD REIKENIS): | | | "REMOVE UNUSED CURB CUTS (TYP)". | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
02-08-2016 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
02-08-2016 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2016-02-08 14:07:31 | SEE COMMENTS UNDER ENG PPRC |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
02-08-2016 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
02-08-2016 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2016-02-08 14:06:58 | SEE COMMENTS UNDER ENG PPRC |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
02-08-2016 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
02-08-2016 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
02-08-2016 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2016-02-08 14:07:15 | SEE COMMENTS UNDER ENG PPRC |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
06-01-2016 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
06-01-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
06-01-2016 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-06-01 16:32:31 | SUBJECT TO THE FOLLOWING CONDITIONS: | | | | | | 1. SIGNAGE IS NOT A PART OF THIS APPROVAL AND SHALL BE | | | REVIEWED SEPARATELY AT TIME OF BUILDING PERMIT. | | | | | | 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES ? PLANNING DIVISION. | | | | | | 3. AN ENGINEERING DEVELOPMENT PERMIT SHALL BE REQUIRED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY. | | | | | | 4. DRIVE APRONS OR ROAD ACCESS NOT NEEDED SHALL BE | | | REPLACED WITH SIDEWALK AND CURB. | | | | | | 5. SIDEWALKS OR ENTRY WAYS IN THE RIGHT-OF-WAY COMPOSED | | | OF PAVER DESIGN OTHER THAN CONCRETE SURFACE AS PER CITY | | | STANDARD WILL REQUIRE A DEVELOPER MAINTENANCE AND | | | RESPONSIBILITY AGREEMENT. | | | | | | 6. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | FOR THE SCHOOL BUILDING, THE APPLICANT SHALL APPLY FOR | | | AN FDOT PERMIT FOR IMPROVEMENTS INCLUDING STREET TREES | | | AT THIRTY FOOT SPACING, STRUCTURAL SOIL, TREE GRATES | | | AND IRRIGATION IN THE SOUTH DIXIE RIGHT OF WAY ADJACENT | | | TO THE PROPERTY FROM FLAMINGO DRIVE TO BISCAYNE DRIVE. | | | TREE SPECIES AND DETAILS WILL BE AS APPROVED AND | | | PERMITTED BY FDOT. THE IMPROVEMENTS PERMITTED BY FDOT | | | SHALL BE INSTALLED WITHIN SIX MONTHS OF THE ISSUANCE OF | | | THE CERTIFICATE OF OCCUPANCY. THE PLANNING AND ZONING | | | ADMINISTRATOR MAY GRANT A ONE-TIME EXTENSION FOR | | | INSTALLATION AT THE REQUEST OF THE APPLICANT WITH GOOD | | | CAUSE. | | | | | | 7. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE LANDSCAPING AND IRRIGATION | | | MAINTENANCE, INCLUDING STREET TREES AT 30 FOOT SPACING, | | | STRUCTURAL SOIL, TREE GRATES AND IRRIGATION IN THE | | | SOUTH DIXIE RIGHT-OF-WAY ADJACENT TO THE PROPERTY FROM | | | FLAMINGO DRIVE TO BISCAYNE DRIVE. A SEPARATE | | | MAINTENANCE AGREEMENT WITH THE CITY SHALL BE REQUIRED. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
05-25-2016 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
05-26-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
05-26-2016 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-05-26 14:29:17 | GENERAL COMMENTS: | | | | | | 1.) REPEAT COMMENT FROM 2/5/16 AND 5/13/16: PROVIDE | | | LETTERS FROM THE FOLLOWING PUBLIC UTILITIES CONFIRMING | | | THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR | | | EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISION OF | | | THEIR SERVICES: FPU AND FPL. LETTERS FROM FPU AND FPL | | | HAVE NOT BEEN PROVIDED TO STAFF. PLEASE NOTE THAT THE | | | UTILITY LETTERS ARE REQUIRED PRIOR TO SITE PLAN | | | APPROVAL. | | | | | | 2.) ALL FINAL PLANS SHALL BE SIGNED, DATED AND SEALED | | | BY A FLORIDA REGISTERED ARCHITECT/LANDSCAPE | | | ARCHITECT/ENGINEER. | | | | | | SITE PLAN: | | | | | | 1.) PROPOSED LIGHT POLE FIXTURES AT THE SOUTH EAST | | | PARKING LOT IS IN CONFLICT WITH THE PARKING SPACES. DUE | | | TO THE BUMP OUT TO ACCOMMODATE THE TWO (2) LIGHT | | | FIXTURES ON THE LOT, WHICH IMPACTS FOUR (4) PARKING | | | STALLS, THE STALLS DO NOT MEET THE MINIMUM REQUIREMENT | | | FOR PARKING STALL DIMENSIONS. PLEASE ADDRESS. | | | | | | 2.) WHY ARE THE PROPOSED LIGHT FIXTURES AT THE | | | SOUTHWEST PARKING LOT LOCATED APPROXIMATELY 19 FT. FROM | | | THE PARKING STALLS? THE PURPOSE OF PROVIDING THE | | | FIXTURES IS TO PROVIDE LIGHTING TO THE PARKING LOT. | | | THIS DOES NOT SEEM LOGICAL. PLEASE ADDRESS AND/OR | | | PROVIDE AN EXPLANATION. | | | | | | ACHITECTURAL FLOOR PLANS AND ELEVATIONS: | | | | | | 1.) THE REVISED FLOOR PLANS/ELEVATIONS SEEM TO BE | | | MISSING FROM THE RESUBMITTAL PACKET. PLEASE INCLUDE | | | REVISED STAMPED AND SEALED FLOOR PLANS AND ELEVATIONS | | | IN THE RESUBMITTAL PACKET. ENSURE THAT THE FLOOR PLAN, | | | ELEVATIONS AND SITE PLAN ARE ALL CONSISTENT. | | | | | | LIGHTING: | | | | | | 1.) PROVIDE A PHOTOMETRIC PLAN SHOWING THE LOCATION OF | | | ALL LIGHT FIXTURES PROPOSED IN THE PROJECT. LIGHT POLES | | | SHALL BE SETBACK AT LEAST 5 FT. FROM THE PROPERTY | | | LINES. PLEASE ENSURE THAT THE LOCATION OF ANY LIGHT | | | POLE FIXTURE WILL NOT BE IN CONFLICT WITH ANY EXISTING | | | UTILITIES AND/OR PROPOSED LANDSCAPING. [ACCORDING TO | | | THE APPLICANT'S RESPONSE LETTER TO ZONING'S COMMENTS, | | | DATED 5/25/16, THE APPLICANT IS WORKING ON REVISING THE | | | PHOTOMETRIC PLAN TO COMPLY WITH ZONING CODE | | | REQUIREMENTS.] | | | | | | NOTES: | | | | | | * A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO | | | THE REMOVAL OF ANY TREES ON THE PROJECT SITE. | | | | | | * AN EMAIL FROM JON SCHMIDT TO STEVE ANDERSON OF PALM | | | TRAN, DATED APRIL 20, 2016, WAS PROVIDED AS PART OF THE | | | RESUBMITTAL PACKET. THE LETTER INDICATES THAT THERE WAS | | | A DISCUSSION ON RELOCATION OF SOUTHBOUND PALM TRAN BUS | | | STOP #114 TO THE NEXT BLOCK TO THE SOUTH. STAFF WILL | | | NEED CONFIRMATION FROM STEVE ANDERSON OF PALM TRAN | | | CONFIRMING THE COORDINATION PRIOR TO THE RELOCATION OF | | | THE BUS STOP. PLEASE PROVIDE THIS DOCUMENTATION UPON | | | RECEIPT. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE | | | (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND | | | AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT | | | CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE | | | ($200). | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
05-13-2016 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
05-13-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
05-13-2016 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-05-13 15:07:17 | GENERAL COMMENTS: | | | | | | 1.) REPEAT COMMENT FROM 2/5/16: PROVIDE LETTERS FROM | | | THE FOLLOWING PUBLIC UTILITIES CONFIRMING THAT THE | | | PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS | | | OR OTHERWISE INTERFERE WITH THE PROVISION OF THEIR | | | SERVICES: AT&T, FPU FPL. PLEASE NOTE THAT THE UTILITY | | | LETTERS ARE REQUIRED PRIOR TO SITE PLAN APPROVAL. | | | | | | 2.) REVISE THE LOCATION MAP ON SHEETS SP-1, LI-1, LP-1 | | | AND TD-1 TO INCLUDE THE PARCELS SOUTH OF BISCAYNE | | | DRIVE. | | | | | | 3.) CONCURRENCY APPROVAL WAS GRANTED FOR 150 STUDENTS | | | PER THE TPS LETTER ISSUED BY THE PALM BEACH COUNTY | | | DEPARTMENT OF ENGINEERING AND PUBLIC WORKS - TRAFFIC | | | DIVISION, DATED APRIL 14, 2016. PLEASE CORRECT THE | | | INFORMATION IN THE SITE DATA TABULAR TO REFLECT THE | | | CONCURRENCY APPROVAL ISSUED BY THE COUNTY. | | | | | | 4.) ALL FINAL PLANS SHALL BE SIGNED, DATED AND SEALED | | | BY A FLORIDA REGISTERED ARCHITECT/LANDSCAPE | | | ARCHITECT/ENGINEER. | | | | | | SITE PLAN: | | | | | | 1.) REPEAT COMMENT FROM 2/5/16: ACCORDING TO GOOGLE | | | STREET VIEW, THERE SEEMS TO BE AN EXISTING BUS STOP AND | | | BENCH IN FRONT OF THE PROPERTY ALONG SOUTH DIXIE HWY | | | WHICH IS NOT DEPICTED IN THE SURVEY. THE BOUNDARY | | | SURVEY SHOULD BE UPDATED TO REFLECT THIS EXISTING | | | FEATURE. | | | | | | 2.) REPEAT COMMENT FROM 2/5/16: THE APPLICANT'S | | | RESPONSE TO SITE PLAN COMMENT #8 STATES THAT A | | | "LIGHTING PLAN WILL BE SUBMITTED WITH BUILDING PERMIT"; | | | HOWEVER, A PHOTOMETRIC PLAN IS NEEDED AT THIS POINT IN | | | TIME TO ENSURE THAT THERE IS NO CONFLICT WITH THE | | | PROPOSED LANDSCAPING FOR THE PROJECT. | | | | | | 3.) THE APPLICANT HAS NOTED IN THE RESPONSE LETTER TO | | | STAFF'S PPRC COMMENTS (FOR ZONING SITE PLAN COMMENT | | | #1), DATED 2/17/16, THAT "THE EXISTING UTILITIES ARE TO | | | BE RELOCATED EITHER UNDERGROUND OR AROUND THE PERIMETER | | | OF THE SITE PENDING FPL'S DETERMINATION." DOES THIS | | | APPLY TO ALL OVERHEAD (O/H) POWER LINES ON THE | | | PROPERTY? THE SITE PLAN INDICATES THAT THE O/H LINES | | | RUNNING ACROSS PARCELS 5 AND 6 WILL BE BURIED ON SITE; | | | HOWEVER, THERE IS ANOTHER O/H LINE RUNNING DIAGONALLY | | | ACROSS PARCEL 1, WHICH IS NOT DEPICTED IN THE SITE | | | PLAN. PLEASE CLARIFY THE PROVISIONS FOR THIS O/H LINE. | | | | | | 4.) PROVIDE A DETAIL OF THE PROPOSED DECORATIVE WALL | | | AND FENCE. | | | | | | 5.) HOW TALL IS THE EXISTING CHAIN LINK FENCE ALONG | | | BISCAYNE DRIVE? | | | | | | 6.) FENCES/WALL SHALL NOT EXCEED 4 FT. IN HEIGHT WITHIN | | | THE REQUIRED FRONT SETBACK. PLEASE CLARIFY THE | | | EXTENT/LOCATION OF THE PROPOSED 8 FT. HIGH CHAIN LINK | | | FENCE ON THE WEST SIDE OF THE SCHOOL PARCEL, AND THE 6 | | | FT. HIGH DECORATIVE FENCE WITH ROLLING GATE ALONG | | | BISCAYNE DRIVE. [ZLDR S.94-302(C)] | | | | | | LANDSCAPE PLAN: | | | | | | 1.) REPEAT COMMENT FROM 2/5/16: A MINIMUM 5 FT. WIDE | | | LANDSCAPE BUFFER SHALL BE PROVIDED ALONG ALL PROPERTY | | | LINES FOR THE PROPOSED SCHOOL PARKING LOTS, SOUTH OF | | | BISCAYNE DRIVE. A VARIANCE TO THE BUFFER WILL BE | | | REQUIRED IF THE BUFFERING REQUIREMENTS CANNOT BE MET BY | | | THE APPLICANT. [PER A TELEPHONE CONVERSATION WITH THE | | | APPLICANT ON 5/11/16, CHANGES ARE BEING PROPOSED TO THE | | | PROPOSED SCHOOL PARKING LOT TO MEET THE MINIMUM ZLDR | | | STANDARDS FOR LANDSCAPING. COMPLIANCE WITH THE ZLDR | | | MUST BE REFLECTED IN THE REVISED PLANS.] | | | | | | ARCHITECTURAL FLOOR PLANS AND ELEVATIONS: | | | | | | 1.) ELEVATIONS DO NOT MATCH WHAT IS DEPICTED IN THE | | | SITE PLAN. PLEASE CORRECT FOR CONSISTENCY (I.E. | | | EXISTING CANOPY AND PROPOSED WALL IS MISSING FROM THE | | | EAST ELEVATION). | | | | | | 2.) PROVIDE DIMENSIONS FOR THE ELEVATIONS. | | | | | | NOTES: | | | * A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO | | | THE REMOVAL OF ANY TREES ON THE PROJECT SITE. | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE | | | (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND | | | AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT | | | CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
02-05-2016 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
02-05-2016 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
02-05-2016 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2016-02-05 16:15:03 | GENERAL COMMENTS: | | | | | | 1.) A CLASS B SPECIAL USE PERMIT IS REQUIRED FOR THE | | | PROPOSED OFFSITE ACCESSORY PARKING AREA. | | | | | | 2.) UNITY OF TITLE, JOINING THE FOLLOWING PCNS WILL BE | | | REQUIRED: 74-43-43-28-06-011-0040, 0050, 0060, 0100, | | | 0120 AND 0131. | | | | | | 3.) A TPS LETTER FROM THE PALM BEACH COUNTY TRAFFIC | | | DIVISION IS REQUIRED. | | | | | | 4.) PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC | | | UTILITIES DEPARTMENT HAS REVIEWED THE PROPOSAL FOR | | | WATER, SEWAGE TREATMENT, STORM DRAINAGE, AND GARBAGE | | | COLLECTION. | | | | | | 5.) PROVIDE LETTERS FROM THE FOLLOWING PUBLIC UTILITIES | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISION OF THEIR SERVICES: AT&T, FPU, FPL, AND | | | COMCAST. | | | | | | 6.) A LICENSE AGREEMENT FOR THE TEMPORARY USE OF THE | | | ALLEYWAY WILL NEED TO BE COORDINATED WITH THE CITY | | | ATTORNEY'S OFFICE, AND APPROVED BY THE CITY COMMISSION. | | | | | | | | | SITE PLAN: | | | | | | 1.) THERE SEEMS TO BE EXISTING UTILITY POLES AND | | | OVERHEAD POWER LINES NEAR THE PROPOSED PLAY AREA AND | | | PLAY FIELDS, WHICH DOES NOT SEEM TO CREATE A SAFE | | | ENVIRONMENT FOR CHILDREN. ARE THERE ANY PROVISIONS TO | | | RELOCATE THE POWER LINES (I.E. UNDERGROUND)? | | | | | | 2.) THE EXISTING METAL CANOPIES ON PARCELS 1 AND 4 (AS | | | DEPICTED IN THE SURVEY) SEEM TO BE IN CONFLICT WITH THE | | | PROPOSED PARKING AND LANDSCAPING IN THE SITE PLAN AND | | | LANDSCAPE PLAN. PLEASE REMOVE THE CANOPIES FROM THE | | | PLANS. | | | | | | 3.) ACCORDING TO GOOGLE STREET VIEW, THERE SEEMS TO BE | | | AN EXISTING BUS STOP AND BENCH IN FRONT OF THE PROPERTY | | | ALONG SOUTH DIXIE HWY WHICH IS NOT DEPICTED IN THE | | | SURVEY OR THE SITE PLAN. THE BOUNDARY SURVEY AND PLANS | | | SHOULD BE UPDATED TO REFLECT THIS EXISTING FEATURE. | | | ALSO, PLEASE ENSURE THAT THE LOCATION OF THE EXISTING | | | TRANSIT FACILITIES WILL NOT BE IN CONFLICT WITH THE | | | PROPOSED DEVELOPMENT. | | | | | | 4.) THE PROJECT IS PROPOSING A TOTAL OF 34 PARKING | | | SPACES. BASED ON THIS TOTAL PARKING COUNT, A MINIMUM OF | | | TWO (2) DISABLED PARKING SPACES IS REQUIRED. [ZLDR | | | S.94-485(O)(1)] | | | | | | 5.) THE MINIMUM SEPARATION BETWEEN EACH BIKE RACK IS 30 | | | INCHES AND THE MINIMUM DISTANCE BETWEEN THE BIKE RACK | | | AND THE EDGE OF THE BIKE PAD IS 24 INCHES. PLEASE | | | ENSURE ALL DIMENSIONS ARE CONSISTENT WITH THE CITY'S | | | BICYCLE PARKING GUIDELINES AND PROVIDE THE DIMENSIONS | | | IN THE BIKE RACK DETAIL. | | | | | | 6.) ARCHITECTURAL ELEVATIONS AND FLOOR PLANS ARE | | | MISSING FROM THE SUBMITTAL. PLEASE PROVIDE. | | | | | | 7.) IS THERE ANY SIGNAGE PROPOSED FOR THE PROJECT? | | | | | | 8.) WILL THERE BE ANY LIGHTING FACILITIES FOR THE | | | PROJECT? IF SO, PROVIDE A PHOTOMETRIC PLAN, | | | ILLUSTRATING THE LOCATION OF THE LIGHT FIXTURES AND | | | LIGHTING INTENSITY. | | | | | | 9.) PROVIDE DIMENSIONS FOR THE OFFSITE ACCESSORY | | | PARKING AREA. | | | | | | 10.) ILLUSTRATE THE TURNING RADIUS AT THE STUDENT DROP | | | OFF/LOADING AREA. | | | | | | 11.) CORRECT THE FOLLOWING IN THE SITE DATA TABULAR: | | | TOTAL SITE AREA: 76,230 SQ. FT. (NOT 76,401 SQ. FT.); | | | BICYCLE PARKING REQUIRED/PROPOSED: 1/6 (NOT 2/3); | | | VISITOR PARKING REQUIRED: 10 PARKING SPACES (NOT 5 | | | PARKING SPACES). | | | | | | 12.) PLEASE ENSURE THAT ALL SITE DATA CALCULATIONS | | | (I.E. PERCENTAGE OF LANDSCAPED AREA, BUILDING COVERAGE, | | | ETC.) IS FOR THE PRIMARY SITE (SCHOOL SITE). | | | | | | 13.) WILL THERE BE ANY SCHOOL/ACTIVITY BUSES? IF SO, | | | WHERE WILL THE BUSES BE STORED? PLEASE NOTE THAT THE | | | STORAGE OF VEHICLES IS PROHIBITED ON SITE AND IN THE | | | PROPOSED ACCESSORY PARKING LOT AREA. | | | | | | | | | LANDSCAPE PLAN: | | | | | | 1.) A MINIMUM 5 FT. WIDE LANDSCAPE BUFFER SHALL BE | | | PROVIDED ALONG ALL PROPERTY LINES FOR EACH ACCESSORY | | | OFF-SITE PARKING AREA. IN ADDITION TO THE CLASS B | | | SPECIAL USE PERMIT TO ALLOW THE OFF-SITE PARKING, THE | | | APPLICANT WILL BE REQUIRED TO SEEK WAIVERS FROM THE | | | LANDSCAPE BUFFERING REQUIREMENTS IF THIS CANNOT BE MET. | | | [ZLDR S.94-273(D)(54)(B.)(7.)] | | | | | | 2.) THERE SEEMS TO BE EXISTING TREES ON THE PROPERTY. A | | | TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO THE | | | REMOVAL OF ANY TREES ON THE PROJECT SITE. | | | | | | | | | SUGGESTED IMPROVEMENTS: | | | | | | 1.) CONSIDER ADDING A LANDSCAPE SCREEN TO WEST SIDE OF | | | THE GUEST PARKING AREA IN ORDER TO SCREEN THE PARKING | | | AREA FROM THE PLAYGROUND. | | | | | | 2.) IS THE BIKE RACK INTENDED FOR STUDENT USE? IF SO, | | | CONSIDER RELOCATING THE BIKE RACK TO A LOCATION AWAY | | | FROM VEHICULAR CIRCULATION AREAS WITH ADEQUATE | | | VISIBILITY TO DETER BICYCLE THEFT. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE | | | (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND | | | AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT | | | CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| |
Print |
|