Plan Review Details - Project Z16010023
Plan Review Stops For Project Z16010023
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 02-10-2016 Cont ID  
Sent By rbrown Date 02-10-2016 Time 10:36 Rev Time 0.00
Received By rbrown Date 02-10-2016 Time 10:36 Sent To  
Notes
2016-02-10 10:50:54DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE
 PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES.
  
 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT
 LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS
 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE,
 CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES
 WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE
 BUILDING OR FACILITY
  
 4. THE CHANGE OF OCCUPANCY CLASSIFICATION FOR THE
 EXISTING BUILDING IS COVERED BY CHAPTER 10 OF THE
 FLORIDA EXISTING BUILDING CODE. EDUCATIONAL OCCUPANCY
 IS A HIGHER RISK OCCUPANCY THAN THE PREVIOUS BUSINESS
 OCCUPANCY. WHEN SUBMITTED FOR PERMIT THE PLANS SHALL BE
 SUCH THAT THE BUILDING ALTERATIONS AND NEW SYSTEMS
 DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF THE
 FLORIDA EXISTING BUILDING CODE AS THEY PERTAIN TO THE
 CHANGE OF OCCUPANCY AND THE CLASSIFICATION OF WORK
 (ALTERATION LEVEL 3) FOR THE PROPOSED/REQUIRED
 ATERATIONS.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 02-08-2016 Cont ID  
Sent By cranford Date 02-08-2016 Time 14:06 Rev Time 0.00
Received By cranford Date 02-08-2016 Time 14:04 Sent To  
Notes
2016-02-11 16:25:47AS DISCUSSED AT THE PPRC MEETING ON 2/10/2016, COMMENT
 NO. 10 IS BEING REVISED TO:
 10. REMOVE THE CURB CUTS ON FLAMINGO AND RESTORE THE
 CURB LINE AND SIDEWALK.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 561-494-1120
2016-02-08 14:06:21CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. PLEASE SHOW THE ALLEY (DB 259 PGS 353 AND 355 ON
 LOTS 7 - 9 OF BLOCK 11) ON BOTH THE SITE PLAN AND
 ENGINEERING PLANS.
  
 2. A LICENSE AGREEMENT WILL BE REQUIRED FOR USE OF THE
 ALLEY.
  
 3. NO PERMANENT STRUCTURES WILL BE ALLOWED IN ALLEY.
 PLAY EQUIPMENT MAY NEED TO BE SHIFTED.
  
 4. SURVEY SHOULD LESS OUT THE WEST 15 FEET OF LOTS 10
 AND 11 PER DB 260/514 AND DB265/237.
  
 5. A TRAFFIC STUDY WILL BE REQUIRED FOR THIS PROJECT
 SHOWING HOW THE PROPOSED DEVELOPMENT WILL AFFECT THE
 TRAFFIC VOLUME AND SURROUNDING LOCAL ROADWAYS. INCLUDE
 TRAFFIC ACCIDENT DATA FOR AFFECTED STREET CORRIDORS.
 ESTIMATE INCREASED OR DECREASED POTENTIAL. SAFETY
 IMPROVEMENTS SHALL BE RECOMMENDED WHERE NECESSARY.
 PLEASE SCHEDULE A MEETING WITH THE CITY TRAFFIC
 ENGINEER (BRIAN COLLINS) TO DETERMINE THE SCOPE OF THE
 REQUIRED STUDY.
  
 6. PLEASE RELOCATED PROPOSED DRAINAGE STRUCTURE S-103
 OUT OF THE ALLEY.
  
 7. POLLUTANT REDUCTION BAFFLES SHOULD BE INSTALLED IN
 THE DRAINAGE STRUCTURES ON EITHER SIDE OF THE
 EXFILTRATION TRENCH.
  
 8. INDICATE VERTICAL DATUM ON ENGINEERING PLANS.
  
 9. SHOW LIMITS OF ROAD MILLING AND RESURFACING ON
 BISCAYNE FOR WATER MAIN CONNECTION.
  
 10. REMOVE THE CURB CUT ON FLAMINGO IN FRONT OF THE
 BUILDING AND RESTORE THE CURB LINE AND SIDEWALK.
  
 11. FDOT PERMIT WILL BE NEEDED FOR ANY WORK IN DIXIE
 HIGHWAY R/W.
  
 12. PER SECTION 2.21.2 OF THE CITY RIGHT OF WAY
 STANDARDS MANUAL, PROJECTS WHICH DISTURB 40% OR MORE OF
 A ROADWAY (LINEAR FOOTAGE) PER BLOCK WILL BE REQUIRED
 TO MILL AND RESURFACE THE ENTIRE BLOCK. THE ALLEY
 BETWEEN PARCELS 3 & 4 WILL ALSO NEED TO BE REPAVED.
 PLEASE SCHEDULE A MEETING WITH THE CITY?S TRAFFIC
 ENGINEER TO FINALIZE THE DESIGN OF THE ALLEY, BICSAYNE
 DRIVE, AND FLAMINGO DRIVE. DESIGN SHOULD INCLUDE
 REPLACEMENT OF SIDEWALKS AND CURBS ADJACENT TO THE
 SCHOOL SITE. SIDEWALK ON NORTH SIDE OF BISCAYNE SHOULD
 EXTEND TO WEST PROPERTY LINE OF APPLICANT.
  
 13. THE EXISTING CMP STORM PIPE IN LOT 11 OF BLOCK 11
 SHALL BE REPLACED BETWEEN INLET IN ALLEY AND MANHOLE IN
 BISCAYNE DRIVE.
  
 14. WHY IS THERE A GATE ACROSS THE WEST END OF BISCAYNE
 DRIVE?
  
 15. WHAT ARE THE LIMITS OF THE CANOPY SHOWN ON SITE
 PLAN?
  
 16. LABEL THE STREETS ON ENGINEERING PLANS.
  
 17. ACCESS TO EXISTING WATER MAIN WILL NEED TO BE
 ADDRESSED. PLEASE CONTACT LAURA LE, PE (561-494-1093 OR
 [email protected]) IF YOU HAVE QUESTIONS REGARDING THE
 CONNECTIONS TO THE CITY?S UTILITY SYSTEM.
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 BRIAN COLLINS, PE
 CITY TRAFFIC ENGINEER
 [email protected]
 561-494-1040
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 561-494-1120
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 02-04-2016 Cont ID  
Sent By pleduc Date 02-04-2016 Time   Rev Time 0.00
Received By pleduc Date 02-04-2016 Time 13:23 Sent To  
Notes
2016-02-04 14:22:39THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES
 INCLUDING, BUT NOT LIMITED TO, NFPA 1, CHAPTER 20,
 OCCUPANCY FIRE SAFETY, 20.2 EDUCATIONAL OCCUPANCIES AND
 NFPA 101, CHAPTER 14, NEW EDICATIONAL OCCUPANCIES.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 HAS A FIRE LOAD CALCUALTION BEEN COMPLETED FOR THIS
 STRUCTURE AND COMPARED TO THE AVAILABLE WATER SUPPLY?
  
 IS A FIRE PUMP PROPOSED ?
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 7. A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATIO
  
 IS THERE A PROPOSED EMERGENCY POWER SUPPLY ?
  
 8. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 IS THERE A PROPOSED EMERGENCY POWER SUPPLY ?
  
 9. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 10. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 11. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 12. ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH
 OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM
 TERMINAL LANDING AND THE TOP TERMINAL LANDING EXCEEDS
 25 FEET MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76 INCHES LONG AND
 24 INCHES WIDE IN THE HORIZONTAL POSITION.
  
 13. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 PROJECT SHALL BE CLEARLY INDICATED AND IDENTIFIED ON
 THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 14. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 THE FDC SHALL BE LOCATED WITHIN 150" OF A FIRE HYDRANT.
  
 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 16. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 17. THE WIDTH OF THE DROP-OFF ENRTY AND EGRESS LANES
 INDICATES 12'; FOR USE OF FIRE APPARATUS/RESCUE
 VEHICLES 20' IS REQUIRED.
  
 PROVIDE 30' RADUIS CURB AT EACH CORNER FOR FD APPARATUS
 CLEARANCE.
  
 18. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 19. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 06-01-2016 Cont ID  
Sent By rcaranci Date 06-01-2016 Time 17:08 Rev Time 0.00
Received By rcaranci Date 06-01-2016 Time 17:07 Sent To  
Notes
2016-06-01 17:09:07FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2001 S DIXIE Z16010023
 JUNE 1, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A TREE INVENTORY, TREE
 DISPOSITION PLAN AND MITIGATION TABLE TO MEET THE
 REQUIREMENTS OF SECTION 94-448.
  
 2. SATISFIED. PLEASE PROVIDE MEASUREMENTS AND
 CALCULATIONS FOR THE BUFFER TREES REQUIRED FOR ALL
 BUFFER LENGTHS PER SECTION 94-443 B.
  
 3. SATISFIED. EXISTING CANOPIES SHOULD BE REMOVED AND
 BUFFER TREES PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS
 AS REQUIRED, AND PROVIDE REQUIRED TREES IN THE TERMINAL
 ISLANDS AT THE END OF ROWS OF PARKING.
  
 4. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN.
  
 5. WITHDRAWN. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL
 OF FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST.
  
 6. CONDITIONALLY SATISFIED. PLEASE INDICATE THE WIDTH
 OF THE SIDEWALK ALONG S DIXIE. IF WIDE ENOUGH, PLEASE
 ADD STREET TREES WITH TREE GRATES. STREET TREES LOCATED
 IN A SIDEWALK SHALL HAVE STRUCTURAL SOIL EXTENDING 5
 FEET IN ALL DIRECTIONS UP TO THE CURB. INDICATE
 STRUCTURAL SOIL LOCATIONS AND PROVIDE A TYPICAL
 STRUCTURAL SOIL DETAIL ON THE LANDSCAPE DETAIL PAGE.
  
 FURTHER INVESTIGATION IS REQUIRED, THE MODIFICATIONS TO
 SOUTH DIXIE ARE SEVERAL YEARS IN THE FUTURE, AND THIS
 SECTION MAY NOT HAVE ANY MODIFICATION TO THE CURB
 LOCATION.
  
 7. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
 LIGHTING PLAN MUST BE SUPPLIED FOR ZONING REVIEW, SO
 COORDINATION WITH LANDSCAPE PLAN CAN BE ACCOMPLISHED
 PRIOR TO APPROVAL.
  
 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 9. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 10. SATISFIED. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE
 AROUND THE WEST SIDE AND REAR OF THE DUMPSTER
 ENCLOSURE.
  
 11. SATISFIED. PLEASE PROVIDE ADDITIONAL LANDSCAPING
 AROUND THE STRUCTURE TO MEET THE 30% REQUIREMENT FOR
 TREES, SHRUBS OR HEDGES PER SECTION 94-443 (E)(1).
  
 THERE ARE LOCATIONS ALONG THE BUILDING WHERE
 LANDSCAPING CAN BE ADDED TO COMPLY.
  
  
 ADDITIONAL COMMENTS 5/9/16:
 12. WITHDRAWN. PLEASE CHANGE THE ROYAL PALMS ADJACENT
 TO THE SPORTS FIELD OR PLAYGROUND TO A DIFFERENT
 SPECIES TO AVOID THE POSSIBILITY OF FRONDS DROPPING ON
 PEOPLE BELOW.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE SCHOOL BUILDING, THE APPLICANT SHALL APPLY FOR
 AN FDOT PERMIT FOR IMPROVEMENTS INCLUDING STREET TREES
 AT THIRTY FOOT SPACING, STRUCTURAL SOIL, TREE GRATES
 AND IRRIGATION IN THE SOUTH DIXIE RIGHT OF WAY ADJACENT
 TO THE PROPERTY FROM FLAMINGO DRIVE TO BISCAYNE DRIVE.
 TREE SPECIES AND DETAILS WILL BE AS APPROVED AND
 PERMITTED BY FDOT. THE IMPROVEMENTS PERMITTED BY FDOT
 SHALL BE INSTALLED WITHIN SIX MONTHS OF THE ISSUANCE OF
 THE CERTIFICATE OF OCCUPANCY. THE PLANNING AND ZONING
 ADMINISTRATOR MAY GRANT A ONE-TIME EXTENSION FOR
 INSTALLATION AT THE REQUEST OF THE APPLICANT WITH GOOD
 CAUSE.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE LANDSCAPING AND IRRIGATION
 MAINTENANCE INCLUDING STREET TREES AT THIRTY FOOT
 SPACING, STRUCTURAL SOIL, TREE GRATES AND IRRIGATION IN
 THE SOUTH DIXIE RIGHT OF WAY ADJACENT TO THE PROPERTY
 FROM FLAMINGO DRIVE TO BISCAYNE DRIVE. A SEPARATE
 MAINTENANCE AGREEMENT WITH THE CITY SHALL BE REQUIRED.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 05-09-2016 Cont ID  
Sent By rcaranci Date 05-09-2016 Time 12:08 Rev Time 0.00
Received By rcaranci Date 05-09-2016 Time 12:08 Sent To  
Notes
2016-05-09 12:11:04FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2001 S DIXIE Z16010023
 MAY 9, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A TREE INVENTORY, TREE
 DISPOSITION PLAN AND MITIGATION TABLE TO MEET THE
 REQUIREMENTS OF SECTION 94-448.
  
 2. SATISFIED. PLEASE PROVIDE MEASUREMENTS AND
 CALCULATIONS FOR THE BUFFER TREES REQUIRED FOR ALL
 BUFFER LENGTHS PER SECTION 94-443 B.
  
 3. SATISFIED. EXISTING CANOPIES SHOULD BE REMOVED AND
 BUFFER TREES PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS
 AS REQUIRED, AND PROVIDE REQUIRED TREES IN THE TERMINAL
 ISLANDS AT THE END OF ROWS OF PARKING.
  
 4. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN.
  
 5. WITHDRAWN. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL
 OF FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST.
  
 6. NOT SATISFIED. PLEASE INDICATE THE WIDTH OF THE
 SIDEWALK ALONG S DIXIE. IF WIDE ENOUGH, PLEASE ADD
 STREET TREES WITH TREE GRATES. STREET TREES LOCATED IN
 A SIDEWALK SHALL HAVE STRUCTURAL SOIL EXTENDING 5 FEET
 IN ALL DIRECTIONS UP TO THE CURB. INDICATE STRUCTURAL
 SOIL LOCATIONS AND PROVIDE A TYPICAL STRUCTURAL SOIL
 DETAIL ON THE LANDSCAPE DETAIL PAGE.
  
 FURTHER INVESTIGATION IS REQUIRED, THE MODIFICATIONS TO
 SOUTH DIXIE ARE SEVERAL YEARS IN THE FUTURE, AND THIS
 SECTION MAY NOT HAVE ANY MODIFICATION TO THE CURB
 LOCATION.
  
 7. NOT SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING
 ON THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH
 LANDSCAPING.
 LIGHTING PLAN MUST BE SUPPLIED FOR ZONING REVIEW, SO
 COORDINATION WITH LANDSCAPE PLAN CAN BE ACCOMPLISHED
 PRIOR TO APPROVAL.
  
 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 9. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 10. SATISFIED. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE
 AROUND THE WEST SIDE AND REAR OF THE DUMPSTER
 ENCLOSURE.
  
 11. NOT SATISFIED. PLEASE PROVIDE ADDITIONAL
 LANDSCAPING AROUND THE STRUCTURE TO MEET THE 30%
 REQUIREMENT FOR TREES, SHRUBS OR HEDGES PER SECTION
 94-443 (E)(1).
  
 THERE ARE LOCATIONS ALONG THE BUILDING WHERE
 LANDSCAPING CAN BE ADDED TO COMPLY.
  
  
 ADDITIONAL COMMENTS 5/9/16:
 12. PLEASE CHANGE THE ROYAL PALMS ADJACENT TO THE
 SPORTS FIELD OR PLAYGROUND TO A DIFFERENT SPECIES TO
 AVOID THE POSSIBILITY OF FRONDS DROPPING ON PEOPLE
 BELOW.
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 02-08-2016 Cont ID  
Sent By rcaranci Date 02-08-2016 Time 16:39 Rev Time 0.00
Received By rcaranci Date 02-08-2016 Time 16:39 Sent To  
Notes
2016-02-08 16:39:27FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2001 S DIXIE Z16010023
 FEBRUARY 8, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A TREE INVENTORY, TREE DISPOSITION
 PLAN AND MITIGATION TABLE TO MEET THE REQUIREMENTS OF
 SECTION 94-448.
  
 2. PLEASE PROVIDE MEASUREMENTS AND CALCULATIONS FOR THE
 BUFFER TREES REQUIRED FOR ALL BUFFER LENGTHS PER
 SECTION 94-443 B.
  
 3. EXISTING CANOPIES SHOULD BE REMOVED AND BUFFER TREES
 PROVIDED ALONG S DIXIE LANDSCAPE BUFFERS AS REQUIRED,
 AND PROVIDE REQUIRED TREES IN THE TERMINAL ISLANDS AT
 THE END OF ROWS OF PARKING.
  
 4. PLEASE INDICATE THE WIDTH OF ALL LANDSCAPE BUFFERS
 ON THE LANDSCAPE PLAN.
  
 5. PLEASE CHANGE THE DROUGHT TOLERANCE LEVEL OF
 FELICIUM DECIPIENS TO MEDIUM ON THE PLANT LIST.
  
 6. PLEASE INDICATE THE WIDTH OF THE SIDEWALK ALONG S
 DIXIE. IF WIDE ENOUGH, PLEASE ADD STREET TREES WITH
 TREE GRATES. STREET TREES LOCATED IN A SIDEWALK SHALL
 HAVE STRUCTURAL SOIL EXTENDING 5 FEET IN ALL DIRECTIONS
 UP TO THE CURB. INDICATE STRUCTURAL SOIL LOCATIONS AND
 PROVIDE A TYPICAL STRUCTURAL SOIL DETAIL ON THE
 LANDSCAPE DETAIL PAGE.
  
 7. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 8. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 9. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED
 EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC.,
 AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT
 AND UTILITIES.
  
 10. PLEASE PROVIDE LANDSCAPE SCREENING HEDGE AROUND THE
 WEST SIDE AND REAR OF THE DUMPSTER ENCLOSURE.
  
 11. PLEASE PROVIDE ADDITIONAL LANDSCAPING AROUND THE
 STRUCTURE TO MEET THE 30% REQUIREMENT FOR TREES, SHRUBS
 OR HEDGES PER SECTION 94-443 (E)(1).
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 02-08-2016 Cont ID  
Sent By cranford Date 02-08-2016 Time 14:06 Rev Time 0.00
Received By cranford Date 02-08-2016 Time 14:06 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 06-01-2016 Cont ID  
Sent By tward Date 06-01-2016 Time 10:57 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2016-06-01 10:56:47REVISED COMMENT NO. 10 OF THE 2/10/16 ENGINEERING PPRC
 COMMENTS HAS BEEN ADDRESSED. THERE IS THE FOLLOWING
 CALLOUT TO A FLAMINGO DRIVE DRIVEWAY APRON ON SHEET 8
 OF 8 (SIGNED AND SEALED 3/16/16 BY RICHARD REIKENIS):
 "REMOVE UNUSED CURB CUTS (TYP)".
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 02-08-2016 Cont ID  
Sent By cranford Date 02-08-2016 Time 14:07 Rev Time 0.00
Received By cranford Date 02-08-2016 Time 14:07 Sent To  
Notes
2016-02-08 14:07:31SEE COMMENTS UNDER ENG PPRC

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 02-08-2016 Cont ID  
Sent By cranford Date 02-08-2016 Time 14:07 Rev Time 0.00
Received By cranford Date 02-08-2016 Time 14:06 Sent To  
Notes
2016-02-08 14:06:58SEE COMMENTS UNDER ENG PPRC

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 02-08-2016 Cont ID  
Sent By cranford Date 02-08-2016 Time 14:07 Rev Time 0.00
Received By cranford Date 02-08-2016 Time 14:07 Sent To  
Notes
2016-02-08 14:07:15SEE COMMENTS UNDER ENG PPRC

Review Stop Z ZONING
Rev No 4 Status P Date 06-01-2016 Cont ID  
Sent By llouie Date 06-01-2016 Time   Rev Time 0.00
Received By llouie Date 06-01-2016 Time   Sent To  
Notes
2016-06-01 16:32:31SUBJECT TO THE FOLLOWING CONDITIONS:
  
 1. SIGNAGE IS NOT A PART OF THIS APPROVAL AND SHALL BE
 REVIEWED SEPARATELY AT TIME OF BUILDING PERMIT.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES ? PLANNING DIVISION.
  
 3. AN ENGINEERING DEVELOPMENT PERMIT SHALL BE REQUIRED
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
  
 4. DRIVE APRONS OR ROAD ACCESS NOT NEEDED SHALL BE
 REPLACED WITH SIDEWALK AND CURB.
  
 5. SIDEWALKS OR ENTRY WAYS IN THE RIGHT-OF-WAY COMPOSED
 OF PAVER DESIGN OTHER THAN CONCRETE SURFACE AS PER CITY
 STANDARD WILL REQUIRE A DEVELOPER MAINTENANCE AND
 RESPONSIBILITY AGREEMENT.
  
 6. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE SCHOOL BUILDING, THE APPLICANT SHALL APPLY FOR
 AN FDOT PERMIT FOR IMPROVEMENTS INCLUDING STREET TREES
 AT THIRTY FOOT SPACING, STRUCTURAL SOIL, TREE GRATES
 AND IRRIGATION IN THE SOUTH DIXIE RIGHT OF WAY ADJACENT
 TO THE PROPERTY FROM FLAMINGO DRIVE TO BISCAYNE DRIVE.
 TREE SPECIES AND DETAILS WILL BE AS APPROVED AND
 PERMITTED BY FDOT. THE IMPROVEMENTS PERMITTED BY FDOT
 SHALL BE INSTALLED WITHIN SIX MONTHS OF THE ISSUANCE OF
 THE CERTIFICATE OF OCCUPANCY. THE PLANNING AND ZONING
 ADMINISTRATOR MAY GRANT A ONE-TIME EXTENSION FOR
 INSTALLATION AT THE REQUEST OF THE APPLICANT WITH GOOD
 CAUSE.
  
 7. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE LANDSCAPING AND IRRIGATION
 MAINTENANCE, INCLUDING STREET TREES AT 30 FOOT SPACING,
 STRUCTURAL SOIL, TREE GRATES AND IRRIGATION IN THE
 SOUTH DIXIE RIGHT-OF-WAY ADJACENT TO THE PROPERTY FROM
 FLAMINGO DRIVE TO BISCAYNE DRIVE. A SEPARATE
 MAINTENANCE AGREEMENT WITH THE CITY SHALL BE REQUIRED.
  

Review Stop Z ZONING
Rev No 3 Status F Date 05-25-2016 Cont ID  
Sent By llouie Date 05-26-2016 Time   Rev Time 0.00
Received By llouie Date 05-26-2016 Time   Sent To  
Notes
2016-05-26 14:29:17GENERAL COMMENTS:
  
 1.) REPEAT COMMENT FROM 2/5/16 AND 5/13/16: PROVIDE
 LETTERS FROM THE FOLLOWING PUBLIC UTILITIES CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISION OF
 THEIR SERVICES: FPU AND FPL. LETTERS FROM FPU AND FPL
 HAVE NOT BEEN PROVIDED TO STAFF. PLEASE NOTE THAT THE
 UTILITY LETTERS ARE REQUIRED PRIOR TO SITE PLAN
 APPROVAL.
  
 2.) ALL FINAL PLANS SHALL BE SIGNED, DATED AND SEALED
 BY A FLORIDA REGISTERED ARCHITECT/LANDSCAPE
 ARCHITECT/ENGINEER.
  
 SITE PLAN:
  
 1.) PROPOSED LIGHT POLE FIXTURES AT THE SOUTH EAST
 PARKING LOT IS IN CONFLICT WITH THE PARKING SPACES. DUE
 TO THE BUMP OUT TO ACCOMMODATE THE TWO (2) LIGHT
 FIXTURES ON THE LOT, WHICH IMPACTS FOUR (4) PARKING
 STALLS, THE STALLS DO NOT MEET THE MINIMUM REQUIREMENT
 FOR PARKING STALL DIMENSIONS. PLEASE ADDRESS.
  
 2.) WHY ARE THE PROPOSED LIGHT FIXTURES AT THE
 SOUTHWEST PARKING LOT LOCATED APPROXIMATELY 19 FT. FROM
 THE PARKING STALLS? THE PURPOSE OF PROVIDING THE
 FIXTURES IS TO PROVIDE LIGHTING TO THE PARKING LOT.
 THIS DOES NOT SEEM LOGICAL. PLEASE ADDRESS AND/OR
 PROVIDE AN EXPLANATION.
  
 ACHITECTURAL FLOOR PLANS AND ELEVATIONS:
  
 1.) THE REVISED FLOOR PLANS/ELEVATIONS SEEM TO BE
 MISSING FROM THE RESUBMITTAL PACKET. PLEASE INCLUDE
 REVISED STAMPED AND SEALED FLOOR PLANS AND ELEVATIONS
 IN THE RESUBMITTAL PACKET. ENSURE THAT THE FLOOR PLAN,
 ELEVATIONS AND SITE PLAN ARE ALL CONSISTENT.
  
 LIGHTING:
  
 1.) PROVIDE A PHOTOMETRIC PLAN SHOWING THE LOCATION OF
 ALL LIGHT FIXTURES PROPOSED IN THE PROJECT. LIGHT POLES
 SHALL BE SETBACK AT LEAST 5 FT. FROM THE PROPERTY
 LINES. PLEASE ENSURE THAT THE LOCATION OF ANY LIGHT
 POLE FIXTURE WILL NOT BE IN CONFLICT WITH ANY EXISTING
 UTILITIES AND/OR PROPOSED LANDSCAPING. [ACCORDING TO
 THE APPLICANT'S RESPONSE LETTER TO ZONING'S COMMENTS,
 DATED 5/25/16, THE APPLICANT IS WORKING ON REVISING THE
 PHOTOMETRIC PLAN TO COMPLY WITH ZONING CODE
 REQUIREMENTS.]
  
 NOTES:
  
 * A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO
 THE REMOVAL OF ANY TREES ON THE PROJECT SITE.
  
 * AN EMAIL FROM JON SCHMIDT TO STEVE ANDERSON OF PALM
 TRAN, DATED APRIL 20, 2016, WAS PROVIDED AS PART OF THE
 RESUBMITTAL PACKET. THE LETTER INDICATES THAT THERE WAS
 A DISCUSSION ON RELOCATION OF SOUTHBOUND PALM TRAN BUS
 STOP #114 TO THE NEXT BLOCK TO THE SOUTH. STAFF WILL
 NEED CONFIRMATION FROM STEVE ANDERSON OF PALM TRAN
 CONFIRMING THE COORDINATION PRIOR TO THE RELOCATION OF
 THE BUS STOP. PLEASE PROVIDE THIS DOCUMENTATION UPON
 RECEIPT.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE
 (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND
 AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT
 CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($200).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 2 Status F Date 05-13-2016 Cont ID  
Sent By llouie Date 05-13-2016 Time   Rev Time 0.00
Received By llouie Date 05-13-2016 Time   Sent To  
Notes
2016-05-13 15:07:17GENERAL COMMENTS:
  
 1.) REPEAT COMMENT FROM 2/5/16: PROVIDE LETTERS FROM
 THE FOLLOWING PUBLIC UTILITIES CONFIRMING THAT THE
 PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS
 OR OTHERWISE INTERFERE WITH THE PROVISION OF THEIR
 SERVICES: AT&T, FPU FPL. PLEASE NOTE THAT THE UTILITY
 LETTERS ARE REQUIRED PRIOR TO SITE PLAN APPROVAL.
  
 2.) REVISE THE LOCATION MAP ON SHEETS SP-1, LI-1, LP-1
 AND TD-1 TO INCLUDE THE PARCELS SOUTH OF BISCAYNE
 DRIVE.
  
 3.) CONCURRENCY APPROVAL WAS GRANTED FOR 150 STUDENTS
 PER THE TPS LETTER ISSUED BY THE PALM BEACH COUNTY
 DEPARTMENT OF ENGINEERING AND PUBLIC WORKS - TRAFFIC
 DIVISION, DATED APRIL 14, 2016. PLEASE CORRECT THE
 INFORMATION IN THE SITE DATA TABULAR TO REFLECT THE
 CONCURRENCY APPROVAL ISSUED BY THE COUNTY.
  
 4.) ALL FINAL PLANS SHALL BE SIGNED, DATED AND SEALED
 BY A FLORIDA REGISTERED ARCHITECT/LANDSCAPE
 ARCHITECT/ENGINEER.
  
 SITE PLAN:
  
 1.) REPEAT COMMENT FROM 2/5/16: ACCORDING TO GOOGLE
 STREET VIEW, THERE SEEMS TO BE AN EXISTING BUS STOP AND
 BENCH IN FRONT OF THE PROPERTY ALONG SOUTH DIXIE HWY
 WHICH IS NOT DEPICTED IN THE SURVEY. THE BOUNDARY
 SURVEY SHOULD BE UPDATED TO REFLECT THIS EXISTING
 FEATURE.
  
 2.) REPEAT COMMENT FROM 2/5/16: THE APPLICANT'S
 RESPONSE TO SITE PLAN COMMENT #8 STATES THAT A
 "LIGHTING PLAN WILL BE SUBMITTED WITH BUILDING PERMIT";
 HOWEVER, A PHOTOMETRIC PLAN IS NEEDED AT THIS POINT IN
 TIME TO ENSURE THAT THERE IS NO CONFLICT WITH THE
 PROPOSED LANDSCAPING FOR THE PROJECT.
  
 3.) THE APPLICANT HAS NOTED IN THE RESPONSE LETTER TO
 STAFF'S PPRC COMMENTS (FOR ZONING SITE PLAN COMMENT
 #1), DATED 2/17/16, THAT "THE EXISTING UTILITIES ARE TO
 BE RELOCATED EITHER UNDERGROUND OR AROUND THE PERIMETER
 OF THE SITE PENDING FPL'S DETERMINATION." DOES THIS
 APPLY TO ALL OVERHEAD (O/H) POWER LINES ON THE
 PROPERTY? THE SITE PLAN INDICATES THAT THE O/H LINES
 RUNNING ACROSS PARCELS 5 AND 6 WILL BE BURIED ON SITE;
 HOWEVER, THERE IS ANOTHER O/H LINE RUNNING DIAGONALLY
 ACROSS PARCEL 1, WHICH IS NOT DEPICTED IN THE SITE
 PLAN. PLEASE CLARIFY THE PROVISIONS FOR THIS O/H LINE.
  
 4.) PROVIDE A DETAIL OF THE PROPOSED DECORATIVE WALL
 AND FENCE.
  
 5.) HOW TALL IS THE EXISTING CHAIN LINK FENCE ALONG
 BISCAYNE DRIVE?
  
 6.) FENCES/WALL SHALL NOT EXCEED 4 FT. IN HEIGHT WITHIN
 THE REQUIRED FRONT SETBACK. PLEASE CLARIFY THE
 EXTENT/LOCATION OF THE PROPOSED 8 FT. HIGH CHAIN LINK
 FENCE ON THE WEST SIDE OF THE SCHOOL PARCEL, AND THE 6
 FT. HIGH DECORATIVE FENCE WITH ROLLING GATE ALONG
 BISCAYNE DRIVE. [ZLDR S.94-302(C)]
  
 LANDSCAPE PLAN:
  
 1.) REPEAT COMMENT FROM 2/5/16: A MINIMUM 5 FT. WIDE
 LANDSCAPE BUFFER SHALL BE PROVIDED ALONG ALL PROPERTY
 LINES FOR THE PROPOSED SCHOOL PARKING LOTS, SOUTH OF
 BISCAYNE DRIVE. A VARIANCE TO THE BUFFER WILL BE
 REQUIRED IF THE BUFFERING REQUIREMENTS CANNOT BE MET BY
 THE APPLICANT. [PER A TELEPHONE CONVERSATION WITH THE
 APPLICANT ON 5/11/16, CHANGES ARE BEING PROPOSED TO THE
 PROPOSED SCHOOL PARKING LOT TO MEET THE MINIMUM ZLDR
 STANDARDS FOR LANDSCAPING. COMPLIANCE WITH THE ZLDR
 MUST BE REFLECTED IN THE REVISED PLANS.]
  
 ARCHITECTURAL FLOOR PLANS AND ELEVATIONS:
  
 1.) ELEVATIONS DO NOT MATCH WHAT IS DEPICTED IN THE
 SITE PLAN. PLEASE CORRECT FOR CONSISTENCY (I.E.
 EXISTING CANOPY AND PROPOSED WALL IS MISSING FROM THE
 EAST ELEVATION).
  
 2.) PROVIDE DIMENSIONS FOR THE ELEVATIONS.
  
 NOTES:
 * A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO
 THE REMOVAL OF ANY TREES ON THE PROJECT SITE.
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE
 (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND
 AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT
 CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 02-05-2016 Cont ID  
Sent By llouie Date 02-05-2016 Time 16:09 Rev Time 0.00
Received By llouie Date 02-05-2016 Time 16:09 Sent To  
Notes
2016-02-05 16:15:03GENERAL COMMENTS:
  
 1.) A CLASS B SPECIAL USE PERMIT IS REQUIRED FOR THE
 PROPOSED OFFSITE ACCESSORY PARKING AREA.
  
 2.) UNITY OF TITLE, JOINING THE FOLLOWING PCNS WILL BE
 REQUIRED: 74-43-43-28-06-011-0040, 0050, 0060, 0100,
 0120 AND 0131.
  
 3.) A TPS LETTER FROM THE PALM BEACH COUNTY TRAFFIC
 DIVISION IS REQUIRED.
  
 4.) PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC
 UTILITIES DEPARTMENT HAS REVIEWED THE PROPOSAL FOR
 WATER, SEWAGE TREATMENT, STORM DRAINAGE, AND GARBAGE
 COLLECTION.
  
 5.) PROVIDE LETTERS FROM THE FOLLOWING PUBLIC UTILITIES
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISION OF THEIR SERVICES: AT&T, FPU, FPL, AND
 COMCAST.
  
 6.) A LICENSE AGREEMENT FOR THE TEMPORARY USE OF THE
 ALLEYWAY WILL NEED TO BE COORDINATED WITH THE CITY
 ATTORNEY'S OFFICE, AND APPROVED BY THE CITY COMMISSION.
  
  
 SITE PLAN:
  
 1.) THERE SEEMS TO BE EXISTING UTILITY POLES AND
 OVERHEAD POWER LINES NEAR THE PROPOSED PLAY AREA AND
 PLAY FIELDS, WHICH DOES NOT SEEM TO CREATE A SAFE
 ENVIRONMENT FOR CHILDREN. ARE THERE ANY PROVISIONS TO
 RELOCATE THE POWER LINES (I.E. UNDERGROUND)?
  
 2.) THE EXISTING METAL CANOPIES ON PARCELS 1 AND 4 (AS
 DEPICTED IN THE SURVEY) SEEM TO BE IN CONFLICT WITH THE
 PROPOSED PARKING AND LANDSCAPING IN THE SITE PLAN AND
 LANDSCAPE PLAN. PLEASE REMOVE THE CANOPIES FROM THE
 PLANS.
  
 3.) ACCORDING TO GOOGLE STREET VIEW, THERE SEEMS TO BE
 AN EXISTING BUS STOP AND BENCH IN FRONT OF THE PROPERTY
 ALONG SOUTH DIXIE HWY WHICH IS NOT DEPICTED IN THE
 SURVEY OR THE SITE PLAN. THE BOUNDARY SURVEY AND PLANS
 SHOULD BE UPDATED TO REFLECT THIS EXISTING FEATURE.
 ALSO, PLEASE ENSURE THAT THE LOCATION OF THE EXISTING
 TRANSIT FACILITIES WILL NOT BE IN CONFLICT WITH THE
 PROPOSED DEVELOPMENT.
  
 4.) THE PROJECT IS PROPOSING A TOTAL OF 34 PARKING
 SPACES. BASED ON THIS TOTAL PARKING COUNT, A MINIMUM OF
 TWO (2) DISABLED PARKING SPACES IS REQUIRED. [ZLDR
 S.94-485(O)(1)]
  
 5.) THE MINIMUM SEPARATION BETWEEN EACH BIKE RACK IS 30
 INCHES AND THE MINIMUM DISTANCE BETWEEN THE BIKE RACK
 AND THE EDGE OF THE BIKE PAD IS 24 INCHES. PLEASE
 ENSURE ALL DIMENSIONS ARE CONSISTENT WITH THE CITY'S
 BICYCLE PARKING GUIDELINES AND PROVIDE THE DIMENSIONS
 IN THE BIKE RACK DETAIL.
  
 6.) ARCHITECTURAL ELEVATIONS AND FLOOR PLANS ARE
 MISSING FROM THE SUBMITTAL. PLEASE PROVIDE.
  
 7.) IS THERE ANY SIGNAGE PROPOSED FOR THE PROJECT?
  
 8.) WILL THERE BE ANY LIGHTING FACILITIES FOR THE
 PROJECT? IF SO, PROVIDE A PHOTOMETRIC PLAN,
 ILLUSTRATING THE LOCATION OF THE LIGHT FIXTURES AND
 LIGHTING INTENSITY.
  
 9.) PROVIDE DIMENSIONS FOR THE OFFSITE ACCESSORY
 PARKING AREA.
  
 10.) ILLUSTRATE THE TURNING RADIUS AT THE STUDENT DROP
 OFF/LOADING AREA.
  
 11.) CORRECT THE FOLLOWING IN THE SITE DATA TABULAR:
 TOTAL SITE AREA: 76,230 SQ. FT. (NOT 76,401 SQ. FT.);
 BICYCLE PARKING REQUIRED/PROPOSED: 1/6 (NOT 2/3);
 VISITOR PARKING REQUIRED: 10 PARKING SPACES (NOT 5
 PARKING SPACES).
  
 12.) PLEASE ENSURE THAT ALL SITE DATA CALCULATIONS
 (I.E. PERCENTAGE OF LANDSCAPED AREA, BUILDING COVERAGE,
 ETC.) IS FOR THE PRIMARY SITE (SCHOOL SITE).
  
 13.) WILL THERE BE ANY SCHOOL/ACTIVITY BUSES? IF SO,
 WHERE WILL THE BUSES BE STORED? PLEASE NOTE THAT THE
 STORAGE OF VEHICLES IS PROHIBITED ON SITE AND IN THE
 PROPOSED ACCESSORY PARKING LOT AREA.
  
  
 LANDSCAPE PLAN:
  
 1.) A MINIMUM 5 FT. WIDE LANDSCAPE BUFFER SHALL BE
 PROVIDED ALONG ALL PROPERTY LINES FOR EACH ACCESSORY
 OFF-SITE PARKING AREA. IN ADDITION TO THE CLASS B
 SPECIAL USE PERMIT TO ALLOW THE OFF-SITE PARKING, THE
 APPLICANT WILL BE REQUIRED TO SEEK WAIVERS FROM THE
 LANDSCAPE BUFFERING REQUIREMENTS IF THIS CANNOT BE MET.
 [ZLDR S.94-273(D)(54)(B.)(7.)]
  
 2.) THERE SEEMS TO BE EXISTING TREES ON THE PROPERTY. A
 TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO THE
 REMOVAL OF ANY TREES ON THE PROJECT SITE.
  
  
 SUGGESTED IMPROVEMENTS:
  
 1.) CONSIDER ADDING A LANDSCAPE SCREEN TO WEST SIDE OF
 THE GUEST PARKING AREA IN ORDER TO SCREEN THE PARKING
 AREA FROM THE PLAYGROUND.
  
 2.) IS THE BIKE RACK INTENDED FOR STUDENT USE? IF SO,
 CONSIDER RELOCATING THE BIKE RACK TO A LOCATION AWAY
 FROM VEHICULAR CIRCULATION AREAS WITH ADEQUATE
 VISIBILITY TO DETER BICYCLE THEFT.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWELVE
 (12) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND
 AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT
 CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  