Plan Review Details - Project Z15110013
Plan Review Stops For Project Z15110013
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-17-2015 Cont ID  
Sent By rbrown Date 12-17-2015 Time 20:23 Rev Time 0.00
Received By rbrown Date 12-17-2015 Time 19:13 Sent To  
Notes
2015-12-17 20:22:51DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN THE PLANS ARE SUBMITTED FOR PERMIT THEY MUST
 CLEARLY IDENTIFY THE LOCATION OF THE TOWER AND
 EQUIPMENT SHELTER. THE LOCATION CALLED OUT AS "CENTER
 PROPOSED TOWER" ON SHEET C-1A APPEARS TO BE WITHIN THE
 FOOTPRINT OF THE "ONE STORY COMMERCIAL BUILDING", AND
 SHEET C-1 DOES NOT SHOW WHERE THE PROPOSED TOWER AND
 EQUIPMENT SHELTER ARE LOCATED ON THE OVERALL SITE PLAN.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 11:46 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-04-2015 Cont ID  
Sent By pleduc Date 12-04-2015 Time   Rev Time 0.00
Received By pleduc Date 12-04-2015 Time 13:38 Sent To  
Notes
2015-12-04 13:40:44THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 7. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By rcaranci Date 12-07-2015 Time 17:04 Rev Time 0.00
Received By rcaranci Date 12-07-2015 Time 17:04 Sent To  
Notes
2015-12-07 17:04:37FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: 501 PALM STREET COMMUNICATIONS TOWER Z15110013
 DECEMBER 3, 2015
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. LANDSCAPING FOR THE COMMUNICATIONS TOWER AND
 ENCLOSURE IS BEING DESIGNED WITH THE SITE PLAN. THE
 FOLLOWING CONDITION OF APPROVAL IS RECOMMENDED :
 CONDITION OF APPROVAL:
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION
 FOR THE TOWER AND ENCLOSURE, LANDSCAPING ADJACENT TO
 THE ENCLOSURE WALL SHALL BE PERMITTED AND INSTALLED PER
 THE LANDSCAPE PLAN APPROVED FOR THE SITE.
  

Review Stop Z ZONING
Rev No 1 Status P Date 12-09-2015 Cont ID  
Sent By jroach Date 12-09-2015 Time   Rev Time  
Received By jroach Date 12-09-2015 Time   Sent To  
Notes
***NONE***