Plan Review Details - Project Z15110008
Plan Review Stops For Project Z15110008
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-17-2015 Cont ID  
Sent By rbrown Date 12-17-2015 Time 18:19 Rev Time 0.00
Received By rbrown Date 12-17-2015 Time 18:19 Sent To  
Notes
2015-12-17 18:24:03NO COMMENTS ON PROPOSED ALLEY ABANDONMENT.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 10:02 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 09:59 Sent To  
Notes
2015-12-07 10:02:05CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 NO OBJECTIONS TO ALLEY ABANDONMENT WITHIN PARCEL
 BOUNDARY.
  
 KELLY CRANFORD, P.E.
 PUBLIC WORKS CIP MANAGER
 [email protected]
 561-494-1098
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-04-2015 Cont ID  
Sent By pleduc Date 12-04-2015 Time   Rev Time 0.00
Received By pleduc Date 12-04-2015 Time 13:26 Sent To  
Notes
2015-12-04 13:35:13THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED ABANDONMENT.
  

Review Stop L LANDSCAPING
Rev No 1 Status P Date 12-04-2015 Cont ID  
Sent By rcaranci Date 12-04-2015 Time 09:14 Rev Time 0.00
Received By rcaranci Date 12-04-2015 Time 09:14 Sent To  
Notes
2015-12-04 09:14:33NO COMMENTS

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 10:03 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 10:03 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 10:03 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 10:03 Sent To  
Notes
2015-12-09 16:07:241. THE SWALE STORAGE VOLUMES FOR SWALES 'A' AND 'B'
 SHOWN IN THE DRAINAGE CALCULATIONS BOX ON SHEET SP-2
 MAY BE OFF BY A FACTOR OF 12. FOR EXAMPLE, SWALE 'B' IS
 SHOWN TO HAVE A (TOP?) SURFACE AREA OF 584 S.F. ON THE
 SITE PLAN. THE TYPICAL SWALE SECTION INDICATES THE
 SWALE DEPTH WILL BE 6 INCHES OR 0.5 FEET. THE VOLUME
 WOULD BE CLOSER TO 270 C.F. INSTEAD OF 3,234 C.F. SHOWN
 IN THE DRAINAGE CALCULATIONS BOX.
  
 2. CORRECTING THE SWALE VOLUMES IN #1 ABOVE RESULTS IN
 THE SWALES PROVIDING ONLY 40% OF THE REQUIRED STORM
 WATER TREATMENT VOLUME (UTILIZING 50% FOR DRY
 RETENTION). INDICATE HOW THE REQUIRED STORM WATER
 TREATMENT VOLUME WILL BE STORED ONSITE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 10:03 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 10:03 Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 12-07-2015 Cont ID  
Sent By cranford Date 12-07-2015 Time 10:02 Rev Time 0.00
Received By cranford Date 12-07-2015 Time 10:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 12-04-2015 Cont ID  
Sent By dkittred Date 12-04-2015 Time 12:17 Rev Time 0.00
Received By dkittred Date 12-04-2015 Time 12:14 Sent To  
Notes
2015-12-04 12:16:57PLANNING AND ZONING COMMENTS:
  
 12/4/15
  
 1. NO COMMENTS REGARDING THE ABANDONMENT REQUEST.
  
 2. REQUEST TO BE SCHEDULED FOR CITY COMMISSION HEARING
 PENDING COMMENTS RECEIVED AT THE DEC. 9, 2015 PPRC
 MEETING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

  Print