Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 11-12-2015 Cont ID  
Sent By rbrown Date 11-12-2015 Time 10:38 Rev Time 0.00
Received By rbrown Date 11-12-2015 Time 10:38 Sent To  
Notes
2015-11-12 10:43:37DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE PROPOSAL TO USE THE EXISTING PARKING LOT IS
 NOTED. THE NEAREST PARKING SPACE TO THE "CONNECT WALK"
 MSUT BE AN ACCESSIBLE PARKING SPACE IF NO MORE THAN 25
 PARKING SPACES ARE REQUIRED FOR THE GOLF FACILITY. IF
 BETWEEN 25 AND 50 PARKING SPACES ARE REQUIRED FOR THE
 GOLF FACILITY, THE NEAREST TWO PARKING SPACES TO THE
 "CONNECT" WALK SHALL BE ACCESSIBLE. THE MINIMUM NUMBER
 OF ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN
 ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY
 CODE. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN
 OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION
 502 OF FLORIDA ACCESSIBILITY CODE
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  
2015-11-04 16:50:26 
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 11-09-2015 Cont ID  
Sent By cranford Date 11-09-2015 Time 13:37 Rev Time 0.00
Received By cranford Date 11-09-2015 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 11-24-2015 Cont ID  
Sent By pleduc Date 11-24-2015 Time   Rev Time 0.00
Received By pleduc Date 11-24-2015 Time 16:15 Sent To  
Notes
2015-11-24 16:16:01AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 11.17.15, FROM ANDERSON ARCHITECTURE, INC, TO THE CITY
 OF WEST PALM BEACH, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED WITH THE
 FOLLOWING ADDITIONALL COMMENTS.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. IS THE SCREENING FOR THE HITTING CAGE FIRE
 RETARDENT?
  
 THE APPLICANT PROVIDED THAT IT IS NOT AND HAS A MELTING
 POINT OF 482 DEGRESS F. THE APPLICANT IS STRONGLY
 ENCOURAGED TO RESEACH AND INSTALL A FIRE RETARDENT
 SCEEN OR APPLY A FIRE RETARDENT MATERIAL ONTO THE
 SCREEN FOR FIRE AND LIFE SAFETY PURPOSES. THE POTENTIAL
 FOR A RAPID BURNING SURFACE AREA IS EXTREMELY HIGH IN
 THE EVENT THE SCEEN WERE TO INTERACT WITH A IGNITION
 SOURCE, I.E. A BICK BUTANE HAND LIGHTER FLAME BURNS AT
 600 DEGREES. THE SCREEN WILL FAIL AND MELT AROUND
 ANYONE WHO IS UNDER IT.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 2. NO SMOKING SIGNS SHALL BE INSTALLED AT THE FRONT OF
 THE HITTING CAGE.
  
 ADDRESSED
  
 3. A FIRE EXTINGUSIHERS SHALL BE INSTALLED AT EACH SIDE
 OF THE FRONT OF THE HITTING CAGE.
  
 ADDRESSED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 11-05-2015 Cont ID  
Sent By pleduc Date 11-05-2015 Time   Rev Time 0.00
Received By pleduc Date 11-05-2015 Time 12:22 Sent To  
Notes
2015-11-05 12:29:53THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. IS THE SCREENING FOR THE HITTING CAGE FIRE
 RETARDENT?
  
 2. NO SMOKING SIGNS SHALL BE INSTALLED AT THE FRONT OF
 THE HITTING CAGE.
  
 3. A FIRE EXTINGUSIHERS SHALL BE INSTALLED AT EACH SIDE
 OF THE FRONT OF THE HITTING CAGE.
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 11-30-2015 Cont ID  
Sent By rcaranci Date 11-30-2015 Time 11:48 Rev Time 0.00
Received By rcaranci Date 11-30-2015 Time 11:47 Sent To  
Notes
2015-11-30 11:48:30FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: NORTHWOOD UNIVERSITY CSPD GOLF TRAINING
 FACILITY Z15100013
 NOVEMBER 30, 2015
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE SHOW ANY TREES OR LANDSCAPING THAT
 MAY BE AFFECTED BY THE INSTALLATION OF THE WALKWAY
 CONNECTING TO THE STUDENT HOUSING SOUTH OF THE PARKING
 AREA.
  
 2. SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL AND
 SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 3. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES INCLUDING THE METER
 RACK.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 11-04-2015 Cont ID  
Sent By rcaranci Date 11-04-2015 Time 16:49 Rev Time 0.00
Received By rcaranci Date 11-04-2015 Time 16:47 Sent To  
Notes
2015-11-05 16:12:34FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: NORTHWOOD UNIVERSITY CSPD GOLF TRAINING
 FACILITY Z15100013
 NOVEMBER 4, 2015
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE SHOW ANY TREES OR LANDSCAPING THAT MAY BE
 AFFECTED BY THE INSTALLATION OF THE WALKWAY SOUTH OF
 THE PARKING AREA CONNECTING TO THE STUDENT HOUSING.
  
 2. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 3. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES INCLUDING THE METER RACK.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 11-09-2015 Cont ID  
Sent By cranford Date 11-09-2015 Time 13:38 Rev Time 0.00
Received By cranford Date 11-09-2015 Time 13:38 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 11-09-2015 Cont ID  
Sent By cranford Date 11-09-2015 Time 13:38 Rev Time 0.00
Received By cranford Date 11-09-2015 Time 13:37 Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 11-09-2015 Cont ID  
Sent By cranford Date 11-09-2015 Time 13:37 Rev Time 0.00
Received By cranford Date 11-09-2015 Time 13:37 Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 11-09-2015 Cont ID  
Sent By cranford Date 11-09-2015 Time 13:37 Rev Time 0.00
Received By cranford Date 11-09-2015 Time 13:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 12-14-2015 Cont ID  
Sent By eschneid Date 12-14-2015 Time 15:55 Rev Time 0.50
Received By eschneid Date 12-14-2015 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 11-05-2015 Cont ID  
Sent By eschneid Date 11-05-2015 Time 16:10 Rev Time 0.50
Received By eschneid Date 11-05-2015 Time 16:09 Sent To  
Notes
2015-11-05 16:10:24CASE NO. PB1069T
 NORTHWOOD UNIVERSITY CSPD GOLF MINOR AMENDMENT
 2331 NORTHWOOD UNIVERSITY DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY FEBRUARY 12,
 2016), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) PLEASE PROVIDE AN ABSTRACTED SURVEY WHICH INCLUDES
 THE AREA INCLUDED AS PART OF THIS AMENDMENT.
  
 2) THE NEW CONNECTING WALK THROUGH THE EXISTING PARKING
 LOT LANDSCAPE ISLAND SHALL BE INCLUDED WITH THE
 LANDSCAPE PLAN. THE LANDSCAPE ISLAND CURRENTLY HAS
 THREE MATURE TREES IN IT. THE LANDSCAPE ISLAND IS
 REQUIRED TO CONTAIN AT LEAST ONE INTERIOR LANDSCAPE
 ISLAND TREE AFTER THE INSTALLATION OF THE CONNECTING
 WALK. THIS NEEDS TO BE VERIFIED ON THE LANDSCAPE PLAN.
 ANY TREES REMOVED SHALL BE INCLUDED ON THE MITIGATION
 TABLE.
  