Plan Review Details - Project Z15090019
Plan Review Stops For Project Z15090019
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 12-15-2015 Cont ID  
Sent By eschneid Date 12-15-2015 Time 10:33 Rev Time 0.00
Received By eschneid Date 12-15-2015 Time 10:33 Sent To  
Notes
2015-12-15 10:33:39SEVEN ADA SPACES PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 10-14-2015 Cont ID  
Sent By rbrown Date 10-14-2015 Time 12:02 Rev Time 0.00
Received By rbrown Date 10-14-2015 Time 12:02 Sent To  
Notes
2015-10-14 12:10:31DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. NUMBER OF ACCESSIBLE PARKING SPACES. SHEET GA-0.1
 SHOWS 5 ACCESSIBLE SPACES PROVIDED. THE PLAN STATES 255
 FOR THE TOTAL NUMBER OF PARKING SPACES PROPOSED. 7
 ACCESSIBLE PARKING SPACES ARE ACTUALLY REQUIRED WHEN
 BETWEEN 200 AND 300 PARKING SPACES ARE BEING PROVIDED.
 IT IS NOTED THAT MANY OF THE SPACES ARE VALET SPACES,
 BUT IT CANNOT BE ASSUMED THAT A VALET CAN DRIVE
 ACCESSIBLE VEHICLES THAT MAY HAVE MODIFIED CONTROLS.
 THE MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES
 PROVIDED SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF
 FLORIDA ACCESSIBILITY CODE.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 10-13-2015 Cont ID  
Sent By cranford Date 10-13-2015 Time 13:31 Rev Time 0.00
Received By cranford Date 10-13-2015 Time 13:29 Sent To  
Notes
2015-10-13 13:31:44CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY?S
 ENGINEERING DESIGN STANDARDS. HTTP://WPB.ORG/ENGINEERIN
 G/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/
  
 2. ANY EXISTING UTILITY SERVICE LINES NOT PROPOSED TO
 BE UTILIZED ARE TO BE REMOVED BACK TO THE MAIN.
 (SECTION 2.23 OF THE CITY RIGHT OF WAY CONSTRUCTION
 STANDARDS MANUAL)
  
 3. PLEASE SHOW THE ACCESSIBLE PATH BETWEEN THE HOTEL
 ENTRANCE AND THE PROPOSED ACCESSIBLE PARKING SPACES.
  
 4. PLEASE REVISE THE RESURFACING OF FLORIDA TO BE EVEN
 FROM EAST TO WEST.
  
 5. FINAL DESIGN OF FLORIDA AVENUE TO BE COORDINATED
 WITH THE CITY TRAFFIC ENGINEER.
  
 6. PLEASE SHOW THE EXISTING SIDEWALK ALONG THE SOUTHERN
 SIDE OF ALABAMA AVENUE. HOW IS THE PROPOSED CURB RAMP
 AT THE SOUTHEASTERN CORNER OF THE PROPERTY PROPOSED TO
 CONNECT TO THE EXISTING SIDEWALK? IS A CROSS WALK
 PROPOSED?
  
 7. THE PROPOSED SIDEWALK ALONG THE NORTH SIDE OF
 ALABAMA ENDS AT THE WESTERN PARKING LOT ENTRANCE. WHERE
 ARE PEDESTRIANS INTENDED TO GO FROM THAT POINT? IS A
 CURB RAMP PROPOSED AT THAT LOCATION?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL MODIFICATION
 (E14020003) WILL BE REQUIRED FROM THE ENGINEERING
 DIVISION OF THE PUBLIC WORKS DEPARTMENT. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 BRIAN COLLINS, PE
 CITY TRAFFIC ENGINEER
 [email protected]
 561-494-1040
  
 FERDINAND RIVERA
 PUBLIC WORKS OPERATIONS MANAGER
 [email protected]
 561-822-2076
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 561-494-1120
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 10-09-2015 Cont ID  
Sent By pleduc Date 10-09-2015 Time   Rev Time 0.00
Received By pleduc Date 10-09-2015 Time 15:09 Sent To  
Notes
2015-10-09 16:18:51THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDINGS SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. THE SEPARATION AND OPENING PROTECTION BETWEEN THE
 PARKING GARAGE AND HOTEL SHALL BE IN ACCORDANCE AND
 COMPLIANCE WITH THE SPECIFIC AND MOST STRINGENT
 PROVISION REQUIREMENT OF EITHER CHAPTER.
  
 8. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THE
 HIGH RISE STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE LEVELS OR THIRTY FEET
 WHILE BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 ADDITIONAL INFPORMATION IS NEEDED TO DETERMINE IF THE
 SEPARATE 3-STORY BUILDING IS REQUIRED TO HAVE A FIRE
 SPRINKLER SYSTEM.
  
 9 . A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR EACH STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 10. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR
 THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND INDICATED
 ON THE PLANS.
  
 11. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE.
  
 12. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN.
  
 13. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 IF AN EMERGENCY POWER GENERATOR IS PROPOSED, WHAT IS
 (ARE) THE PRIMARY AND SECONDARY POWER SOURCES?
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 15. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 16. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
 17. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 18. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY
 INDICATED ON THE BUILDING PLAN.
  
 19. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT
 AND/OR TENANT SHALL BE CLEARLY INDICATED AND
 ILLUSTRATED ON THE BUILDING PLAN.
  
 20. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY
 INDICATED AND ILLUSTRATED ON THE BUILDING PLAN.
  
 21. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 22. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 23. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 24. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED
 TO EACH APARTMENT AND/OR TENANT. THESE INSTRUCTIONS ARE
 TO INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND
 ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR ALARM
 ACTIVATION.
  
 25. IT APPEARS THAT THE12TH FLOOR POOL DECK REQUIRES
 ACCESS TO A SECOND EXIT. ONLY ACCESS TO ONE IS
 INDICATED.
  
 26. DOORS TO ACCESS EXIT STAIRS 1 & 2 ARE NOT INDICATED
 ON FLOORS 5 & 6.
  
 27. COMMAND ROOM
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 5. A WORK TABLE.
 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 13. FIRE PUMP STATUS INDICATORS
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 16. CONTROLS REQUIRED FOR SMOKE CONTROL
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 28. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM
 FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE
 RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 29. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 30. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-01-2015 Cont ID  
Sent By rcaranci Date 12-01-2015 Time 16:26 Rev Time 0.00
Received By rcaranci Date 12-01-2015 Time 16:26 Sent To  
Notes
2015-12-01 16:37:35FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: CONVENTION CENTER HOTEL PARKING Z15090019
 NOVEMBER 30, 2015
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE SEPARATE CALCULATIONS FOR
 THE AREA OF CHANGE FOR THIS PETITION, INCLUDING OVERALL
 TREE AND SHRUB REQUIREMENTS FOR 40 PERCENT REQUIRED
 OPEN SPACE PER 94-442(B)(2), BUFFER TREE CALCULATIONS
 PER 94-443(B), AND PARKING LOT LANDSCAPE REQUIREMENTS
 PER 94-443(C).
  
 2. SATISFIED. PLEASE PROVIDE A 5 FOOT LANDSCAPE BUFFER
 ALONG THE EAST PROPERTY LINE PER 94-443 (B), AND
 INDICATE THE 5 FOOT BUFFER ALONG THE NORTH, WEST AND
 SOUTH PROPERTY LINES.
  
 3. SATISFIED. PLEASE PROVIDE A SEPARATE PLANT LIST OF
 TREES AND SHRUBS FOR THE PARKING LOT AREA WITH ALL
 REQUIRED INFORMATION TO SHOW COMPLIANCE WITH THE ABOVE
 REFERENCED SECTIONS.
  
 ADDITIONAL COMMENTS 12/1/15:
 4. PLEASE PROVIDE A TREE OR PALM CLUSTER IN THE
 INTERIOR LANDSCAPE ISLANDS ADJACENT TO EACH ROW OF
 PARKING.
  
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 10-13-2015 Cont ID  
Sent By rcaranci Date 10-13-2015 Time 14:53 Rev Time 0.00
Received By rcaranci Date 10-13-2015 Time 14:53 Sent To  
Notes
2015-10-13 14:54:22I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE SEPARATE CALCULATIONS FOR THE AREA OF
 CHANGE FOR THIS PETITION, INCLUDING OVERALL TREE AND
 SHRUB REQUIREMENTS FOR 40 PERCENT REQUIRED OPEN SPACE
 PER 94-442(B)(2), BUFFER TREE CALCULATIONS PER
 94-443(B), AND PARKING LOT LANDSCAPE REQUIREMENTS PER
 94-443(C).
  
 2. PLEASE PROVIDE A 5 FOOT LANDSCAPE BUFFER ALONG THE
 EAST PROPERTY LINE PER 94-443 (B), AND INDICATE THE 5
 FOOT BUFFER ALONG THE NORTH, WEST AND SOUTH PROPERTY
 LINES.
  
 3. PLEASE PROVIDE A SEPARATE PLANT LIST OF TREES AND
 SHRUBS FOR THE PARKING LOT AREA WITH ALL REQUIRED
 INFORMATION TO SHOW COMPLIANCE WITH THE ABOVE
 REFERENCED SECTIONS.
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 RAY CARANCI, LANDSCAPE PLANNER
 561-822-1462
  
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2015-10-23 10:17:24SEE COMMENTS UNDER ENGINEERING STOP.

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2015-10-23 10:17:36SEE COMMENTS UNDER ENGINEERING STOP.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2015-10-23 10:17:45SEE COMMENTS UNDER ENGINEERING STOP.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By eschneid Date 12-15-2015 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 10-13-2015 Cont ID  
Sent By eschneid Date 10-13-2015 Time 20:46 Rev Time 3.00
Received By eschneid Date 10-13-2015 Time 20:46 Sent To  
Notes
2015-10-13 20:47:00CASE NO. PB 950TTTT
 HILTON HOTEL SURFACE PARKING LOT
 900 FLORIDA AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 DECEMBER 14, 2015), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) THE PARKING LOT IS FOR 255 PARKING SPACES, WHICH
 REQUIRES THE PROVISION OF SEVEN (7) ADA PARKING SPACES.
  
 2) STAFF HAS CONCERNS WITH THE THREE DEEP VALET SPACES
 AND THE MANEUVERING NEEDED TO GET CARS FROM THE
 FURTHEST INSIDE SPACE. PLEASE REMEMBER THAT THE HILTON
 HOTEL PARKING MANAGEMENT PLAN GOVERNS THE VALET
 OPERATIONS. ADDITIONALLY, THE HOTEL PARKING MAY NOT
 CONVERT TO NON-VALET OPERATIONS AT ANY TIME DUE TO THE
 USE OF THE TANDEM SPACES FOR REQUIRED PARKING.
  
 3) DIMENSION LINES WERE NOT PROVIDED FOR THE WIDTHS OF
 THE PARKING ROWS FOR STAFF TO VERIFY THE PROPER
 DIMENSION EXISTS.
  
 4) THE DIMENSION FOR THE INTERIOR OF THE PARKING
 ISLANDS WAS NOT PROVIDED TO VERIFY THAT THERE IS A
 MINIMUM OF FIVE (5) FEET FOR EACH INTERIOR AND TERMINAL
 ISLAND.
  
 5) THE LANDSCAPE BUFFER ALONG ALABAMA AVENUE AND L
 STREET SHALL BE A MINIMUM OF FIVE (5) FEET, WITH A
 HEDGE AND TREES, ON THE PARKING LOT PARCEL. THE
 REQUIRED HEDGE AND TREES MAY NOT BE INSTALLED IN THE
 RIGHT-OF-WAY. NOTE: L STREET IS SHOWN MEETING THIS
 REQUIREMENT; HOWEVER THE DATA CHART ON SHEET GA-0.1
 SHALL BE AMENDED TO SHOW THE CORRECT ?PROVIDED?
 SETBACK.
  
 6) IF THE PARKING LOT SHIFTS TOWARD FLORIDA AVENUE TO
 MAKE UP THE 3.5 FEET FOR THE REQUIRED ALABAMA AVENUE
 LANDSCAPE BUFFER, THEN THE APPLICANT SHALL PROVIDE THE
 REDUCTION IN THE CITY PLACE OPEN SPACE/PARK AREA
 PROVIDED. THE QUICK STAFF CALCULATION SHOWS AN
 APPROXIMATELY 900 SQUARE FOOT REDUCTION. THE HOTEL
 PROJECT STILL HAS SUFFICIENT OPEN SPACE/PARK SURPLUS.
  
 7) A CHART SHALL BE INCLUDED TO SHOW THAT THE PARKING
 LOT COMPLIES WITH SECTION 94-443(C)3 & 4.
 8) EACH ROW OF PARKING SHALL BE TERMINATED BY AN ISLAND
 CONTAINING A TREE. THE INTERIOR TANDEM ROWS SHALL
 COMPLY WITH THIS REQUIREMENT.
  
 9) HOW ARE THE LIGHT FIXTURES SHIELDED SO THAT THERE IS
 NO GLARE ON THE SURROUNDING RIGHTS-OF-WAY OR THE SOUTH
 TOWER?
  
 10) THE PLANS SHALL SHOW THE FLORIDA AVENUE CROSSWALK
 BEING CONSTRUCTED BY PALM BEACH COUNTY.
  
 11) SHOW THE CROSSWALK AT THE SOUTHEAST CORNER OF THE
 SITE AT ALABAMA AND L STREET TO PERMIT CROSSING TO THE
 SIDEWALK BEHIND THE TOWNHOUSES.
  
 12) THE PARKING NUMBERS ON SHEET GA-0.1 DO NOT TOTAL
 CORRECTLY. IT APPEARS YOU HAVE TOO FEW SPACES IN THE
 TANDEM LINE.
  
 13) THE VALETS MAY NOT STACK CARS THAT THEY ARE
 SHIFTING AROUND IN TRAVEL LANES BETWEEN THE ADA SPACES
 AND THE EXIT (I.E. NO REDUCTION OF LANE WIDTH BELOW 24
 FEET). THE PLANS SHALL BE MARKED AS SUCH AND THE
 PAVEMENT SHALL BE PAINTED WITH TO THAT EFFECT.
  
  