Plan Review Details - Project Z15070033
| Plan Review Stops For Project Z15070033 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
08-12-2015 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-12-2015 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-12-2015 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2015-08-12 10:50:23 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
06-02-2016 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-02-2016 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-06-02 12:59:30 | THE FOLLOWING COMMENTS WERE GENERATED AFTER THE REVIEW | | | OF THE ARCHITECTURAL AND LANDSCAPE PLANS RECEIVED MAY | | | 3, 2016 BY THE CITY: | | | | | | 1. NO ENGINEERING PLANS OTHER THAN A CONCEPTUAL | | | DRAINAGE PLAN WERE SUBMITTED. | | | | | | 2. PROVIDE A SCALE BAR ON THE SURVEY. BASED ON THE | | | DIMENSIONS LISTED ON THE DRAWING, IT APPEARS THE | | | GRAPHIC WAS REDUCED AND THE LISTED 1" = 20' SCALE IS | | | NOT CORRECT. | | | | | | 3. THE SITE IS BEING TOTALLY REDEVELOPED. STORMWATER | | | TREATMENT WILL NEED TO BE PROVIDED IN ACCORDANCE WITH | | | SFWMD CRITERIA. | | | | | | 4. THE STORM PIPE CONNECTION TO THE EXISTING INLET ON | | | DIXIE HIGHWAY WILL REQUIRE FDOT APPROVAL. DIXIE HIGHWAY | | | IS A FDOT ROADWAY IN THIS AREA. | | | | | | 5. PLEASE PROVIDE SEPARATE DRAWING SHOWING AUTOTURN | | | ANALYSIS DEMONSTRATING THE SOLID WASTE COLLECTION | | | VEHICLE CAN ACCESS THE PROPOSED DUMPSTER LOCATION. | | | | | | 6. SHOW LIGHT POLES, PROPOSED UTILITIES AND EXISTING | | | UTILITIES THAT WILL REMAIN ON THE LANDSCAPE PLAN. IT | | | APPEARS SOME OAKS, CRAPE MIRTLES AND SILVER BUTTONWOOD | | | TREES ARE PROPOSED NEAR OR OVER SOME OF THE STORM | | | PIPES. | | | | | | 7. EXISTING DRIVEWAY OPENING ON DIXIE HIGHWAY THAT WILL | | | NO LONGER BE USED WILL NEED TO BE REPLACED WITH | | | SIDEWALK, CURB AND GUTTER TO MATCH ADJACENT | | | RIGHT-OF-WAY ITEMS. | | | | | | 8. IT APPEARS THE DRIVEWAY ACCESS ON PALM BEACH LAKES | | | BLVD IS BEING SHIFTED TO THE EAST. THE PORTION OF THE | | | EXISTING DRIVEWAY THAT WILL NOT BE NEEDED FOR THE | | | PROPOSED DRIVEWAY WILL NEED TO BE REMOVED AND REPLACED | | | WITH STANDARD SIDEWALK, CURB AND GUTTER. | | | | | | 9. STOP SIGNS WILL BE NEEDED AT ALL DRIVEWAYS TO PUBLIC | | | RIGHTS OF WAY. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-11-2015 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
08-11-2015 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2015-08-11 14:15:48 | CITY OF WEST PALM BEACH | | | PUBLIC WORKS DEPARTMENT | | | | | | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL. | | | | | | 1. PLEASE SUBMIT ESTIMATES FOR THE PEAK POTABLE WATER | | | DEMAND, SANITARY SEWER FLOW, AND SOLID WASTE COLLECTION | | | YARDAGE. | | | | | | 2. PLEASE INCLUDE THE DUMPSTER ENCLOSURE DETAIL ON THE | | | PLANS. MINIMUM DIMENSIONAL REQUIREMENTS FOR THE | | | ENCLOSURE ARE LISTED IN CODE OF ORDINANCES, SECTION | | | 94-444(B), ALSO SEE FIGURE XIV-3 OF THE SAME SECTION. | | | | | | 3. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING | | | THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE | | | PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH | | | DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY | | | SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER | | | PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. | | | | | | 4. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE | | | AVAILABLE AT HTTP://WWW.CO.PALM-BEACH.FL.US/NEWSROOM/08 | | | 14/08-26-14-FLOOD_MAPS.HTM. PLEASE REVIEW THE MAPS AND | | | VERIFY THAT THE NEW MAPS WILL NOT IMPACT THE PROPOSED | | | PROJECT. | | | | | | 5. PLEASE SHOW A SCHEMATIC OF THE PROPOSED DRAINAGE | | | SYSTEM ON THE SITE PLAN. (ITEM 13 ON THE SITE PLAN | | | CHECKLIST). THE SCHEMATIC SHOULD REFLECT CONVEYANCE OF | | | ANY OFF SITE FLOWS WHICH CURRENTLY ENTER THE SITE. | | | | | | 6. PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY?S | | | ENGINEERING DESIGN STANDARDS. HTTP://WPB.ORG/ENGINEERIN | | | G/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/ | | | | | | 7 PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS OF | | | ALL WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC. | | | ROOT BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE NEAR | | | UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER | | | LINES. | | | | | | 8 PLEASE SHOW THE SIGHT TRIANGLES ON THE GROUND FLOOR | | | LANDSCAPING PLAN FOR THE INTERSECTIONS AND VEHICULAR | | | EXITS. (SECTION 94-305E, CODE OF ORDINANCES) | | | | | | 9 WHAT IS THE PURPOSE OF THE PROPOSED 20 FT UTILITY | | | EASEMENT SHOWN ON SP-1.0? | | | | | | 10. ON THE SITE LOCATION MAP ON SP-1.0, THE ROAD | | | LABELED AS FEDERAL HIGHWAY IS ACTUALLY OLIVE AVENUE. | | | ALSO ON SP-1.0, ?CLEARANCE? IS MISSPELLED ON THE NOTE | | | WITHIN THE PUBLIC ALLEY. | | | | | | 11. PLEASE INCLUDE A STRIPING DETAIL SHOWING THE | | | PROPOSED STRIPING COMPLIES WITH CITY OF WEST PALM BEACH | | | CODE OF ORDINANCES, ARTICLE XV, SECTIONS 94-111 AND | | | 94-485. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC | | | WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION FORMS CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | 2. A UNITY OF TITLE APPLICATION WILL BE REQUIRED FROM | | | THE ENGINEERING DIVISION OF THE PUBLIC WORKS | | | DEPARTMENT. THE APPLICATION FOR UNITY OF TITLE CAN BE | | | DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | 3. SOLID WASTE YARDAGE WILL NEED TO BE VERIFIED AS PART | | | OF THE FINAL DESIGN TO VERIFY THAT THE DESIGN INCLUDES | | | APPROPRIATE NUMBER AND SIZE OF TRASH BINS. | | | | | | 4. PLEASE IDENTIFY THE SOURCE OF THE AS-BUILT | | | INFORMATION UTILIZED FOR THE POTABLE WATER, SANITARY | | | SEWER, AND STORM SEWER DESIGN. | | | | | | 5. INDICATE ON THE PLANS WHICH PORTIONS OF THE POTABLE | | | WATER, SANITARY SEWER, AND STORMWATER SYSTEM WILL | | | REMAIN PUBLICALLY OWNED AND WHICH SECTIONS WILL BE | | | MAINTAINED BY THE APPLICANT. TYPICALLY, THE CITY'S | | | OWNERSHIP STOPS AT THE RIGHT-OF-WAY LINE UNLESS | | | EXTENUATING CIRCUMSTANCES REQUIRED THE OWNERSHIP | | | DIVISION TO TAKE PLACE AT ANOTHER LOCATION. | | | | | | 6. EASEMENTS WILL NEED TO BE PROVIDED OVER ALL ON-SITE | | | PUBLICALLY OWNED UTILITIES. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1098 (OFFICE) | | | | | | VINCE NOEL, PSM | | | CITY SURVEYOR / REAL ESTATE SUPERVISOR | | | [email protected] | | | 561-494-1096 | | | | | | BRIAN COLLINS, PE | | | CITY TRAFFIC ENGINEER | | | [email protected] | | | 561-494-1040 | | | | | | FERDINAND RIVERA | | | PUBLIC WORKS OPERATIONS MANAGER | | | [email protected] | | | 561-822-2076 | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
05-18-2016 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-18-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-18-2016 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2016-05-18 16:34:49 | 2ND REVIEW RESPONSE | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED APRIL | | | 28, 2016, FROM DTI, INC, AND MAY 10, 2016, FROM KEVIN | | | MARITN, URBAN DESIGN PLANNER, THE PREVIOUSLY SUBMITTED | | | FIRE PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
08-10-2015 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-10-2015 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-10-2015 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2015-08-10 16:55:14 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | OVERALL PROPOSED PROJECT; HOWEVER, THE ONLY CONCERN IS | | | REGARDING THE USE OF THE ALLEYWAY AS A MEANS OF | | | EMERGENCY VEHICLE ENTRANCE AND EGRESS. SHOULD AN | | | EMERGECNY VEHILCE MAKE ENTRANCE TO THE PROPERTY EXITING | | | IN OR OUT BY WAY OF THE ALLEYWAY WOULD NOT BE APPROVED. | | | THE WIDTH OF THE ALLEY, CONDIITON OF THE TRAVEL WAY, | | | AND TURNING RADIUSES WOULD NEED EVALUATION. | | | | | | THE FOLLOWING ARE REGULAR COMMENTS REGARDING THE | | | PROPOSED PROJECT SHOULD IT MOVE FORWARD: | | | | | | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 7. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY | | | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS | | | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. | | | | | | 8. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED | | | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY | | | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE | | | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES | | | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED | | | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED | | | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. | | | STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE MARKED | | | WITH THE LETTER "R". | | | | | | 9. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. | | | ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH | | | CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND | | | PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF | | | FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF | | | FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID | | | MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS | | | RELATED TO EGRESS REQUIREMENTS. | | | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | | EGRESS SIDE. | | | | | | INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY | | | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A | | | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE | | | RELEASED FROM THE EGRESS SIDE OF THE DOOR. | | | | | | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING | | | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT | | | MORE THAN ONE RELEASING OPERATION. THE RELEASING | | | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING | | | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT | | | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO | | | OPERATE. | | | | | | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY | | | DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS | | | PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH | | | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE | | | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO | | | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. | | | | | | IF INSTALLED ON OTHER EXIT DOORS, THUMB-TURN LOCK TO BE | | | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH | | | AS ADAMS RITE 4089 OR SIMILAR). | | | | | | 10. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 11. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
06-03-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-03-2016 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-03-2016 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2016-06-03 09:57:07 | FROM: RAY CARANCI, LANDSCAPE PLANNER | | | PROJECT: BURGER KING 1210 N DIXIE | | | JUNE 2, 2016 | | | STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS FOR THE ABOVE REFERENCED PETITION AND | | | PROVIDES THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE PROVIDE A LANDSCAPE PLAN AT THE | | | PROPER SIZE AND SCALE. | | | | | | 2. SATISFIED. PLEASE SHOW A 5 FOOT LANDSCAPE BUFFER AT | | | THE PROPERTY LINE ON ALL SIDES OF THE BUILDING PARCEL. | | | | | | 3. NOT SATISFIED. PLEASE PROVIDE A TREE OR TWO PALMS AT | | | THE NORTH END OF THE BUILDING. | | | | | | TREE OR PALMS NOT SHOWN ON PLAN. | | | | | | 4. SATISFIED. PLEASE PROVIDE A CONTINUOUS HEDGE IN THE | | | 5 FOOT LANDSCAPE BUFFERS. | | | | | | 5. NOT SATISFIED. PLEASE CHANGE THE MONTGOMERY PALMS | | | FROM SINGLE TO DOUBLE TRUNK. | | | | | | PLANT LIST IS DOES NOT SPECIFY DOUBLE TRUNK. | | | | | | 6. SATISFIED. ONE OF THE CAESALPINIA TREES IS SHOWN | | | OUTSIDE THE CURB LINE NEXT TO THE DRIVE THROUGH. PLEASE | | | REVISE. | | | | | | 7. SATISFIED. PLEASE SHOW WHEEL STOPS FOR THE PARKING | | | SPACES OR SHOW OVERHANG AREA BEHIND CURB. | | | | | | 8. SATISFIED. PLEASE PROVIDE A TREE SURVEY IDENTIFYING | | | EXISTING TREES ON THE PROPERTY AND PROVIDE A TREE | | | DISPOSITION LIST INDICATING THE SPECIES, SIZE, AND IF | | | THEY WILL BE REMOVED, RELOCATED, OR REMAIN. | | | | | | 9. NOT SATISFIED. PLEASE PROVIDE WATER NEEDS CATEGORY | | | FOR EACH SPECIES ON THE PLANT LIST FROM THE SFWMD | | | WATERWISE GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA | | | FRIENDLY LANDSCAPE CHART. | | | | | | PROVIDE A COLUMN FOR WATER NEEDS, AND RATE AS LOW, | | | MEDIUM OR HIGH. | | | | | | 10. SATISFIED. PLEASE CLARIFY THE ITEMS CLAIMED ON THE | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS OF SECTION | | | 94-442 (G). | | | | | | 11. NOT SATISFIED. PLEASE REVISE THE LANDSCAPE AND | | | ENGINEERING PLANS TO AVOID CONFLICTS BETWEEN | | | LANDSCAPING AND WATER, SEWER, DRAINAGE, LIGHTING AND | | | FPL EQUIPMENT. PLEASE SHOW LOCATIONS OF ALL UTILITIES | | | AND EASEMENTS ON THE LANDSCAPE PLAN. | | | | | | UTILITIES NOT SHOWN ON PLAN, ENGINEERING PLAN NOT | | | INCLUDED IN SUBMITTED PLAN SET. | | | | | | 12. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED EQUIPMENT AND UTILITIES AND SOUTH SIDE OF | | | DUMPSTER ENCLOSURE. | | | | | | 13. NOT SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL | | | AND SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT | | | INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES | | | WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY | | | FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS. | | | | | | DETAIL NOT PROVIDED, LOCATIONS NOT SHOWN. | | | | | | 14. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL | | | EQUIPMENT SUCH AS A/C COMPRESSORS, ETC. THAT WILL BE | | | GROUND MOUNTED. | | | | | | 15. SATISFIED. PLEASE PROVIDE A LANDSCAPE ISLAND IN THE | | | ROW OF PARKING ALONG THE EAST PROPERTY LINE TO PROVIDE | | | A MAXIMUM OF 10 SPACES IN A ROW. | | | | | | 16. WITHDRAWN. EXISTING LIVE OAK ALONG DIXIE SHALL BE | | | REPLACED WITH A NEW HIGHRISE OAK. STRUCTURAL SOIL SHALL | | | BE INSTALLED UNDER SIDEWALK AREAS WITHIN 5 FEET OF THE | | | TREE, AND THE TREE GRATE REUSED. PLEASE PROVIDE A | | | STRUCTURAL SOIL DETAIL. | | | | | | 17. WITHDRAWN. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE | | | SOUTH PARKING AREA. | | | ADDITIONAL COMMENTS 6/2/16: | | | 18. PLEASE PROVIDE A TREE PROTECTION BARRIER DETAIL TO | | | PROVIDE PROTECTION FOR EXISTING TREES TO REMAIN DURING | | | SITE CONSTRUCTION. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-11-2015 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-11-2015 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2015-08-11 11:06:21 | STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS FOR THE ABOVE REFERENCED PETITION AND | | | PROVIDES THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE PROVIDE A LANDSCAPE PLAN AT THE PROPER SIZE | | | AND SCALE. | | | | | | 2. PLEASE SHOW A 5 FOOT LANDSCAPE BUFFER AT THE | | | PROPERTY LINE ON ALL SIDES OF THE BUILDING PARCEL. | | | | | | 3. PLEASE PROVIDE A TREE OR TWO PALMS AT THE NORTH END | | | OF THE BUILDING. | | | | | | 4. PLEASE PROVIDE A CONTINUOUS HEDGE IN THE 5 FOOT | | | LANDSCAPE BUFFERS. | | | | | | 5. PLEASE CHANGE THE MONTGOMERY PALMS FROM SINGLE TO | | | DOUBLE TRUNK. | | | | | | 6. ONE OF THE CAESALPINIA TREES IS SHOWN OUTSIDE THE | | | CURB LINE NEXT TO THE DRIVE THROUGH. PLEASE REVISE. | | | | | | 7. PLEASE SHOW WHEEL STOPS FOR THE PARKING SPACES OR | | | SHOW OVERHANG AREA BEHIND CURB. | | | | | | 8. PLEASE PROVIDE A TREE SURVEY IDENTIFYING EXISTING | | | TREES ON THE PROPERTY AND PROVIDE A TREE DISPOSITION | | | LIST INDICATING THE SPECIES, SIZE, AND IF THEY WILL BE | | | REMOVED, RELOCATED, OR REMAIN. | | | | | | 9. PLEASE PROVIDE WATER NEEDS CATEGORY FOR EACH | | | SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE | | | GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY | | | LANDSCAPE CHART. | | | | | | 10. PLEASE CLARIFY THE ITEMS CLAIMED ON THE FLORIDA | | | FRIENDLY LANDSCAPE REQUIREMENTS OF SECTION 94-442 (G). | | | | | | 11. PLEASE REVISE THE LANDSCAPE AND ENGINEERING PLANS | | | TO AVOID CONFLICTS BETWEEN LANDSCAPING AND WATER, | | | SEWER, DRAINAGE, LIGHTING AND FPL EQUIPMENT. PLEASE | | | SHOW LOCATIONS OF ALL UTILITIES AND EASEMENTS ON THE | | | LANDSCAPE PLAN. | | | | | | 12. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | EQUIPMENT AND UTILITIES AND SOUTH SIDE OF DUMPSTER | | | ENCLOSURE. | | | | | | 13. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW | | | LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE | | | AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER, | | | DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES | | | THAT COULD BE IMPACTED BY TREE ROOTS. | | | | | | 14. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH | | | AS A/C COMPRESSORS, ETC. THAT WILL BE GROUND MOUNTED. | | | | | | 15. PLEASE PROVIDE A LANDSCAPE ISLAND IN THE ROW OF | | | PARKING ALONG THE EAST PROPERTY LINE TO PROVIDE A | | | MAXIMUM OF 10 SPACES IN A ROW. | | | | | | 16. EXISTING LIVE OAK ALONG DIXIE SHALL BE REPLACED | | | WITH A NEW HIGHRISE OAK. STRUCTURAL SOIL SHALL BE | | | INSTALLED UNDER SIDEWALK AREAS WITHIN 5 FEET OF THE | | | TREE, AND THE TREE GRATE REUSED. PLEASE PROVIDE A | | | STRUCTURAL SOIL DETAIL. | | | | | | 17. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE SOUTH | | | PARKING AREA. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES, TREE GRATES, RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING, TREE GRATES, AND IRRIGATION. THIS WILL | | | BE THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE | | | CITY. | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | RAY CARANCI, LANDSCAPE PLANNER | | | 561-822-1462 | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-11-2015 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
08-11-2015 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2015-08-11 14:17:57 | SEE COMMENTS UNDER ENG - PPRC |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-11-2015 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
08-11-2015 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2015-08-11 14:16:44 | SEE COMMENTS UNDER ENG - PPRC |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-11-2015 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
08-11-2015 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2015-08-11 14:17:15 | SEE COMMENTS UNDER ENG - PPRC |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2015 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-11-2015 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
08-11-2015 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2015-08-11 14:17:37 | SEE COMMENTS UNDER ENG - PPRC |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
01-04-2017 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-04-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
kmartin |
Date |
01-04-2017 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2017-01-04 10:24:40 | 1. SETBACK ALONG DIXIE HIGHWAY SHALL BE 16 FEET FROM | | | THE BACK OF THE CURB. | | | 2. DUMPSTER SHALL BE FULLY ENCLOSED WITH A FENCE AND | | | LANDSCAPING. | | | 3. TRANSPARENCY ALONG PALM BEACH LAKES BOULEVARD AND | | | DIXIE HIGHWAY SHALL BE 50% OF THE FACADE, INCLUDE | | | DETAILS AND CALCULATIONS. | | | 4. SIGNS ARE NOT COVERED BY THIS PERMIT; A SEPARATE | | | PERMIT SHALL BE REQUIRED. | | | 5. PERMEABLE PAVES SHALL BE INSTALLED THROUGHOUT THE | | | PARKING AREA INCLUDING CIRCULATION LANES. | | | | | | FOR MORE INFORMATION, PLEASE CONTACT KEVIN J MARTIN AT | | | 561-822-1426 OR [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
06-14-2016 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-14-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
kmartin |
Date |
06-14-2016 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2016-06-14 11:55:30 | EXISTING BURGER KING IS CONSIDERED A NONCONFORMING | | | BUILDING AND A NONCONFORMING USE (DRIVE THRU). | | | | | | 1. ACTIVE USE, 60% IS REQUIRED ALONG PALM BEACH LAKES | | | BOULEVARD, AND 65% IS REQUIRED ALONG DIXIE HIGHWAY. A | | | VARIANCE FROM DAC WILL BE REQUIRED IF NOT IN | | | COMPLIANCE. | | | 2. TRANSPARENCY, 50% IS REQUIRED ALONG PALM BEACH LAKES | | | BOULEVARD AND DIXIE HIGHWAY. PROJECT DOES NOT MEET THE | | | REQUIREMENT ALONG PALM BEACH LAKES BOULEVARD. | | | 3. SOUTH WINDOW ALONG DIXIE HIGHWAY MUST BE SHIFTED | | | NORTH; CURRENT PLANS SHOW THE WINDOW ADJACENT TO THE | | | FREEZER WHICH IS NOT AN ACTIVE USE. FACADE CHANGES WILL | | | BE NECESSARY TO KEEP THE WINDOW CENTERED IN | | | RELATIONSHIP TO OTHER ELEMENTS. | | | 4. PLEASE PROVIDE BIKE PARKING DETAILS. | | | 5. PROVIDE AUTO TURN TO CONFIRM THE MOVEMENT OF THE | | | DRIVE THRU IS ADEQUATE. | | | 6. PRIVATE OPEN SPACE REQUIREMENT IS NOT MET. THE CITY | | | WILL INITIATED A CODE AMENDMENT TO DECREASE THE AMOUNT | | | REQUIRED, BUT 4.71% WILL STILL BE INSUFFICIENT. | | | 7. DUMPSTER SHALL REMAIN AT EXISTING LOCATION, WITH | | | APPROPRIATE MODIFICATIONS TO MEET CODE. THIS ALLOWS THE | | | PARKING TO BE RECONFIGURED AND SUBSEQUENTLY ALLOW | | | ADDITIONAL PRIVATE OPEN SPACE. | | | 8. LANDSCAPE CURBS SHALL BE SHIFTED TO THE LOCATION OF | | | WHEEL STOPPERS TO INCREASE LANDSCAPE AREA. | | | 9. PROPOSED SIGNS SHALL COMPLY WITH SECTION 94-110(D) | | | OF THE ZONING CODE. | | | 10. PLEASE INCLUDE THE BUS STOP/BENCH ON THE SURVEY. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT KEVIN MARTIN | | | AT 561-822-1426. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2015 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
08-10-2015 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
08-10-2015 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2015-08-10 11:46:12 | EXISTING BURGER KING IS CONSIDERED A NONCONFIRMING | | | BUILDING AND A NONCONFORMING USE BECAUSE OF THE DRIVE | | | THRU. | | | | | | 1- SETBACK ON PALM BEACH LAKES BOULEVERD SHALL BE 16' | | | FROM THE BACK OF THE CURB CLOSER TO THE PROPERTY LINE. | | | 2- PLEASE INDICATE THE PERCENTAGE OF ACTIVE USE | | | PROVIDED ALONG PALM BEACH LAKES BLVD AND DIXIE HWAY. | | | 60% OF ACTIVE USE IS REQUIRED ALONG PBL, AND 65% IS | | | REQUIRED ALONG DIXIE HWAY. A VARIANCE FROM DAC WILL BE | | | REQUIRED IF NOT IN COMPLIANCE. | | | 3- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE | | | WITH MINIMUM 50% TRANSPARENCY REQUIRED ALONG STREET | | | FRONTAGES. | | | 4- PLEASE CONFIRM THE SOUTH ELEVATION COMPLIES WITH THE | | | BLANK WALL REQUIREMENTS (BLANK WALLS ARE NOT PERMITTED. | | | BLANK WALL MEANS AN AREA GREATER THAN 20% OF THE ENTIRE | | | FACADE ELEVATION THAT IS ABSENT OF FENESTRATION AND IS | | | ABSENT OF A PLANAR BREAK OF AT LEAST TWO FEET IN DEPTH. | | | 5- PLEASE PROVIDE AUTO TURN TO CONFIRM THE MOVEMENT OF | | | THE DRIVE THRU IS ADEQUATE. | | | 6- A LANDSCAPE ISLAND IS REQUIRED EVERY 10 PARKING | | | SPACES. THE PARKING ROW ON THE EAST SIDE HAS 11 SPACES | | | ON A ROW. | | | 7- TERMINAL ISLANDS SHALL BE PROVIDED FOR PARKING ROWS. | | | SUCH ISLANDS SHALL BE AT LEAST 5' IN WITH AND INCLUDE A | | | SHADE OR FLOWERING TREE. | | | 8- DUMPSTER SHALL HAVE A HEDGE AROUND THE ENCLOSURE. | | | 9- DUE TO THE SHORT STACKING DISTANCE FOR THE DRIVE | | | THRU, STAFF RECOMMENDS ORDERS SHALL BE TAKEN AT THE 1ST | | | WINDOW AND NOT AT THE MANY BOARD. | | | 10- EXISTING LIVE OAK ALONG DIXIE HWAY SHALL BE REMOVED | | | AND REPLACED WITH A NEW LIVE OAK. STRUCTURAL SOIL SHALL | | | BE INSTALLED AROUND THE TREE GRATE. | | | 11- LANDSCPE AREAS ON EXISTING SURFACE PARKING LOT | | | SOUTH OF THE ALLEY SHALL BE RESTORED. | | | 12- AT LEAST ONE BIKE PARKING SPACE SHALL BE PROVIDED. | | | STAFF RECOMMENDS THE BIKE RACK TO BE LOCATED ADJACENT | | | TO THE DIXIE HWAY ENTRANCE ON A HARD SURFACE PAD. | | | 13- THE DEAD END PARKING AREA SHALL PROVIDE ONE BACK | | | OUT SPACE AT THE END. | | | 14- PROPOSED SIGNS SHALL COMPLY WITH SECTION 94-110(D) | | | OF THE ZONING CODE. | | | 15- 25% OF THE LOT ARE SHALL BE DEDICATED TO PRIVATE | | | OPEN SPACE. LANDSCAPE BUFFERS REQUIRED FOR PARKING AND | | | REQUIRED SETBACKS CANNOT BE COUNTED AS PRIVATE OPEN | | | SPACE. STAFF WILL INITIATE A CODE AMENDMENT TO ADJUST | | | REGULATION. | | | 16- DRAWINGS SHALL BE AT SCALE. | | | | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| |
Print |
|