Plan Review Details - Project Z15060029
Plan Review Stops For Project Z15060029
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-12-2015 Cont ID  
Sent By rcaranci Date 08-12-2015 Time 09:32 Rev Time 0.00
Received By rbrown Date 08-12-2015 Time 09:32 Sent To  
Notes
2015-08-12 09:39:31DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. SHEET SP-1, SITE PLAN, SHOWS REGULAR PARKING SPACES
 THAT ARE CLOSER THAN THE ACCESSIBLE PARKING SPACE TO
 THE ENTRANCE OF THE NORTH BUILDING. ALSO, THE PLAN DOES
 NOT SHOW AN ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING SPACE TO THE NORTH BUILDING. PER SECTION 208.3
 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE
 FOR EACH BUILDING. THE DESIGN OF ACCESSIBLE PARKING
 SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 11-20-2015 Cont ID  
Sent By cranford Date 11-20-2015 Time 09:33 Rev Time 0.00
Received By cranford Date 11-20-2015 Time 09:21 Sent To  
Notes
2015-11-20 09:26:03PER MESSLER & ASSOCIATES REPORT:
  
 POTABLE WATER DEMAND: 262 GPD (5 PEOPLE PER BUILDING)
 SANITARY FLOW: 0.15 GAL/SF/DAY X 7641 SF = 1146 GPD
 SOLID WASTE: 1 LB/SF/DAY X 7641 SF = 764.1 LBS PER DAY

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-11-2015 Cont ID  
Sent By cranford Date 08-11-2015 Time 13:52 Rev Time 0.00
Received By cranford Date 08-11-2015 Time 13:50 Sent To  
Notes
2015-08-11 13:52:39CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. THE PRELIMINARY DRAINAGE AND UTILITY PLAN SHOWS
 SANITARY LINES TYING INTO WATER MAINS AND SANITARY
 LINES RUNNING THROUGH DRAINAGE STRUCTURES. PLEASE
 REVISE THE PLAN TO SHOW THE INTENDED CONNECTION POINTS.
 WATER SERVICES SHOULD CONNECT TO 8 INCH WATER MAIN
 RATHER THAN THE 20 INCH.
  
 2. THE EXISTING UTILITIES UNDER GEORGIA AVENUE DO NOT
 APPEAR TO BE SHOWN CORRECTLY. PLEASE CONTACT THE
 ENGINEERING DIVISION TO OBTAIN AS-BUILT INFORMATION.
  
 3 PLEASE SUBMIT ESTIMATES FOR THE PEAK POTABLE WATER
 DEMAND, SANITARY SEWER FLOW, AND SOLID WASTE COLLECTION
 YARDAGE.
  
 4. PLEASE INCLUDE THE DUMPSTER ENCLOSURE DETAIL ON THE
 PLANS. MINIMUM DIMENSIONAL REQUIREMENTS FOR THE
 ENCLOSURE ARE LISTED IN CODE OF ORDINANCES, SECTION
 94-444(B), ALSO SEE FIGURE XIV-3 OF THE SAME SECTION.
  
 5. PLEASE CORRECT THE NORTH ARROW ORIENTATION ON THE
 PRELIMINARY DRAINAGE AND UTILITY PLAN AND LANDSCAPE
 PLAN LP-1.
  
 6. ON SUBMITTED SURVEY, BEARINGS DO NOT MATCH NORTH
 ARROW DIRECTION.
  
 7. ON SHEET SP-1, ?SOUTHERN? IS MISSPELLED ON THE
 LOCATION MAP.
  
 8. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT HTTP://WWW.CO.PALM-BEACH.FL.US/NEWSROOM/08
 14/08-26-14-FLOOD_MAPS.HTM. PLEASE REVIEW THE MAPS AND
 VERIFY THAT THE NEW MAPS WILL NOT IMPACT THE PROPOSED
 PROJECT.
  
 9. PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY?S
 ENGINEERING DESIGN STANDARDS. HTTP://WPB.ORG/ENGINEERIN
 G/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/
  
 10. CONSTRUCTION WITHIN GEORGIA AVENUE RIGHT-OF-WAY
 WILL NEED TO BE COORDINATED WITH CITY PROJECT WHICH IS
 SCHEDULED TO BE ADVERTISED SOON. PLEASE CONTACT TRACY
 WARD AT 561-494-1120. THE DEVELOPER MAY BE RESPONSIBLE
 FOR CONSTRUCTION THAT IS NOT CONSISTENT WITH CITY?S BID
 DOCUMENTS.
  
 11. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS
 OF ALL WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES,
 ETC. ROOT BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE
 NEAR UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER
 LINES.
  
 12. PLEASE SHOW THE SIGHT TRIANGLES ON THE GROUND FLOOR
 LANDSCAPING PLAN FOR THE INTERSECTIONS AND VEHICULAR
 EXITS. (SECTION 94-305E, CODE OF ORDINANCES)
  
 13. NORTH PROPERTY CORNERS MUST BE SET. SURVEY NOTES
 THAT PROPERTY CORNER IS UNDER CONCRETE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 2. A UNITY OF TITLE APPLICATION WILL BE REQUIRED FROM
 THE ENGINEERING DIVISION OF THE PUBLIC WORKS
 DEPARTMENT. THE APPLICATION FOR UNITY OF TITLE CAN BE
 DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 3. SOLID WASTE YARDAGE WILL NEED TO BE VERIFIED AS PART
 OF THE FINAL DESIGN TO VERIFY THAT THE DESIGN INCLUDES
 APPROPRIATE NUMBER AND SIZE OF TRASH BINS.
  
 4. PLEASE IDENTIFY THE SOURCE OF THE AS-BUILT
 INFORMATION UTILIZED FOR THE POTABLE WATER, SANITARY
 SEWER, AND STORM SEWER DESIGN.
  
 5. INDICATE ON THE PLANS WHICH PORTIONS OF THE POTABLE
 WATER, SANITARY SEWER, AND STORMWATER SYSTEM WILL
 REMAIN PUBLICALLY OWNED AND WHICH SECTIONS WILL BE
 MAINTAINED BY THE APPLICANT. TYPICALLY, THE CITY'S
 OWNERSHIP STOPS AT THE RIGHT-OF-WAY LINE UNLESS
 EXTENUATING CIRCUMSTANCES REQUIRED THE OWNERSHIP
 DIVISION TO TAKE PLACE AT ANOTHER LOCATION.
  
 6. THE PRELIMINARY DRAINAGE AND UTILITY PLAN SHOWS AN
 EXISTING SANITARY SERVICE LINE BEING UTILIZED BY THE
 PROPOSED SOUTHERN WAREHOUSE. THE SERVICE LINE IS SHOWN
 PARTIALLY ON LOT 72A. IS THERE A UTILITY EASEMENT WHICH
 WILL ALLOW THE USE OF THIS LINE?
  
 7. EASEMENTS WILL NEED TO BE PROVIDED OVER ALL ON-SITE
 PUBLICALLY OWNED UTILITIES.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 BRIAN COLLINS, PE
 CITY TRAFFIC ENGINEER
 [email protected]
 561-494-1040
  
 FERDINAND RIVERA
 PUBLIC WORKS OPERATIONS MANAGER
 [email protected]
 561-822-2076
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 561-494-1120
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-10-2015 Cont ID  
Sent By pleduc Date 08-10-2015 Time 11:13 Rev Time 0.00
Received By pleduc Date 08-10-2015 Time 11:12 Sent To  
Notes
2015-08-10 11:23:09THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 7. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 8. KNOX-BOX KEY SYSTEM IS STRONGLY RECOMMEND AT EACH
 BUILDING FOR 24HR EMERGENCY ACCESS.
  
 9. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE MARKED
 WITH THE LETTER "R".
  
 10. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK ON OTHER EXIT DOORS ARE TO BE EQUIPPED
 WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS
 RITE 4089 OR SIMILAR).
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 12-31-2015 Cont ID  
Sent By rcaranci Date 12-31-2015 Time 11:00 Rev Time 0.00
Received By rcaranci Date 12-31-2015 Time 11:00 Sent To  
Notes
2015-12-31 11:01:03FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: 4510 GEORGIA AVE RESUBMITTAL
 DECEMBER 31, 2015
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE WATER NEEDS CATEGORY FOR
 EACH SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE
 GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE CHART.
  
 2. SATISFIED. PLEASE REVISE THE LANDSCAPE AND
 ENGINEERING PLANS TO AVOID CONFLICTS BETWEEN
 LANDSCAPING AND WATER, SEWER, DRAINAGE, LIGHTING AND
 FPL EQUIPMENT. PLEASE SHOW LOCATIONS OF ALL UTILITIES
 AND EASEMENTS ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 4. SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL AND
 SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 5. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL
 EQUIPMENT SUCH AS A/C COMPRESSORS, ETC.
  
 6. SATISFIED. TREES ADJACENT TO THE LOADING AREA WILL
 CONFLICT WITH TRAFFIC AS THEY GROW. REVISE TREE SPECIES
 IN ISLAND AND BUFFER OR LOCATION OF THE LANDSCAPE
 ISLAND TO RECTIFY.
  
 7. SATISFIED. THE PLACEMENT OF THE FAKAHATCHEE GRASS
 BETWEEN THE COCOPLUM HEDGE AND THE FENCE WILL BE
 DIFFICULT TO MAINTAIN, PLEASE REVISE SPECIES AND
 PLACEMENT TO ALLOW ROOM FOR GROWTH AND LONG TERM
 MAINTENANCE OF THE LANDSCAPING. THE AREA BETWEEN THE
 BUILDING AND FENCE STILL DOES NOT HAVE ENOUGH ROOM TO
 ALLOW ACCESS TO MAINTAIN THE HEDGE.
  
 ADDITIONAL COMMENTS 12/13/15:
  
 8. SATISFIED. PLEASE PROVIDE TRIPLE PALMS IN THE
 LANDSCAPE ISLANDS ON EITHER SIDE OF THE DUMPSTER.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 11-16-2015 Cont ID  
Sent By rcaranci Date 11-16-2015 Time 10:51 Rev Time 0.00
Received By rcaranci Date 11-16-2015 Time 10:51 Sent To  
Notes
2015-11-16 10:53:38NOVEMBER 13, 2015
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE WATER NEEDS CATEGORY FOR
 EACH SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE
 GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE CHART.
  
 2. SATISFIED. PLEASE REVISE THE LANDSCAPE AND
 ENGINEERING PLANS TO AVOID CONFLICTS BETWEEN
 LANDSCAPING AND WATER, SEWER, DRAINAGE, LIGHTING AND
 FPL EQUIPMENT. PLEASE SHOW LOCATIONS OF ALL UTILITIES
 AND EASEMENTS ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 4. SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL AND
 SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 5. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL
 EQUIPMENT SUCH AS A/C COMPRESSORS, ETC.
  
 6. SATISFIED. TREES ADJACENT TO THE LOADING AREA WILL
 CONFLICT WITH TRAFFIC AS THEY GROW. REVISE TREE SPECIES
 IN ISLAND AND BUFFER OR LOCATION OF THE LANDSCAPE
 ISLAND TO RECTIFY.
  
 7. NOT SATISFIED. THE PLACEMENT OF THE FAKAHATCHEE
 GRASS BETWEEN THE COCOPLUM HEDGE AND THE FENCE WILL BE
 DIFFICULT TO MAINTAIN, PLEASE REVISE SPECIES AND
 PLACEMENT TO ALLOW ROOM FOR GROWTH AND LONG TERM
 MAINTENANCE OF THE LANDSCAPING.
 THE AREA BETWEEN THE BUILDING AND FENCE STILL DOES NOT
 HAVE ENOUGH ROOM TO ALLOW ACCESS TO MAINTAIN THE HEDGE.
  
 ADDITIONAL COMMENTS 12/13/15:
  
 8. PLEASE PROVIDE TRIPLE PALMS IN THE LANDSCAPE ISLANDS
 ON EITHER SIDE OF THE DUMPSTER.
  
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-03-2015 Cont ID  
Sent By rcaranci Date 08-03-2015 Time 14:38 Rev Time 0.00
Received By rcaranci Date 08-03-2015 Time 14:37 Sent To  
Notes
2015-08-03 14:40:39STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE WATER NEEDS CATEGORY FOR EACH
 SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE
 GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE CHART.
  
 2. PLEASE REVISE THE LANDSCAPE AND ENGINEERING PLANS TO
 AVOID CONFLICTS BETWEEN LANDSCAPING AND WATER, SEWER,
 DRAINAGE, LIGHTING AND FPL EQUIPMENT. PLEASE SHOW
 LOCATIONS OF ALL UTILITIES AND EASEMENTS ON THE
 LANDSCAPE PLAN.
  
 3. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
 4. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 5. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH
 AS A/C COMPRESSORS, ETC.
  
 6. TREES ADJACENT TO THE LOADING AREA WILL CONFLICT
 WITH TRAFFIC AS THEY GROW. REVISE TREE SPECIES IN
 ISLAND AND BUFFER OR LOCATION OF THE LANDSCAPE ISLAND
 TO RECTIFY.
  
 7. THE PLACEMENT OF THE FAKAHATCHEE GRASS BETWEEN THE
 COCOPLUM HEDGE AND THE FENCE WILL BE DIFFICULT TO
 MAINTAIN, PLEASE REVISE SPECIES AND PLACEMENT TO ALLOW
 ROOM FOR GROWTH AND LONG TERM MAINTENANCE OF THE
 LANDSCAPING.
 PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE
 REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS
 THE REVIEW PROCESS CONTINUES.
 RAY CARANCI, LANDSCAPE PLANNER
 561-822-1462
 [email protected]
  

Review Stop PARK PARKING
Rev No 1 Status F Date 08-12-2015 Cont ID  
Sent By ssamuels Date 08-12-2015 Time 11:46 Rev Time 0.00
Received By ssamuels Date 08-12-2015 Time 11:46 Sent To  
Notes
2015-08-12 11:49:55Z - 15060029
  
 BIKE RACK IS NOT SHOWN ON THE SITE PLAN.
  
 SEAN SAMUELS
 PARKING FACILITY SUPERVISOR
 PARKING ADMINSTRATION
 500 BANYAN BLVD
 WPB, 33401
 TEL 561-822-1507

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 08-11-2015 Cont ID  
Sent By cranford Date 08-11-2015 Time 13:53 Rev Time 0.00
Received By cranford Date 08-11-2015 Time 13:53 Sent To  
Notes
2015-08-11 13:53:33SEE COMMENTS UNDER ENG - PPRC

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-11-2015 Cont ID  
Sent By cranford Date 08-11-2015 Time 13:53 Rev Time 0.00
Received By cranford Date 08-11-2015 Time 13:53 Sent To  
Notes
2015-08-11 13:53:51SEE COMMENTS UNDER ENG - PPRC

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-11-2015 Cont ID  
Sent By cranford Date 08-11-2015 Time 13:54 Rev Time 0.00
Received By cranford Date 08-11-2015 Time 13:54 Sent To  
Notes
2015-08-11 13:54:09SEE COMMENTS UNDER ENG - PPRC

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-11-2015 Cont ID  
Sent By cranford Date 08-11-2015 Time 13:54 Rev Time 0.00
Received By cranford Date 08-11-2015 Time 13:54 Sent To  
Notes
2015-08-11 13:54:37SEE COMMENTS UNDER ENG - PPRC

Review Stop Z ZONING
Rev No 4 Status P Date 02-03-2016 Cont ID  
Sent By eschneid Date 02-03-2016 Time 13:48 Rev Time 0.50
Received By eschneid Date 02-03-2016 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 01-08-2016 Cont ID  
Sent By eschneid Date 01-08-2016 Time 17:13 Rev Time 1.00
Received By eschneid Date 01-08-2016 Time 16:21 Sent To  
Notes
2016-01-08 17:13:42INFORMAL SITE PLAN REVIEW 15-03
 12/18/15 RESUBMITTAL #2
 GENERAL LAND ACRES
 4600 BLOCK (EAST SIDE) GEORGIA AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THESE COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE COMMENTS (BY MARCH 8, 2016), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($400).
  
 1) REPEAT COMMENT: THE SITE, CIVIL AND LANDSCAPE PLANS
 SHOW DIFFERENT CONDITIONS (EX. BELOW). ALL PLANS SHALL
 SHOW SAME CONDITIONS.
  
 A. THE DRIVEWAYS/ENTRANCES ARE SHOWN IN DIFFERENT
 CONFIGURATIONS ON SITE/LANDSCAPE VS. CIVIL PLANS. THE
 CURBED, ISLAND RADII ARE NOT DEPICTED ON THE
 SITE/LANDSCAPE PLANS.
  
 2) REPEAT COMMENT: THE PARKING DETAIL SHOWS THE ADA
 SIGN IN THE NEIGHBORING PARKING SPACE (HEAD TO HEAD
 PARKING). THE ADA STRIPING LOCATIONS (2 INCHES APART)
 DO NOT MATCH THE CITY STANDARD DETAIL, WHICH REQUIRES
 THE SAME SIX (6) INCH SPACING AS THE REGULAR PARKING
 SPACES HAVE.
  
 3) REPEAT COMMENT: THE BICYCLE PAD DIMENSION SHALL BE
 INCLUDED ON THE SITE AND/OR CIVIL PLANS. NOTE: WHILE
 THE DETAIL SHOWS THEM AS FOUR (4) FEET WIDE, SCALING
 THE PLANS SHOWS LESS THAN FOUR (4) FEET.
  
 4) REPEAT COMMENT: THE SITE DATA TABLE SHALL BE
 CORRECTED AS FOLLOWS:
  
 A. THERE ARE TWO BICYCLE RACKS SO THERE ARE FOUR (4)
 PROVIDED BICYCLE PARKING SPACES.
  
 5) RECOMMENDATION: VERIFY ALL THE DIMENSION TAGS
 BETWEEN THE SITE AND CIVIL PLANS. SOME APPEAR TO USE
 DIFFERING MEASURE POINTS (EX. THE 43 FOOT EAST/WEST
 DIMENSION) AND SOME SCALE CORRECTLY AND OTHER DO NOT.
 STAFF IS CONCERNED THAT THIS COULD LEAD TO DELAYS AT
 THE TIME OF PERMITTING.
  
 6) RECOMMENDATION: THE CITY REQUIRES A 12 FOOT 6 INCH
 WIDE OPENING FOR DUMPSTER ENCLOSURES. WHILE THIS IS
 SHOWN ON THE STANDARD CITY DETAIL PROVIDED, THERE IS NO
 DIMENSION TAG ON THE PLANS FOR THE OPENING AND IT
 SCALES AT LESS THAN THE REQUIRED 12 FEET 6 INCHES.
 STAFF RECOMMENDS VERIFYING THIS OPENING TO FORGO
 PROBLEMS AT TIME OF PERMITTING.
  

Review Stop Z ZONING
Rev No 2 Status F Date 12-08-2015 Cont ID  
Sent By eschneid Date 12-08-2015 Time 17:21 Rev Time 4.00
Received By eschneid Date 12-08-2015 Time 17:20 Sent To  
Notes
2015-12-08 17:29:31INFORMAL SITE PLAN REVIEW 15-03
 10/9/15 RESUBMITTAL #1
 4600 BLOCK OF GEORGIA AVENUE WAREHOUSES
 4600 BLOCK (EAST SIDE) GEORGIA AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE THESE COMMENTS WITHIN 60
 DAYS FROM THE DATE OF THE COMMENTS (BY FEBRUARY 8,
 2016), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($200).
  
 1) THE SITE, CIVIL AND LANDSCAPE PLANS SHOW DIFFERENT
 CONDITIONS (EX. BELOW). ALL PLANS SHALL SHOW SAME
 CONDITIONS.
  
 A. THE DRIVEWAYS/ENTRANCES ARE SHOWN IN DIFFERENT
 CONFIGURATIONS ON SITE/LANDSCAPE VS. CIVIL. NOTE: THE
 WALKWAY TO THE RIGHT-OF-WAY BY THE NORTH BUILDING DOES
 NOT LOOK LIKE IT WILL FUNCTION PROPERLY AS SHOWN ON THE
 SITE AND LANDSCAPE PLANS.
 B. THE BICYCLE RACK BY THE NORTH BUILDING SHOWN ON THE
 CIVIL PLAN DOES NOT APPEAR ON EITHER THE SITE OR
 LANDSCAPE PLAN, THOUGH THERE IS TAG MARKER FOR A
 BICYCLE RACK ON THE SITE PLAN.
 C. THE CIVIL PLAN SHOWS A CURB AT THE HEAD OF THE
 PARKING SPACES WHILE THE SITE AND LANDSCAPE PLAN SHOW
 NO CURB. PLEASE REMEMBER THAT LANDSCAPE SHALL BE
 PROTECTED FROM VEHICULAR ENCROACHMENT.
  
 2) THE PARKING DETAIL SHOWS 8.5 FOOT WIDE SPACES AND
 THE SPACES ON THE PLAN SCALE THAT DIMENSION. THE
 DIMENSION TAG IS NINE (9) FEET. ADDITIONALLY, THE
 PARKING SPACES SCALE AT 18.5 FEET DEEP, WHICH CONFLICTS
 WITH THE DIMENSION TAG AND THE DETAIL.
  
 3) PROVIDE THE WIDTH DIMENSIONS FOR THE TERMINAL AND
 INTERIOR PARKING ISLANDS.
  
 4) REPEAT COMMENT: THE PARKING DETAIL SHOWS THE ADA
 SIGN IN THE NEIGHBORING PARKING SPACE (HEAD TO HEAD
 PARKING). THE ADA STRIPING LOCATIONS (2 INCHES APART)
 DO NOT MATCH THE CITY STANDARD DETAIL, WHICH REQUIRES
 THE SAME SIX (6) INCH SPACING AS THE REGULAR PARKING
 SPACES HAVE. ADDITIONALLY, NO WHEEL STOPS ARE SHOWN ON
 THE PARKING DETAIL. BASED ON THE DEPICTED FIVE (5) FOOT
 WIDE LANDSCAPE BUFFER, WHEEL STOPS WILL BE REQUIRED AND
 SHALL BE SHOWN ON THE DETAIL AND THE PLAN.
  
 5) THE SOUTH BUILDING HAS TWO ELEVATIONS LABELED AS
 WEST ELEVATION - PLEASE CORRECT.
  
  
 6) REPEAT COMMENT: THE PBC TRAFFIC LETTER ONLY APPROVES
 7,605 SQUARE FEET OF WAREHOUSE USE. THE TWO BUILDINGS
 TOTAL 7,641 SQUARE FEET. THE REVISED TRAFFIC APPROVAL
 LETTER HAS NOT BEEN RECEIVED BY STAFF.
  
 7) THE BICYCLE PARKING DETAIL SHOWS TWO RACKS ON ONE
 PAD. THE PLANS SHOW EITHER ONE OR TWO PADS HAVING ONE
 RACK. ALL DETAILS SHALL SHOW SITE CONDITIONS AND THE
 CORRECT DIMENSIONS. THE BICYCLE PAD DIMENSION SHALL BE
 INCLUDED ON THE SITE AND/OR CIVIL PLANS.
  
 8) THE SITE DATA TABLE SHALL BE CORRECTED AS FOLLOWS:
  
 A. THE PARKING REQUIRED FOR 400 SQUARE FEET OF OFFICE
 IS ONE (1) PARKING SPACE (LESS THAN 50% OF A PARKING
 SPACE ROUNDS DOWN).
 B. THE TOTAL NUMBER OF PARKING SPACES REQUIRED IS EIGHT
 (8) PARKING SPACES.
 C. THERE ARE TWO (2) PROVIDED ADA PARKING SPACES.
 D. THERE ARE TWO (2) PROVIDED LOADING SPACES.
 E. THERE ARE EITHER TWO (2) OR FOUR (4) PROVIDED
 BICYCLE PARKING SPACES.
  
 9) PROVIDE THE DIMENSION OF THE LOADING SPACES ON THE
 SITE PLAN.
  
 10) PROVIDE THE DIMENSION OF THE DUMPSTER ENCLOSURE ON
 THE SITE PLAN. PLEASE NOTE THAT STAFF HAS SCALED THE
 ENCLOSURE AS SHOWN AND IT DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF THE CITY STANDARD DETAIL INCLUDED ON
 THE SITE PLAN.
  
 11) THE LANDSCAPE ISLANDS ADJACENT TO THE DUMPSTER
 SHALL INCLUDE TREES TO TERMINATE THE PARKING ROWS.
  
 12) REPEAT COMMENT: THE ROOT BARRIER DETAIL SHALL
 REFERENCE CITY OF WEST PALM BEACH UTILITIES NOT PALM
 BEACH COUNTY UTILITIES.
  
 13) AT THE PPRC MEETING, THE ENGINEERING SERVICES
 REPRESENTATIVES PERMITTED THE TWO DRIVEWAYS AND THE
 SPACING BETWEEN THEM - WAIVER FROM SECTION 94-313(1)
 AND SECTION 94-313(2).
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-10-2015 Cont ID  
Sent By eschneid Date 08-10-2015 Time 16:19 Rev Time 4.00
Received By eschneid Date 08-10-2015 Time 16:19 Sent To  
Notes
2015-08-10 16:22:18INFORMAL SITE PLAN REVIEW 15-03
 4600 BLOCK OF GEORGIA AVENUE WAREHOUSES
 4600 BLOCK (EAST SIDE) GEORGIA AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY OCTOBER 10,
 2015), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($400).
  
 1) PLEASE NOTE THAT IF THE CONSTRUCTION VALUE OF THE
 BUILDINGS EXCEEDS $500,000, THEN THE PROJECT WILL BE
 SUBJECT TO THE ARTS IN PUBLIC PLACES REQUIREMENTS.
  
 2) SECTION 94-313(1) LIMITS THE NUMBER OF ACCESS POINTS
 FOR THIS PROJECT TO ONE ACCESS POINT. PLEASE REVISE THE
 SITE PLAN TO CONFORM TO THIS REQUIREMENT. NOTE: GEORGIA
 AVENUE IS CLASSIFIED AS A COLLECTOR ROADWAY AND THUS
 WOULD REQUIRE A 125 FOOT SEPARATION BETWEEN ACCESS
 POINTS IF THE TWO ACCESS POINTS SHOWN WERE PERMITTED
 -SECTION 94-313(2).
  
 3) PROVIDE THE DRIVEWAY WIDTH DIMENSIONS ON THE SITE
 PLAN, BOTH AT THE NARROWEST POINT AND AT THE PROPERTY
 LINE. STAFF HAS SCALED THE PLAN AND IT APPEARS THAT THE
 GEORGIA AVENUE FRONTAGE IS INTERRUPTED BY MORE THAN THE
 25 PERCENT PERMITTED BY SECTION 94-443(B)(2).
  
 4) PROVIDE THE DIMENSION OF THE SIDEWALK TO THE ADA
 ACCESS AISLE.
  
 5) HOW DOES SOMEONE PARKING IN THE ADA SPACE ACCESS THE
 NORTHERN BUILDING?
  
 6) THE LANDSCAPE ISLAND ADJACENT TO THE LOADING SPACE
 SHALL BE A MINIMUM OF FIVE (5) FEET IN WIDTH WHEN
 MEASURED INSIDE THE CURB. PLEASE SHOW A DIMENSION LINE
 ON THE PLAN TO VERIFY THIS DISTANCE (IT SEEMS TO SCALE
 AT ONLY FOUR (4) FEET IN WIDTH).
  
 7) WHY DO THE DRIVE AISLES NEED TO BE SO WIDE?
  
 8) THE PARKING DETAIL SHOWS THE ADA SIGN IN THE
 NEIGHBORING PARKING SPACE. THE ADA STRIPING LOCATIONS
 (2 INCHES APART) DO NOT MATCH THE CITY STANDARD DETAIL,
 WHICH INCLUDES THE SAME 6 INCH SPACING AS THE REGULAR
 PARKING SPACES HAVE.
  
 9) THE SITE DATE TABLE MENTIONS THERE IS A CANOPY ON
 THE SITE. THE SITE PLANS AND ELEVATIONS DO NOT SHOW ANY
 CANOPIES. PLEASE CLARIFY.
  
 10) THE BUILDINGS ARE SHOWN WITH DIFFERENT DIMENSIONS
 ON THE ELEVATIONS AND SITE PLAN. PLEASE CLARIFY.
  
 11) PLEASE CONSIDER ADDING SOME ARCHITECTURAL DETAILS
 TO THE WEST, EAST AND NORTH ELEVATIONS OF THE NORTH
 BUILDING AND THE WEST, EAST AND SOUTH ELEVATIONS ON THE
 SOUTH BUILDING. THIS CAN BE AS SIMPLE AS ADDITIONAL
 HORIZONTAL OR VERTICAL BANDING (SIMILAR TO HOW THE
 GARAGE DOORS ARE FRAMED OUT) OR MORE ELABORATE SUCH AS
 REAL OR FAKE WINDOWS. NOTE: SOUTH BUILDING HAS TWO
 ELEVATIONS MISLABELED.
  
 12) THE SITE DATA TABLE INCORRECTLY LISTS THE REQUIRED
 PARKING FOR THE OFFICE PORTION OF THE BUILDING. THE
 OFFICE RATIO IS AT 1 PARKING SPACE PER 350 SQUARE FEET.
  
 13) PLEASE CLARIFY WHO THE END USER IS ANTICIPATED TO
 BE FOR THESE BUILDINGS. THESE BUILDINGS APPEAR TO BE
 CONSTRUCTED FOR FLEX INDUSTRIAL PURPOSES YET THE PBC
 TRAFFIC LETTER AND PARKING CALCULATIONS IS FOR
 WAREHOUSE USE. THIS SEEMS TO SEVERELY RESTRICT THE
 ABILITY TO LEASE THE PROPERTY (I.E. NO CONTRACTORS,
 MANUFACTURING OR ANY KIND, ETC. IS PERMITTED). NOTE:
 THE FLEX INDUSTRIAL PARKING RATIO IS COUNTED AT 1
 PARKING SPACE PER 500 SQUARE FEET.
  
 14) THE PBC TRAFFIC LETTER ONLY APPROVES 7,605 SQUARE
 FEET OF WAREHOUSE USE. THE TWO BUILDINGS TOTAL 7,641
 SQUARE FEET. THE BUILDINGS SHALL BE MADE SMALLER AND
 MAY NOT INCLUDE OFFICE AREA AS A SEPARATE USE UNDER THE
 SITE DATA CONCURRENCY APPROVAL BOX.
  
 15) THANK YOU FOR PROVIDING THE BICYCLE RACK DETAIL.
 WHERE WILL THIS BE LOCATED ON THE SITE PLAN?
 ADDITIONALLY, ONLY TWO BICYCLE PARKING SPACES ARE
 REQUIRED, WHICH EQUATES TO ONE RACK ELEMENT, NOT TWO AS
 SHOWN ON THE DETAIL.
  
 16) EACH BUFFER IS DEFICIENT ONE REQUIRED BUFFER TREE.
 SECTION 94-443(B)(4) STATES, "AT LEAST ONE SHADE OR
 FLOWERING TREE SHALL BE PLANTED IN A REQUIRED BUFFER
 STRIP FOR EACH 30 LINEAR FEET OR PORTION THEREOF." THE
 LANDSCAPE REQUIREMENTS TABLE SHALL SHOW THE "PORTION
 THEREOF" ROUNDED UP, WHICH RESULTS IN ONE MORE TREE PER
 SIDE.
  
 17) WHILE THE ZONING AND LAND DEVELOPMENT REGULATIONS
 PERMIT TWO PALMS TO BE COUNTED AS ONE TREE EQUIVALENT,
 PALMS ARE REQUIRED TO BE IN GROUPS OF THREE. THE TWO
 GROUPS OF TWO SABLE PALMS ARE SPACED 40 FEET APART,
 WHICH MAY NOT BE COUNTED AS A GROUPING OF THREE. THE
 NORTHERN TWO SABLE PALMS DO NOT HAVE THE THIRD REQUIRED
 PALM.
  
 18) THE FOUNDATION PLANTING LINE ITEM SHALL BE BROKEN
 DOWN PER BUILDING.
  
 19) THE SITE AND LANDSCAPE PLANS SHALL SHOW THE
 UTILITIES. THE BACKFLOW PREVENTER SHALL BE SCREENED.
  
 20) WHERE WILL THE A/C UNITS BE PLACED? THESE SHALL BE
 SCREENED FROM THE VIEW OF THE PUBLIC.
  
 21) THE ROOT BARRIER DETAIL SHALL REFERENCE CITY OF
 WEST PALM BEACH UTILITIES NOT PALM BEACH COUNTY
 UTILITIES.
  