Plan Review Details - Project Z15020009
Plan Review Stops For Project Z15020009
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 03-11-2015 Cont ID  
Sent By rbrown Date 03-11-2015 Time 10:27 Rev Time 0.00
Received By rbrown Date 03-11-2015 Time 10:27 Sent To  
Notes
2015-03-11 10:36:31DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A
 RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL
 INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT
 APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL
 ALONG THE PROPERTY LINE, PER SECTION 702 OF FLORIDA
 BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE.
  
 3. DISPERSION OF ACCESSIBLE PARKING SPACES. SHEET SP-1
 CURRENTLY SHOWS REGULAR PARKING SPACES CLOSER TO THE
 ENTRANCES OF THE INDIVIDUAL SHOWROOMS (ROLLS ROYCE,
 BENTLEY, PRSCHE, ETC.) THAN THE ACCESSIBLE PARKING
 SPACES. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN
 OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION
 502 OF FLORIDA ACCESSIBILITY CODE
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. IN CASE THE NEW SERVICE BAY BUILDING WILL BE
 CONSIDERED AN ADDITION TO THE EXISTING SERVICE BAY
 BUILDING, THE ADDITION TO THE EXISTING BUILDING IS
 COVERED BY CHAPTER 10 OF THE FLORIDA EXISTING BUILDING
 CODE. THE HEIGHT AND/OR AREA INCREASE DUE TO THE
 PROPOSED ADDITION SHALL NOT INCREASE THE TOTAL BUILDING
 HEIGHT AND/OR AREA BEYOND THAT ALLOWED UNDER THE
 APPLICABLE PROVISIONS OF CHAPTER 5 OF THE FLORIDA
 BUILDING CODE FOR THE TYPE OF CONSTRUCTION USED.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SWIMMING POOLS AND SPAS, GAS SYSTEMS, GENERATORS,
 FIRE ALARM SYSTEMS, FIRE SPRINKLER AND OTHER FIRE
 SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, SITE
 LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, GIS
 SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 05-26-2015 Cont ID  
Sent By cranford Date 05-26-2015 Time 14:05 Rev Time 0.00
Received By cranford Date 05-26-2015 Time 13:45 Sent To  
Notes
2015-05-26 14:05:46PRIOR TO CONDUCTING ANY LAND DISTURBING OR LAND
 DEVELOPMENT ACTIVITIES:
  
 1. A BOND OR DEPOSIT IN AN AMOUNT COVERING THE COST
 ASSOCIATED WITH IMPLEMENTATION OF THE STORMWATER
 POLLUTANT PREVENTION PLAN (SWPPP) AND LAND
 STABILIZATION OF THE SITE MUST BE SUBMITTED TO THE
 PUBLIC WORKS DEPARTMENT. THE BOND WILL BE RELEASED UPON
 APPROVED INSPECTION OF TIE-BEAMS OR SIMILAR VERTICAL
 CONSTRUCTION. (CITY CODE SECTION 94-450)
  
 2. ENGINEERING DEVELOPMENT APPROVAL IS REQUIRED.
 TECHNICAL DETAILS OF THE WATER, SEWER, STORMWATER
 (INCLUDING SWPPP), TRAFFIC CIRCULATION, AND SOLID WASTE
 COLLECTION WILL BE REVIEWED AS PART PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION PROCESSES.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 04-06-2015 Cont ID  
Sent By cranford Date 04-06-2015 Time 15:01 Rev Time 0.00
Received By cranford Date 04-06-2015 Time 14:55 Sent To  
Notes
2015-04-06 15:01:242ND REVIEW COMMENTS
  
 1. TRAFFIC CONCURRENCY LETTER FROM PALM BEACH COUNTY
 HAS NOT YET BEEN SUBMITTED.
  
 ONCE CONCURRENCY LETTER HAS BEEN RECEIVED, STAFF WILL
 PASS THE SUBMITTAL CONTINGENT ON THE APPROVAL OF THE
 WAIVER FOR THE NUMBER AND LOCATION OF DRIVEWAYS.
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-10-2015 Cont ID  
Sent By cranford Date 03-10-2015 Time 10:41 Rev Time 0.00
Received By cranford Date 03-10-2015 Time 08:26 Sent To  
Notes
2015-03-10 09:57:52PUBLIC WORKS DEPT.
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 1. THE SITE LAYOUT SHOWN ON SHEET SP-1 IS NOT
 CONSISTENT WITH THE LAYOUT SHOWN ON SHEETS SP-2. WHICH
 LAYOUT IS THE PROPOSED SITE CONFIGURATION?
  
 2. WE WILL DEFER TO THE CITY'S LEGAL DEPARTMENT FOR
 DETERMINATION OF THE DOCUMENT REQUIRED TO DEMONSTRATE
 COMPLIANCE WITH SECTION 94-305(B) OF THE CODE OF
 ORDINANCES. "SETBACK ENCROACHMENTS. JOINT USE
 PROHIBITED. THE SETBACK OR OPEN SPACE OF A BUILDING ON
 ONE LOT SHALL NOT BE CONSIDERED AS THE SETBACK OR OPEN
 SPACE FOR A BUILDING ON ANY OTHER LOT EXCEPT WHERE
 UNITY OF TITLE IS PROVIDED FOR ALL AFFECTED
 PROPERTIES."
  
 3. FLORIDA DEPARTMENT OF TRANSPORTATION APPROVAL WILL
 BE REQUIRED FOR THE WORK ALONG OKEECHOBEE BLVD.
  
 4. PLEASE SUBMIT A COPY OF THE TRAFFIC CONCURRENCY
 LETTER FROM PALM BEACH COUNTY.
  
 5. PLEASE SUBMIT APPLICATIONS FOR A DEVELOPMENT PERMIT
 AND RIGHT-OF-WAY PERMIT FROM THE ENGINEERING
 DEPARTMENT. APPLICATION FORMS CAN BE FOUND AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
 (SECTIONS 2-421 AND 78-432, CODE OF ORDINANCES)
  
 6. PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY'S
 ENGINEERING DESIGN STANDARDS. PLEASE ALSO INCLUDE THE
 DETAILS FOR THE SIDEWALK RAMPS, HTTP://WPB.ORG/ENGINEER
 ING/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/
  
 7. THE NUMBER OF PROPERTY ACCESS DRIVES EXCEEDS THE
 MAXIMUM NUMBER AND WIDTH ALLOWED FOR COMMERCIAL
 PROPERTIES. PER CODE OF ORDINANCES SECTION 94-313,
 NON-RESIDENTIAL PROPERTIES WITH LESS THAN 300 REQUIRED
 PARKING SPACES MAY HAVE UP TO ONE ACCESS POINT ONTO
 EACH RIGHT-OF-WAY.
  
 8. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS
 OF ALL WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES,
 UNDERGROUND UTILITIES (WATER, SANITARY, STORM, GAS,
 ELECTRIC), ETC.
  
 9. PLEASE SHOW THE SIGHT TRIANGLES ON THE LANDSCAPING
 PLAN FOR THE INTERSECTIONS AND VEHICULAR EXITS.
 (SECTION 94-305E, CODE OF ORDINANCES)
  
 10. PLEASE REVISE PLANS TO INCLUDE THE CITY OF WEST
 PALM BEACH GARBAGE RECEPTACLE DETAIL. THE SHOWN DETAIL
 DOES NOT MEET THE MINIMUM DIMENSIONAL REQUIREMENTS OF
 CODE OF ORDINANCES, SECTION 94-444(B), ALSO SEE FIGURE
 XIV-3 OF THE SAME SECTION. CITY STANDARD DETAIL GC-8
 MAY BE DOWNLOADED AT HTTP://WPB.ORG/ENGINEERING/ENGINEE
 RING-SERVICES/ENGINEERING-STANDARDS/
  
 11. WILL SOLID WASTE COLLECTION SERVICE BE PROVIDED BY
 THE CITY OR BY A PRIVATE COMPANY? PER SECTION 74-31 OF
 THE CODE OF ORDINANCES, EVERY COMMERCIAL ESTABLISHMENT
 WITHIN THE CITY SHALL SUBSCRIBE FOR REGULAR COMMERCIAL
 SOLID WASTE COLLECTION AND DISPOSAL SERVICES FROM THE
 CITY EXCEPT THOSE COMMERCIAL ESTABLISHMENTS FOR WHICH
 THE CITY IS UNABLE TO PROVIDE THE NEEDED SERVICES,
 E.G., CONTAINERS AND COMPACTORS OVER EIGHT CUBIC YARDS.
 FOR THESE SERVICES, THE COMMERCIAL ESTABLISHMENT MUST
 USE THE SERVICES OF A PROVIDER APPROVED TO OPERATE
 WITHIN THE CITY PURSUANT TO A FRANCHISE AGREEMENT. NO
 PERSON SHALL ATTEMPT TO USE CITY SERVICES WITHOUT
 HAVING FIRST SUBSCRIBED FOR SUCH SERVICES OR WITHOUT
 HAVING REQUESTED THE CITY TO PERFORM A SPECIAL SOLID
 WASTE COLLECTION AND DISPOSAL.
  
 12. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES.
  
 13. SOLID WASTE YARDAGE WILL NEED TO BE ESTIMATED AS
 PART OF THE FINAL DESIGN TO VERIFY THAT THE ENCLOSURE
 SIZE IS APPROPRIATE FOR THE REQUIRED NUMBER AND SIZE OF
 TRASH BINS.
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  
 VINCE NOEL, PSM
 CITY SURVEYOR / REAL ESTATE SUPERVISOR
 [email protected]
 561-494-1096
  
 BRIAN COLLINS, PE
 CITY TRAFFIC ENGINEER
 [email protected]
 561-494-1040
  
 FERDINAND RIVERA
 PUBLIC WORKS OPERATIONS MANAGER
 [email protected]
 561-822-2076
  
 TRACY WARD, PE
 CITY STORMWATER ENGINEER
 561-494-1120
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 05-27-2015 Cont ID  
Sent By pleduc Date 05-27-2015 Time 15:48 Rev Time 0.00
Received By pleduc Date 05-27-2015 Time 15:48 Sent To  
Notes
2015-05-27 15:56:24AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED MAY
 19, 2015, FROM ERIC SCHNEIDER, PRINCIPAL PLANNER, THE
 PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS
 HAVE BEEN ADDRESSED.
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-09-2015 Cont ID  
Sent By pleduc Date 03-09-2015 Time   Rev Time 0.00
Received By pleduc Date 03-09-2015 Time 13:10 Sent To  
Notes
2015-03-09 13:42:52THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. PLEASE PROVIDE THE OCCUPANCY TYPE OF EACH BUILDING.
 ARE THE BUILDINGS FUNCTIONING AS MULTIUSE OCCUPANCIES?
 INDICATE IF THE BUILDINGS ARE DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14 OF
 NFPA 101. FOR NON-SEPARATED MIXED USE OCCUPANCIES, THE
 MOST STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF
 EACH OCCUPANCY SHALL APPLY TO THE BUILDING.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR EACH STRUCTURE, INCLUDING THE GARAGE WITH
 A NFPA 14 COMPLIANT WET STANDPIPE SYSTEM. TEMPORARY
 STANDPIPES ARE REQUIRED WHEN THE BUILDING REACHES THREE
 LEVELS OR THIRTY FEET WHILE BEING CONSTRUCTED. SEPARATE
 SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED
 AND APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 7. PARKING STRUCTURES SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 88A 2011 EDITION,AND NFPA 101,
 CHAPTER 42 AND ALL OTHER APPLICABLE CODES.\
  
 8. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 9. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR
 THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND INDICATED
 ON THE PLANS.
  
 10. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE.
  
 11. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN. SHEET A-1.0 INDICATES A
 STAIRWAY EXIT DOOR THAT DISCHARGES INTO A PARTS STORAGE
 ROOM. THIS IS A NONCOMFORMING EXIT AND WILL BE DENIED.
 AN ALTERNATIVE EXIT SHALL BE DESIGNED IN COMPLIANCE
 WITH NFPA CHAPTER 7.
  
 12. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 13. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM
 RISE, RUN, AND TREAD DEPTH.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 15. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 16. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
 17. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 18. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 19. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 20. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY
 INDICATED ON THE BUILDING PLAN.
  
 21. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 22. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 23. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 24. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 05-20-2015 Cont ID  
Sent By rcaranci Date 05-20-2015 Time 08:17 Rev Time 0.00
Received By rcaranci Date 05-20-2015 Time 08:17 Sent To  
Notes
2015-05-20 08:18:59ALL PREVIOUS COMMENTS SATISFIED.
 ADDITIONAL COMMENTS 4/13/15:
 12. SATISFIED. THE EASTERN BUFFER HAS BEEN INCREASED IN
 WIDTH, ALLOWING THE ADDITION OF LARGER BUFFER TREES TO
 BUFFER THE IMPACT OF THE MASS OF THE BUILDING. PLEASE
 ADD LARGER TREES TO THE BUFFER.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-13-2015 Cont ID  
Sent By rcaranci Date 04-13-2015 Time 12:01 Rev Time 0.00
Received By rcaranci Date 04-13-2015 Time 12:01 Sent To  
Notes
2015-04-13 12:03:32RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 APRIL 13, 2015
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. REVISE THE LANDSCAPE PLAN TO INCLUDE A
 LIST OF THE EXISTING TREES LOCATED ON THE PROPERTY AND
 INCLUDE THE SIZE, SPECIES AND WHETHER THEY WILL BE
 REMOVED, RELOCATED, OR PRESERVED IN PLACE. A TREE
 ALTERATION PERMIT IS REQUIRED FOR TREES BEING REMOVED
 (SOUTH AND EAST SIDES OF EXISTING SERVICE BUILDING) PER
 SECTION 94-448.
  
 2. SATISFIED. THE BUFFER LOCATED AT THE SOUTHEAST
 CORNER OF THE SITE IS REQUIRED TO BE FIVE (5) FEET
 WIDE, THE LANDSCAPE BUFFER ALONG OKEECHOBEE BOULEVARD
 IS REQUIRED TO BE FIVE (5) FEET IN WIDTH. SECTIONS OF
 THE NORTH BUFFER MEASURE LESS THAN THE REQUIRED 5 FEET
 PER SECTION 94-443. THE DIMENSIONS SHALL BE CLEARLY
 SHOWN ON THE SITE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE A SEPARATE SHEET LABELED
 ?SITE PLAN AREA CALCULATIONS? SHOWING THE CAD LAYERS
 FOR THE FOLLOWING: TOTAL SITE AREA, TOTAL OPEN SPACE,
 LANDSCAPED OPEN SPACE, PERVIOUS AREA, IMPERVIOUS AREA
 AND SOD AREA WITH CORRESPONDING SQUARE FOOTAGES SHOWN.
  
 4. SATISFIED. PLEASE USE THE REQUIRED OPEN SPACE OF 40%
 FOR THE ENTIRE SITE TO CALCULATE THE NUMBER OF SHADE
 TREES, FLOWERING TREES AND SHRUBS REQUIRED BY SECTION
 94-442.
  
 5. SATISFIED. PROVIDE THE DATA TABLES/CALCULATIONS TO
 VERIFY THE COMPLIANCE OF THE ENTIRE BRAMAN MOTORCARS
 SITE WITH THE CITY?S LANDSCAPE REGULATIONS. THIS
 INCLUDES THE REQUIRED NUMBER OF TREES AND SHRUBS
 (SECTION 94-442 (B)(2) B.), THE REQUIRED NUMBER OF
 PERIMETER TREES BY BUFFER (SECTION 94-443 (B)), THE
 PERCENTAGE OF PALM TREES SUBSTITUTED FOR SHADE OR
 FLOWERING TREES (SECTION 94-442(C).), REQUIRED PARKING
 LOT LANDSCAPE (SECTION 94-443 (C)), AND REQUIRED
 FOUNDATION PLANTING (SECTION 94-443(E)(1)).
  
 6. SATISFIED. THE LIGHT POLES SHALL BE SHOWN ON THE
 LANDSCAPE PLAN. LIGHT POLES SHALL NOT INTERFERE WITH
 THE LONG TERM GROWTH OF THE TREES.
  
 7. SATISFIED. THERE IS NO TERMINAL TREE SHOWN AT THE
 SOUTHWESTERN ROW OF NEW PARKING OR NEXT TO THE PORSCHE
 SERVICE AREA ENTRANCE PARKING REQUIRED PER SECTION
 94-443(C).
  
 8. SATISFIED. ALL THE UTILITY FEATURES SHOWN ON THE
 CIVIL PLANS SHALL BE SHOWN ON LANDSCAPE PLAN AND IN THE
 SAME LOCATIONS. EX. NORTHEAST CORNER DOES NOT SHOW
 WATER METER, ETC. ITEMS. THE NEW SIX (6) INCH SANITARY
 SEWER SERVICE IS NOT SHOWN AND A TREE IS SHOWN ON TOP
 OF IT.
  
 9. SATISFIED. ALL HEDGES SHALL BE ALLOWED TO GROW TO
 THE MINIMUM 40 INCH HEIGHT WITHIN TWO YEARS OF PLANTING
 AS REQUIRED BY SECTION 94-445(4)E OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS. THE WAX JASMINE WILL NOT
 GROW TO 40 INCHES WITHIN THE TWO YEAR TIME FRAME, SO IT
 MAY NOT BE USED AS A HEDGE MATERIAL ALONG OKEECHOBEE
 BOULEVARD.
  
 10. SATISFIED. WHAT IS GOING TO BE USED TO PROTECT THE
 LANDSCAPE FROM VEHICULAR ENCROACHMENT AT THE SOUTHWEST
 CORNER OF THE SITE, IN THE MIDDLE PARKING BY THE GARAGE
 ENTRANCE AREA AND IN THE REAR OF THE SITE BY THE MINI
 SERVICE AREA?
  
 11. SATISFIED. PLEASE PROVIDE LANDSCAPING AND SCREENING
 FOR ALL GROUND MOUNTED EQUIPMENT INCLUDING FPL, WATER
 AND PHONE/ CABLE, GENERATORS, A/C UNITS ETC.
  
 ADDITIONAL COMMENTS 4/13/15:
 12. THE EASTERN BUFFER HAS BEEN INCREASED IN WIDTH,
 ALLOWING THE ADDITION OF LARGER BUFFER TREES TO BUFFER
 THE IMPACT OF THE MASS OF THE BUILDING. PLEASE ADD
 LARGER TREES TO THE BUFFER.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-10-2015 Cont ID  
Sent By eschneid Date 03-10-2015 Time 22:07 Rev Time 0.00
Received By eschneid Date 03-10-2015 Time 22:07 Sent To  
Notes
2015-03-10 22:08:32RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: BRAMAN MOTORCARS
 MARCH 10, 2015
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. REVISE THE LANDSCAPE PLAN TO INCLUDE A LIST OF THE
 EXISTING TREES LOCATED ON THE PROPERTY AND INCLUDE THE
 SIZE, SPECIES AND WHETHER THEY WILL BE REMOVED,
 RELOCATED, OR PRESERVED IN PLACE. A TREE ALTERATION
 PERMIT IS REQUIRED FOR TREES BEING REMOVED (SOUTH AND
 EAST SIDES OF EXISTING SERVICE BUILDING) PER SECTION
 94-448.
  
 2. THE BUFFER LOCATED AT THE SOUTHEAST CORNER OF THE
 SITE IS REQUIRED TO BE FIVE (5) FEET WIDE, THE
 LANDSCAPE BUFFER ALONG OKEECHOBEE BOULEVARD IS REQUIRED
 TO BE FIVE (5) FEET IN WIDTH. SECTIONS OF THE NORTH
 BUFFER MEASURE LESS THAN THE REQUIRED 5 FEET PER
 SECTION 94-443. THE DIMENSIONS SHALL BE CLEARLY SHOWN
 ON THE SITE PLAN.
  
 3. PLEASE PROVIDE A SEPARATE SHEET LABELED ?SITE PLAN
 AREA CALCULATIONS? SHOWING THE CAD LAYERS FOR THE
 FOLLOWING: TOTAL SITE AREA, TOTAL OPEN SPACE,
 LANDSCAPED OPEN SPACE, PERVIOUS AREA, IMPERVIOUS AREA
 AND SOD AREA WITH CORRESPONDING SQUARE FOOTAGES SHOWN.
  
 4. PLEASE USE THE REQUIRED OPEN SPACE OF 40% FOR THE
 ENTIRE SITE TO CALCULATE THE NUMBER OF SHADE TREES,
 FLOWERING TREES AND SHRUBS REQUIRED BY SECTION 94-442.
  
 5. PROVIDE THE DATA TABLES/CALCULATIONS TO VERIFY THE
 COMPLIANCE OF THE ENTIRE BRAMAN MOTORCARS SITE WITH THE
 CITY?S LANDSCAPE REGULATIONS. THIS INCLUDES THE
 REQUIRED NUMBER OF TREES AND SHRUBS (SECTION 94-442
 (B)(2) B.), THE REQUIRED NUMBER OF PERIMETER TREES BY
 BUFFER (SECTION 94-443 (B)), THE PERCENTAGE OF PALM
 TREES SUBSTITUTED FOR SHADE OR FLOWERING TREES (SECTION
 94-442(C).), REQUIRED PARKING LOT LANDSCAPE (SECTION
 94-443 (C)), AND REQUIRED FOUNDATION PLANTING (SECTION
 94-443(E)(1)).
  
 6. THE LIGHT POLES SHALL BE SHOWN ON THE LANDSCAPE
 PLAN. LIGHT POLES SHALL NOT INTERFERE WITH THE LONG
 TERM GROWTH OF THE TREES.
  
 7. THERE IS NO TERMINAL TREE SHOWN AT THE SOUTHWESTERN
 ROW OF NEW PARKING OR NEXT TO THE PORSCHE SERVICE AREA
 ENTRANCE PARKING REQUIRED PER SECTION 94-443(C).
  
 8. ALL THE UTILITY FEATURES SHOWN ON THE CIVIL PLANS
 SHALL BE SHOWN ON LANDSCAPE PLAN AND IN THE SAME
 LOCATIONS. EX. NORTHEAST CORNER DOES NOT SHOW WATER
 METER, ETC. ITEMS. THE NEW SIX (6) INCH SANITARY SEWER
 SERVICE IS NOT SHOWN AND A TREE IS SHOWN ON TOP OF IT.
  
 9. ALL HEDGES SHALL BE ALLOWED TO GROW TO THE MINIMUM
 40 INCH HEIGHT WITHIN TWO YEARS OF PLANTING AS REQUIRED
 BY SECTION 94-445(4)E OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. THE WAX JASMINE WILL NOT GROW
 TO 40 INCHES WITHIN THE TWO YEAR TIME FRAME, SO IT MAY
 NOT BE USED AS A HEDGE MATERIAL ALONG OKEECHOBEE
 BOULEVARD.
  
 10. WHAT IS GOING TO BE USED TO PROTECT THE LANDSCAPE
 FROM VEHICULAR ENCROACHMENT AT THE SOUTHWEST CORNER OF
 THE SITE, IN THE MIDDLE PARKING BY THE GARAGE ENTRANCE
 AREA AND IN THE REAR OF THE SITE BY THE MINI SERVICE
 AREA?
  
 11. PLEASE PROVIDE LANDSCAPING AND SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT INCLUDING FPL, WATER AND
 PHONE/ CABLE, GENERATORS, A/C UNITS ETC.
  
  
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 05-26-2015 Cont ID  
Sent By cranford Date 05-26-2015 Time 14:06 Rev Time 0.00
Received By cranford Date 05-26-2015 Time 14:06 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 03-10-2015 Cont ID  
Sent By cranford Date 03-10-2015 Time 10:41 Rev Time 0.00
Received By cranford Date 03-10-2015 Time 08:26 Sent To  
Notes
2015-03-10 10:42:00PLEASE REFER TO ENGINEERING PPRC COMMENTS.

Review Stop STORM STORMWATER
Rev No 1 Status P Date 03-10-2015 Cont ID  
Sent By cranford Date 03-10-2015 Time 10:42 Rev Time 0.00
Received By cranford Date 03-10-2015 Time 08:26 Sent To  
Notes
2015-03-10 10:42:27PLEASE REFER TO ENGINEERING PPRC COMMENTS.

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 03-10-2015 Cont ID  
Sent By cranford Date 03-10-2015 Time 10:43 Rev Time 0.00
Received By cranford Date 03-10-2015 Time 10:42 Sent To  
Notes
2015-03-10 10:42:51PLEASE REFER TO ENGINEERING PPRC COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 05-26-2015 Cont ID  
Sent By cranford Date 05-26-2015 Time 14:07 Rev Time 0.00
Received By cranford Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 03-10-2015 Cont ID  
Sent By cranford Date 03-10-2015 Time 10:43 Rev Time 0.00
Received By cranford Date 03-10-2015 Time 08:26 Sent To  
Notes
2015-03-10 10:43:18PLEASE REFER TO ENGINEERING PPRC COMMENTS.

Review Stop Z ZONING
Rev No 3 Status F Date 07-01-2015 Cont ID  
Sent By eschneid Date 07-01-2015 Time 15:06 Rev Time 0.00
Received By eschneid Date 07-01-2015 Time 15:05 Sent To  
Notes
2015-07-01 15:09:12PB 1222M - POST PB RESUBMITTAL
 BRAMAN MOTORCARS CPD
 2901 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THESE COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON THURSDAY,
 JULY 9, 2015, TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 AUGUST 17, 2015 CITY COMMISSION MEETING.
  
 1) PRIOR TO SCHEDULING A PUBLIC HEARING BEFORE THE CITY
 COMMISSION, THE APPLICANT SHALL:
  
 A. REPEAT COMMENT: SHOW ALL THE PARKING SPACES IN FRONT
 OF BUILDING D HAVING WHEEL STOPS OR OTHER BARRIER TO
 PREVENT CUSTOMERS FROM PARKING ACROSS THE SIDEWALK. NOT
 ALL SPACES SHOW A BARRIER.
 B. REPEAT COMMENT: REVISE THE PLANS TO SHOW THE BICYCLE
 RACK PAD BEHIND THE EXISTING BMW BUILDING WITH THE
 DIMENSIONS LABELED ON THE SITE PLAN AND THE CORRECT
 SIZE ON THE LANDSCAPE PLAN. THE PAD IS SHOWN ON THE
 PLANS AT FOUR (4) FEET DEEP. THIS PAD NEEDS TO BE SHOWN
 TO SCALE TO VERIFY THAT IT WILL FIT IN THIS LOCATION.
 THE DETAIL INCLUDED ON SHEET SP-4 SHALL ALSO INCLUDE
 THIS SPECIFIC PAD, WITH RACK ELEMENTS AND DIMENSIONS.
 THE DIMENSION BETWEEN EACH RACK IS ELEMENT IS NOT SHOWN
 (30 INCHES ON CENTER).
  
 C. REPEAT COMMENT: CORRECT THE DATA ON THE MASTER SIGN
 PLAN, TO INCLUDE THE PROVISION OF SIGN DIMENSIONS ON
 THE ELEVATION DRAWINGS FOR ALL EXISTING AND PROPOSED
 SIGNS.
 - OKEECHOBEE AND PALM BEACH LAKES BOULEVARD FRONTAGE
 DIMENSIONS ARE INCORRECTLY SHOWN ON THE MASTER SIGN
 PLAN AT 1,816.21 LINEAR FEET. THE CORRECT LINEAR FEET
 ARE 1767.17 FEET. THE KEY DRAWING SHOWS A PORTION OF
 EXCHANGE COURT AS PART OF THE FRONTAGE.
 - ID SIGN "A" IS NOT SHOWN WITH THE ENTIRE HEIGHT AND
 FA?ADE DIMENSION. THIS IS A LOW FREESTANDING SIGN BY
 CODE DEFINITION AND SHALL BE INCLUDED (X2) UNDER THE
 LOW FREESTANDING SIGN TABLE.
 - THE BUILDING D&E FA?ADE SQUARE FOOTAGE AND TOTAL SIGN
 SQUARE FOOTAGE PERMITTED FOR EACH FA?ADE TABLE IS NOT
 INCLUDED. THIS WAS TO REMAIN ON THE PLANS; JUST WITHOUT
 CALLING OUT THE PROPOSED NUMBER OF SIGNS AND EXCESS
 SIGN SQUARE FOOTAGE, PER THE DISCUSSION AT THE LAST
 MEETING.
 - REMOVE THE LOGO SECTION FROM THE HIGH FREESTANDING
 SIGN CALCULATIONS - THIS AREA IS ALREADY INCLUDED ON
 THE SIGN BODY. REVISE THE TOTAL SIGN SQUARE FOOTAGE
 PROVIDED ACCORDINGLY..
 - THERE ARE INCORRECT HEIGHTS ON THE BRAMAN AND BMW
 SERVICE WALL SIGN DETAILS BASED ON THE APPROVED SIGN
 PERMITS.
 - THE "CERTIFIED PRE-OWNED" WAS SIGN DIMENSIONS ARE NOT
 PROVIDED.
  
 D. CORRECTLY LISTS THE WAIVERS THAT ARE BEING REQUESTED
 ON THE WAIVER TABLE. SEE PB REPORT FOR ACTUAL WAIVERS.
 ADDITIONALLY, THE HIGH FREESTANDING LINE SHOULD STATE:
 REQUIRED: OKEECHOBEE BOULEVARD LINEAR FRONTAGE
 PROPOSED: OKEECHOBEE AND PALM BEACH LAKES BOULEVARDS
 LINEAR FRONTAGE
 WAIVER: USE ENTIRE ARTERIAL FRONTAGE FOR ONE SIGNAGE
 CALCULATION.
  
 E. REVISE THE LANDSCAPE PLAN TO REMOVE THE LABEL ON
 BUILDING C WHICH STATES "PROPOSED NEW FACILITY".
  

Review Stop Z ZONING
Rev No 2 Status F Date 03-30-2015 Cont ID  
Sent By eschneid Date 03-30-2015 Time 19:09 Rev Time 5.00
Received By eschneid Date 03-30-2015 Time 19:09 Sent To  
Notes
2015-03-30 19:12:32PB 1222M ? RESUBMITTAL 3/20/2015
 BRAMAN MOTORCARS CPD
 2901 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 APRIL 17, 2015, TO BE SCHEDULED FOR THE MAY 19, 2015
 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY MAY 30, 2015), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT THIS RESUBMITTAL DID NOT ADDRESS
 PREVIOUSLY-ISSUED COMMENTS; THEREFORE, THE APPLICANT
 WILL BE ACCESSED A RESUBMITTAL FEE OF 20% OF THE
 ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 GENERAL
  
 1) CONTINUE TO EVALUATE AS PROJECT MOVES FORWARD: WHAT
 INNOVATIVE FEATURES OF THE PROJECT WHICH MAKE THIS
 PROJECT MORE DESIRABLE AND ATTRACTIVE THAN AN AUTO
 DEALERSHIP THAT MEETS ALL CODE REQUIREMENTS? AT A
 MINIMUM THE PROPOSED DEVELOPMENT REQUIRES WAIVERS TO
 THE SIGNAGE, INTERNAL SETBACKS AND LANDSCAPE, AND
 NUMBER OF ACCESS POINTS.
  
 2) REVISED COMMENT: THE LANDSCAPE FOR THE SITE NEEDS TO
 BE SHOWN ON ONE UNIFIED PLAN. SUBMITTING TWO PLANS WITH
 CHANGED OVERLAPPING AREAS AND UNDEFINED DATA TABLES IS
 NOT ACCEPTABLE.
  
 3) CONDITION: A UNITY OF TITLE IS REQUIRED PRIOR TO THE
 CONSTRUCTION OF THE FIRST BUILDING COMPRISING OF THE
 NEW PORSCHE, BENTLEY, ROLLS BUILDING.
  
 4) WAIVERS REQUESTED: THE PROPOSED DEVELOPMENT PLAN
 DOES NOT COMPLY WITH THE SETBACK AND LANDSCAPE
 REQUIREMENTS FOR THE INTERIOR LOT LINES WITH THE
 EXISTING BRAMAN MOTORCARS DSI. ANY NON-COMPLAINANT
 AREAS WOULD NEED TO BE SPECIFICALLY APPROVED AS WAIVERS
 WITHIN THE CPD.
  
 5) CONDITION: PROVIDE VERIFICATION OF THE UTILITY
 EASEMENTS BEING ABANDONED PRIOR TO APPROVAL OF THE
 BUILDING PERMIT FOR THE BUILDING LOCATED ON THE
 EASEMENT.
  
 6) REPEAT COMMENT: PARKING AND LANDSCAPE COMPLIANCE
 SHALL BE SHOWN AND INSTALLED TO COMPLY WITH THE ZLDR
 FOR EACH PHASE OF THE DEVELOPMENT. STAFF HAS CALCULATED
 THAT THE NEW PORSCHE BUILDING WILL REQUIRE 49 PARKING
 SPACES (TWO OF WHICH ADA) WHEN IT BECOMES OPERATIONAL.
 THE PLANS ONLY SHOW 26 WITH ONE ADA SPACE.
 ADDITIONALLY, THE WESTERN BUFFER OF THE PARKING LOT
 DOES NOT HAVE A TURNAROUND SPACE FOR THE CUSTOMER
 PARKING. HOW WILL TRASH SERVICE BE PROVIDED? PLEASE
 VERIFY THAT THE BENTLEY, ROLLS, USED CAR AND BALANCE OF
 THE GARAGE WILL BE CONSTRUCTED AT ONE TIME.
  
 TRAFFIC
  
 7) REPEAT COMMENT: PROVIDE THE PALM BEACH COUNTY
 TRAFFIC CONCURRENCY APPROVAL LETTER.
  
 8) WAIVER REQUESTED: THE JUSTIFICATION STATEMENT LISTS
 SEVEN CURB CUTS BEING USED WHILE THE LATEST STREET VIEW
 SHOWS ONLY SIX BEING USED. PLEASE BE AWARE THE SITE
 EXCEEDS THE NUMBER OF PERMITTED ACCESS POINTS TO THE
 STREET NETWORK. OPENINGS ALONG BOTH OKEECHOBEE
 BOULEVARD AND EXCHANGE COURT NEED TO BE REDUCED.
  
 9) REPEAT COMMENT: PROVIDE A DRIVEWAY PREDETERMINATION
 LETTER OF APPROVAL FROM FDOT FOR THE WORK WITHIN THE
 OKEECHOBEE BOULEVARD RIGHT-OF-WAY.
  
 10) CONDITION: A RIGHT-OF-WAY PERMIT WILL BE REQUIRED
 FOR ANY WORK WITHIN THE FDOT OR THE CITY RIGHT-OF-WAY.
  
 11) CONDITION: ALL CURB CUTS THAT ARE NOT BEING USED
 SHALL BE REMOVED AND THE SIDEWALK MADE FLUSH WITH THE
 ADJACENT SIDEWALK.
  
 12) CONDITION: THE PROPOSAL TO PLANT IN THE EXCHANGE
 COURT RIGHT-OF-WAY REQUIRES THE APPROVAL OF THE
 ENGINEERING SERVICES DIVISION. IRRIGATION SHALL BE
 SUPPLIED TO THESE TREES. A RECORDED AGREEMENT TO
 MAINTAIN AND REPLACE THE TREES AND IRRIGATION IS
 REQUIRED FROM BRAMAN.
  
 SITE
  
 13) CONDITION: ALL MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, UTILITY EQUIPMENT, GENERATORS,
 TRANSFORMERS, ETC. SHALL BE SCREENED FROM VIEW OF THE
 PUBLIC.
  
 14) WAIVER REQUESTED: THE EAST SIDE SETBACK IS REQUIRED
 TO BE 27 FEET SINCE THE BUILDING THAT IS BEING
 CONSTRUCTED IS 75 FEET 8 INCHES TALL.
  
 15) REPEAT COMMENT: HOW TALL ARE THE GATES? THE COMMENT
 RESPONSE LISTS THE GATES AS 10 FEET TALL. PROVIDE A
 DETAIL THAT INCLUDES THE FENCE HEIGHT. PLEASE NOTE THAT
 THE GATES ALONG EXCHANGE COURT MAY NOT EXCEED EIGHT (8)
 FEET TALL. STAFF WILL NOT SUPPORT 10 FOOT TALL GATES
 ALONG OKEECHOBEE BOULEVARD AS THESE WILL BE OUT OF
 SCALE WITH THE SITE CONDITIONS AT THE FRONTAGE LINE.
  
 16) NEW COMMENT: IS THE DOOR ON THE WEST SIDE OF THE
 ROLLS ROYCE DEALERSHIP INTENDED TO OPEN INTO THE
 LANDSCAPED AREA WITH THE HEDGE?
  
 17) NEW COMMENT: THE NEW DUMPSTER ENCLOSURE/COMPACTOR
 SHALL BE IN AN ENCLOSURE WITH A PERIMETER HEDGE ON
 THREE SIDES. THE PLANS SHALL SHOW A DIMENSIONED DETAIL
 OF THE DUMPSTER ENCLOSURE AND HAVE THE DIMENSION LINES
 SHOWN ON THE PLAN. THE ENCLOSURE MAY NOT BE ACCESSED
 FROM THE EAST SIDE DUE TO THE ADJACENT PARKING SPACES.
 THERE CONCEPTUAL PAVING, DRAINAGE, WATER AND WASTEWATER
 PLAN SHOWS TWO WATER METERS IN THE DRIVE AISLE TO
 ACCESS THE WEST SIDE OF THE DUMPSTER ENCLOSURE. PLEASE
 FIX THESE ITEMS.
  
 PARKING
  
 18) REPEAT COMMENT: STAFF IS UNABLE TO VERIFY THE
 PARKING REQUIRED FOR THE SITE DUE THE VARIOUS PLANS
 SHOWING DIFFERING SQUARE FOOTAGE FOR THE SAME AREAS
 (EX. THE BUILDING D AREAS AND THE PORSCHE SERVICE
 RECEPTION LIST DIFFERING SQUARE FOOTAGE ON THE SITE AND
 ARCHITECTURAL PLANS AND THE PRE-OWNED AREA IS LISTED
 WITH A DIFFERENT SQUARE FOOTAGE ON SHEETS SP-1.0 AND
 A-1.1). THE SITE PLAN PARKING DATA TABLE INCORRECTLY
 EXCLUDES THE SERVICE PARTS AND STORAGE AREAS BY SHOWING
 IT COMBINED WITH THE NUMBER OF SERVICE BAYS. PARKING
 SHALL BE PROVIDED FOR THE SERVICE PARTS AND STORAGE
 AREAS USING THE ENCLOSED AREA RATE OF 1 PARKING SPACE
 PER 500 SQUARE FEET. PROVIDE A COLOR CODED FLOOR PLAN
 THAT DEMARCATES THE INTERIOR SQUARE FOOTAGE, THE
 SERVICE BAY AREAS AND INTERNAL VEHICLE CIRCULATION
 AREAS. THE SQUARE FOOTAGES OF EACH AREA SHALL BE
 PROVIDED SO THAT STAFF CAN CALCULATE THE PARKING
 REQUIREMENTS.
  
 19) REVISED COMMENT: THE BICYCLE PAD AND RACK DETAILS
 DO NOT SHOW THE DIMENSIONS FOR THE BICYCLE PADS. THE
 DETAIL INCLUDED ON SHEET SP-4 ONLY SHOWS PARKING FOR
 SIX BICYCLES, NOT SEVEN AS STATED ON THE PLANS. PLEASE
 REMEMBER THAT ONE BICYCLE RACK ELEMENT HOLDS TWO
 BICYCLES, SO EACH BICYCLE PAD WILL HAVE AN EVEN NUMBER
 OF BICYCLE PARKING SPACES. THE BICYCLE PADS SHALL SHOW
 CODE COMPLIANT DIMENSIONS ON THE PLAN (THE BICYCLE PADS
 DO NOT SCALE AT THE REQUIRED SIX FOOT DEPTH).
  
 20) NEW COMMENT: THE SITE PLAN SHOWS A BICYCLE PAD
 BEING LOCATED UNDER THE RAMP IN THE GARAGE. THIS
 BICYCLE RACK IS NOT SHOWN ON THE ARCHITECTURAL PLAN.
 PLEASE INDICATE HOW IT WILL BE ACCESSED IN LIGHT OF THE
 PLANS SHOWING THIS AREA SURROUNDED BY SOLID WALLS. WHAT
 IS THE CLEARANCE AT THE PROPOSED LOCATION?
  
 21) REVISED COMMENT: THE AREA BEHIND THE FUTURE MINI
 DEALERSHIP (UNDER THE CANOPY) IS SHOWN AS HAVING A
 DEAD-END DOUBLE ROW OF PARKING. THERE SHALL BE ONE
 SPACE AT THE END MARKED AS A TURNAROUND SPACE WITH THE
 BACK-OUT ASSIST AREA INDENTING THREE (3) FEET FROM THE
 WEST SIDE OF THE SPACE.
  
 22) REPEAT COMMENT: PROVIDE DIMENSION TAGS FOR EACH NEW
 PARKING BAY - CURB FACE TO CURB FACE. THE WIDTH OF THE
 PARKING SPACES FLUCTUATES BETWEEN 8.5 FEET WIDE OR 9
 FEET WIDE IN DIFFERING ROWS, SO THE DIMENSION LINES
 WILL ENSURE THAT THE CURBING IS INSTALLED IN THE PROPER
 LOCATIONS.
  
 23) REVISED COMMENT: THE FLOOR GARAGE FLOOR PLANS SHALL
 INDICATE THE AREAS OF VEHICLE STORAGE AND SERVICE
 PARKING.
  
 24) NEW COMMENT: WHAT OCCURS IN THE "RECONDITIONING
 SPACE"?
  
 25) NEW COMMENT: HOW WILL THE WASH BAY ON THE 5TH FLOOR
 OF THE GARAGE FUNCTION? IT DOES NOT APPEAR THAT THERE
 IS ANYWHERE FOR THE WATER TO DRAIN.
  
 26) REVISED COMMENT: THE LOADING ZONE MENTIONED IN THE
 RESPONSE AS ON THE GROUND FLOOR OF THE PHASE 1 GARAGE
 NEEDS TO BE CLEARLY LABELED ON THE GARAGE SITE PLAN.
  
 27) NEW COMMENT: THE ADA PARKING SPACE IN FRONT OF THE
 PORSCHE DEALERSHIP IS REQUIRED TO HAVE A WHEEL STOP TO
 KEEP CARS FROM DRIVING ONTO THE SIDEWALK.
  
 SIGNAGE
  
 28) ADDITIONAL INFORMATION REQUIRED: PLEASE NOTE THAT
 MINI IS ONLY PERMITTED THREE FACADE SIGNS BASED ON THE
 CURRENT LAYOUT OF BUILDING A. CHANGES TO CONNECT THIS
 BUILDING TO BUILDING B WOULD REDUCE THE NUMBER OF
 PERMITTED FACADE SIGNS. WITHOUT FURTHER INFORMATION,
 STAFF IS UNABLE TO VERIFY COMPLIANCE, BUT IT APPEARS
 THAT THE AT LEAST THE SOUTH ELEVATION SIGN IS TWICE AS
 LARGE AS PERMITTED.
  
 29) ADDITIONAL INFORMATION REQUIRED: THE NEW BUILDING
 HAS 12 FACADE SIGNS. ONLY SIX FACADE SIGNS ARE
 PERMITTED.
  
 30) ADDITIONAL INFORMATION REQUIRED: DIMENSIONS WERE
 NOT PROVIDED FOR STAFF TO DETERMINE HOW MUCH FACADE
 SIGN SQUARE FOOTAGE IS PERMITTED, NOR WAS INFORMATION
 PROVIDED ON HOW MUCH FACADE SIGN SQUARE FOOTAGE IS
 PROPOSED.
  
 31) REVISED COMMENT: HF SIGN A IS NOT SHOWN IN
 ACCORDANCE WITH ITS ORIENTATION ON THE SURVEY.
  
 32) ADDITIONAL INFORMATION REQUIRED: STAFF CALCULATES
 1,640 SQ. FT. OF HIGH FREESTANDING SIGNAGE PROPOSED
 ALONG OKEECHOBEE BOULEVARD (HF SIGNS B, C, D1, D2 AND
 E). WHICH EXCEEDS THE PERMITTED 1,363 SQ. FT.
 PERMITTED. USING LOW FREESTANDING SIGNS LIKE IN THE
 CONCEPT SKETCH COULD ALLEVIATE THIS SQUARE FOOTAGE
 EXCESS.
  
 33) ADDITIONAL INFORMATION REQUIRED: THERE ARE
 FREESTANDING SIGNS SHOWN ON THE PLAN WITH NO DETAILS
 ASSOCIATED WITH THEM IN FRONT OF THE NEW BUILDINGS.
  
 LIGHTING
  
 34) REVISED PHOTOMETRIC PLANS NOT SUBMITTED: THE
 SOUTHWEST CORNER OF THE SUBMITTED PHOTOMETRIC BASE PLAN
 DIFFERS FROM THE SITE PLAN AT THE NUMBER OF PARKING
 SPACES. ALL PLANS SHALL SHOW THE SAME BASE CONDITIONS.
  
 35) REVISED PHOTOMETRIC PLANS NOT SUBMITTED:
 ILLUMINATION WITHIN A COMMERCIAL PLANNED DEVELOPMENT
 MAY NOT EXCEED ONE FOOTCANDLE AT OR BEYOND THE
 BOUNDARIES OF THE DEVELOPMENT. THE SOUTH, EAST AND
 NORTH PROPERTY LINES ALL HAVE VALUES EXCEEDING ONE
 FOOTCANDLE AT THE PROPERTY LINE. THE PHOTOMETRIC
 NUMBERS SHALL BE EXTENDED PAST THE PROPERTY LINE AND
 VERIFY THAT THE ONE FOOTCANDLE STANDARD IS NOT
 EXCEEDED.
  
 36) REVISED PHOTOMETRIC PLANS NOT SUBMITTED: THERE ARE
 INCONSISTENCIES WITH THE LIGHT POLE LOCATIONS INDICATED
 AS REMAINING ON THE CIVIL PLANS AND THE LIGHT POLE
 LOCATIONS SHOWN ON THE LIGHTING PLAN. THIS
 INCONSISTENCY IS ON THE SITE PLAN AS WELL.
  

Review Stop Z ZONING
Rev No 1 Status F Date 03-10-2015 Cont ID  
Sent By eschneid Date 03-10-2015 Time 21:57 Rev Time 10.00
Received By eschneid Date 03-10-2015 Time 21:56 Sent To  
Notes
2015-03-10 22:04:49PB 1222M
 BRAMAN MOTORCARS CPD
 2901 OKEECHOBEE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 MARCH 20, 2015, TO BE SCHEDULED FOR THE APRIL 21, 2015
 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 MAY 11, 2015), THE CASE SHALL BE CONSIDERED WITHDRAWN.
 ANY FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 GENERAL
  
 1) WHAT INNOVATIVE FEATURES OF THE PROJECT WHICH MAKE
 THIS PROJECT MORE DESIRABLE AND ATTRACTIVE THAN AN AUTO
 DEALERSHIP THAT MEETS ALL CODE REQUIREMENTS? AT A
 MINIMUM THE PROPOSED DEVELOPMENT REQUIRES WAIVERS TO
 THE SIGNAGE, INTERNAL SETBACKS AND LANDSCAPE, AND
 NUMBER OF ACCESS POINTS.
  
 2) PROVIDE FULL PLANS FOR THE ENTIRE AREA COVERED BY
 THE PROPOSED BRAMAN CPD. THIS INCLUDES SITE, LANDSCAPE,
 ELEVATIONS AND LIGHTING.
  
 3) THE JUSTIFICATION STATEMENT INDICATES THAT THE
 OWNERS DO NOT WANT TO PLAT OR UNIFY ANY OF THE NEW
 PARCELS EITHER AMONG THEMSELVES OR WITH THE EXISTING
 BRAMAN DSI PARCELS. AT A MINIMUM, THE EASTERN PARCELS
 WILL NEED TO BE JOINED SINCE THE PROPOSED DEVELOPMENT
 PLAN HAS THE NEW BUILDING STRADDLING MULTIPLE PARCEL
 LINES UNDER THE CURRENT PARCEL CONFIGURATION.
  
 4) THE PROPOSED DEVELOPMENT PLAN DOES NOT COMPLY WITH
 THE SETBACK AND LANDSCAPE REQUIREMENTS FOR THE INTERIOR
 LOT LINES WITH THE EXISTING BRAMAN MOTORCARS DSI. ANY
 NON-COMPLAINANT AREAS WOULD NEED TO BE SPECIFICALLY
 APPROVED AS WAIVERS WITHIN THE CPD.
  
 5) ALL OVERHEAD UTILITY LINES IN THE AREAS WHERE ANY
 DEMOLITION OR CONSTRUCTION IS BEING DONE SHALL BE
 BURIED.
  
 6) PLEASE PROVIDE VERIFICATION OF THE UTILITY EASEMENTS
 BEING ABANDONED. STAFF CANNOT APPROVED A BUILDING
 CONSTRUCTED ON TOP OF A UTILITY EASEMENT.
  
 7) PARKING AND LANDSCAPE COMPLIANCE SHALL BE SHOWN AND
 INSTALLED TO COMPLY WITH THE ZLDR FOR EACH PHASE OF THE
 DEVELOPMENT.
  
 8) THE SITE HAS AN EXPIRED IRRIGATION PERMIT AND
 MISCELLANEOUS PERMIT THAT NEED TO BE RECTIFIED -
 09010281 AND 10080754.
  
 TRAFFIC
  
 9) PROVIDE THE PALM BEACH COUNTY TRAFFIC CONCURRENCY
 APPROVAL LETTER.
  
 10) THE JUSTIFICATION STATEMENT LISTS SEVEN CURB CUTS
 BEING USED WHILE THE LATEST STREET VIEW SHOWS ONLY SIX
 BEING USED. PLEASE BE AWARE THE SITE EXCEEDS THE NUMBER
 OF PERMITTED ACCESS POINTS TO THE STREET NETWORK.
 OPENINGS ALONG BOTH OKEECHOBEE BOULEVARD AND EXCHANGE
 COURT NEED TO BE REDUCED.
  
 11) PROVIDE A DRIVEWAY PREDETERMINATION LETTER OF
 APPROVAL FROM FDOT FOR THE WORK WITHIN THE OKEECHOBEE
 BOULEVARD RIGHT-OF-WAY.
  
 12) A RIGHT-OF-WAY PERMIT WILL BE REQUIRED FOR ANY WORK
 WITHIN THE FDOT OR THE CITY RIGHT-OF-WAY.
  
 13) ALL CURB CUTS THAT ARE NOT BEING USED SHALL BE
 REMOVED AND THE SIDEWALK MADE FLUSH WITH THE ADJACENT
 SIDEWALK.
  
 14) THE PROPOSAL TO PLANT IN THE EXCHANGE COURT
 RIGHT-OF-WAY REQUIRES THE APPROVAL OF THE ENGINEERING
 SERVICES DIVISION. IRRIGATION SHALL BE SUPPLIED TO
 THESE TREES. A RECORDED AGREEMENT TO MAINTAIN AND
 REPLACE THE TREES AND IRRIGATION IS REQUIRED FROM
 BRAMAN.
  
 SITE
  
 15) PROVIDE THE SITE PLAN AT A LARGER SCALE.
  
 16) PROVIDE THE SETBACK DIMENSIONS FOR THE NEW MINI
 SERVICE DROP OFF BUILDING.
  
 17) ALL MECHANICAL EQUIPMENT, WHETHER GROUND OR ROOF
 MOUNTED, UTILITY EQUIPMENT, GENERATORS, TRANSFORMERS,
 ETC. SHALL BE SCREENED FROM VIEW OF THE PUBLIC.
  
 18) PROVIDE PLANS (ROOF, SITE, ETC.) SHOWING WHERE THE
 A/C AND OTHER MECHANICAL EQUIPMENT (TO INCLUDE
 GENERATORS) WILL BE LOCATED.
  
 19) THE EAST SIDE SETBACK IS REQUIRED TO BE 27 FEET,
 NOT 13 FEET, SINCE THE BUILDING THAT IS BEING
 CONSTRUCTED IS 75 FEET 8 INCHES TALL.
  
 20) HOW TALL ARE THE GATES?
  
 21) PROVIDE A CONTINUOUS CONNECTION FOR THE FRONT
 PARKING LOT BETWEEN THE BMW AND THE FUTURE BENTLEY
 DEALERSHIPS.
  
 22) WHY IS THE DRIVEWAY LEADING TO THE PORSCHE SERVICE
 DROP-OFF 40 FEET WIDE WHEN THERE ARE ONLY TWO 10 FOOT
 WIDE DOORWAYS INTO THE SERVICE BAY? THE PAVEMENT SHALL
 BE REDUCED AT THIS LOCATION AND A WIDER LANDSCAPE
 BUFFER INSTALLED.
  
 23) WHY IS THE DRIVEWAY LEADING OUT OF THE PORSCHE
 SERVICE DROP-OFF 35 TO 39 FEET WIDE, WHEN ONLY TWO CARS
 CAN EXIT AT THE SAME TIME? THE PAVEMENT SHALL BE
 REDUCED AT THIS LOCATION AND A WIDER LANDSCAPE BUFFER
 INSTALLED.
  
 24) THE SITE AND CIVIL PLANS DO NOT MATCH IN THE DEPTH
 OF THE PARKING SPACES AND THE DRIVE AISLES IN FRONT OF
 THE NEW BUILDINGS. EX. 18.5 FEET VS 18 FEET AND 24 FEET
 VS 24.5 FEET.
  
 25) THE SITE PLAN NEEDS TO SHOW THE AREA BEHIND THE
 TWO-STORY SALES AND SERVICE BUILDING IN ACCORDANCE WITH
 APPROVED PERMIT NO. 13060158, TO INCLUDE THE REQUIRED
 DIMENSIONS OF THE DRIVE AISLES AND PARKING SPACES.
 THESE SHALL BE INSTALLED AND REMAIN PER PLAN.
  
 PARKING
  
 26) STAFF IS UNABLE TO VERIFY THE PARKING REQUIRED FOR
 THE SITE DUE THE DIFFERING PLANS SHOWING SQUARE FOOTAGE
 THAT IN SOME INSTANCES DOUBLE COUNTS AREAS (EX. LISTS
 SQ. FT. OF ENTIRE SERVICE AREA TO INCLUDE THE SERVICE
 BAYS) OR DOES NOT LIST ALL THE INTERIOR AREA (EX.
 HALLWAYS ON THE ARCHITECTURAL FLOOR PLANS). PROVIDE A
 COLOR CODED FLOOR PLAN THAT DEMARCATES THE INTERIOR
 SQUARE FOOTAGE, THE SERVICE BAY AREAS AND INTERNAL
 VEHICLE CIRCULATION AREAS. THE SQUARE FOOTAGES OF EACH
 AREA SHALL BE PROVIDED SO THAT STAFF CAN CALCULATE THE
 PARKING REQUIREMENTS.
  
 27) THE BICYCLE RACK SHOWN SOUTH OF THE BMW SERVICE
 ENTRANCE ON THE BRAMAN DSI PLAN DOES NOT APPEAR TO HAVE
 BEEN INSTALLED. THIS LOCATION DOES NOT ADHERE TO THE
 CITY'S BICYCLE PARKING LOCATIONAL REQUIREMENTS. THE PAD
 SHALL BE SHOWN IN COMPLIANCE WITH THE CITY'S
 REGULATIONS.
  
 28) STAFF IS UNABLE TO LOCATE THE SIX SPACES NOT CITED
 IN THE PREVIOUS COMMENT.
  
 29) NO BICYCLE PAD OR RACK DETAILS, WITH DIMENSIONS,
 WERE PROVIDED ON THE PLANS.
  
 30) THE AREA BEHIND THE FUTURE MINI DEALERSHIP (UNDER
 THE CANOPY) IS SHOWN AS HAVING A DOUBLE ROW OF PARKING.
 THIS AREA IS CURRENTLY A NINE SPACE PARKING AREA (TEN
 SPACES DO NOT FIT WITH THE WALKWAY ON THE SOUTH SIDE)
 WITH A DETAIL AREA ON THE NORTH SIDE. THE DIMENSION IS
 NOT WIDE ENOUGH FOR A DOUBLE ROW OF PARKING AS THE
 AISLE IS SHOWN ON THE PROPOSED PLAN AT 22.6 FEET IN
 WIDTH. PLEASE NOTE IF PARKING ALONG THE NORTH SIDE OF
 THIS AREA CAN BE ACHIEVED, THEN A TERMINAL ISLAND TREE
 IS REQUIRED ON THE EAST SIDE.
  
 31) PROVIDE DIMENSION TAGS FOR EACH NEW PARKING BAY -
 CURB FACE TO CURB FACE.
  
 32) PROVIDE FLOOR PLANS FOR ALL LEVELS OF THE PARKING
 STRUCTURE, TO INCLUDE THE ROOF DECK. THE FLOOR PLANS
 SHALL INDICATE THE AREAS OF VEHICLE STORAGE, GARAGE
 EMPLOYEE PARKING AND SERVICE PARKING. IF THERE WILL BE
 INVENTORY STORAGE ON THE ROOF, THEN THIS SHALL BE
 COUNTED IN THE OUTDOOR DISPLAY AREA REQUIREMENTS.
  
 33) VERIFY WITH THE CONSTRUCTION SERVICES DIVISION IF
 ADA OR VAN ACCESSIBLE SPACES ARE REQUIRED IN THE
 PARKING STRUCTURE FOR THE 20 GARAGE EMPLOYEE AND
 SERVICE PARKING.
  
 34) ONLY TWO FUNCTIONAL, NOT THREE LOADING ZONES ARE
 SHOWN ON THE PLAN. THE ONE BY THE BENTLEY PARTS CANNOT
 BE ACCESSED BY THE TRUCK ITS DESIGNED FOR.
  
 SIGNAGE
  
 35) THE ZONING AND LAND DEVELOPMENT REGULATIONS
 PROHIBIT THE USE OF THREE DIMENSIONAL SCULPTURAL
 FIGURES THAT REPRESENT PRODUCTS SOLD BY A BUSINESS. THE
 MINI MOUNTED TO THE WALL IS NOT PERMITTED.
  
 36) PLEASE NOTE THAT MINI IS ONLY PERMITTED THREE
 FACADE SIGNS BASED ON THE CURRENT LAYOUT OF BUILDING A.
 CHANGES TO CONNECT THIS BUILDING TO BUILDING B WOULD
 REDUCE THE NUMBER OF PERMITTED FACADE SIGNS. WITHOUT
 FURTHER INFORMATION, STAFF IS UNABLE TO VERIFY
 COMPLIANCE, BUT IT APPEARS THAT THE AT LEAST THE SOUTH
 ELEVATION SIGN IS TWICE AS LARGE AS PERMITTED.
  
 37) THE NEW BUILDING HAS 12 FACADE SIGNS. ONLY SIX
 FACADE SIGNS ARE PERMITTED.
  
 38) DIMENSIONS WERE NOT PROVIDED FOR STAFF TO DETERMINE
 HOW MUCH FACADE SIGN SQUARE FOOTAGE IS PERMITTED, NOR
 WAS INFORMATION PROVIDED ON HOW MUCH FACADE SIGN SQUARE
 FOOTAGE IS PROPOSED.
  
 39) PROVIDE THE SIGN SETBACKS ON THE SITE AND LANDSCAPE
 PLANS. THE SIGNS SHALL NOT INTERFERE WITH THE LONG TERM
 GROWTH OF THE ADJACENT TREES.
  
 40) PLEASE CONFIRM THAT THE PLANS SHOW THE
 REORIENTATION OF HF SIGN A.
  
 41) THE LOCATION FOR HF SIGN E WILL NOT BE SUPPORTED BY
 STAFF AS IT CREATES AN UNSAFE VISIBILITY SITUATION FOR
 CARS EXITING THE SITE ONTO OKEECHOBEE BOULEVARD.
  
 42) STAFF CALCULATES 1,640 SQ. FT. OF HIGH FREESTANDING
 SIGNAGE PROPOSED ALONG OKEECHOBEE BOULEVARD (HF SIGNS
 B, C, D1, D2 AND E). WHICH EXCEEDS THE PERMITTED 1,363
 SQ. FT. PERMITTED. USING LOW FREESTANDING SIGNS LIKE IN
 THE CONCEPT SKETCH COULD ALLEVIATE THIS SQUARE FOOTAGE
 EXCESS.
  
 43) PLEASE NOTE THAT HF SIGN A AND C HAVE EXPIRED
 PERMITS THAT NEED TO BE RECTIFIED FOR THOSE TWO SIGNS.
 PERMITS 08120414 AND 08120415.
  
 44) THERE ARE FREESTANDING SIGNS SHOWN ON THE PLAN THAT
 DETAILS ASSOCIATED WITH THEM IN FRONT OF THE NEW
 BUILDINGS.
  
 LIGHTING
  
 45) THE SOUTHWEST CORNER OF THE SUBMITTED PHOTOMETRIC
 BASE PLAN DIFFERS FROM THE SITE PLAN AT THE NUMBER OF
 PARKING SPACES. ALL PLANS SHALL SHOW THE SAME BASE
 CONDITIONS.
  
 46) PLEASE EXPLAIN THE DIFFERENCE BETWEEN THE SMALL
 NUMBERS AND THE LARGE NUMBERS ON THE PHOTOMETRIC PLAN.
  
 47) ILLUMINATION WITHIN A COMMERCIAL PLANNED
 DEVELOPMENT MAY NOT EXCEED ONE FOOTCANDLE AT OR BEYOND
 THE BOUNDARIES OF THE DEVELOPMENT. THE SOUTH, EAST AND
 NORTH PROPERTY LINES ALL HAVE VALUES EXCEEDING ONE
 FOOTCANDLE AT THE PROPERTY LINE. THE PHOTOMETRIC
 NUMBERS SHALL BE EXTENDED PAST THE PROPERTY LINE AND
 VERIFY THAT THE ONE FOOTCANDLE STANDARD IS NOT
 EXCEEDED.
  
 48) PLEASE PROVIDE HOW THE LIGHTING WILL BE SHIELDED TO
 REFLECT LIGHT OR GLARE AWAY FROM THE ADJACENT PUBLIC
 THOROUGHFARES?
  
 49) THE LIGHT POSTS SHALL MEET THE REQUIRED FIVE (5)
 FOOT SETBACK REQUIREMENT. PLEASE PROVIDE SETBACK
 DIMENSIONS FOR THE LIGHT POSTS ON THE PLANS.
  
 50) THERE ARE INCONSISTENCIES WITH THE LIGHT POLE
 LOCATIONS INDICATED AS REMAINING ON THE CIVIL PLANS AND
 THE LIGHT POLE LOCATIONS SHOWN ON THE LIGHTING PLAN.
 THIS INCONSISTENCY IS ON THE SITE PLAN AS WELL.
  