Plan Review Details - Project Z14120032
Plan Review Stops For Project Z14120032
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By rbrown Date 01-13-2015 Time 21:24 Rev Time 0.00
Received By mgonzale Date 01-13-2015 Time 21:24 Sent To  
Notes
2015-01-13 21:43:37DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. NUMBER OF ACCESSIBLE PARKING SPACES. PLAN SHEETS
 A210 AND A211 SHOWS THAT 6 ACCESSIBLE PARKING SPACES
 ARE PROPOSED OUT OF A TOTAL 357 PARKING SPACES. PER
 TABLE 208.2 OF FLORIDA ACCESSIBILITY CODE, FOR PARKING
 FACILITIES WITH BETWEEN 301 AND 400 PARKING SPACES, 8
 ACCESSIBLE PARKING SPACES ARE TO BE PROVIDED.
  
 3. ACCESSIBLE ROUTE FROM ACCESSIBLE PARKING SPACE. PLAN
 SHEETS A210 SHOWS THE NORTH ACCESSIBLE PARKING SPACE ON
 THE GROUND LEVEL WITH AN ACCESSIBLE ROUTE THAT FORCES
 THE USER TO ENTER THE VEHICLE TRAVEL LANE AND PASS
 BEHIND ANOTHER PARKED VEHICLE. PER SECTION 208.3 OF
 FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE
 FOR EACH BUILDING AND SERVED BY AN ACCESSIBLE ROUTE
 THAT DOES NOT COMPEL THE USER TO PASS BEHIND ANOTHER
 PARKED VEHICLE.
  
 4. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4
 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX
 ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE). AS 8 ACCESSIBLE
 PARKING SPACES ARE REQUIRED, 2 VAN ACCESSIBLE SPACES
 ARE TO BE PROVIDED.
  
 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 6. FOR STREET ADDRESSING CONTACT MICHAEL ORIO, GIS
 SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - APP2 ENGINEERING APP. REVIEW TELCOM
Rev No 1 Status P Date 05-23-2016 Cont ID  
Sent By   Date 05-23-2016 Time   Rev Time 0.00
Received By cranford Date 03-17-2015 Time 12:39 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 03-17-2015 Cont ID  
Sent By cranford Date 03-17-2015 Time 12:40 Rev Time 0.00
Received By mgonzale Date 03-17-2015 Time 12:40 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 01-14-2015 Cont ID  
Sent By cranford Date 01-14-2015 Time 08:02 Rev Time 0.00
Received By cranford Date 01-14-2015 Time 07:58 Sent To  
Notes
2015-01-14 08:02:32PUBLIC WORKS DEPT.
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 PLEASE REVISE THE PLANS TO REFERENCE VERTICAL DATUM
 NGVD 29. SECTION 78-9 OF THE CITY?S CODE OF ORDINANCES
 SPECIFIES NGVD 1929 AS THE OFFICIAL CITY VERTICAL
 DATUM.
  
 PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY'S
 ENGINEERING DESIGN STANDARDS. PLEASE ALSO INCLUDE THE
 DETAILS FOR THE DETECTABLE WARNING STRIPS FOR THE
 SIDEWALK RAMPS, HTTP://WPB.ORG/ENGINEERING/ENGINEERING-
 SERVICES/ENGINEERING-STANDARDS/
  
 PLEASE PROVIDE ESTIMATES FOR THE POTABLE WATER DEMAND
 AND SANITARY FLOWS. ONCE THE INSPECTION OF THE EXISTING
 UTILTIIES HAS BEEN COMPLETED, THIS INFORMATION WILL BE
 UTILIZED TO DETERMINE THE CONNECTION REQUIREMENTS FOR
 THE PROPOSED COURT HOUSE.
  
 PLEASE PROVIDE AN ESTIMATE OF THE SOLID WASTE YARDAGE
 TO BE GENERATED BY THE PROPOSED FACILITY.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 03-16-2015 Cont ID  
Sent By pleduc Date 03-16-2015 Time 14:20 Rev Time 0.00
Received By pleduc Date 03-16-2015 Time 14:16 Sent To  
Notes
2015-03-16 14:20:17AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 FEBRUARY 3, 2015, FROM KBJ ARCHITECTS, INC., TO ROBERT
 BROWN, BUILDING OFFICIAL, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
 PETER LEDUC
  
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 01-08-2015 Cont ID  
Sent By pleduc Date 01-08-2015 Time   Rev Time 0.00
Received By pleduc Date 01-08-2015 Time 13:40 Sent To  
Notes
2015-01-08 14:12:00THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 8. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 9. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGECNY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. PROVIDE ILLUSTRATED JUSTIFICATION THAT THE
 STAIRWELL EXITS MEET THE MINIMUM EXIT SEPARATION
 DISTANCE REQUIRMENT.
  
 12. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 13. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 14. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN. PROVIDE A FIRE LOAD CALCULATIONS.
  
 15. UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITIONS OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 16. STAIRWAY IDENTIFICATION: NEW ENCLOSED STAIRS
 SERVING THREE OR MORE STORIES SHALL COMPLY WITH (A)
 THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 17. EACH ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS
 TO AT LEAST ONE EXIT. EXIT ACCESS SHALL NOT REQUIRE THE
 USE OF A KEY, TOOL, SPECIAL KNOWLEDGE, OR SPECIAL
 EFFORT.
  
 18. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME,
 SAFETY CODE FOR ELEVATORS.
  
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status F Date 01-15-2015 Cont ID  
Sent By ssamuels Date 01-15-2015 Time 14:14 Rev Time 0.00
Received By ssamuels Date 01-15-2015 Time 14:14 Sent To  
Notes
2015-01-15 14:30:34PARKING DEPARTMENT
 SEAN SAMUELS CPP
 PARKING FASCILITY SUPERVISOR
 561-822-1507
  
 SPACES DON'T MATCH NUMBER
 BICYCLE RACK NEED TO BE PROVIDED ACCORDINGLY WITH THE
 CITY SPECIFICATION.
  
 BASED ON OBSERVATION OF THE PLAN. PARKING MIGHT BE
 LOSING ON - STREET SPACE/S.
  
 PERMANENT REMOVAL OF A METER PARKING SPACE IS SIXTEEN
 THOUSAND EIGHT HUNDRED DOLLARS ( $16,800.00 )
  
  
  
  
  
  
  

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 04-07-2015 Cont ID  
Sent By cranford Date 04-07-2015 Time 09:36 Rev Time 0.00
Received By cranford Date 04-07-2015 Time 09:36 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 03-17-2015 Cont ID  
Sent By cranford Date 03-17-2015 Time 12:41 Rev Time 0.00
Received By cranford Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By tward Date 01-13-2015 Time 13:27 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2015-01-13 13:26:461. PLANS REFERENCE VERTICAL DATUM AS NGVD 1929 AND NAVD
 1988 ON DIFFERENT SHEETS. ALL SHEETS SHOULD REFERENCE
 NGVD 1929.
  
 2. REVISE GRADING OF STREET IN FRONT OF SOUTH DRIVEWAY
 TO ELIMINATE THE APPARENT SAG CONDITION NEXT TO THE
 CURB.
  
 3. UPDATED FEMA FLOOD INSURANCE RATE MAPS (DRAFT
 VERSION) ARE AVAILABLE.
  
 4. SWPPP EROSION AND SEDIMENT CONTROL PLAN WILL BE
 REQUIRED WITH THE ENGINEERING PERMIT SUBMITTAL.
  
 5. NPDES CONSTRUCTION PERMIT REQUIRED BEFORE START OF
 CONSTRUCTION.
  
 6. SFWMD ERP REQUIRED BEFORE START OF CONSTRUCTION.
  
 7. STORMWATER QUALITY TREATMENT TO BE PROVIDED THAT
 MEETS SFWMD CRITERIA.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 [email protected]
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 01-08-2015 Cont ID  
Sent By vnoel Date 01-08-2015 Time 13:17 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2015-01-08 13:33:381. SEPARATE SUBMITTAL WILL BE REQUIRED FOR SITE/CIVIL
 REVIEW.
 2. TERMINATION OF 14 FOOT UE WILL NEED TO BE PROCESSED.
 APPLICATION IS MADE THROUGH ENGINEERING SERVICES.
 3. HOW WILL SANITATION ACCESS DUMPSTER OFF OF DATURA?
 APPEARS TO BE GATED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 04-07-2015 Cont ID  
Sent By cranford Date 04-07-2015 Time 09:35 Rev Time 0.00
Received By cranford Date 04-07-2015 Time 09:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 05-24-2016 Cont ID  
Sent By aaponte Date 05-24-2016 Time 11:53 Rev Time 0.00
Received By aaponte Date 05-24-2016 Time 11:53 Sent To  
Notes
2016-05-24 11:54:091. PLEASE INCLUDE THE SURROUNDING SIDEWALK AND STREET
 IN THE SITE PLAN DRAWINGS.
 2.PLEASE INCLUDE A TABLE WITH THE REQUIRED PARKING
 SPACES FOR THE COURTHOUSE TO DEMONSTRATE COMPLIANCE
 WITH THE PARKING FOR THE ENTIRE SITE (DOH, DMS PLUS
 COURTHOUSE). PLEASE INCLUDE THE TOTAL COUNT OF COMPACT
 SPACES (SEC 94-486(N)(1)).
 3. PLEASE INLCUDE A TABLE IN THE SITE PLAN SHEET
 INDICATING THE FAR CALCULATIONS FOR THE ENTIRE SITE.
 4.THE MASONRY VENEER SHALL BE MAINTAINED AS PRESENTED
 AND APPROVED BY THE BOARD (NO STUCCO).
 5. PLEASE USE THE STANDARD TREE GRATE (US FOUNDRY 9590
 OR APPROVED EQUAL).
 6.PLEASE RELOCATE BIKE RACKS TO ONE OF THE PUBLIC OPEN
 SPACES AT THE CORNERS. PLEASE INCLUDE THE CALCULATION
 FOR THE BIKE RACK IN THE PARKING TABLE.
 7. PLEASE SUBMIT A HARDSCAPE DRAWINGS INDICATING ALL
 THE TREATMENTS ON THE EXTERIOR, AND THE STREET
 LIGHTING.
 8. PLEASE PROVIDE SPECS FOR THE MASONRY VENEER,
 INDICATING THE COLOR. ACCORDING TO THE DAC APPROVAL, "A
 DARKER COLOR LIMESTONE SHALL BE USED WITHIN THE
 VERTICAL ELEMENTS OF THE WINDOW, SIMILAR IN COLOR TO
 THE GLAZING. THE PILASTERS SHALL BE KEPT CONSISTENT AND
 LIGHTER IN COLOR".
 9. PLEASE PROVIDE DETAILS ON THE DUMPSTER ENCLOSURE AND
 ANY MECHANICAL ENCLOSURED. IN ADDITION TO A WALL OR
 OPAQUE FENCE A HEDGE IS REQUIRED.
 10.PLEASE LABEL ALL ELEVATIONS.
 11.PLEASE INDICATE THE ADDITIONAL ALLUMINUM FRAME
 ORIGINALLY PROPOSED FOR NORTH AND SOUTH GARAGE
 ELEVATIONS.
 12. PLEASE PROVIDE DETAILS FOR THE DESIGN OF THE
 REQUIRED GARDEN PLAZA BASED ON THE PUBLIC OPEN SPACE
 REGULATION.
 13. PLEASE PROVIDE DETAIL FOR THE STRUCTURAL SOIL
 REQUIRED AROUND THE TREE GRATES (5 FOOT AROUND THE
 GRATE ON EACH DIRECTION EXCEPT THE CURB LINE).
 14. PLEASE PROVIDE SCREENING HEDGE FOR GROUND MOUNTED
 UTILITY VALVES NEAR GARAGE ENTRANCE ON DATURA STREET.
 15. PLEASE LABEL THE TWO TREES ALONG THE GARAGE DATURA
 ELEVATION LOCATED BETWEEN PINK HIBISCUS AND THE PIGEUM
 PLUM.
 16. THE PROPOSED 6' HIGH PINK HIBISCUS DOES NOT COMPLY
 WITH THE DEFINITION OF A TREE. A TREE MUST BE ABLE TO
 GROW UP TO A MINIMUM OF 15 FEET.
 17. STREET TREES ALONG DATURA ST SHALL BE A MINIMUM OF
 14' OVERALL HEIGHT.
 18. PLEASE PROVIDE INFORMATION TO INDICATE HOW THE
 PROJECT INTENDS TO COMPLY WITH THE REGULATION REGARDING
 EXPOSED PARKING ON ROOF TOP GARAGE STRUCTURES.
 19. PLEASE REVIEW ALL THE COMMENTS PROVIDED BY THE
 DIFFERENT DISCIPLINES THROUGH THE SITE PLAN APPROVAL
 AND CONFIRM COMPLIANCE.

Review Stop Z ZONING
Rev No 2 Status F Date 03-25-2015 Cont ID  
Sent By aaponte Date 03-25-2015 Time 09:10 Rev Time 0.00
Received By aaponte Date 03-09-2015 Time 09:09 Sent To  
Notes
2015-03-25 09:57:371. A VARIANCE FROM DAC WILL BE REQUIRED REGARDING
 COMPLIANCE WITH MINIMUM PERCENTAGE OF ACTIVE USES
 REQUIRED ALONG A PRIMARY STREET (CLEMATIS AND DATURA).
 2. FACADES WITH NON-ACTIVE USES SHALL BE
 ARCHITECTURALLY TREATED. SUBMITTED GARAGE ELEVATIONS DO
 NOT MEET EXPECTATIONS FOR ARCHITECTURALLY TREATED
 NON-ACTIVE USES. PLEASE ENHANCE ELEVATIONS WITH
 ARCHTIECTURAL ELEMENTS AND LANDSCAPE.
 3. PLEASE RE-CONSIDER THE TREATMENT OF THE GREEN SPACES
 ON EITHER SIDE OF THE COURTHOUSE BUILDING. STAFF
 SUGGEST ITS TREATMENT AS A SPACE USABLE BY PEDESTRIANS.
 AN EXAMPLE OF A PUBLIC SPACE MEETING THE SAFETY
 REQUIREMENTS OF A COURTHOUSE COULD BE FOUND IN THE
 RECENTLY FINISHED FORT PIERCE US COURTHOUSE.
 4. PARKING IS PROHIBITED ON ANY EXPOSED ROOF SURFACE
 (SEC 94-111(Q)(4)). A VARIANCE IS NOT POSSIBLE FOR THIS
 REGULATION. PLEASE PROVIDE SOME TYPE OF
 COVERAGE/SCREENING. THE USE OF TRELLIS, SHADE SAILS OR
 PERGOLAS IS ALLOWED.
 5.IF THE EAST ELEVATION OF THE GARAGE SHALL REMAINED
 TOTALLY ABSENT OF OPENNINGS, STAFF SUGGESTS THE
 INTERNAL GARAGE RAMP TO BE LOCATED ON THE WEST BAY
 ALLOWING THE DESIGN ON THE EAST ELEVATIONS WITHOUT THE
 RAMP OBSTRUCTION/VISIBILITY.
 6. REVISED GATE LOCATION IS ADEQUATE.
 7. STRIPING DETAIL SHALL BE INCLUDED IN THE SITE PLAN
 DRAWINGS. PLEASE ENSURE CITY STANDARD IS INCLUDED.
 8. PLEASE INDICATE LOCATION OF PROPOSED BIKE RACKS AND
 INCLUDE DETAIL OF SELECTED RACK. "WAVE" RACK IS NOT
 ALLOWED.
 9. PLEASE PROVIDE REVISED LANDSCAPE DRAWINGS TO CONFIRM
 COMPLIANCE WITH SURFACE PARKING LOT LANDSCAPE
 REQUIREMENTS.
 10. ARCHTIECTURAL DESIGN TO BE FURTHER DISCUSSED .
 11. PLEASE INDICATE THE EXACT BOUNDARIES OF THE AREA
 COUNTED FOR THE PUBLIC OPEN SPACE REQUIREMENT. AREA
 WITHIN THE REQUIRED SETBACK CANNOT BE COUNTED AS PART
 OF THE PUBLIC OPEN SPACE. PLEASE CONFIRM COMPLIANCE
 WITH ALL THE REQUIREMENTS OF THE PUBLIC OPEN SPACE.
 12. PLEASE REVISE NUMBERS FOR TRANSPARENCY ACCORDING TO
 DEFINITION ON SECTION 94-109.
 13. PLEASE PROVIDE TECHNICAL INFORMATION INDICATING THE
 EXACT LOCATION OF FIBER OPTIC LINE ON DATURA STREET TO
 DETERMINE THE FEASIBILITY OF THE STREET TREES.
 14. PLEASE INDICATE LOCATION OF STREET LIGHTING TO
 COMPLY WITH MINIMUM 0.6 FOOTCANDLE REQUIREMENTS AT THE
 CURB LINE ONE FOOT ABOVE GRADE.
 15. COMPLIED.
 16. PLEASE RESUBMIT COLOR ELEVATION WITH REVISIONS.
 17. COMPLIED.
 18. PLEASE SUBMIT TREE SURVEY INDICATING THE EXACT
 NUMBER OF TREES REMOVED OR PROPOSED FOR RELOCATION, AND
 THE REVISED LANDSCAPE DRAWINGS.
 19. DAC APPLICATION REQUIRED.
 20. ART IN PUBLIC PLACES ORDINANCE IS APPLICABLE.
 PLEASE INDICATE SOME INITIAL IDEAS FOR COMPLIANCE WITH
 REQUIREMENT.
 21. PEDESTRIAN EXIT FROM GARAGE SHALL CONNECT TO THE
 SIDEWALK. PLEASE INDICATE PATH OF TRAVEL.
 22. PLEASE INDICATE PATH OF TRAVEL FROM HANDICAP SPACES
 TO EXIT/SIDEWALK.
 23. INTERIOR COURTYARD SHALL INCLUDE LANDSCAPE TO
 COMPLY WITH THE PRIVATE OPEN SPACE REQUIREMENTS.
 24. A NEW LOCATION FOR A BIKE SHARING STATION IS
 PROPOSED AT THE CORNER OF CLEMATIS STREET AND TAMARIND
 AVENUE WITHIN THE PUBLIC RIGHT-OF-WAY. CITY WILL
 PROVIDE EXACT LOCATION AS SOON AS AVAILABLE.
  
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 01-12-2015 Cont ID  
Sent By aaponte Date 01-12-2015 Time 11:28 Rev Time 0.00
Received By aaponte Date 12-16-2014 Time 11:28 Sent To  
Notes
2015-01-12 14:16:26THE PROJECT REVIEW IS BASED ON THE CONCEPT OF THE STATE
 BLOCK AS ONE SIGLE PROJECT UNDER ONE SINGLE PROPERTY.
  
 1-PLEASE PROVIDE INFORMATION TO CONFIRM ACTIVE USE
 REQUIREMENT ALONG DATURA STREET AND CLEMATIS STREET
 MEETS THE MINIMUM 80% REQUIRED FOR A PRIMARY STREET.
 2- FACADES WITH NO-ACTIVE USES SHALL BE ARCHITECTURALLY
 TREATED. PLEASE SUBMIT GARAGE ELEVATIONS TO CONFIRM
 COMPLIANCE. (SEC 94-109)
 3- PROPOSED COURTHOUSE BUILDING EXCEEDS MAXIMUM SETBACK
 ON DATURA STREET AND CLEMATIS STREET.
 4- PARKING IS PROHIBITED ON ANY EXPOSED ROOF SURFACE
 (SEC 94-111(Q)(4)).
 5- CIRCULATION RAMPS SHALL BE INTERNALIZE TO AVOID
 VISIBILITY OF THE RAMPS FROM THE STREET (SEC 94-111
 (Q)(3)) .
 6- PARKING ENTRANCE GATE SHALL BE MOVED AT LEAST 20
 FEET BACK FROM THE BACK OF THE SIDEWALK TO ALLOW FOR
 STACKING.
 7- STRIPING DETAIL SHALL FOLLOW CITY STANDARDS.
 8- BICYCLE PARKING IS REQUIRED IN A RATIO OF 1 SPACE
 FOR EVERY 15 PARKING SPACES PROVIDED. IN ADDITION, A
 SHOWER AND CHANGING FACILITY SHALL BE PROVIDED WITHIN
 THE BUILDING OR WITHIN 200 FEET OF THE BUILDING
 ENTRANCE.
 9- THE SURFACE PARKING LOT MAINTAINED ON SITE SHALL
 COMPLY WITH ALL THE SURFACE PARKING REQUIREMENTS,
 INCLUDING TERMINAL ISLANDS.
 10- THE PROPOSED CLASICAL DESIGN OF THE BUILDING ON THE
 EXTERIOR IS NOT CONSISTENT WITH THE MORE MODERN DESIGN
 PROPOSED FOR THE BUILDING ITSELF. THE PROPOSED ROOF
 MATERIAL, AND THE STOREFRONT TREATMENT PROPOSED FOR THE
 TYMPANUM ARE NOT CONSISTENT WITH THE CLASSICAL BUILDING
 DESIGN.
 11- PLEASE PROVIDE INFORMATION TO INDICATE COMPLIANCE
 WITH THE PRIVATE AND PUBLIC OPEN SPACE REQUIRED
 ACCORDING TO TABLE IV-22.
 12- PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH THE MINIMUM TRANSPARENCY REQUIRED FOR ACTIVE USES
 ON GROUND FLOOR ACCORDING TO TABLE IV-22.
 13- ALONG THE ENTIRE FRONTAGE, STREET TREES SHALL BE
 PLANTED ON TREE GRATES ADJACENT TO THE CURB EVERY 30
 FEET.
 14- STREET LIGHTING SHALL BE PROVIDED. EXTERIOR
 LIGHTING SHALL BE AT LEAST 0.6 FOOTCANDLES AS MEASURE
 AT THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK.
 15- PLEASE PROVIDE A SITE PLAN DRAWING WHICH INCLUDES
 INFORMATION REGARDING THE WIDTH OF THE PROPOSED
 SIDEWALK, BUILDING SETBACKS, ON-STREET PARKING, AND
 OTHER SITE PLAN ELEMENTS, AND INCLUDES THE ENTIRE BLCOK
 FROM TAMARIND AVENUE TO THE DOH BUILDING.
 16- PLEASE PROVIDE COLOR ELEVATIONS FOR THE PROPOSED
 BUILDING (COURTHOUSE AND GARAGE), INCLUDING THE
 ADJACENT BUILDINGS IN THE SAME BLOCK AND ACROSS THE
 STREET.
 17- PLEASE PROVIDE A GROSS BUILDING AREA TABLE (USE
 DEFINITION IN SEC 94-109), AND A PARKING TABLE TO
 INDICATE THE PARKING REQUIRED VS PROVIDED FOR THE
 COURTHOUSE, AND THE OTHER STATE BUILDINGS TO BE
 SERVICED BY THE GARAGE.
 18- PLEASE SUBMIT A TREE ALTERATION PERMIT APPLICATION.
 19. PROPOSED PROJECT IS REQUIRED TO TO GO TO THE
 DOWNTOWN ACTION COMMITTEE FOR SPECIAL REVIEW.
 20. NOTE THAT ALL NEW PRIVATE DEVELOPMENT, NEW
 CONSTRUCTION, RENOVATION OR REMODELING, WHERE TOTAL
 VERTICAL CONSTRUCTION COSTS OF ALL BUILDINGS ON A
 PROJECT SITE ARE EQUAL TO OR GREATER THAN $500,000.00,
 IS SUBJECT TO THE ART IN PUBLIC PLACES REQUIREMENTS
 OUTLINED IN CHAPTER 78, ARTICLE V OF THE CITY?S CODE OF
 ORDINANCES.