Plan Review Details - Project Z14120028
Plan Review Stops For Project Z14120028
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 01-13-2015 Cont ID  
Sent By rbrown Date 01-13-2015 Time 20:13 Rev Time 0.00
Received By rbrown Date 01-13-2015 Time 20:13 Sent To  
Notes
2015-01-13 20:17:03DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 03-13-2015 Cont ID  
Sent By cranford Date 03-13-2015 Time 13:36 Rev Time 0.00
Received By cranford Date 03-13-2015 Time 13:36 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 01-12-2015 Cont ID  
Sent By cranford Date 01-12-2015 Time 11:55 Rev Time 0.00
Received By cranford Date 01-12-2015 Time 10:03 Sent To  
Notes
2015-01-12 11:02:17PUBLIC WORKS DEPT.
 LAND DEVELOPMENT
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. TECHNICAL DETAILS OF
 THE WATER, SEWER, STORMWATER, TRAFFIC CIRCULATION,
 SOLID WASTE COLLECTION AND THE STORMWATER POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 CIVIL PLANS WERE NOT SUBMITTED FOR REVIEW.
  
 SHEET AE120 SHOWS AN ARROW POINTING TOWARD THE WEST
 CONNECTING THE MIDDLE RAMP TO THE ADJACENT RAMP TO THE
 EAST. PLEASE INDICATE THE PROPOSED GRADING FOR THIS
 AREA.
  
 INDICATE THE LOCATIONS OF THE DUMPSTERS INTENDED TO BE
 SERVICE BY THE CITY OF WEST PALM BEACH SANITATION
 DEPARTMENT. DUMPSTERS MUST BE EASILY ACCESSIBLE BY THE
 CITY EQUIPMENT AND MANPOWER. INCLUDE AN ESTIMATE OF THE
 SOLID WASTE YARDAGE ANTICIPATED TO BE GENERATED BY THE
 EXPANDED FACILITY.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 03-10-2015 Cont ID  
Sent By pleduc Date 03-10-2015 Time   Rev Time 0.00
Received By pleduc Date 03-10-2015 Time 08:46 Sent To  
Notes
2015-03-10 09:02:50 
 AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 FEBRUARY 24, 2015, FROM COTLEUR & HEARING, TO ERIC
 SCHNEIDER, PRINCIPAL PLANNER, THE PREVIOUSLY SUBMITTED
 FIRE PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 01-12-2015 Cont ID  
Sent By pleduc Date 01-12-2015 Time   Rev Time 0.00
Received By pleduc Date 01-12-2015 Time 13:15 Sent To  
Notes
2015-01-12 14:04:47THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 8. THE TWO NORTH STAIRWELLS ARE ENCLOSED AND THE TWO
 SOUTH STAIRWELLS ARE OPEN. ALL STAIRWELLS ARE REQUIRED
 TO BE ENCLOSED. PLEASE CORRECT OR PROVIDE SUPPORTING
 JUSTIFICATION.
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGECNY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. EACH ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS
 TO AT LEAST ONE EXIT. EXIT ACCESS SHALL NOT REQUIRE THE
 USE OF A KEY, TOOL, SPECIAL KNOWLEDGE, OR SPECIAL
 EFFORT.
  
 11. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44,
  
 12. ALL EXISTING ELEVATORS HAVING A TRAVEL DISTANCE OF
 25 FEET OR MORE ABOVE OR BELOW THE LEVEL THAT BEST
 SERVES THE NEEDS OF EMERGENCY PERSONNEL FOR
 FIRE-FIGHTING OR RESCUE PURPOSES SHALL CONFORM TO THE
 FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF THE
 SAFETY CODE FOR ELEVATORS.
  
 13. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 14. ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH
 OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM
 TERMINAL LANDING AND THE TOP TERMINAL LANDING EXCEEDS
 25 FEET MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76 INCHES LONG AND
 24 INCHES WIDE IN THE HORIZONTAL POSITION.
  
 15. PROVIDE FIRE LOAD CALCULATION SHOWING COMPLIANCE
 WITH WATER SUPPLY.
  
 16. THE PROPOSED FIRE TRUCK ACCESS ROAD IS NOT
 APPROVED. THE ROAD APPEARS TOO NARROW, 20' IS THE
 MINIMUM, AND THE TURNING RADIUSES TOO SHARP.
  
 17. ALL GATES SHALL BE EQUIPPED WITH A KNOX PADLOCK FOR
 24 HOUR EMERGENCY ACCESS.
  
 18. THE FINAL FDC AND FIRE HYDRANT LOCATIONS SHALL BE
 COORDINATED WITH THE FIRE PREVENTION BUREAU.
  
  
  
  
  
  
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 03-13-2015 Cont ID  
Sent By cranford Date 03-13-2015 Time 13:40 Rev Time 0.00
Received By cranford Date 03-13-2015 Time 13:40 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 01-14-2015 Cont ID  
Sent By cranford Date 01-14-2015 Time 08:21 Rev Time 0.00
Received By cranford Date 01-14-2015 Time 08:21 Sent To  
Notes
2015-01-14 08:22:06SEE ENG PPRC COMMENTS

Review Stop STORM STORMWATER
Rev No 2 Status P Date 03-13-2015 Cont ID  
Sent By cranford Date 03-13-2015 Time 13:37 Rev Time 0.00
Received By cranford Date 03-13-2015 Time 13:37 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-12-2015 Cont ID  
Sent By tward Date 01-12-2015 Time 06:59 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2015-01-12 07:07:081. NO ENGINEERING PLANS PROVIDED.
  
 2. ON SCHEMATIC DESIGN SHEET, USE HATCHING OR DISTINCT
 LINE TYPE FOR ITEMS TO BE REMOVED.
  
 3. ONLY ONE DRAINAGE STRUCURE INDICATED TO BE REMOVED
 WITHIN THE GARAGE FOOT PRINT. WHAT HAPPENS TO THE REST
 OF THE DRAINAGE SYSTEM?
  
 4. UPDATED FEMA FLOOD INSURANCE RATE MAPS (DRAFT
 VERSION) ARE AVAILABLE.
  
 5. SWPPP EROSION AND SEDIMENT CONTROL PLAN WILL BE
 REQUIRED WITH THE ENGINEERING PERMIT SUBMITTAL.
  
 6. NPDES CONSTRUCTION PERMIT REQUIRED BEFORE START OF
 CONSTRUCTION.
  
 7. SFWMD ERP MODIFICATION REQUIRED BEFORE START OF
 CONSTRUCTION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 03-13-2015 Cont ID  
Sent By cranford Date 03-13-2015 Time 13:39 Rev Time 0.00
Received By cranford Date 03-13-2015 Time 13:39 Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 01-14-2015 Cont ID  
Sent By cranford Date 01-14-2015 Time 08:24 Rev Time 0.00
Received By cranford Date 01-14-2015 Time 08:23 Sent To  
Notes
2015-01-14 08:23:52SEE ENG PPRC COMMENTS
2015-01-12 09:22:49NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date 05-27-2015 Cont ID  
Sent By eschneid Date 05-27-2015 Time 15:11 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2015-05-27 15:11:18PASSED WITH CONDITIONS

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 03-25-2015 Time   Rev Time 0.00
Received By bcollins Date 03-25-2015 Time 08:16 Sent To  
Notes
2015-03-25 08:18:32ADDITIONAL TRAFFIC COMMENTS ARE COVERED IN THE ZONING
 REVIEW

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 03-13-2015 Cont ID  
Sent By cranford Date 03-13-2015 Time 13:58 Rev Time 0.00
Received By cranford Date 03-13-2015 Time 13:58 Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 01-14-2015 Cont ID  
Sent By cranford Date 01-14-2015 Time 08:22 Rev Time 0.00
Received By cranford Date 01-14-2015 Time 08:22 Sent To  
Notes
2015-01-14 08:23:21SEE ENG PPRC COMMENTS

Review Stop Z ZONING
Rev No 4 Status P Date 05-27-2015 Cont ID  
Sent By eschneid Date 05-27-2015 Time 15:09 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2015-05-27 15:10:15PASSED WITH CONDITIONS

Review Stop Z ZONING
Rev No 3 Status F Date 03-24-2015 Cont ID  
Sent By eschneid Date 03-24-2015 Time 18:26 Rev Time 3.00
Received By eschneid Date 03-24-2015 Time 18:26 Sent To  
Notes
2015-03-24 18:32:33PB 950QQQQ - 1ST RESUBMITTAL 2/25/15 - UPDATED COMMENTS
 PALM BEACH COUNTY CONVENTION CENTER GARAGE
 650 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 MAY 25, 2015), THE CASE SHALL BE CONSIDERED WITHDRAWN.
 ANY FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 GENERAL
  
 1) CONDITION: STAFF HAS SPOKEN WITH RELATED REGARDING
 THE AREA SOUTH OF THE HOTEL LOADING ZONE THAT IS
 CURRENTLY NOT INCLUDED ON EITHER THE HOTEL SITE PLAN OR
 THIS SITE PLAN. RELATED HAS AGREED TO SUPPLY PLANS FOR
 THE MISSING PIECE ONCE THIS GARAGE APPLICATION IS
 APPROVED, SO THEY CAN INTEGRATE THEIR PLANS WITH THE
 APPROVED GARAGE DESIGN. RELATED HAS STATED THEY WILL
 CONSTRUCT THE LOADING AREA CHANGES IF THE GARAGE IS
 UNDER CONSTRUCTION BEFORE THEY HAVE COMPLETED THE HOTEL
 CONSTRUCTION. IF THE HOTEL IS COMPLETED AND THE GARAGE
 CONSTRUCTION HAS NOT BEGUN, THE LOADING ZONE
 MODIFICATION CONSTRUCTION WILL BE BORNE BY THE COUNTY
 AS PART OF THE GARAGE CONSTRUCTION. THIS CONDITION WILL
 APPLY TO BOTH APPROVALS.
  
 2) REPEAT COMMENT: PLEASE PROVIDE DETAILS ON HOW THE
 PROPOSED GARAGE COMPLIES WITH THE EXHIBIT D "ENERGY
 SAVING METHODS" OF THE CITYPLACE DRI. - THE RESPONSE
 SHALL LIST THE SPECIFIC ITEMS IN EXHIBIT D THAT WILL BE
 USED AND WHY OTHERS ARE NOT BEING IMPLEMENTED.
  
 SITE PLAN
  
 3) REVISED COMMENT: THE SITE DATA TABLE WAS UPDATED TO
 INCLUDE THE ENTIRE CONVENTION CENTER PARCEL. THE AMOUNT
 OF LANDSCAPE AREA APPROVED BY RES. NO. 44-99 WAS
 15.03%. THE PROPOSED OVERALL CONVENTION CENTER SITE
 ONLY HAS 13.6% LANDSCAPE. PROVIDE THE ADDITIONAL
 LANDSCAPE AREA.
  
 4) REVISED COMMENT: PROVIDE A PARKING MANAGEMENT PLAN
 THAT CONSOLIDATES THE APPLICANT RESPONSES INCLUDED WITH
 ITEMS 8 A THROUGH G IN ONE CENTRAL DOCUMENT THAT WILL
 BE INCLUDED WITH THE ULTIMATE APPROVAL LETTER. THE
 PARKING MANAGEMENT PLAN SHALL INCLUDE REMEDIES IN THE
 EVENT THAT THE PLAN IS NOT SUCCESSFUL IN SAFELY AND
 EFFICIENTLY CIRCULATING VEHICULAR TRAFFIC THROUGH THE
 AREA. PLEASE NOTE THAT THE CITY'S TRAFFIC ENGINEER HAS
 SAFETY CONCERNS WITH THE PROPOSED MOVEMENTS AND SIGNAGE
 OF THESE MOVEMENTS IN THE VICINITY OF THE NORTH
 ENTRANCE TO THE GARAGE.
  
 5) REPEAT COMMENT: THE APPROVED PHASE 2 PLAN SHOWS
 APPROXIMATELY 110 FEET OF THE FLORIDA AVENUE FRONTAGE
 INTERRUPTED BY VEHICULAR ACCESS POINTS. THE PROPOSED
 PLAN EXPANDS THIS TO APPROXIMATELY 140 FEET (NOT
 INCLUDING THE STABILIZED FIRE DEPARTMENT ACCESS
 ROADWAY). THERE HAS BEEN NO JUSTIFICATION PROVIDED TO
 CHANGE THE CONDITIONS OF THE CURRENT APPROVAL TO
 SUPPORT THIS ENLARGEMENT OF THE DRIVEWAYS ALONG THE
 FRONTAGE AREA. STAFF DOES NOT SUPPORT THE EXPANSION OF
 THE FRONTAGE INTERRUPTION FOR VEHICULAR ACCESS TO THE
 SITE SHOWN ON THE PROPOSED PLANS. STAFF WILL SUPPORT
 ADDITIONAL INTERRUPTION FOR VEHICULAR ACCESS ONLY UNDER
 THE FOLLOWING CONDITIONS, WHICH SHALL BE SHOWN ON THE
 PLANS:
  
 A. THERE SHALL BE ONLY TWO LANES, NOT THREE, TO ENTER
 THE SITE LEADING TO THE VALET AREA (NOTE: WITH ONLY TWO
 LANES ON FLORIDA AVENUE, NO MORE THAN TWO LANES INTO
 THE SITE ARE NEEDED, WHICH IS THE EXISTING CONDITION
 TODAY). THIS MAY EXPAND TO THREE LANES ONCE A DRIVER IS
 FURTHER ONTO THE SITE.
 B. THE CURRENT PLAN SHOWS LANE WIDTHS OF 12 FEET. THESE
 ARE EXCESSIVE AND SHALL BE NARROWED TO NO GREATER THAN
 11 FEET IN WIDTH.
  
 THE ITEMS LISTED ABOVE WILL ONLY INTERRUPT THE APPROVED
 PHASE 2 FRONTAGE OF 110 FEET BY AN ADDITIONAL 11 FEET,
 NOT 30 FEET.
  
 6) REVISED COMMENT: THE TURNING RADIUS DRAWINGS FOR
 FIRE DEPARTMENT ACCESS ROADWAY DO NOT INCLUDE THE
 EXISTING TREES. IT APPEARS THAT THERE IS AT LEAST ONE
 TREE THAT WILL BE HIT BY A TRUCK NEGOTIATING THE
 SOUTHEAST CURVE. SHOW THE TREES ON THE TURNING RADIUS
 DRAWING.
  
 7) NEW COMMENT: THE RECONFIGURED FIRE DEPARTMENT ACCESS
 ROADWAY IS SHOWN CROSSING TRACT 7. TRACT 7 IS NOT UNDER
 OWNERSHIP OF PALM BEACH COUNTY, BUT RATHER THE
 COMMUNITY REDEVELOPMENT AGENCY AND MAY NOT BE USED AS
 PART OF THE PLANS APPROVED BY A MINOR AMENDMENT. TRACT
 7 INCLUDES LANDSCAPE TO BUFFER THE REAR OF THE BUFFER
 TOWNHOUSES THAT MAY NOT BE REMOVED AS PART OF THE
 GARAGE PROJECT. PLEASE NOTE THAT THE RESTRICTIVE
 COVENANT REQUIRED AS PART OF CRA RESOLUTION 99-10 ONLY
 PERMITS TRACT 7 TO BE USED FOR LANDSCAPED AREA,
 UNDERGROUND UTILITIES AND APPROVED SIGNAGE. ROADWAYS
 ARE PROHIBITED.
  
 8) REVISED COMMENT: STAFF STRONGLY SUGGESTS INSTALLING
 A SIDEWALK ON THE WEST SIDE OF FLORIDA AVENUE, ALONG
 THE CONVENTION CENTER PROPERTY LINE, TO CONNECT THE
 SIDEWALK IN FRONT OF THE HOTEL TO THE EXISTING SIDEWALK
 ON THE NORTH SIDE OF THE TOWNHOUSES TO PROVIDE MAXIMUM
 PEDESTRIAN OPTIONS IN THE AREA. DURING THE MAJORITY OF
 THE TIME THE CONVENTION CENTER GARAGE WILL NOT BE
 OPERATING AT PEAK FLOW, SO A CROSSWALK AT THE PROPOSED
 INTERSECTIONS IS A SAFER ALTERNATIVE THAN A SIDEWALK AT
 A MIDBLOCK CROSSING. DURING THE TIMES OF PEAK FLOW WHEN
 CONVENTION CENTER TRAFFIC PERSONNEL ARE DEPLOYED, THEY
 CAN FACILITATE THE MOVEMENT OF PEDESTRIANS ACROSS THE
 INTERSECTIONS. THIS IS THE EXISTING CONDITION TODAY
 WITH SIDEWALKS CROSSING THE ACCESS POINTS ON THE WEST
 SIDE OF FLORIDA AVENUE.
  
 IF A MIDBLOCK CROSSING OF FLORIDA AVENUE CONTINUES TO
 BE UTILIZED, STAFF WILL NOT SUPPORT ITS LOCATION AS
 SHOWN ON THE SUBMITTED PLANS BETWEEN THE HOTEL SERVICE
 COURT AND THE CONVENTION CENTER ENTRANCE DRIVE. INSTEAD
 THE CROSSWALK SHALL BE RELOCATED NORTH OF THE HOTEL
 SERVICE COURT AND BISECT THE FLORIDA AVENUE MEDIAN
 ISLAND TO PROVIDE FOR A PROTECTED PEDESTRIAN. THE CITY
 DOES NOT ACCEPT RUMBLE STRIPS AS A WARNING DEVICE FOR
 MIDBLOCK PEDESTRIAN CROSSINGS, BUT INSTEAD REQUIRES
 RECTANGULAR RAPID FLASHING BEACONS. THESE SHALL BE
 CLEARLY LABELED ON THE PLANS. THE MIDBLOCK CROSSING
 SHALL BE TEN FEET WIDE AND SHALL BE CONSTRUCTED OF A
 DIFFERENT MATERIAL THAN THE ROADWAY, FOR EXAMPLE
 STAMPED ASPHALT.
  
 THE SIDEWALK/PEDESTRIAN CROSSING SHALL INCLUDE
 APPROPRIATE PEDESTRIAN LIGHTING.
  
 9) NEW COMMENT: IF THE SIDEWALK IS ONLY SUPPLIED ON THE
 EAST SIDE OF FLORIDA AVENUE, THEN THE COUNTY SHALL BE
 RESPONSIBLE FOR REMOVING THE STRETCH OF SIDEWALK THAT
 WILL NO LONGER SERVE A PURPOSE IN THE RIGHT-OF-WAY
 NORTH OF TRACT 7. THIS IS NOT UNIFORMLY SHOWN ON ALL
 THE PLANS.
  
 10) CONDITION: PLEASE NOTE THAT ALL LIGHT POLES AND
 FIXTURES IN THE ENTRY AREA AND BEING AFFECTED BY
 CONSTRUCTION SHALL MATCH THE STYLE BEING INSTALLED BY
 THE HOTEL.
  
 11) CONDITION: THE DRI REQUIRES THE SUBMITTAL OF A
 SIGNAGE PROGRAM FOR ANY NEW SIGNS. THE SIGNAGE PROGRAM
 SHALL BE SUBMITTED FOR REVIEW AS A MINOR PLANNED
 DEVELOPMENT AMENDMENT PRIOR TO THE SIGNAGE FOR THE
 CONVENTION CENTER GARAGE REVIEW AS PART OF A BUILDING
 PERMIT.
  
 12) REPEAT COMMENT: THE STAFF HAS DETERMINED THAT THE
 CURRENT PLANS DO NOT SHOW COMPLIANCE WITH THE
 REQUIREMENT THAT ROOFTOP PARKING SPACES BE SCREENED.
 THE RECENT APPROVAL OF THE GARAGE ROOFTOP TREATMENTS
 FOR THE SEA PALM DEVELOPMENT AT THE LANDS OF THE
 PRESIDENTS BY THE CITY COMMISSION GIVES GUIDANCE ON
 WHAT COULD BE USED TO COVER ADDITIONAL ROOFTOP PARKING
 AREA.
  
 13) NEW COMMENT: DUE TO THE PROVISION OF COVERED
 PARKING SPACES ON THE ROOF, THERE NEED TO BE AT LEAST
 ADA SPACES THAT ARE COVERED. PLEASE CONTACT ROBERT
 BROWN, CHIEF BUILDING OFFICIAL, DIRECTLY FOR FURTHER
 DETAILS.
  
 14) NEW COMMENT: PLEASE DESCRIBE WHAT THE DIAMOND
 SHAPES ARE THAT ARE SHOWN SURROUNDING THE SUPPORT
 COLUMNS. IF THESE EXTEND ABOVE THE HEIGHT OF THE WHEEL
 STOPS, THEN SOME, TO INCLUDE ONES AT THE HEAD OF THE
 ADA SPACES MAKE THOSE SPACES NON-FUNCTIONING FOR
 PARKING (INSUFFICIENT DEPTH).
  
 15) REVISED COMMENT: THANK YOU FOR PROVIDING THE
 REQUIRED/PROVIDED NUMBER OF BICYCLE PARKING SPACES FOR
 THE SITE. PLEASE PROVIDE THE LOCATIONS AND NUMBER OF
 THE EXISTING BICYCLE PARKING SPACES SO THAT STAFF CAN
 VERIFY THAT THE DISTRIBUTION ADEQUATELY SERVES THE
 SITE. THE NEW SPACES ON THE WEST SIDE OF THE GARAGE ARE
 NOT READILY VISIBLE TO THE BICYCLE USER. SOME OF THE
 SPACES SHOULD BE MOVED TO THE WESTERN EDGE OF THE PLAZA
 AREA AT THE CONVENTION CENTER ENTRANCE TO BE MORE
 VISIBLE.
  
 16) NEW COMMENT: SHOW HOW THE 19 BICYCLE RACKS WILL BE
 ALIGNED IN THE WESTERN BUILDING LOCATION BY THE LOADING
 DOCKS. THIS INCLUDES THE CORRECT BICYCLE PAD
 DIMENSIONS. PLEASE REMEMBER THAT A MINIMUM OF TWO (2)
 FEET ARE REQUIRED AT THE END OF THE ROW WHEN AGAINST A
 FIXED OBJECT SUCH AS A WALL.
  
 17) REPEAT COMMENT: THE STAIRWELL THAT LEADS TO THE PAY
 STATION ON THE BASEMENT LEVEL IN NORTHEAST CORNER OF
 THE GARAGE LEADS TO A SIDEWALK THAT DEAD ENDS INTO THE
 DRIVE AISLE. THIS SIDEWALK HAS TO CONNECT INTO A
 SIDEWALK SO PEOPLE ARE NOT FORCED INTO THE DRIVE AISLE.
 IN REVIEWING THE APPLICANT'S RESPONSE, A CONDITION WILL
 BE ADDED TO THE ULTIMATE GARAGE APPROVAL THAT REQUIRES
 INTERNAL SIGNAGE SHALL BE INSTALLED TO GUIDE USERS TO
 THE ELEVATORS AND STAIRWELLS AT THE NORTHWEST CORNER OF
 THE GARAGE. THE REMAINING STAIRWELLS SHALL BE SIGNED AS
 EMERGENCY EGRESS ONLY. HOWEVER; BOTH ROBERT BROWN,
 CHIEF BUILDING OFFICIAL, AND BRIAN COLLINS, CITY
 TRAFFIC ENGINEER, RAISED CONCERNS WITH PEOPLE PARKING
 IN THE GARAGE AND UTILIZING THE NORTHEAST STAIR AS
 EGRESS FROM THE GARAGE, DUE TO THE PROXIMITY TO THE
 CONVENTION CENTER AND THE HOTEL DESTINATIONS, AND THEN
 BEING ISOLATED AT THE DRIVE AISLE. BOTH REVIEWERS, IN
 ADDITION TO THE ZONING REVIEWER, ARE REQUIRING THAT A
 PEDESTRIAN CONNECTION TO THE SIDEWALK NETWORK BE
 PROVIDED FROM THE NORTHEAST STAIRWELL EXIT. MR. BROWN
 WILL PERMIT THE INSTALLATION OF THE INTERNAL SIGNAGE TO
 SUFFICE TO NOT REQUIRE A PEDESTRIAN CONNECTION FOR THE
 STAIRWELL EXIT POINTS ON THE SOUTH PORTION OF THE
 GARAGE SINCE THERE IS NO DESTINATION FOR SOMEONE USING
 THOSE STAIRWELLS. NOTE: THE PLANS STILL INCLUDE THE PAY
 STATION AT ON THE BASEMENT LEVEL AT THE NORTHEAST EXIT
 STAIRWELL.
  
 18) REPEAT COMMENT: THE EVENT STAGING AREA SHALL BE
 SEPARATED FROM THE WESTERN GARAGE EXIT LANES BY A
 LANDSCAPE BUFFER AND IT SHALL BE BROKEN UP BY THE
 PLACEMENT OF INTERNAL LANDSCAPE. THE BUFFER WILL SERVE
 TO VISUALLY SCREEN THE STAGING AREA FROM THE GARAGE
 PATRONS. ADDITIONALLY THE BUFFER AND THE INTERNAL
 LANDSCAPE WILL BREAK UP THE LARGE EXPANSE OF PAVING AT
 THE STAGING AREA IN ACCORDANCE WITH THE DRI REQUIREMENT
 TO "REDUCE COVERAGE BY ASPHALT, CONCRETE, ROCK, AND
 SIMILAR SUBSTANCES IN STREETS, PARKING LOTS, AND OTHER
 AREAS TO REDUCE LOCAL AIR TEMPERATURES AND REFLECT
 LIGHT AND HEAT."
  
 19) NEW COMMENT: THE APPLICANT'S RESPONSE STATES THAT
 ONLY ONE STATIC EXIT LANE WILL BE PROVIDED AT THE
 NORTHEAST CORNER OF THE GARAGE; HOWEVER, THIS IS NOT
 VERIFIED BY THE STRIPING PLAN, WHICH DOES NOT INCLUDE
 PAVEMENT MARKINGS TO GUIDE A DRIVER TO THE SINGLE EXIT
 LANE.
  
 LANDSCAPE
  
 20) REPEAT COMMENT: THE APPROVED PLAN REQUIRES PLANTER
 BOXES 42 INCHES ABOVE EACH PARKING DECK TO BREAK UP THE
 FACADE OF THE GARAGE. IF THE ROOFTOP PARKING WILL NOT
 BE SCREENED, THEN THE PLANTER BOXES SHOWN ON THE PHASE
 2 SITE PLAN APPROVED AS PART OF RESOLUTION NO. 44-99
 SHALL BE INSTALLED UNLESS THE CONDITION IS AMENDED BY
 CITY COMMISSION ACTION TO CHANGE THE CONDITION OF
 APPROVAL.
  
 21) NEW COMMENT: THE TOTAL SITE AREA LISTED ON SHEET
 AS000 IS 848,549 SQ. FT., BUT THE TOTAL SITE AREA
 LISTED ON SHEET LD-4 OF 4 IS 841,373. WHICH IS CORRECT?
 ALL DATA CALCULATIONS SHALL BE BASED ON ACCURATE
 NUMBERS.
  
 22) REVISED COMMENT: THE EAST PROPERTY CONTAINS 17, NOT
 16 PROVIDED TREES. PLEASE UPDATE THE TABLE.
  
 23) REPEAT COMMENT: THE CONVENTION CENTER HAS NOT
 MAINTAINED ITS PARKING LOT TREES SINCE THEY WERE
 ORIGINALLY INSTALLED AS EVIDENCED BY THE MANY PARKING
 LOT ISLANDS WITHOUT TREES. THESE MISSING TREES ARE
 STILL REQUIRED TO BE MITIGATED AS PART OF THE TREE
 ALTERATION PERMIT. A TABLE VERIFYING THAT ALL OF THE
 REMOVED TREES HAVE BEEN MITIGATED IS REQUIRED AS PART
 OF THE TREE ALTERATION PERMIT. PLEASE NOTE THAT THERE
 WAS NOT INFORMATION PROVIDED AS TO THE CANOPY SIZE OF
 ANY OF THE TREES PROPOSED FOR REMOVAL. DO ANY OF THESE
 TREES HAVE GREATER THAN 35 FEET OF CANOPY?
  
 ELEVATION
  
 24) REVISED COMMENT: THE FINAL COLOR ELEVATIONS THAT
 INCORPORATE THE NEIGHBORHOOD COMMENTS WERE NOT
 PROVIDED.
  
 25) REPEAT COMMENT: PROVIDE A LINE OF SIGHT DRAWING
 NORTH ALONG GEORGIA AVENUE FROM SOUTH OF O STREET.
  
 26) NEW COMMENT: THE SOUTH AND WEST ELEVATION DRAWINGS
 CALL OUT THE FIRE DEPARTMENT ACCESS ROADWAY GATE AS
 GALVANIZED, NOT COATED, CHAIN LINK AS IS SHOWN ON THE
 SITE PLANS.
  
 27) NEW COMMENT: THE EAST ELEVATION DRAWING CALLS OUT A
 DIGITAL MONUMENT SIGN. THIS SHALL BE REMOVED FROM THE
 PLAN.
  
 28) NEW COMMENT: WHY DOES THE NORTH/SOUTH BUILDING
 SECTION SHOW BICYCLE RACKS IN THE BUILDING?
  

Review Stop Z ZONING
Rev No 2 Status F Date 03-18-2015 Cont ID  
Sent By eschneid Date 03-18-2015 Time 20:24 Rev Time 8.00
Received By eschneid Date 03-18-2015 Time 20:24 Sent To  
Notes
2015-03-18 20:28:07PB 950QQQQ - 1ST RESUBMITTAL 2/25/15
 PALM BEACH COUNTY CONVENTION CENTER GARAGE
 650 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 THIS SET OF INTERIM COMMENTS IS BEING ISSUED TO ALLOW
 THE DESIGN TEAM TO ADDRESS SOME OF THE DEFICIENCIES
 WHILE STAFF CONTINUES TO ANALYZE THE APPLICANT'S
 2/25/15 RESPONSES TO THE COMMENTS LISTED AS "STILL
 UNDER STAFF REVIEW". THE "REVISED COMMENT" CATEGORY
 REQUIRES ADDITIONAL FOLLOW UP INFORMATION BASED ON THE
 REVISED PLANS AND THE "NEW COMMENT" CATEGORY IS A
 RESULT OF CHANGES MADE TO THE ORIGINAL PLANS. THE
 "CONDITION" COMMENTS WILL BE ADDED AS PART OF THE
 ULTIMATE APPROVAL LETTER. THE "REPEAT COMMENTS" WERE
 NOT SUFFICIENTLY ADDRESSED.
  
 GENERAL
  
 1) CONDITION: STAFF HAS SPOKEN WITH RELATED REGARDING
 THE AREA SOUTH OF THE HOTEL LOADING ZONE THAT IS
 CURRENTLY NOT INCLUDED ON EITHER THE HOTEL SITE PLAN OR
 THIS SITE PLAN. RELATED HAS AGREED TO SUPPLY PLANS FOR
 THE MISSING PIECE ONCE THIS GARAGE APPLICATION IS
 APPROVED, SO THEY CAN INTEGRATE THEIR PLANS WITH THE
 APPROVED GARAGE DESIGN. RELATED HAS STATED THEY WILL
 CONSTRUCT THE LOADING AREA CHANGES IF THE GARAGE IS
 UNDER CONSTRUCTION BEFORE THEY HAVE COMPLETED THE HOTEL
 CONSTRUCTION. IF THE HOTEL IS COMPLETED AND THE GARAGE
 CONSTRUCTION HAS NOT BEGUN, THE LOADING ZONE
 MODIFICATION CONSTRUCTION WILL BE BORNE BY THE COUNTY
 AS PART OF THE GARAGE CONSTRUCTION. THIS CONDITION WILL
 APPLY TO BOTH APPROVALS.
  
 2) REPEAT COMMENT: PLEASE PROVIDE DETAILS ON HOW THE
 PROPOSED GARAGE COMPLIES WITH THE EXHIBIT D "ENERGY
 SAVING METHODS" OF THE CITYPLACE DRI. - THE RESPONSE
 SHALL LIST THE SPECIFIC ITEMS IN EXHIBIT D THAT WILL BE
 USED AND WHY OTHERS ARE NOT BEING IMPLEMENTED.
  
 SITE PLAN
  
 3) REVISED COMMENT: THE SITE DATA TABLE WAS UPDATED TO
 INCLUDE THE ENTIRE CONVENTION CENTER PARCEL. THE AMOUNT
 OF LANDSCAPE AREA APPROVED BY RES. NO. 44-99 WAS
 15.03%. THE PROPOSED OVERALL CONVENTION CENTER SITE
 ONLY HAS 13.6% LANDSCAPE. PROVIDE THE ADDITIONAL
 LANDSCAPE AREA.
  
 4) REVISED COMMENT: PROVIDE A PARKING MANAGEMENT PLAN
 THAT CONSOLIDATES THE APPLICANT RESPONSES INCLUDED WITH
 ITEMS 8 A THROUGH G IN ONE CENTRAL DOCUMENT THAT WILL
 BE INCLUDED WITH THE ULTIMATE APPROVAL LETTER.
  
 5) STILL UNDER STAFF REVIEW: THE APPROVED PHASE 2 PLAN
 SHOWS APPROXIMATELY 110 FEET OF THE FLORIDA AVENUE
 FRONTAGE INTERRUPTED BY VEHICULAR ACCESS POINTS. THE
 PROPOSED PLAN EXPANDS THIS TO APPROXIMATELY 140 FEET
 (NOT INCLUDING THE STABILIZED FIRE DEPARTMENT ACCESS
 ROADWAY). THERE HAS BEEN NO JUSTIFICATION PROVIDED TO
 CHANGE THE CONDITIONS OF THE CURRENT APPROVAL TO
 SUPPORT THIS ENLARGEMENT OF THE DRIVEWAYS ALONG THE
 FRONTAGE AREA.
  
 7) REVISED COMMENT: THE TURNING RADIUS DRAWINGS FOR
 FIRE DEPARTMENT ACCESS ROADWAY DO NOT INCLUDE THE
 EXISTING TREES. IT APPEARS THAT THERE IS AT LEAST ONE
 TREE THAT WILL BE HIT BY A TRUCK NEGOTIATING THE
 SOUTHEAST CURVE.
  
 8) NEW COMMENT: THE RECONFIGURED FIRE DEPARTMENT ACCESS
 ROADWAY IS SHOWN CROSSING TRACT 7. TRACT 7 IS NOT UNDER
 OWNERSHIP OF PALM BEACH COUNTY, BUT RATHER THE
 COMMUNITY REDEVELOPMENT AGENCY AND MAY NOT BE USED AS
 PART OF THE PLANS APPROVED BY A MINOR AMENDMENT. TRACT
 7 INCLUDES LANDSCAPE TO BUFFER THE REAR OF THE BUFFER
 TOWNHOUSES THAT MAY NOT BE REMOVED AS PART OF THE
 GARAGE PROJECT. PLEASE NOTE THAT THE RESTRICTIVE
 COVENANT REQUIRED AS PART OF CRA RESOLUTION 99-10 ONLY
 PERMITS TRACT 7 TO BE USED FOR LANDSCAPE, HARDSCAPE,
 UNDERGROUND UTILITIES AND PEDESTRIAN ACCESS. ROADWAYS
 ARE PROHIBITED.
  
 9) STILL UNDER STAFF REVIEW: A SIDEWALK SHALL BE
 PROVIDED ON THE WEST SIDE OF FLORIDA AVENUE TO CONNECT
 THE SIDEWALK IN FRONT OF THE HOTEL TO THE EXISTING
 SIDEWALK ON THE NORTH SIDE OF THE TOWNHOUSES. THIS
 SIDEWALK SHALL INCLUDE APPROPRIATE PEDESTRIAN LIGHTING.
  
 10) NEW COMMENT: IF THE SIDEWALK IS ONLY SUPPLIED ON
 THE EAST SIDE OF FLORIDA AVENUE, THEN THE COUNTY SHALL
 BE RESPONSIBLE FOR REMOVING THE STRETCH OF SIDEWALK
 THAT WILL NO LONGER SERVE A PURPOSE IN THE RIGHT-OF-WAY
 NORTH OF TRACT 7. THIS IS NOT UNIFORMLY SHOWN ON ALL
 THE PLANS.
  
 11) CONDITION: PLEASE NOTE THAT ALL LIGHT POLES AND
 FIXTURES IN THE ENTRY AREA SHALL MATCH THE STYLE BEING
 INSTALLED BY THE HOTEL.
  
 12) CONDITION: THE DRI REQUIRES THE SUBMITTAL OF A
 SIGNAGE PROGRAM FOR ANY NEW SIGNS. THE SIGNAGE PROGRAM
 SHALL BE SUBMITTED FOR REVIEW AS A MINOR PLANNED
 DEVELOPMENT AMENDMENT PRIOR TO THE SIGNAGE FOR THE
 CONVENTION CENTER GARAGE REVIEW AS PART OF A BUILDING
 PERMIT.
  
 13) STILL UNDER STAFF REVIEW: THE STAFF HAS DETERMINED
 THAT THE CURRENT PLANS DO NOT SHOW COMPLIANCE WITH THE
 REQUIREMENT THAT ROOFTOP PARKING SPACES BE SCREENED.
 PLEASE PROVIDE INFORMATION ON HOW COMPLIANCE WITH THIS
 REQUIREMENT WILL BE ACHIEVED.
  
 14) NEW COMMENT: DUE TO THE PROVISION OF COVERED
 PARKING SPACES ON THE ROOF, THERE NEED TO BE AT LEAST
 ADA SPACES THAT ARE COVERED. PLEASE CONTACT ROBERT
 BROWN, CHIEF BUILDING OFFICIAL, DIRECTLY FOR FURTHER
 DETAILS.
  
 15) NEW COMMENT: PLEASE DESCRIBE WHAT THE DIAMOND
 SHAPES ARE THAT ARE SHOWN SURROUNDING THE SUPPORT
 COLUMNS. IF THESE EXTEND ABOVE THE HEIGHT OF THE WHEEL
 STOPS, THEN SOME, TO INCLUDE ONES AT THE HEAD OF THE
 ADA SPACES MAKE THOSE SPACES NON-FUNCTIONING FOR
 PARKING (INSUFFICIENT DEPTH).
  
 16) REVISED COMMENT: THANK YOU FOR PROVIDING THE
 REQUIRED/PROVIDED NUMBER OF BICYCLE PARKING SPACES FOR
 THE SITE. PLEASE PROVIDE THE LOCATIONS AND NUMBER OF
 THE EXISTING BICYCLE PARKING SPACES SO THAT STAFF CAN
 VERIFY THAT THE DISTRIBUTION ADEQUATELY SERVES THE
 SITE. THE NEW SPACES ON THE WEST SIDE OF THE GARAGE ARE
 NOT READILY VISIBLE TO THE BICYCLE USER. SOME OF THE
 SPACES SHOULD BE MOVED TO THE WESTERN EDGE OF THE PLAZA
 AREA AT THE CONVENTION CENTER ENTRANCE TO BE MORE
 VISIBLE.
  
 17) NEW COMMENT: SHOW HOW THE 19 BICYCLE RACKS WILL BE
 ALIGNED IN THE WESTERN BUILDING LOCATION BY THE LOADING
 DOCKS. THIS INCLUDES THE CORRECT BICYCLE PAD
 DIMENSIONS. PLEASE REMEMBER THAT A MINIMUM OF TWO (2)
 FEET ARE REQUIRED AT THE END OF THE ROW WHEN AGAINST A
 FIXED OBJECT SUCH AS A WALL.
  
 18) CONDITION: INTERNAL SIGNAGE SHALL BE INSTALLED TO
 GUIDE USERS TO THE ELEVATORS AND STAIRWELLS AT THE
 NORTHWEST CORNER OF THE GARAGE. THE REMAINING
 STAIRWELLS SHALL BE SIGNED AS EMERGENCY EGRESS ONLY.
  
 19) STILL UNDER STAFF REVIEW: THE EVENT STAGING AREA
 SHALL BE SEPARATED FROM THE WESTERN GARAGE EXIT LANES
 BY A LANDSCAPE BUFFER AND IT SHALL BE BROKEN UP BY THE
 PLACEMENT OF INTERNAL LANDSCAPE. THE BUFFER WILL SERVE
 TO VISUALLY SCREEN THE STAGING AREA FROM THE GARAGE
 PATRONS. ADDITIONALLY THE BUFFER AND THE INTERNAL
 LANDSCAPE WILL BREAK UP THE LARGE EXPANSE OF PAVING AT
 THE STAGING AREA IN ACCORDANCE WITH THE DRI REQUIREMENT
 TO "REDUCE COVERAGE BY ASPHALT, CONCRETE, ROCK, AND
 SIMILAR SUBSTANCES IN STREETS, PARKING LOTS, AND OTHER
 AREAS TO REDUCE LOCAL AIR TEMPERATURES AND REFLECT
 LIGHT AND HEAT."
  
 20) NEW COMMENT: THE APPLICANT'S RESPONSE STATES THAT
 ONLY ONE STATIC EXIT LANE WILL BE PROVIDED AT THE
 NORTHEAST CORNER OF THE GARAGE; HOWEVER, THIS IS NOT
 VERIFIED BY THE STRIPING PLAN, WHICH DOES NOT INCLUDE
 PAVEMENT MARKINGS TO GUIDE A DRIVER TO THE SINGLE EXIT
 LANE.
  
 LANDSCAPE
  
 21) STILL UNDER STAFF REVIEW: THE APPROVED PLAN
 REQUIRES PLANTER BOXES 42 INCHES ABOVE EACH PARKING
 DECK TO BREAK UP THE FACADE OF THE GARAGE. PLEASE
 PROVIDE JUSTIFICATION AS TO WHY NOT PROVIDING THE
 PLANTER BOXES IS NOT A CHANGED CONDITION OF APPROVAL,
 WHICH WOULD NECESSITATE A REVIEW OF THE GARAGE BY THE
 CITY COMMISSION.
  
 22) NEW COMMENT: THE TOTAL SITE AREA LISTED ON SHEET
 AS000 IS 848,549 SQ. FT., BUT THE TOTAL SITE AREA
 LISTED ON SHEET LD-4 OF 4 IS 841,373. WHICH IS CORRECT?
 ALL DATA CALCULATIONS SHALL BE BASED ON ACCURATE
 NUMBERS.
  
 23) REVISED COMMENT: THE EAST PROPERTY CONTAINS 17, NOT
 16 PROVIDED TREES. PLEASE UPDATE THE TABLE.
  
 24) STILL UNDER STAFF REVIEW: THE CONVENTION CENTER HAS
 NOT MAINTAINED ITS PARKING LOT TREES SINCE THEY WERE
 ORIGINALLY INSTALLED AS EVIDENCED BY THE MANY PARKING
 LOT ISLANDS WITHOUT TREES. THESE MISSING TREES ARE
 STILL REQUIRED TO BE MITIGATED AS PART OF THE TREE
 ALTERATION PERMIT. A TABLE VERIFYING THAT ALL OF THE
 REMOVED TREES HAVE BEEN MITIGATED IS REQUIRED AS PART
 OF THE TREE ALTERATION PERMIT. PLEASE NOTE THAT THERE
 WAS NOT INFORMATION PROVIDED AS TO THE CANOPY SIZE OF
 ANY OF THE TREES PROPOSED FOR REMOVAL. DO ANY OF THESE
 TREES HAVE GREATER THAN 35 FEET OF CANOPY?
  
 ELEVATION
  
 25) REVISED COMMENT: THE FINAL COLOR ELEVATIONS THAT
 INCORPORATE THE NEIGHBORHOOD COMMENTS WERE NOT
 PROVIDED.
  
 26) REPEAT COMMENT: PROVIDE A LINE OF SIGHT DRAWING
 NORTH ALONG GEORGIA AVENUE FROM SOUTH OF O STREET.
  
 27) NEW COMMENT: THE SOUTH AND WEST ELEVATION DRAWINGS
 CALL OUT THE FIRE DEPARTMENT ACCESS ROADWAY GATE AS
 GALVANIZED, NOT COATED, CHAIN LINK AS IS SHOWN ON THE
 SITE PLANS.
  
 28) NEW COMMENT: THE EAST ELEVATION DRAWING CALLS OUT A
 DIGITAL MONUMENT SIGN. THIS SHALL BE REMOVED FROM THE
 PLAN.
  
 29) NEW COMMENT: WHY DOES THE NORTH/SOUTH BUILDING
 SECTION SHOW BICYCLE RACKS IN THE BUILDING?
  

Review Stop Z ZONING
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By eschneid Date 01-13-2015 Time 17:40 Rev Time 8.00
Received By eschneid Date 01-13-2015 Time 17:39 Sent To  
Notes
2015-01-13 18:07:30PB 950QQQQ
 PALM BEACH COUNTY CONVENTION CENTER GARAGE
 650 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY MARCH 14, 2015),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 ADMINISTRATIVE
  
 1) THE CITY DOES NOT HAVE A RECORD OF THE PAYMENT FOR
 THE TREE ALTERATION PERMIT.
  
 2) THIS PROJECT WILL BE REQUIRED TO MEET THE CITY?S ART
 IN PUBLIC PLACES REQUIREMENTS.
  
 3) THE PROJECT FACT SHEET SHALL INCLUDE THE ENTIRE
 CONVENTION CENTER PARCEL FOR THE PURPOSES OF AREA
 CALCULATIONS.
  
 4) STAFF HAS SPOKEN WITH RELATED REGARDING THE AREA
 SOUTH OF THE HOTEL LOADING ZONE THAT IS CURRENTLY NOT
 INCLUDED ON EITHER THE HOTEL SITE PLAN OR THIS SITE
 PLAN. RELATED HAS AGREED TO SUPPLY PLANS FOR THE
 MISSING PIECE ONCE THIS GARAGE APPLICATION IS APPROVED,
 SO THEY CAN INTEGRATE THEIR PLANS WITH THE APPROVED
 GARAGE DESIGN. RELATED HAS STATED THEY WILL CONSTRUCT
 THE LOADING AREA CHANGES IF THE GARAGE IS UNDER
 CONSTRUCTION BEFORE THEY HAVE COMPLETED THE HOTEL
 CONSTRUCTION. IF THE HOTEL IS COMPLETED AND THE GARAGE
 CONSTRUCTION HAS NOT BEGUN, THE LOADING ZONE
 MODIFICATION CONSTRUCTION WILL BE BORNE BY THE COUNTY
 AS PART OF THE GARAGE CONSTRUCTION. THIS CONDITION WILL
 APPLY TO BOTH APPROVALS.
  
 5) PLEASE PROVIDE DETAILS ON HOW THE PROPOSED GARAGE
 COMPLIES WITH THE EXHIBIT D "ENERGY SAVING METHODS" OF
 THE CITYPLACE DRI.
  
 SITE PLAN
  
 6) THE SITE DATA TABLE NEEDS TO INCLUDE THE ENTIRE
 CONVENTION CENTER PARCEL. THE CITY CODE REQUIRED
 MINIMUM IMPERVIOUS SURFACE AREA AND LOT COVERAGE SHALL
 BE PROVIDED ACROSS THE ENTIRE SITE.
  
 7) THE CONFIGURATION OF FLORIDA AVENUE AT THE NORTHEAST
 CORNER ENTRANCE TO THE GARAGE ON SHEET AS000 DOES NOT
 MATCH THE REMAINDER OF THE PLANS SUBMITTED FOR REVIEW.
 THE MEDIAN IS SHOWN WITH A DIFFERENT CONFIGURATION.
  
 8) ONCE YOU HAVE DETERMINED THE FINAL MEDIAN
 CONFIGURATION, PLEASE PROVIDE TURNING RADIUS DRAWINGS
 AND VEHICULAR MOVEMENT PLANS FOR THIS AREA. THERE ARE A
 LOT OF TRAFFIC LANES THAT DO NOT APPEAR TO STAFF TO
 ALLOW FOR EFFICIENT, OR IN SOME CASES POSSIBLE TRAFFIC
 MOVEMENTS.
  
 A. WHY ARE THERE THREE LANES LEADING AROUND THE VALET
 CIRCLE?
 B. IS IT THE INTENT TO ALLOW DRIVERS TO ENTER THE NORTH
 SIDE OF THE GARAGE BY GOING THROUGH THE MEDIAN BREAK
 INSTEAD OF CIRCLING AROUND TO THE VALET?
 C. THERE ARE FIVE LANES THAT LEAVE THE SITE IMMEDIATELY
 ADJACENT TO EACH OTHER. HOW DO THESE CARS NEGOTIATE OUT
 OF THE SITE GIVEN THAT THERE ARE NOT FIVE TRAVEL LANES
 IN THE AREA?
 D. WHAT IS THE VALET ROUTE TO AND FROM THE GARAGE TO
 PARK CARS?
 E. HOW IS THE VALET TRAFFIC INTEGRATED OR KEPT SEPARATE
 FROM SELF-PARK TRAFFIC?
 F. WHERE ARE THE VALET PARKING SPACES?
 G. WHAT DESIGN FEATURES WILL CARS LEAVING THE BASEMENT
 LEVEL OF THE GARAGE FROM UNSAFE EXIT SPEEDS ONTO
 FLORIDA AVENUE.
  
 9) THE APPROVED PHASE 2 PLAN SHOWS APPROXIMATELY 110
 FEET OF THE FLORIDA AVENUE FRONTAGE INTERRUPTED BY
 VEHICULAR ACCESS POINTS. THE PROPOSED PLAN EXPANDS THIS
 TO APPROXIMATELY 140 FEET (NOT INCLUDING THE STABILIZED
 FIRE DEPARTMENT ACCESS). THERE HAS BEEN NO
 JUSTIFICATION PROVIDED TO CHANGE THE CONDITIONS OF THE
 CURRENT APPROVAL TO SUPPORT THIS ENLARGEMENT OF THE
 DRIVEWAYS ALONG THE FRONTAGE AREA.
  
 10) PLEASE EXPLAIN HOW VISITORS WILL KNOW TO GO TO THE
 NORTH GARAGE ENTRANCE OR THE CORNER GARAGE ENTRANCE.
  
 11) PROVIDE TURNING RADIUS DRAWINGS FOR THE CURVED
 AREAS OF THE FIRE DEPARTMENT ACCESS. PLEASE VERIFY WITH
 THE CITY'S FIRE MARSHALL WHICH TRUCK SIZE IS
 APPROPRIATE TO USE FOR THE DRAWINGS.
  
 12) PROVIDE A CROSS SECTION, WITH ELEVATION MARKERS,
 FOR THE RAMPED DOWN ENTRY INTO THE NORTHEAST CORNER OF
 THE GARAGE. THE TRANSITION FOR THE FIRE DEPARTMENT
 ACCESS SHALL BE SHOWN ON THIS CROSS SECTION.
  
 A. HOW IS THE EDGE OF THE ACCESS ROAD RETAINED?
 B. WHAT IS THE GRADE DIFFERENCE?
 C. IS BARRIER REQUIRED TO KEEP THE TRUCK FROM GOING OFF
 THE EDGE OF THE ACCESS ROAD?
  
 13) A SIDEWALK SHALL BE PROVIDED ON THE WEST SIDE OF
 FLORIDA AVENUE TO CONNECT THE SIDEWALK IN FRONT OF THE
 HOTEL TO THE EXISTING SIDEWALK ON THE NORTH SIDE OF THE
 TOWNHOUSES. THIS SIDEWALK SHALL INCLUDE APPROPRIATE
 PEDESTRIAN LIGHTING.
  
 14) PROVIDE A LIGHTING PLAN WHICH VERIFIES COMPLIANCE
 WITH THE CITY'S LIGHTING REGULATIONS. PLEASE NOTE THAT
 ALL LIGHT POLES AND FIXTURES IN THE ENTRY AREA SHALL
 MATCH THE STYLE BEING INSTALLED BY THE HOTEL.
  
 15) THE CITY DOES NOT PERMIT CHAIN LINK FENCES WITH
 SLATS IN THEM. IF THE GOAL OF THE FENCES AND GATES ON
 EITHER END OF THE FIRE DEPARTMENT ACCESS IS FOR
 SCREENING, A DIFFERENT OPTION NEEDS TO BE USED. FROM A
 SECURITY STANDPOINT, STAFF RECOMMENDS USING FENCING
 THAT HAS OPENINGS SO THAT THERE IS THE ABILITY TO SEE
 INTO THE GATED OFF AREA.
  
 16) THE CONVENTION CENTER MAY ONLY HAVE AN ELECTRONIC
 MESSAGE SIGN LOCATED ON A ROADWAY CLASSIFIED AS AN
 ARTERIAL OR EXPRESSWAY. FLORIDA AVENUE IS NEITHER OF
 THESE; THEREFORE THE ELECTRONIC MESSAGE SIGN IS NOT
 PERMITTED AS SHOWN.
  
 17) THE DRI REQUIRES THE SUBMITTAL OF A SIGNAGE PROGRAM
 FOR ANY NEW SIGNS.
  
 18) THE STAFF HAS DETERMINED THAT THE CURRENT PLANS DO
 NOT SHOW COMPLIANCE WITH THE REQUIREMENT THAT ROOFTOP
 PARKING SPACES BE SCREENED. PLEASE PROVIDE INFORMATION
 ON HOW COMPLIANCE WITH THIS REQUIREMENT WILL BE
 ACHIEVED.
  
 19) THE GARAGE PLAN SHEET AE140 CALLS OUT LEVELS 3-8.
 SHEET AE150 THE SHOWS AN ADDITIONAL TOP LEVEL FOR A
 TOTAL OF 9 LEVELS. IT IS STAFF'S UNDERSTANDING THAT THE
 8TH LEVEL IS THE TOP LEVEL AS SHOWN IN THE ELEVATIONS.
 PLEASE CLARIFY.
  
 20) ARE LEVELS 3-8 MISSING A DOWN ARROW FOR A RAMP?
  
 21) THE PARKING STALL DETAIL SHALL SHOW WHITE STRIPING
 TO COMPLY WITH CITY REQUIREMENTS.
  
 22) PROVIDE A TABLE SHOWING THE REQUIRED AND PROVIDED
 BICYCLE PARKING.
  
 23) THE CITY DOES NOT PERMIT THE WAVE STYLE BICYCLE
 RACK. PROVIDE CITY COMPLIANT BICYCLE RACK AND PAD
 DETAILS AND SHOW THE PAD DIMENSIONS ON THE PLAN.
  
 24) PLEASE SHOW HOW SOMEONE UTILIZING THE BICYCLE RACK
 ON THE BASEMENT LEVEL OF THE GARAGE GETS TO THE
 ENTRANCE OF THE CONVENTION CENTER.
  
 25) PLEASE ELABORATE ON WHAT THE UTILITY ROOMS AND THE
 OFFICES WILL BE USED FOR AND WHO WILL USE THEM.
  
 26) THERE ARE PAYMENT STATIONS SHOWN IN THE GARAGE.
 WILL THE GARAGE BE UNMANNED?
  
 27) THE STAIRWELL THAT LEADS TO THE PAY STATION ON THE
 BASEMENT LEVEL IN NORTHEAST CORNER OF THE GARAGE LEADS
 TO A SIDEWALK THAT DEAD ENDS INTO THE DRIVE AISLE. THIS
 SIDEWALK HAS TO CONNECT INTO A SIDEWALK SO PEOPLE ARE
 NOT FORCED INTO THE DRIVE AISLE.
  
 28) THERE APPEAR TO BE SOME PARKING SPACES THAT ARE
 ADJACENT TO WALLS WITHOUT PROVIDING THE REQUIRED ONE
 (1) FOOT ADDITIONAL SEPARATION (COMPACT SPACES IN
 MIDDLE ROWS IN BASEMENT). IS THIS AN ACCURATE READING
 OF THE PLANS BY STAFF? IF THERE IS A WALL, PLEASE
 PROVIDE THE DIMENSION LINE TO VERIFY THE ONE (1) FOOT
 SETBACK.
  
 29) PROVIDE DIMENSION LINES FOR THE PARKING ROWS AND
 DRIVE AISLES IN THE GARAGE.
  
 30) HOW ARE PATRONS RESTRICTED FROM USING THE DOORS TO
 THE STAIRWELLS ON THE EAST, SOUTH AND WEST SIDES OF THE
 BUILDING, ESPECIALLY SINCE THESE EXIT OUT BEHIND THE
 FENCES TO THE FIRE DEPARTMENT ACCESS ROAD?
  
 31) THE EVENT STAGING AREA SHALL BE SEPARATED FROM THE
 WESTERN GARAGE EXIT LANES BY A LANDSCAPE BUFFER AND IT
 SHALL BE BROKEN UP BY THE PLACEMENT OF INTERNAL
 LANDSCAPE. THE BUFFER WILL SERVE TO VISUALLY SCREEN THE
 STAGING AREA FROM THE GARAGE PATRONS. ADDITIONALLY THE
 BUFFER AND THE INTERNAL LANDSCAPE WILL BREAK UP THE
 LARGE EXPANSE OF PAVING AT THE STAGING AREA IN
 ACCORDANCE WITH THE DRI REQUIREMENT TO "REDUCE COVERAGE
 BY ASPHALT, CONCRETE, ROCK, AND SIMILAR SUBSTANCES IN
 STREETS, PARKING LOTS, AND OTHER AREAS TO REDUCE LOCAL
 AIR TEMPERATURES AND REFLECT LIGHT AND HEAT."
  
 32) THE STAGING AREA SHALL BE SCREENED FROM THE
 CONVENTION CENTER ENTRANCE AT ITS NORTHEAST CORNER.
  
 LANDSCAPE
  
 33) ALL LIGHT POLES SHALL BE SHOWN ON THE LANDSCAPE
 PLAN. THE LIGHT POLES SHALL NOT INTERFERE WITH THE
 LANDSCAPE GROWTH.
  
 34) THE APPROVED PLAN REQUIRES PLANTER BOXES 42 INCHES
 ABOVE EACH PARKING DECK TO BREAK UP THE FA?ADE OF THE
 GARAGE. PLEASE PROVIDE JUSTIFICATION AS TO WHY NOT
 PROVIDING THE PLANTER BOXES IS NOT A CHANGED CONDITION
 OF APPROVAL, WHICH WOULD NECESSITATE A REVIEW OF THE
 GARAGE BY THE CITY COMMISSION.
  
 35) LANDSCAPE MATERIAL LISTED UNDER THE "SHRUB" PORTION
 OF THE LANDSCAPE TABLE MAY NOT BE COUNTED TO MEET THE
 TREE REQUIREMENTS ON THE SITE.
  
 36) PROVIDE JUSTIFICATION FOR COUNTING THE BAMBOO AS A
 2:1 TREE REPLACEMENT.
  
 37) PLEASE NOTE THAT ONLY 35% OF THE REQUIRED SHADE
 TREES MAY BE SUBSTITUTED BY PALMS (AND POTENTIALLY
 BAMBOO). PROVIDE A VERIFICATION TABLE.
  
 38) THE EAST PROPERTY LENGTH LISTED IN THE TABLE DOES
 NOT INCLUDE THE ENTIRE EAST PROPERTY LINE DIMENSION.
 THIS WILL CHANGE THE NUMBER OF REQUIRED TREES.
  
 39) THERE ARE TREES THAT APPEAR EXTREMELY CLOSE TO
 UNDERGROUND DRAINAGE FACILITIES, ESPECIALLY IN THE
 SOUTHWEST CORNER OF THE SITE. PLEASE VERIFY THAT THERE
 WILL BE NO DISRUPTION OF THESE LINES. NOTE: THE ROOT
 BARRIERS SHOWN ON THE DETAIL SHEET ONLY SEEM TO BE
 PLANNED TO PROTECT SIDEWALKS.
  
 40) THE CONVENTION CENTER HAS NOT MAINTAINED ITS
 PARKING LOT TREES SINCE THEY WERE ORIGINALLY INSTALLED
 AS EVIDENCED BY THE MANY PARKING LOT ISLANDS WITHOUT
 TREES. THESE MISSING TREES ARE STILL REQUIRED TO BE
 MITIGATED AS PART OF THE TREE ALTERATION PERMIT. A
 TABLE VERIFYING THAT ALL OF THE REMOVED TREES HAVE BEEN
 MITIGATED IS REQUIRED AS PART OF THE TREE ALTERATION
 PERMIT. PLEASE NOTE THAT THERE WAS NOT INFORMATION
 PROVIDED AS TO THE CANOPY SIZE OF ANY OF THE TREES
 PROPOSED FOR REMOVAL. DO ANY OF THESE TREES HAVE
 GREATER THAN 35 FEET OF CANOPY?
  
 ELEVATION
  
 41) STAFF WILL WAIT TO COMPLETE A FULL REVIEW UNTIL THE
 FINAL ELEVATIONS THAT INCORPORATE THE NEIGHBORHOOD
 COMMENTS ARE PROVIDED.
  
 42) PROVIDE SECTION DRAWINGS TO SHOW HOW THE CAR
 HEADLIGHTS WILL NOT SHINE OUT OF THE GARAGE.
  
 43) PROVIDE SECTION DRAWINGS TO DETAIL HOW THE VARIOUS
 APPLIED METAL PANELS, PILASTERS, ALUMINUM TUBES,
 RECESSED OPENINGS, ETC. INTERACT ALONG THE FACE OF THE
 BUILDING. THESE SHALL PROVIDE VARYING AMOUNTS OF DEPTH
 AND SHADOWS.
  
 44) PROVIDE A LINE OF SIGHT DRAWINGNORTH ALONG GEORGIA
 AVENUE FROM SOUTH OF O STREET.
  
 45) PROVIDE DETAILS OF THE CANOPIES AND OTHER ROOF
 COVERINGS THAT CONNECT THE CONVENTION CENTER TO THE
 GARAGE.
  
  