Plan Review Details - Project Z14120012
Plan Review Stops For Project Z14120012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 01-13-2015 Cont ID  
Sent By rbrown Date 01-13-2015 Time 20:50 Rev Time 0.00
Received By rbrown Date 01-13-2015 Time 20:50 Sent To  
Notes
2015-01-13 20:56:58DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 IT IS NOTED THAT THE SCOPE OF THE MINOR AMENDEMENT IS
 PRIMARILY THE ADDITION OF A GENERATOR, RECONFIGURATION
 OF PARKING, AND REDUCTION IN BUILDING SQUARE FOOTAGE AS
 A RESULT OF MODIFICATION AT A COURTYARD.
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 3. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK. SEPARATE PERMITS,
 PLANS AND FEES, ARE REQUIRED FOR SWIMMING POOLS AND
 SPAS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 04-15-2015 Cont ID  
Sent By cranford Date 04-15-2015 Time 14:26 Rev Time 0.00
Received By cranford Date 04-15-2015 Time 14:16 Sent To  
Notes
2015-04-15 14:25:443RD REVIEW
  
 THE DUMPSTER ENCLOSURE GATE SHOWN ON SHEET L102 IS ONLY
 7 FEET WIDE. ACCORDING TO SECTION 94-444(B), FIGURE
 XIV-3 OF THE CITY'S CODE OF ORDINANCES, THE GATE
 OPENING MUST BE A MINIMUM OF 12 FT 6 INCHES TO ALLOW
 TRUCK ACCESS. AS MENTIONED IN OUR PREVIOUS COMMENTS,
 PLEASE REVISE THE ENCLOSURE TO MEET THE CITY'S CODE
 REQUIREMENTS.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 03-03-2015 Cont ID  
Sent By cranford Date 03-03-2015 Time 11:03 Rev Time 0.00
Received By cranford Date 03-03-2015 Time 10:57 Sent To  
Notes
2015-03-03 11:03:51PLEASE REVISE THE COMPACTOR GATE OPENING (SHEET L102)
 TO BE AT LEAST 12'6". THE PROPOSED WIDTH OF 7 FEET WILL
 NOT ALLOW THE TRUCK TO ACCESS THE COMPACTOR RECEPTACLE.
 CODE OF ORDINANCES SECTION 94-444(B).
  
 KELLY CRANFORD, PE
 (561)494-1098

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By cranford Date 01-13-2015 Time 10:38 Rev Time 0.00
Received By cranford Date 01-13-2015 Time 10:17 Sent To  
Notes
2015-01-13 10:19:38PUBLIC WORKS DEPT.
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 1. PLEASE SHOW AN AUTOTURN ANALYSIS SHOWING HOW THE
 SANITATION TRUCKS WILL ACCESS THE DUMPSTER ENCLOSURE.
  
 2. A MODIFICATION REQUEST WILL NEED TO BE SUBMITTED TO
 THE ENGINEERING DEPARTMENT FOR APPROVAL E10070002.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 02-26-2015 Cont ID  
Sent By pleduc Date 02-26-2015 Time   Rev Time 0.00
Received By pleduc Date 02-26-2015 Time 12:33 Sent To  
Notes
2015-02-26 12:37:472ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 FEBRUARY 12, 2015, FROM COTLEUR & HEARING, TO ERIC
 SCHNEIDER, PRINCIPAL PLANNER, THE PREVIOUSLY SUBMITTED
 FIRE PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 01-08-2015 Cont ID  
Sent By pleduc Date 01-08-2015 Time   Rev Time 0.00
Received By pleduc Date 01-08-2015 Time 11:54 Sent To  
Notes
2015-01-08 13:30:27THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2012 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE
 SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY,
 CHAPTER 30, NEW APARTMENTS.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 10. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
 11. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGECNY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 12. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 13. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 14. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 16. FIRE LOAD CALCULATIONS SHALL BE PROVIDED THAT
 DEMONSTRATE COMPLIANCE WITH THE WATER SUPPLY.
  
 17. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 18. EACH ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS
 TO AT LEAST ONE EXIT.
  
 19. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME,
 SAFETY CODE FOR ELEVATORS.
  
 20. FIRE LANES SHALL BE A MINIMUM 20' WIDE.
  
 21. THE ACTUAL FOOT PRINT OF THE PROPOSED PROJECT IS
 UNCLEAR. THERE INSUFFICIENT INFORMATION PROVIDED TO
 PROVIDE FURTHER PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status N Date 04-15-2015 Cont ID  
Sent By cranford Date 04-15-2015 Time 14:29 Rev Time 0.00
Received By cranford Date 04-15-2015 Time 14:27 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 04-15-2015 Cont ID  
Sent By cranford Date 04-15-2015 Time 14:31 Rev Time 0.00
Received By cranford Date 04-15-2015 Time 14:30 Sent To  
Notes
2015-04-15 14:31:31PLEASE SEE COMMENTS UNDER ENGINEERING PPRC

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By cranford Date 01-13-2015 Time 10:40 Rev Time 0.00
Received By cranford Date 01-13-2015 Time 10:40 Sent To  
Notes
2015-01-13 10:40:48SEE ENGINEERING PPRC COMMENTS

Review Stop STORM STORMWATER
Rev No 2 Status P Date 04-15-2015 Cont ID  
Sent By cranford Date 04-15-2015 Time 14:28 Rev Time 0.00
Received By cranford Date 04-15-2015 Time 14:28 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By cranford Date 01-13-2015 Time 10:41 Rev Time 0.00
Received By cranford Date 01-13-2015 Time 10:40 Sent To  
Notes
2015-01-13 10:41:14SEE ENGINEERING PPRC COMMENTS

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 01-12-2015 Cont ID  
Sent By vnoel Date 01-12-2015 Time 09:23 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2015-01-12 09:24:09PLAT HAS BEEN SUBMITTED AND IS IN REVIEW.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 04-15-2015 Cont ID  
Sent By cranford Date 04-15-2015 Time 14:27 Rev Time 0.00
Received By cranford Date 04-15-2015 Time 14:27 Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 01-13-2015 Cont ID  
Sent By cranford Date 01-13-2015 Time 10:42 Rev Time 0.00
Received By cranford Date 01-13-2015 Time 10:41 Sent To  
Notes
2015-01-13 10:41:55SEE ENGINEERING PPRC COMMENTS

Review Stop Z ZONING
Rev No 3 Status P Date 06-23-2015 Cont ID  
Sent By eschneid Date 06-23-2015 Time 16:34 Rev Time 0.00
Received By eschneid Date 04-21-2015 Time 18:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 03-16-2015 Cont ID  
Sent By eschneid Date 03-16-2015 Time 16:03 Rev Time 3.00
Received By eschneid Date 03-16-2015 Time 16:03 Sent To  
Notes
2015-03-16 16:32:13PB 1248Y
 MORSELIFE TRADITIONS PHASE II RECONFIGURATION AND
 MASTER PLAN CHANGES MINOR AMENDMENT
 1ST RESUBMITTAL
 FRED GLADSTONE & LORING DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THE COMMENTS (BY MAY 16, 2015), THE CASE
 SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT NOT ALL OF THE PREVIOUSLY-ISSUED
 COMMENTS WERE SUFFICIENTLY ADDRESSED; THEREFORE, A
 RESUBMITTAL FEE OF $60 IS REQUIRED AS PART OF THE NEXT
 RESUBMITTAL.
  
 TRADITIONS PHASE II
  
 1) REVISED COMMENT: THE TOTAL LINE UNDER THE PARKING
 CALCULATIONS ACCESSIBLE SPACES AREA DOES NOT MATCH THE
 TOTAL NO. PROV. +13 SPACES. 704 VS. 706
  
 2) REPEAT COMMENT: THE PARKING STALL DETAILS SHALL BE
 AMENDED TO PUT THE WHEEL STOP IN THE FULL SIZE PARKING
 SPACE.
  
 3) REPEAT COMMENT: PROVIDE THE BICYCLE RACK PAD
 DIMENSIONS ON THE SITE PLAN. ONLY ONE OF THE TWO PADS
 HAS DIMENSIONS; HOWEVER, THE DIMENSION DOES NOT MATCH
 THE DIMENSION ON THE BIKE RACK DETAIL. PLEASE NOTE THAT
 THE DIMENSION ON THE BIKE RACK DETAIL FOR THE NUMBER OF
 RACKS SHOWN IS ONLY 14 FEET WIDE, NOT 14 FEET 4 INCHES
 AS LISTED.
  
 4) REVISED COMMENT: PROVIDE A DETAIL OF THE PACE
 PARKING SPACES TO VERIFY THAT THE SPACES HAVE
 SUFFICIENT DEPTH FOR THE PACE VANS. THE VANS WERE
 STATED TO BE LONGER THAN 18 FEET YET THE PACE SPACES
 SEEM TO BE 18 FEET LONG. PLEASE REMEMBER THAT THE DRIVE
 AISLE NEEDS TO REMAIN AT 24 FEET IN WIDTH.
  
 5) CONDITION OF APPROVAL: ANY MISSING BUFFER TREES AND
 HEDGES NEED TO BE FILLED IN AS PART OF THE
 CONSTRUCTION.
  
 THE COURTYARD AND ENTRY ROAD LANDSCAPE ITEMS HAVE BEEN
 SUFFICIENTLY ADDRESSED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 01-14-2015 Cont ID  
Sent By eschneid Date 01-14-2015 Time 12:29 Rev Time 4.00
Received By eschneid Date 01-14-2015 Time 12:29 Sent To  
Notes
2015-01-14 12:34:06PB 1248Y
 MORSELIFE TRADITIONS PHASE II RECONFIGURATION AND
 MASTER PLAN CHANGES MINOR AMENDMENT
 FRED GLADSTONE & LORING DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY MARCH 14, 2015),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 TRADITIONS PHASE II
  
 1) THIS BUILDING WILL BE REQUIRED TO COMPLY WITH THE
 CITY'S ARTS IN PUBLIC PLACES REQUIREMENTS.
  
 2) PLEASE CHECK THE "PARKING PROVIDED" NUMBER. STAFF
 COUNTS 193 SPACES AROUND THE TRADITIONS PHASE II
 BUILDING (THIS VALUE IS ALSO SHOWN ON THE LANDSCAPE
 PLAN).
  
 3) THE PARKING STALL DETAILS SHALL BE AMENDED TO PUT
 THE WHEEL STOP IN THE FULL SIZE PARKING SPACE, NOT IN
 THE ONE WITH THE CURBED OVERHANG.
  
 4) PROVIDE THE BICYCLE RACK PAD DIMENSIONS ON THE SITE
 PLAN.
  
 5) WHERE WILL THE PACE BUS PARKING BE RELOCATED TO?
 THIS SHALL BE SHOWN ON THE PLANS.
  
 6) THE PLANS CALL OUT A DUMPSTER AND RECYCLING WITH AN
 OPAQUE GATE; HOWEVER, THE DETAIL STATES THERE IS A
 COMPACTOR. PLEASE CLARIFY. THE TRASH FACILITY NEEDS TO
 BE ENCLOSED ON ALL SIDES WITH AN OPAQUE, LANDSCAPED
 ENCLOSURE.
  
 7) THE CURRENTLY APPROVED SITE PLAN SHOWS A SIDEWALK
 ALONG A LONG PORTION OF THE SOUTHERN LAKE THAT WAS
 DESIGNED TO BE A WALKING PATH FOR THE RESIDENTS. THE
 WALKING PATH DISTANCE NEEDS TO BE MAINTAINED, EVEN IF
 IT LEADS TO A DIFFERENT PORTION OF THE LAKE.
  
 8) THERE NEEDS TO BE SCREENING LANDSCAPE ON THE NORTH
 SIDE OF THE COOLING TOWER ENCLOSURE.
  
 9) SINGLE, SOLO TRUNK ADONIDIA PALMS DO NOT QUALIFY FOR
 TERMINAL ISLAND TREES.
  
 10) ONE OF THE TERMINAL PARKING ISLANDS SOUTH OF THE
 BUILDING IS MISSING A REQUIRED TREE.
  
 11) THE FRACTIONS ARE ROUNDED UP FOR THE REQUIRED TREE
 NUMBERS. PLEASE VERIFY YOUR MATH - EX. REQUIRED BUFFER
 TREES ARE INCORRECT.
  
 12) THERE ARE MORE "PROVIDED" BUFFER TREES THAN ARE
 SHOWN IN THE TABLE. PLEASE VERIFY ALL PLANT COUNTS.
  
 13) ANY MISSING BUFFER TREES AND HEDGES NEED TO BE
 FILLED IN AS PART OF THE CONSTRUCTION.
  
 14) THE ARCHITECTURAL PLANS REFERENCE SHEET A108 FOR
 THE GENERATOR PLAN. PLEASE PROVIDE THIS SHEET.
  
 EDWARDS COURTYARDS
  
 15) PLEASE REMOVE THE BOARDROOM EXPANSION SQUARE
 FOOTAGE FROM THE EDWARDS BUILDING LINE ITEMS ON THE
 MASTER PLAN (PARKING AND SQUARE FOOTAGE).
  
 16) SHEET L105 WILL VOID PREVIOUSLY APPROVED BOARDROOM
 SHEETS LP-1 AND LD-1.
  
 17) AN UPDATED TREE ALTERATION PERMIT IS REQUIRED FOR
 THE RELOCATED TREES.
  
 ENTRY ROAD LANDSCAPE
  
 18) THE ENTRY MEDIAN BETWEEN THE SPECIAL CARE FACILITY
 AND THE PORTE COCHERE HAS CHANGED LANDSCAPE
 CONFIGURATION ON THE LATEST SUBMITTED BUILDING PERMIT.
 PLEASE REVISE THE LANDSCAPE SHEETS TO REFLECT THE
 PROPOSED LANDSCAPE.
  
 SITE DATA TABLE
  
 19) THE MASTER SITE DATA TABLE NEEDS TO BE UPDATED TO
 REFLECT THE CONVERSION OF THE 144 UNITS IN PHASE I TO
 144 BEDS AND MOVING 40 OF THE 44 UNITS TO BEDS IN PHASE
 I. THUS PHASE I IS COUNTED AS HAVING 184 BEDS AND ZERO
 UNITS. NOTATIONS SHALL BE ADDED.
  