Plan Review Details - Project Z14110026
Plan Review Stops For Project Z14110026
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-10-2014 Cont ID  
Sent By rbrown Date 12-10-2014 Time 11:49 Rev Time 0.00
Received By rbrown Date 12-10-2014 Time 11:49 Sent To  
Notes
2014-12-10 11:49:43DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 10 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 3. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK. SEPARATE PERMITS,
 PLANS AND FEES, ARE REQUIRED FOR SWIMMING POOLS AND
 SPAS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 02-04-2015 Cont ID  
Sent By cranford Date 02-04-2015 Time 15:16 Rev Time 0.00
Received By cranford Date 02-04-2015 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-04-2014 Cont ID  
Sent By pleduc Date 12-04-2014 Time   Rev Time 0.00
Received By pleduc Date 12-04-2014 Time 15:44 Sent To  
Notes
2014-12-04 15:49:50THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 ALL CONSTRUCTION SHALL BE CONSISTENT WITH THE OCCUPANCY
 CODE REQUIREMENTS WITH THE LIFE SAFETY FEATURES FULLY
 INTERGRATED INTO THE MAIN OCCUPANCY'S SYSTEMS.
  

Review Stop L LANDSCAPING
Rev No 1 Status P Date 02-26-2015 Cont ID  
Sent By llouie Date 02-26-2015 Time   Rev Time  
Received By llouie Date 02-18-2015 Time   Sent To  
Notes
2015-02-26 16:42:31SUBJECT TO THE FOLLOWING CONDITIONS:
  
 1.) AT THE TIME OF FINAL LANDSCAPE INSPECTION, ALL
 GROUND MOUNTED UTILITY EQUIPMENT, INCLUDING, FPL, WATER
 AND PHONE SHALL BE SCREEN FROM PUBLIC VIEW.
  
 2.) AT THE TIME OF FINAL LANDSCAPE INSPECTION, ANY
 MISSING OR DEAD PLANTS IN ALL EXISTING HEDGES SHALL BE
 REPLACED.

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 02-26-2015 Cont ID  
Sent By llouie Date 02-26-2015 Time   Rev Time 0.00
Received By llouie Date 02-17-2015 Time   Sent To  
Notes
2015-02-26 16:25:46PASSED WITH THE FOLLOWING CONDITIONS:
  
 1.) AT THE TIME OF FINAL LANDSCAPE INSPECTION, ALL
 GROUND MOUNTED UTILITY EQUIPMENT, INCLUDING FPL, WATER
 AND PHONE SHALL BE SCREENED FROM PUBLIC VIEW.
  
 2.) AT THE TIME OF FINAL LANDSCAPE INSPECTION, ANY
 MISSING OR DEAD PLANS IN ALL EXISTING HEDGES SHALL BE
 REPLACED.

Review Stop Z ZONING
Rev No 2 Status F Date 01-30-2015 Cont ID  
Sent By llouie Date 01-30-2015 Time   Rev Time 0.00
Received By llouie Date 01-22-2015 Time   Sent To  
Notes
2015-01-30 11:25:09** FAILED **
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 SITE PLAN
  
 1.) PLEASE CHECK THE CALCULATIONS FOR THE FOLLOWING:
 GROSS BUILDING, FLOOR AREA RATIO, BUILDING AREA LOT
 COVERAGE. THE NUMBERS/CALCULATIONS SEEM TO BE
 INCORRECT.
  
 2.) CLARITY NEEDS TO BE PROVIDED TO THE "EXISTING"
 SQUARE FOOTAGE AND THE "PROPOSED" SQUARE FOOTAGE.
  
 3.) BASED ON STAFF'S CALCULATIONS, A MINIMUM OF 989
 SHARED PARKING SPACES WILL BE REQUIRED FOR THE SHOPPING
 CENTER. PLEASE ILLUSTRATE HOW THIS PARKING REQUIREMENT
 WILL BE MET ON THE PROPERTY. (NOTE: THE SURVEY SHOWS A
 TOTAL OF 974 PARKING SPACES ARE PROVIDED ON THE
 PROPERTY).
  
 4.) THE NOTE REGARDING THE 50 PERCENT REDUCTION IN
 RESTAURANT SHARED PARKING IS INCORRECT AND DOES NOT
 APPLY. PLEASE DELETE THE NOTE FROM THE TABLE AND REVISE
 THE CALCULATIONS ACCORDING TO THE CITY'S ZLDR PARKING
 REQUIREMENTS.
 THE 10.8% LANDSCAPE COVERAGE IS "PROPOSED" AND NOT
 "EXISTING."
  
 5.) CLARIFY THAT THE 1 PARKING SPACE PER 250 SQ. FT. IS
 THE PARKING REQUIREMENT FOR RETAIL USES.
  
 6.) REVIEW THE NUMBER OF HANDICAP PARKING SPACES
 PROVIDED ON THE PROPERTY. THERE SEEMS TO BE 27 SPACES
 PROVIDED AND NOT 25 SPACES AS NOTED IN THE DATA
 TABULAR.
  
 7.) CALCULATIONS FOR THE SHARED PARKING REQUIREMENT IS
 INACCURATE. PLEASE REVIEW AND CORRECT.
  
  
 LANDSCAPE PLAN:
  
 1.) CHECK ALL CALCULATIONS IN THE CODE COMPLIANCE
 TABLE. THE NUMBERS DO NOT ADD UP BASED ON INFORMATION
 PROVIDED IN THE EXISTING TREE PLAN AND THE PLANT LIST
 TABULAR.
  
 2.) PLEASE SHOW/CLARIFY HOW THE 325 REQUIRED TREES HAD
 BEEN DETERMINED IN THE CALCULATIONS.
  
 3.) A 5 FT. WIDE BUFFER STRIP SHALL BE PROVIDED ALONG
 THE ENTIRE EDGE OF THE PROPERTY. AT LEAST ONE (1) SHADE
 OR FLOWERING TREE SHALL BE PLANTED IN THE REQUIRED
 BUFFER STRIP FOR EACH LINEAR FEET; A HEDGE SHALL BE
 PLANTED AT 2 FT. INTERVALS. [ZLDR S.94-443, TABLE XIV]
  
 4.) ALL REQUIRED SHADE AND FLOWERING TREES SHALL
 POSSESS A MINIMUM OF 5 FT. OF CLEAR TRUNK SPACE. [ZLDR
 S.94-445(4)(A)]
  
 5.) THE LANDSCAPE PLAN DOES NOT MATCH THE CHANGES MADE
 TO THE SITE PLAN. THE NEW TRASH COMPACTOR AND LOADING
 ZONE ARE MISSING. PLEASE ADD THESE FEATURES TO MATCH
 THE SITE PLAN.
  
 6.) THE TRASH COMPACTOR SHALL BE SCREENED FROM VIEW.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD OR STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES AT 2 FT. INTERVALS. [ZLDR
 S.94-444(B)]
  
 7.) ADD VISIBILITY TRIANGLES IN ACCORDANCE WITH ZLDR S.
 94-305(E) AT ALL ACCESS POINTS. [REPEAT COMMENT]
  
 OTHER NOTES:
  
 1.) PRIOR TO THE REMOVAL OF ANY TREES ON THE PROPERTY,
 THE APPLICANT SHALL APPLY FOR AND OBTAIN A TREE
 ALTERATION PERMIT FROM THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION.
  
 RESUBMITTAL INSTRUCTIONS:
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX
 (6) PAPER COPIES, ONE (1) REDUCED COPY IN 8 1/2 INCHES
 X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES,
 AND AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT
 CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.

Review Stop Z ZONING
Rev No 1 Status F Date 12-05-2014 Cont ID  
Sent By llouie Date 12-05-2014 Time   Rev Time  
Received By llouie Date 12-05-2014 Time   Sent To  
Notes
2014-12-05 13:54:12GENERAL COMMENTS:
  
 1.) AN UPDATED SURVEY (<1 YEAR OLD) OF THE PROPERTY IS
 NEEDED TO EXAMINE THE EXISTING FEATURES IN THE AREA OF
 THE PROPOSED BUILDING ADDITION.
  
 2.) A LETTER FROM PALM BEACH COUNTY TRAFFIC DIVISION
 (561-684-4030), ESTABLISHING CONCURRENCY IS REQUIRED.
  
 3.) A LANDSCAPE PLAN, SHOWING THE PROPOSED LANDSCAPING
 IMPROVEMENTS SHALL BE SUBMITTED PRIOR TO FINAL APPROVAL
 OF THIS PROJECT.
  
  
 SITE PLAN COMMENTS:
  
 1.) PURSUANT TO THE DEVELOPMENT APPLICATION, PROVIDE A
 DATA TABLE WHICH INDICATES THE FOLLOWING:
 EXISTING/PROPOSED LAND USE AND ZONING; TOTAL ACRES OF
 THE PROJECT; TOTAL GROSS BUILDING SQUARE FOOTAGE;
 PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING COVERAGE
 AND IMPERMEABLE SURFACE; PARKING COMPUTATIONS (PARKING
 REQUIRED, PROVIDED, ETC.); LOT COVERAGE CALCULATIONS
 (BUILDING AREA; PARKING AND SIDEWALK; TOTAL IMPERVIOUS;
 TOTAL PERVIOUS, ETC.); FLOOR AREA RATIO (FAR).
  
 2.) PROVIDE TENANT INFORMATION, INCLUDING THE BREAKDOWN
 IN SQUARE FOOTAGE FOR EACH TENANT BAY AND OUTPARCEL
 BUILDING. INFORMATION IS NEEDED TO CALCULATE THE
 PARKING REQUIREMENTS FOR THE SITE.
  
 3.) THE PROPOSED ADDITION WILL GENERATE AN ADDITIONAL
 FOURTEEN (14) PARKING SPACES REQUIRED FOR THE SITE.
 ILLUSTRATE HOW THIS PARKING REQUIREMENT WILL BE MET IN
 THE PARKING CALCULATIONS AND IN THE SITE PLAN (IF
 NECESSARY).
  
 4.) SHOW DIMENSIONS FOR THE LOADING ZONE AREA. PURSUANT
 TO SECTION 94-485(P) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS A MINIMUM 10 FT. BY 50 FT. LOADING ZONE IS
 REQUIRED.
  
 5.) IDENTIFY THE LOCATION OF THE NEW TRASH COMPACTOR
 THAT WILL BE ELIMATED BY THE BUILDING ADDITION. PLEASE
 WORK WITH SANITATION ON AN APPROPRIATE LOCATION.
  
  
 LANDSCAPE COMMENTS:
  
 1.) PROVIDE TABULATION NECESSARY FOR THE EVALUATION OF
 COMPLIANCE WITH ARTICLE XIV (CLEARLY INDICATE THE
 AMOUNT OF PLANT MATERIAL THAT WILL BE REMOVED, ETC.)
  
 2.) SHOW THE LOCATION OF ALL EXISTING AND PROPOSED
 TREES, SHRUBS, GROUND COVERS, PLANT COMMUNITIES AND
 OTHER LANDSCAPE MATERIALS. IDENTIFY ALL PALMS AND/OR
 CANOPY TREES ON NEIGHBORING PROPERTY THAT ARE LOCATED
 IN CLOSE PROXIMITY TO THE SUBJECT PROPERTY.
  
 3.) SHOW THE LOCATION OF ALL UTILITY AND DRAINAGE
 EASEMENTS, OVERHEAD LINES, WATER METERS, TRANSFORMER
 CHECK VALVES, CLEAN-OUTS, FIRE HYDRANTS, LIGHT POLES
 AND OTHER STRUCTURES THAT MAY IMPACT LANDSCAPING.
  
 4.) ONE (1) SHADE TREE SHALL BE PLANTED FOR EACH 1,600
 SQ. FT. OF OPEN SPACE. [ZLDR S.94-442(B)(2)(B)]
  
 5.) ONE (1) FLOWERING TREE SHALL BE PLANTED FOR EACH
 6,400 SQ. FT. OF OPEN SPACE. [ZLDR S.94-442(B)(2)(B)]
  
 6.) ONE (1) SHRUB SHALL BE PLANTED FOR EACH 500 SQ. FT.
 OF OPEN SPACE. [ZLDR S.94-442(B)(2)(B)]
  
 7.) ALL LANDSCAPED AREAS AND PLANT MATERIALS WITHIN OR
 ADJACENT TO VEHICULAR USE AREAS SHALL BE PROTECTED FROM
 VEHICULAR ENCROACHMENT BY WHEEL STOPS OR A 2 FT. CURB
 OVERHANG ILLUSTRATED IN THE PLANS. [ZLDR
 S.94-442(B)(4)]
  
 8.) PALM TREES MAY NOT BE SUBSTITUTED FOR MORE THAN 35
 PERCENT OF THE SHADE OR FLOWERING TREES REQUIRED FOR
 THE SITE. PLEASE PROVIDE CALCULATIONS TO SHOW THAT THIS
 REQUIREMENT HAS BEEN MET. [ZLDR S.94-422(C)]
  
 9.) EACH TERMINAL ISLAND SHALL CONTAIN AT LEAST ONE (1)
 SHADE OR FLOWERING TREE. [ZLDR S.94-443(C)(3)(A)]
  
 10.) EACH INTERIOR ISLAND SHALL CONTAIN ONE (1) SHADE
 OR FLOWERING TREE. [ZLDR S.94-443(C)(3)(B)]
  
 11.) PROVIDE VISIBILITY TRIANGLES IN ACCORDANCE WITH
 ZLDR S.94-305(E)]
  
 12.) PRIOR TO THE REMOVAL OF ANY TREES ON THE PROPERTY,
 THE APPLICANT SHALL OBTAIN A TREE ALTERATION PERMIT
 FROM THE DEVELOPMENT SERVICES ? PLANNING DIVISION.
  
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX
 (6) COPIES, ONE (1) REDUCED COPY (8 1/2 BY 11), AND AN
 ELECTRONIC COPY IN .PNG FORMAT OF ALL PLANS. PLEASE
 NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% ($60) OF THE ORIGINAL APPLICATION FEE.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458, IF THERE ARE
 QUESTIONS.