Plan Review Details - Project Z14090017
Plan Review Stops For Project Z14090017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 10-07-2014 Cont ID  
Sent By rbrown Date 10-07-2014 Time 18:00 Rev Time 0.00
Received By rbrown Date 10-07-2014 Time 17:59 Sent To  
Notes
2014-10-07 18:13:58DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE AE. THE
 ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL
 ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS
 ETC.) SHALL BE 6 INCHES (FREEBOARD) ABOVE BASE FLOOD
 ELEVATION.
  
 3. PARKING GARAGE STAIRWELLS. ON SHEETS A2.02 AND A2.04
 THE TWO PARKING GARAGE STAIRWELLS ARE CURRENTLY SHOWN
 WITH NO DOORS TO PROTECT THE STAIRWELLS AT THE 2ND AND
 3RD FLOORS.
  
 4. PARKING GARAGE ELEVATOR VESTIBULE. ON SHEET A2.04
 THE 3RD FLOOR ELEVATOR VESTIBULE IS CURRENTLY SHOWN
 WITH NO DOORS TO PROTECT THE ELEVATOR SHAFT.
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 6. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 7. IF THE PARKING GARAGE DOES NOT HAVE WALL OPENINGS,
 OR SUFFICIENT WALL OPENINGS TO MEET THE DEFINITION OF
 AN OPEN PARKING GARAGE, IT WILL BE CONSIDERED AN
 ENCLOSED PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS.
 THE EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE
 LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED
 METHODS.
  
 8. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK. SEPARATE PERMITS,
 PLANS AND FEES, ARE REQUIRED FOR SWIMMING POOLS AND
 SPAS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 09-30-2014 Cont ID  
Sent By cranford Date 09-30-2014 Time 12:45 Rev Time 0.00
Received By cranford Date 09-30-2014 Time 10:18 Sent To  
Notes
2014-09-30 10:43:22ENGINEERING/PUBLIC WORKS DEPT.
 LAND DEVELOPMENT AND STORMWATER
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION DETAILS
 WILL BE REVIEWED AS PART OF THE ENGINEERING DEVELOPMENT
 APPROVAL AND BUILDING PERMIT APPLICATION PROCESSES. THE
 APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. PLEASE REVISE THE DRIVEWAY APRONS TO MEET THE CITY'S
 ENGINEERING DESIGN STANDARDS. PLEASE ALSO INCLUDE THE
 DETAILS FOR THE SIDEWALK RAMPS, HTTP://WPB.ORG/ENGINEER
 ING/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/
  
 2. SHOW CROSS-SECTIONS SHOWING THE PROPOSED GRADING
 ALONG FLAGLER DRIVE AND ARKONA CT.
  
 3. INDICATE WHICH PORTIONS OF THE POTABLE WATER,
 SANITARY SEWER, AND STORMWATER SYSTEM WILL REMAIN
 PUBLICALLY OWNED AND WHICH SECTIONS WILL BE MAINTAINED
 BY THE APPLICANT.
  
 4. REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS OF ALL
 WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC.
 ROOT BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE NEAR
 UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER
 LINES.
  
 5. . WATER METERS ARE PROPERTY OF THE CITY. THEREFORE,
 METERS ARE TO BE LOCATED IN THE RIGHT-OFWAY UNLESS
 SHOWN ON THE PLANS JUST INSIDE THE PROPERTY, WITHIN AN
 EASEMENT. IF THE METER(S) ARE TO BE LOCATED WITHIN AN
 EASEMENT, A SKETCH AND LEGAL DESCRIPTION WILL BE
 REQUIRED.
  
 6. VERIFY THAT THE PROPOSED SIZE AND QUANTITY OF TRASH
 BINS IS APPROPRIATE FOR THE WASTE YARDAGE ANTICIPATED
 TO BE GENERATED BY THE COMPLEX. CONSIDER USING A
 COMPACTOR TO REDUCE THE YARDAGE OF WASTE THAT WILL NEED
 TO BE COLLECTED.
  
 7. THE PROJECT MUST PROVIDE ADEQUATE STORMWATER
 MANAGEMENT, INCLUDING NOT MODIFYING THE VELOCITY OR
 VOLUME OF OFF-SITE STORMWATER DISCHARGE. DESCRIBE HOW
 THIS WILL BE ACHIEVED. COMPLIANCE WITH CHAPTER 40E-4
 FAC WILL DEMONSTRATE COMPLIANCE WITH THIS PROVISION.
 [CODE OF ORDINANCES SECTIONS 90-201, 94-35(C )(11),
 94-307, AND 94-580] THE CALCULATIONS SHOULD ADDRESS THE
 IMPACT OF THE ROOF-DRAIN VELOCITY AND SEEPAGE FROM THE
 ADJOINING PROPERTIES THROUGH THE PROPOSED RETAINING
 WALLS.
  
 8. THE TRASH DUMPSTER/COMPACTORS MUST LOCATED IN AREAS
 EASILY SERVICED BY THE CITY SANITATION EQUIPMENT AND
 MANPOWER. HOW WILL THE DUMPSTER AREA BE ACCESSED BY
 CITY SANITATION CREWS? (SECTION 74-35(A)(5) OF THE CODE
 OF ORDINANCES.)
  
 9. PROVIDE VERTICAL PROFILES FOR THE PARKING GARAGE
 RAMPS INCLUDING THE TRANSITION AREA GEOMETRY.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED IN THE
 CONSTRUCTION PLANS SUBMITTED FOR DEVELOPMENT APPROVAL
 FROM THE ENGINEERING DEPARTMENT.
  
 1. COORDINATE THE BACKFLOW PREVENTER LOCATIONS WITH THE
 ARCHITECT AND OWNER. THEY ARE AN ABOVE GROUND FEATURE
 AND COULD DISTURB THEIR VIEW OR BE IN CONFLICT WITH THE
 VISUAL DESIGN OF THE SITE.
  
 2. THE AVAILABLE WATER PRESSURE WITHIN THE CITY MAY NOT
 BE ACCEPTABLE AT ELEVATIONS HIGHER THAN THE 2ND FLOOR.
 WE RECOMMEND THAT A LONG-TERM PRESSURE STUDY BE
 PERFORMED ON THE POTABLE WATER LINES PRIOR TO
 FINALIZATION OF THE DESIGN.
  
 3. SEWAGE DEMAND CALCULATIONS WILL NEED TO BE PROVIDED
 AS PART OF THE FINAL DESIGN. THE CONDITION OF THE
 EXISTING SERVICE LATERAL AND MANHOLE MAY NOT BE
 SUFFICIENT FOR THE PROPOSED DEMAND AND MAY NEED TO BE
 REPLACED. WE RECOMMEND AN INSPECTION OF THE EXISTING
 SYSTEM BE REQUESTED FROM OUR OPERATION AND MAINTENANCE
 DIVISION PRIOR TO FINALIZING THE DESIGN.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 10-07-2014 Cont ID  
Sent By eschneid Date 10-07-2014 Time 11:12 Rev Time 0.00
Received By eschneid Date 10-07-2014 Time 11:12 Sent To  
Notes
2014-10-07 11:13:43THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. PAY CLOSE ATTENTION TO THE SEPARATION
 DIMENSIONS OF ANY CONSTRUCTION TRAILERS AS FIRE
 SPRINKLERS MAY BE REQUIRED.
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE
 SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY,
 CHAPTER 30, NEW APARTMENTS.
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
 7. THE SEPARATION AND OPENING PROTECTION BETWEEN THE
 PARKING GARAGE AND HOTEL SHALL BE IN ACCORDANCE AND
 COMPLIANCE WITH THE SPECIFIC AND MOST STRINGENT
 PROVISION REQUIREMENT OF EITHER CHAPTER.
 8. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE, INCLUDING THE PARKING GARAGE. TEMPORARY
 STANDPIPES ARE REQUIRED WHEN THE BUILDING REACHES THREE
 LEVELS OR THIRTY FEET WHILE BEING CONSTRUCTED. SEPARATE
 SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED
 AND APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
 9. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
 10. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
 11. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
 12. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY
 INDICATED ON THE BUILDING PLAN.
 13. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 14. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
 16. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN.
 17. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 18. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 19. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 20. OFF STREET ACCESS TO THE FIRE PUMP ROOM IS
 REQUIRED. THE LOCATION OF THE DOOR INSIDE THE GARAGE
 AREA IS NOT APPROVED.
  
 21. BOTH STAIRWELLS OF THE PARKING GARAGE APPEAR TO BE
 UNPROTECTED. NO DOOR IS SHOWN AT THE STAIRWELL
 ENTRANCE.
  
 22. THE VESTIBULE DOOR AREAS OF THE PARKING GARAGE AREA
 SHALL BE PROTECTED FROM VEHICULAR TRAFFIC WITH
 BOLLARDS.
  
 23. THE VESTIBULE ON THE THIRD FLOOR OF THE PARKING
 GARAGE DOES NOT SHOW DOORS.
  
 24. ALL UNDERGROUND FIRE LINE WORK REQUIRES AN
 INSPECTION BY THE BUREAU OF FIRE PREVENTION.
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-10-08 12:34:51SEE ZONING REVIEW

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 10-02-2014 Cont ID  
Sent By vnoel Date 10-02-2014 Time 13:16 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2014-10-02 13:16:441. REPLAT WILL BE REQUIRED. SEPARATE SUBMITTAL FOR
 TECHNICAL REVIEW TO ENGINEERING SERVICES.
 2. UTILITY EASEMENT IN REAR OF PARCELS 1 & 2 WILL NEED
 TO BE ABANDONED.
 3. PLEASE NOTE THAT ARKONA COURT IS SUBJECT TO A
 MAINTENANCE MAP IN ROAD PLAT BOOK 9, PG. 3.
 4. SEPARATE SUBMITTAL TO ENGINEERING SERVICES FOR
 SITE/CIVIL REVIEW IS REQUIRED.
 5. HOW IS GARBAGE BEING PLANNED FOR COLLECTION? WRITTEN
 APPROVAL FROM FERDINAND RIVERA WILL BE REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 10-08-2014 Time   Rev Time 0.00
Received By bcollins Date 10-08-2014 Time 07:51 Sent To  
Notes
2014-10-08 07:55:411. REFERENCED TRAFFIC STUDY RECEIVED AND UNDER REVIEW.
 PLEASE NOTE THAT THIS IS AN IMMEDIATE AREA IMPACT STUDY
 NOT A CONCURRENCY STUDY.
 2. HOW DOES DROP OFF WORK?
 3. HOW DOES LOADING WORK? DO TRUCKS HAVE TO BACK UP
 INTO STREET. PROVIDE AUTOTURN FOR ALL TRUCK, INCLUDING
 GARBAGE TRUCKS, MOVEMENTS TO AND FROM THE SITE.

Review Stop Z ZONING
Rev No 1 Status F Date 10-08-2014 Cont ID  
Sent By eschneid Date 10-08-2014 Time 08:42 Rev Time 6.00
Received By eschneid Date 10-06-2014 Time 13:45 Sent To  
Notes
2014-10-08 08:42:13CASE NO. PB 1559G
 FIFTEEN 15 RPD
 1515 S. FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 OCTOBER 17, 2014, TO BE SCHEDULED FOR THE NOVEMBER 18,
 2014 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY DECEMBER 8,
 2014), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR).
  
 1) IS THE NAME OF THE FIFTEEN 15 OR 15 FIFTEEN? BOTH
 ARE USED.
  
 2) THE PROPOSED DENSITY OF 69.8 DWELLING UNITS PER ACRE
 IS INCONSISTENT WITH MAXIMUM PERMITTED DENSITY IN
 ACCORDANCE WITH SECTION 94-207(A)(1)B OF THE ZLDR.
  
 3) THE JUSTIFICATION STATEMENT INCORRECTLY STATES THAT
 THE CURRENTLY APPROVED RPD INCLUDES 87 DWELLING UNITS.
 THERE ARE ONLY 84 DWELLING UNITS APPROVED. THE THREE
 GUEST UNITS MAY NOT BE COUNTED AS DWELLING UNITS AS
 THEY ARE PROHIBITED FROM HAVING KITCHEN FACILITIES, AND
 THEREFORE ARE NOT DWELLING UNITS. ALL CALCULATIONS
 BASED ON 87 UNITS SHALL BE CORRECTED.
  
 4) THE JUSTIFICATION STATEMENT INCORRECTLY STATES THAT
 THE ZLDR HAVE BEEN AMENDED TO NO LONGER REQUIRE A
 MINIMUM LOT SIZE FOR RPDS.
  
 5) ANY EASEMENTS CONFLICTING WITH THE PROPOSED BUILDING
 WILL NEED TO BE ABANDONED PRIOR TO CONSTRUCTION.
  
 6) THE BASE CIVIL, ARCHITECTURAL AND LANDSCAPE PLANS DO
 NOT ALL MATCH. EX. THE STAIRWELL NEXT TO THE BIKE
 STORAGE ROOM.
  
 7) PROVIDE DIMENSION LINES TO THE BALCONIES.
  
 8) THE APPLICATION IS REQUESTING A PARKING WAIVER. THE
 JUSTIFICATION PROVIDED FOR THE PARKING WAIVER IS
 INSUFFICIENT FOR THE CITY'S PLANNING DIVISION TO
 CONSIDER SUPPORTING A WAIVER. THE RESPONSE TO CRITERIA
 2 IMPLIES THAT THE PROVISION OF FEWER PARKING SPACES
 THAN ARE REQUIRED MAKES THE PROPOSED PROJECT CONFORM TO
 THE CONCEPTS OF NEW URBANISM, WHICH IS AN INACCURATE
 SUPPOSITION. THE RESPONSE TO CRITERIA 3 DOES NOT
 PROVIDE SPECIFIC EVIDENCE OR STUDIES, BUT RATHER STATES
 IN PARKING WAIVERS HAVE BEEN GRANTED WITHOUT PRESENTING
 WHERE AND FOR WHAT TYPE OF PROJECT THE WAIVERS WERE
 GRANTED. WHILE CRITERIA 4 AND 5 WERE NOT USED, THE
 APPLICATION INCORRECTLY STATES THAT THERE IS PARKING
 THAT COULD COMPLY WITH THE CRITERIA.
  
 9) THE ECONOMIC IMPACT ANALYSIS ESTIMATES THAT 8 FULL
 TIME WORKERS WILL BE NEEDED TO OPERATE THE RENTAL
 APARTMENT BUILDING. A PARKING SPACE SHALL BE PROVIDED
 FOR EACH OF THESE WORKERS IN ADDITION TO THE PARKING
 REQUIRED FOR THE RESIDENTS AND GUESTS.
  
 10) THE REQUIRED PARKING TABLE SHALL BE BROKEN DOWN TO
 SHOW ONE BEDROOM, TWO BEDROOM, GUEST, HC, ETC.
 REQUIREMENTS.
  
 11) THE PROJECT DOES NOT PROVIDE SUFFICIENT ADA SPACES
 FOR THE TOTAL NUMBER OF SPACES PROVIDED.
  
 12) THE SITE PLAN SHALL INCLUDE PARKING NUMBER TAGS FOR
 EACH ROW OF PARKING AND DIMENSION LINES FOR EACH
 PARKING ROW (DEPTH AND LENGTH) AND DRIVE AISLE.
  
 13) THERE ARE EIGHT PARKING SPACES THAT ARE NOT USABLE
 DUE TO THE COLUMN PLACEMENT, TO INCLUDE ONE ADA SPACE.
  
 14) THE PARKING TABLE STATES THERE ARE FOUR COMPACT
 SPACES IN THE GARAGE. THESE SHALL BE CLEARLY DESIGNATED
 ON THE PLANS.
  
 15) PROVIDE A TURNING RADIUS DIAGRAM FOR THE RAMP TO
 THE SOUTH OLIVE ACCESS POINT AND ON EACH FLOOR. SOME OF
 THE PARKING SPACES LOOK LIKE THEY WILL NOT FUNCTION DUE
 TO PROXIMITY TO THE TURN.
  
 16) PROVIDE THE WIDTHS OF ALL OF THE DRIVE AISLES AND
 SITE INGRESS/EGRESS POINTS ON THE PLANS.
  
 17) WHEEL STOPS ARE REQUIRED AT THE HEAD OF ALL THE
 PARKING SPACES WHICH ABOUT THE BUILDING OR GARAGE
 WALLS, COLUMNS, ETC.
  
 18) USING A DIAGRAM, PLEASE SHOW HOW THE DROP OFF WILL
 WORK IN FRONT OF THE BUILDING GIVEN THE GEOMETRY OF THE
 AREA. ADDITIONALLY, HOW WILL FIRST TIME USERS BE
 STOPPED FROM DRIVING TOO FAR FORWARD AND THEN HAVING TO
 BACK DOWN THE ENTRY DRIVE TO PULL INTO THE MOTOR COURT?
  
 19) PLEASE CLEARLY DELINEATE THE PATH FROM THE ADA
 PARKING SPACE IN THE MOTOR COURT TO THE FRONT DOOR OF
 THE BUILDING.
  
 20) BICYCLE PARKING IS REQUIRED FOR THIS PROJECT.
 PROVIDE THE BICYCLE PARKING TABLE. SHOW THE BICYCLE
 PARKING LOCATIONS ON THE PLAN AND INCLUDE A BICYCLE
 PARKING DETAIL WHICH INCLUDES THE PAD AND THE TYPE OF
 RACK USED.
  
 21) IS IT CORRECT THAT RESIDENTS ON THE SECOND FLOOR
 NEED TO WALK THROUGH THE ELEVATOR TO GET TO THEIR UNITS
 IF PARKED ON THE SECOND LEVEL OF THE PARKING GARAGE?
 PLEASE EXPLAIN HOW THAT TIMING WORKS.
  
 22) THE PLANS DO NOT SHOW ACCESS FROM THE TOP LEVEL OF
 THE GARAGE TO THE ELEVATORS.
  
 23) THE PLANS ARE DIFFICULT TO READ. THE HEDGE AND
 GROUND COVER LAYERS SHALL BE TURNED OFF ON THE SITE AND
 CIVIL PLANS AS BLACK OUT MANY OF THE FEATURES SUCH AS
 TREE AND UTILITY LOCATIONS.
  
 24) A SIDEWALK EASEMENT WILL BE REQUIRED FOR THE
 PORTION OF THE SIDEWALK ALONG ARKONA CT. ON THE SITE.
  
 25) PLEASE CLEARLY DELINEATE THE ADA PATH FROM THE
 ARKONA COURT SIDEWALK TO THE FRONT DOOR OF THE
 BUILDING.
  
 26) HOW DO RESIDENTS ACCESS FLAGLER DRIVE FROM THE BIKE
 STORAGE AREA WITH THEIR BICYCLES OR FROM THE FITNESS
 AREA IN THEIR WORKOUT ATTIRE? THERE IS NO DIRECT
 WALKWAY ACCESS FROM THESE AREAS TO FLAGLER DRIVE. THE
 EXIT DOOR ON THE SOUTH SIDE OF THE BIKE STORAGE AREA
 OPENS INTO A PLANTING BED. A LACK OF RESIDENT
 PEDESTRIAN ACCESS ALL OF THE SURROUNDING STREETS DOES
 NOT SUPPORT THE STATEMENT THAT THIS PROJECT FOLLOWS NEW
 URBAN CONCEPTS.
  
 27) PLEASE CONSIDER A WALKWAY FROM THE DOORWAYS ALONG
 THE EAST SIDE OF THE BUILDING TO FLAGLER DRIVE. A LACK
 OF RESIDENT PEDESTRIAN ACCESS ALL OF THE SURROUNDING
 STREETS DOES NOT SUPPORT THE STATEMENT THAT THIS
 PROJECT FOLLOWS NEW URBAN CONCEPTS.
  
 28) PROVIDE DIMENSIONS FOR THE WALKWAYS SHOWN ON THE
 SITE PLAN.
  
 29) THE UPPER PARKING DECK SITE PLAN SHALL SHOW THE
 LIGHT POLE LOCATIONS.
  
 30) PROVIDE DETAILS OF THE LIGHT POLES AND FIXTURES.
 WHY DO THESE NEED TO BE SO TALL? THEY BADLY DETRACT
 FROM THE ARCHITECTURE OF THE BUILDING.
  
 31) PROVIDE A PHOTOMETRIC PLAN IN ACCORDANCE WITH CITY
 REQUIREMENTS.
  
 32) HOW ARE THE TRASH RECEPTACLES PICKED UP?
  
 33) IS TRASH AREA COVERED?
  
 34) FENCE, WALL AND GATE DETAILS, TO INCLUDE HEIGHT.
 PLEASE NOTE THAT THE WALLS LOCATED WITHIN THE SETBACK
 ALONG ARKONA CT., FLAGLER DRIVE AND S. OLIVE AVENUE MAY
 NOT EXCEED SIX (6) FEET IN HEIGHT. A SIX (6) FOOT HIGH
 WALL ALONG THE STREET FRONTAGES DOES NOT FOLLOW NEW
 URBAN CONCEPTS.
  
 35) THE WALL ALONG VIKING ARMS IS LISTED AT SIX (6)
 FEET TALL, BUT EYEBALLS AT HIGHER THAN THIS ON SHEET
 C2.00. PLEASE BE AWARE THAT THE MEASURE IS FROM THE
 OUTSIDE GRADE.
  
 36) WHY IS THERE A GATE ALONG SOUTH OLIVE AVENUE AT THE
 SOUTHWEST CORNER OF THE SITE, WHEN THE DRIVEWAY THAT IS
 15 FEET AWAY HAS NO GATE?
  
 37) THE SITE DESIGN FLEXIBILITY TABLE TAKES CREDIT FOR
 BERMS TO ACT AS SCREENING. NO CROSS SECTIONS WERE
 PROVIDED TO SHOW HOW THE BERMS FUNCTION. FURTHERMORE,
 IF BERMS ARE USED, THE PROJECT IS NOT ADHERING TO NEW
 URBAN CONCEPTS.
  
 38) PLEASE PROVIDE THE DATA TO VERIFY THE POINTS
 CLAIMED IN THE SITE FLEXIBILITY TABLE ON THE PLANS.
  
 39) THE TRANSFORMER PADS AND THE BACKFLOW PREVENTERS
 AND METERS NEED TO BE SCREENED FROM ARKONA COURT.
  
 40) THE LANDSCAPE PLAN SHALL SHOW THE UTILITY LINES,
 BACKFLOW PREVENTER, ETC., AND THERE SHALL BE NO
 CONFLICTS. PLEASE NOTE THAT THE BACKFLOW PREVENTER AND
 THE METERS APPEAR TO BE CONFLICTING WITH TREES.
  
 41) THE OPEN SPACE TABLE FOR SHADE TREES SHALL NOT
 INCLUDE THE FLOWERING TREES AS THESE ARE SEPARATE
 ITEMS.
  
 42) PLEASE EXPLAIN WHY NOT ALL THE TREES PROVIDED IN
 THE BUFFERS ARE COUNTED TO MEET THE BUFFER TREE
 REQUIREMENTS. A COUNT BY STAFF INDICATES THAT THE
 BUFFER TREE REQUIREMENTS ARE MET WITHOUT THE NEED TO
 COUNT ANY PALMS, OR AT WORST LESS THAN 35% OF ANY
 BUFFER IS PLANTED WITH PALMS.
  
 43) THE OPEN SPACE SHRUB REQUIREMENTS AND PROVIDED
 TABLE IS NEEDED.
  
 44) THE SHRUBS USED AS HEDGE MATERIAL NEED TO BE CALLED
 OUT AS INSTALLED AT A MINIMUM OF 24 INCHES IN HEIGHT,
 NOT BY CONTAINER SIZE.
  
 45) HOW IS THE LANDSCAPE IN THE ENTRY DRIVE AND THE
 MOTOR COURT PROTECTED FROM VEHICULAR ENCROACHMENT?
  
 46) PROVIDE A TABLE SHOWING COMPLIANCE WITH THE
 MULTIFAMILY FOUNDATION PLANTING REQUIREMENTS FOUND IN
 SECTION 94-443(D)(2) OF THE ZLDR.
  
 47) THE REQUIRED LANDSCAPE BUFFER ALONG THE SOUTH OLIVE
 AVENUE RIGHT-OF-WAY IS INTERRUPTED BY MORE THAN THE
 PERMITTED 20% AND THEREFOR REQUIRES A WAIVER.
  
 48) PROVIDE HOW THE SITE MEETS THE MITIGATION
 REQUIREMENTS AND CONDITIONS FROM THE PREVIOUSLY
 APPROVED TREE ALTERATION PERMITS AND MITIGATES ANY
 TREES NOT PREVIOUSLY INCLUDED.
  
 49) PROVIDE DETAILS ON THE SIGNAGE.
  
 50) IN ACCORDANCE WITH THE COMMENTS FROM THE
 NEIGHBORHOOD MEETINGS, PLEASE PROVIDE INFORMATION ON
 HOW THE CARS ON THE ROOF WILL BE SCREENED FROM VIEW
 FROM ABOVE.
  