Plan Review Details - Project Z14070023
Plan Review Stops For Project Z14070023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 08-13-2014 Cont ID  
Sent By rbrown Date 08-13-2014 Time 11:35 Rev Time 0.00
Received By rbrown Date 08-13-2014 Time 11:34 Sent To  
Notes
2014-08-13 11:40:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACESSIBLE PARKING. BASED ON THE PLANS SUBMITTED IT
 APPEARS THAT NO EXISTING ACCESSIBLE PARKING WILL BE
 REMOVED OR REPLACED AS PART OF THIS PROJECT, AND THAT
 TWO ADDITIONAL ACCESSIBLE PARKING SPACES ARE BEING
 PROVIDED. PLEASE CONFIRM THAT TO BE THAT CASE SO THAT
 THE FOLLOWING BUILDING CODE SECTION WILL NOT BE
 APPLICABLE. IF APPLICABLE, PER SECTION 208.3 OF FLORIDA
 ACCESSIBILITY CODE ACCESSIBLE PARKING SPACES ARE TO BE
 LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH
 BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE.
  
 3. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-04-2014 Cont ID  
Sent By cranford Date 08-04-2014 Time 14:39 Rev Time 0.00
Received By pleduc Date 08-01-2014 Time 09:17 Sent To  
Notes
2014-08-04 14:27:50THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PARKING AND/OR THE DRIVE THROUGH LANE.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 6. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 7. THE PROPOSED OCCUPANCY SHALL COMPLY WITH THE
 APPROPRIATE CHAPTER OF THE 2010 FLORIDA FIRE PREVENTION
 CODE IF SUBMITTED FOR PERMIT PRIOR TO DECEMBER 31,
 2014. THE 2013 EDITION THEREAFFTER.
  
  
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 08-01-2014 Cont ID  
Sent By cranford Date 08-01-2014 Time 09:17 Rev Time 1.00
Received By cranford Date 08-01-2014 Time 09:16 Sent To  
Notes
2014-08-01 09:13:39NO OBJECTIONS TO NEW CONFIGURATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-04-2014 Cont ID  
Sent By   Date 08-04-2014 Time   Rev Time 0.00
Received By pleduc Date 08-04-2014 Time 14:09 Sent To  
Notes
2014-11-14 11:29:01THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PARKING AND/OR THE DRIVE THROUGH LANE.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 6. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
  
 7. THE PROPOSED OCCUPANCY SHALL COMPLY WITH THE
 APPROPRIATE CHAPTER OF THE 2010 FLORIDA FIRE PREVENTION
 CODE IF SUBMITTED FOR PERMIT PRIOR TO DECEMBER 31,
 2014. THE 2013 EDITION THEREAFFTER.
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status F Date 08-12-2014 Cont ID  
Sent By ssamuels Date 08-12-2014 Time 16:56 Rev Time 0.00
Received By ssamuels Date 08-12-2014 Time 16:56 Sent To  
Notes
2014-08-12 17:01:02PARKING DEPT
 SEAN SAMUELS
 PARKING FACILITY SUPERVISOR
  
 Z - 14070023
  
 PLEASE SHOW DIRECTIONAL ARROW ON SITE PLAN.
  
 ANGLE PARKING FOR H.C STALL ARE NOT SHOWING LENGHT OR
 ACCESS AISLE SIZE.

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 08-07-2014 Cont ID  
Sent By Jackson Date 08-07-2014 Time   Rev Time 0.00
Received By   Date 08-07-2014 Time   Sent To  
Notes
2014-08-11 16:18:54AUGUSUT 7, 2014
  
  
  
  
 GREASE INTERCEPTOR WAS INSPECTED BY IPP STAFF ON AUGUST
 7, 2014. BELOW ARE THEIR COMMENTS.
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  
  
 GOOD AFTERNOON JACKSON,
  
 THE ABOVE-REFERENCED ADDRESS WAS FORMERLY A CHINESE
 RESTAURANT (CHINA STAR #5). THE LAST PUMP-OUT PERFORMED
 ON THE GREASE INTERCEPTOR WAS OCTOBER 15, 2013.
 ACCORDING TO SANDRA'S NOTES IN THE DATABASE, THE
 INTERCEPTOR (STRUCTURE) IS IN GOOD CONDITION. WE OPENED
 THE INTERCEPTOR (SEE ATTACHED PICTURE) AND IT NEEDS TO
 BE PUMPED OUT BEFORE ANOTHER BUSINESS COMES IN AND
 BEGINS OPERATION. THE TOP LAYER IS VERY HARD AND THE
 INLET PIPE (COMING FROM THE RESTAURANT), APPEARS
 PARTIALLY CLOGGED.
  
 OCTOBER 15, 2013 IS THE ONLY PUMP-OUT EVENT ON FILE FOR
 THIS INTERCEPTOR.
  
  
  
 SINCERELY,
  
 JOCELYN BROWN
 IPP SUPERVISOR
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-2172
 CELL: (561) 662-0215
 EMAIL: [email protected]
  
  
  
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 08-12-2014 Cont ID  
Sent By tward Date 08-12-2014 Time 15:19 Rev Time  
Received By tward Date 08-12-2014 Time   Sent To  
Notes
2014-08-12 15:28:371. SHOW UTILITIES ON LANDSCAPE PLAN.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 08-05-2014 Cont ID  
Sent By vnoel Date 08-05-2014 Time 09:02 Rev Time  
Received By vnoel Date 08-05-2014 Time   Sent To  
Notes
2014-08-05 09:03:45PASSED, BUT APPROVAL FROM FERDINAND RIVERA, SANITATION
 SUPERVISOR, IS REQUIRED FOR DUMPSTER LOCATION.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-07-2014 Cont ID  
Sent By   Date 08-07-2014 Time   Rev Time 0.00
Received By bcollins Date 08-07-2014 Time 08:03 Sent To  
Notes
2014-08-07 08:10:09THE LAST 2-3 PARKING SPACES ON THE EAST END OF THE
 PARKING ADJACENT TO 45TH STREET ARE PROBLEMMATIC.
 VEHICLES WILL BE BACKING OUT OF THESE SPACES INTO
 TRAFFIC THAT IS MAKING A 90 DEGREE TURN SUCH THAT
 VISIBILITY MAY BE RESTRICTED. A STOP BAR AND STOP SIGN
 SHOULD BE INSTALLED AT THE EXIT FROM THE PARKING
 ADJACENT TO 45TH STREET. CONGRESS AVENUE AND 45TH
 STREET ARE BOTH COUNTY MAINTAINED ROADS.

Review Stop Z ZONING
Rev No 1 Status F Date 08-07-2014 Cont ID  
Sent By jroach Date 08-07-2014 Time 10:46 Rev Time 0.00
Received By jroach Date 08-07-2014 Time 10:46 Sent To  
Notes
2014-08-07 10:46:57ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.07.2014
 PROJECT NO.: Z14070023
 CASE NO.: PB 785G
 ADDRESS: 2100 45TH STREET
 APPLICANT/CONTACT: CHRIS TRAIKOFF
 TELEPHONE NO.: 561.684.6141
 SCOPE OF REVIEW: CONVERSION OF EXISTING RESTAURANT INTO
 DRIVE-THRU AND ASSOCIATED SITE IMPROVEMENTS.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. UTILITY LETTERS SHALL BE PROVIDED.
  
 2. THERE ARE CONCERNS WITH REGARD TO THE AMOUNT OF
 STACKING. DO CUSTOMERS ORDER AT THE WINDOW, OR IS THERE
 A CALL BOX? STACKING SHOULD NOT BACK UP INTO THE NEARBY
 TRAVEL LANES.
  
 3. BECAUSE OF THE NEW PARKING SPACES BEING PLACED AT AN
 ANGLE, THE PROPOSED HANDICAP SPACES ARE TOO SHORT.
  
 4. THE CURBING IN THE NORTHEAST CORNER OF THE SITE
 SHOULD BE RECONFIGURED TO CONVERT THE STRIPED AREA INTO
 ADDITIONAL LANDSCAPING.
  
 5. A TURN-AROUND SPACE WILL NEED TO BE PROVIDED IN THE
 PARKING ROW FRONTING 45TH STREET AS THIS HAS NOW BECOME
 A DEAD-END PARKING ROW.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  