Plan Review Details - Project Z14070022
| Plan Review Stops For Project Z14070022 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:33:26 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
08-13-2014 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-13-2014 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-13-2014 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2014-08-13 12:16:08 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW | | | ADEQUATE EGRESS FROM THE WAREHOUSE BUILDING. AT THIS | | | STAGE THERE DOES NOT APPEAR TO BE ENOUGH EXIT DOORS | | | FROM THE WAREHOUSE SPACE TO MEET THE REQUIREMENTS, OF | | | CHAPTER 10 OF THE FLORIDA BUILDING CODE, FOR MAXIMUM | | | COMMON PATH OF TRAVEL AND MINIMUM SPACING OF EXITS. | | | | | | 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL | | | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS | | | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND | | | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA | | | BUILDING CODE | | | | | | 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH | | | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND | | | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF | | | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. | | | | | | 5. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE | | | OBTAINED BEFORE COMMENCING THE WORK. | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2014-08-04 16:12:35 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 | | | TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM | | | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH | | | TABLE 4.2.1. PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF 150 | | | FEET IN LENGTH SHALL BE PROVIDED WITH APPROVED | | | PROVISIONS FOR THE FIRE APPARATUS TO TURN AROUND. | | | PROVIDE DETAILED | | | DIMENSIONS SHOWING A 50FT CENTERLINE RADIUS, A T-TURN | | | OR Y-TURN WITH THE EXTENSION TO BE A MINIMUM 50FT FROM | | | THE EDGE OF THE ROADWAY | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE | | | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF | | | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. ALL CONSTRUCTION SHALL COMPLY WITH THE 2010 EDITION | | | OF THE FLORIDA FIRE PREVENTION CODE, | | | | | | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. | | | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE | | | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 | | | OF NFPA 101 | | | FLORIDA EDITION 2009. FOR NON-SEPARATED MIXED USE | | | OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY | | | REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE | | | BUILDING. | | | | | | 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 7. A MONITORED NFPA 72 COMPLAINT FIRE ALARM SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION | | | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. | | | | | | 8. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY | | | ILLUSTRATED ON THE PLAN. | | | | | | 9. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING | | | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. | | | | | | 10. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | 11. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, DEAD-END CORRIDORS, FIRE RATED WALLS, EXIT | | | SIGNS, EMERGENCY LIGHTING, COMMON PATHS OF TRAVEL ETC. | | | | | | 12. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR | | | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR | | | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE | | | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY | | | DOOR. | | | | | | 13. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | 14. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS SIDE. | | | | | | 15. A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN | | | ENTRY DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN | | | ENTRY IS PERMITTED TO BE EQUIPPED WITH A KEYED LOCK | | | WITH LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING | | | THE DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. | | | NO OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. | | | THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? | | | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). | | | | | | 16. ONE FIRE HYDRANT IS PROPOSED FOR THIS BUILDING. | | | PLEASE PROVIDE DETAILED INFORMATION REGARDING THE | | | NEEDED FIRE FLOW FOR THIS PROPOSED PROJECT AND THAT THE | | | ONE HYDRANT MEETS THE REQUIREMENT. | | | | | | 17. THE PROPOSED LOCATION OF THE HYDRANT AND FDC MAY | | | CREATE A BOTTLE-NECK TYPE SITUATION LIMITING THE | | | ARRIVAL OF ADDITIONAL FIRE UNITS. ALTERNATIVE LOCATIONS | | | SHOULD BE PROPOSED FOR CONSIDERATION. CLOSE | | | COORDINATION WITH THE FIRE PREVENTION BUREAU IS | | | STRONGLY ENCOURAGED. | | | | | | | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:33:48 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
P |
Date |
08-01-2014 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-01-2014 |
Time |
09:28 |
Rev Time |
2.00 |
| Received By |
cranford |
Date |
08-01-2014 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2014-08-01 09:27:52 | 1. REVISE PLAN TO SHOW INGRESS/EGRESS EASEMENT FOR THE | | | CITY TO ACCESS TRACT W. | | | | | | 2. DRIVEWAY CONNECTION NEEDS TO UTILIZE CITY STANDARD | | | DETAIL GC-6 OR GC-7. | | | | | | 3. WATER METERS NEEDS TO BE LOCATED WITHIN THE CITY | | | RIGHT-OF-WAY OR EASEMENT. | | | | | | 4. SHOW CROSS-WALK AND STOP BAR AT EXIT. | | | | | | 5. DUMPSTER APPEARS TO DRAIN DIRECTLY INTO PROPOSED | | | CATCH BASIN. FINAL DESIGN WILL NEED TO ADDRESS WATER | | | QUALITY CONCERNS AND PREVENT TRASH FROM ENTERING | | | STORMWATER SYSTEM. | | | | | | 6. A MODIFICATION OF SFWMD PERMIT WILL NEED TO BE | | | OBTAINED TO ENSURE COMPLIANCE WITH SECTION 94-307 OF | | | THE CODE OF ORD. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
12-08-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
12-08-2014 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
12-08-2014 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2014-12-11 09:52:19 | OUTSTANDING COMMENT REGARDING MEZZANINE AND SECOND | | | MEANS OF EGRESS WAS ADDED AS A CONDITION OF APPROVAL. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT (561) 822-1448 OR [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
11-17-2014 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
11-17-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
11-17-2014 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2014-11-17 15:16:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS WAS THE FIRST I HAVE HAD THE OPPORTUNITY TO REVIEW | | | THE FLOOR PLAN. | | | | | | THE MEZZANINE REQUIRES A SECOND MEAS OF EGRESS AND | | | SHALL NOT BE APPROVED IF IT IS TO BE SUBMITTED WITH | | | ONLY ONE. | | | | | | PLEASE REVIEW AND PROVIDE YOUR JUTIFICATION FOR ONLY | | | PROVIDING FOR THE ONE AND/OR REDESIGN WITH A SECOND | | | EXIT REMOTE FROM THE OTHER. | | | | | | ALL OTHER COMMENTS HAVE BEEN ADDRESSED. | | | | | | THIS CONCERN CAN BE ADDRESSED DURING FORMAL BUILDING | | | PLAN REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-04-2014 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-04-2014 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-04-2014 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
2 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:34:10 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
P |
Date |
08-12-2014 |
|
|
Cont ID |
|
| Sent By |
ssamuels |
Date |
08-12-2014 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
ssamuels |
Date |
08-12-2014 |
Time |
18:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
Jackson |
Date |
11-17-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-17-2014 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-11-17 16:18:56 | 11-17-14 | | | | | | | | | | | | I HAVE REVIEWED THE SUBMITTED PLANS AND DEVELOPER | | | RESPONSES TO MY ORIGINAL COMMENTS. | | | | | | THESE ORIGINAL CONCERNS HAVE BEEN ADDRESSED AND THE | | | SUBMITTED PLANS ACCURATELY REFLECT THOSE CHANGES. | | | | | | PASSED AS SUBMITTED. | | | | | | | | | | | | | | | | | | | | | | | | | | | JACKSON LOEBIG | | | O&M SUPERINTENDENT | | | PUBLIC UTILITIES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | | | | TEL: 561 494-1067 | | | CELL: 561 951-7656 | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
08-12-2014 |
|
|
Cont ID |
|
| Sent By |
jackson |
Date |
08-12-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
08-12-2014 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-08-12 16:07:02 | AUGUST 12, 2014 | | | | | | FAILED (DOMESTIC WATER AND SANITARY SEWER) | | | | | | DOMESTIC WATER | | | THE PROPOSED CONNECTION TO THE CITY?S WATER SYSTEM IS | | | IMPROPERLY SITED. THE METER AND BACKFLOWS (FIRE AND | | | DOMESTIC) SHOULD BE LOCATED AT/OR NEAR THE POINT OF | | | CONNECTION WHICH IS AT THE CUL-DE-SAC AT LEEPER DRIVE. | | | THE PROPOSED PROPOSED FIRE HYDRANT AND SUPPORTING | | | APPURTENANCES WOULD BE ?PRIVATE? AND THE RESPONSIBILITY | | | OF THE OWNER. | | | | | | SANITARY SEWER | | | THE PROPOSED CONNECTION TO THE CITY?S SANITARY | | | COLLECTION SYSTEM IS IMPROPERLY SITED. THE FINAL (DUE | | | TO DISTANCE OTHERS WILL BE NEEDED) SHOULD BE LOCATED | | | AT/OR NEAR THE POINT OF CONNECTION WHICH IS AT THE | | | CUL-DE-SAC AT LEEPER DRIVE. | | | | | | NOTE: | | | IN BOTH CASES (WATER AND SANITARY SEWER) STUB OUTS TO | | | THE CITY?S WATER AND SANITARY SYSTEM WERE PROVIDED AT | | | THE TIME THE HAVERHILL COMMERCE PARK WAS CONSTRUCTED. | | | FOR YOUR CONVENIENCE, A COPY OF THE RECORD DRAWINGS FOR | | | WATER, SEWER AND DRAINAGE WILL BE PROVIDED AT THE PPRC | | | MEETING ON AUGUST 13, 2014. | | | | | | JACKSON LOEBIG | | | O&M SUPERINTENDENT | | | PUBLIC UTILITIES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | | | | TEL: 561 494-1067 | | | CELL: 561 951-7656 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:34:48 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
P |
Date |
08-12-2014 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-12-2014 |
Time |
15:39 |
Rev Time |
|
| Received By |
tward |
Date |
08-12-2014 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-08-12 15:53:13 | 1. SUGGEST RELOOCATING SANITARY SEWER LATERAL FROM | | | WITHIN THE LANDSCAPE AREA. | | | 2. THE FOLLOWING WILL NEED TO BE SUBMITTED WITH THE | | | ENGINEERING PERMIT APPLICATION: | | | A. STORMWATER QUALITY TREATMENT CALCULATIONS | | | B. LAND USE (PERVIOUS/IMPERVIOUS) AREAS | | | C. SWPPP (EROSION CONTROL) PLAN | | | D. FINAL ENGINEERING PLANS | | | 3. THE FOLLOWING WILL NEED TO BE SUBMITTED BEFORE START | | | OF CONSTRUCTION | | | A. MODIFICATION OF SFWMD ERP PERMIT. | | | B. FDEP NPDES NOI. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | (561) 494-1120 |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:35:04 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] | | | | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-05-2014 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-05-2014 |
Time |
09:08 |
Rev Time |
|
| Received By |
vnoel |
Date |
08-05-2014 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-08-05 09:18:47 | 1. PACKAGE INCOMPLETE - NO SURVEY PROVIDED. | | | 2. ENGINEERING PLAN HAS REAR OF PROPERTY LABELED AS | | | SOUTHERN BLVD. (S.R. 80). | | | 3. RELOCATE METER ASSEMBLY TO RIGHT-OF-WAY. | | | 4. SITE/CIVIL PLANS WILL REQUIRE SUBMITTAL TO | | | ENGINEERING SERVICES. | | | 5. RELOCATE DUMPSTER AWAY FROM CATCH BASIN. FINAL | | | LOCATION WILL REQUIRE APPROVAL FROM FERDINAND RIVERA, | | | SANITATION SUPERVISOR. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:35:23 | PURSUANT TO AN EMAIL SENT TO ALL REVIEWERS ON | | | 11/17/2014, ANY OUTSTANDING COMMENTS WERE TO BE MADE | | | PRIOR TO THE CLOSE OF BUSINESS ON MONDAY, NOVEMBER 24, | | | 2014. IF COMMENTS WERE NOT MADE BY THIS TIME, OR NO | | | OTHER COMMUNICATION WAS MADE, IT WAS TO BE ASSUMED THAT | | | ALL PREVIOUS COMMENT HAD BEEN ADDRESSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
08-13-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
bcollins |
Date |
08-13-2014 |
Time |
07:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
12-08-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
12-08-2014 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
12-08-2014 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2014-12-11 09:48:21 | THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING | | | CONDITION(S): | | | | | | 1. AS REQUIRED BY PETER LEDUC, CITY OF WEST PALM BEACH | | | FIRE MARSHALL, THE PROPOSED MEZZANINE SHALL PROVIDE A | | | SECOND REMOTE MEANS OF EGRESS. | | | | | | 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | ALL LANDSCAPING MISSING WITHIN THE LEEPER DRIVE | | | MEDIAN(S) SHALL BE REPLACED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT (561) 822-1448 OR [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
11-26-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
11-26-2014 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
11-26-2014 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2014-11-26 14:27:48 | ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 11.26.2014 | | | PROJECT NO.: Z14070022 | | | CASE NO.: PB 1259C | | | ADDRESS: 5483 LEEPER DRIVE | | | APPLICANT/CONTACT: CHRIS TRAIKOFF | | | TELEPHONE NO.: 561.684.6141 | | | SCOPE OF REVIEW: NEW 35,000 SQUARE FOOT WAREHOUSE | | | FACILITY. | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. AS REQUIRED BY SECTION 5, PARAGRAPH 4 OF ORDINANCE | | | NO. 3198-98, "PRIOR TO THE ISSUANCE OF ANY PERMITS FOR | | | ANY SITE PREPARATION OR IMPROVEMENTS, THE | | | APPLICANT/OWNER SHALL PROVIDE DOCUMENTATION FROM A | | | CERTIFIED ENGINEER, DEMONSTRATING COMPLIANCE WITH | | | POLICY 1.9.5 OF THE FUTURE LAND USE ELEMENT OF THE | | | CITY'S COMPREHENSIVE PLAN." THIS COMMENT WILL BE MADE A | | | CONDITION OF APPROVAL. | | | | | | 2. ALL LANDSCAPING MISSING IN THE MEDIAN OF LEAPER | | | DRIVE SHALL BE REPLACED. THIS COMMENT WILL BE MADE A | | | CONDITION OF APPROVAL. | | | | | | 3. SITE DATA TABLE INDICATES THAT THE BUILDING HEIGHT | | | IS 42 FEET 3/4 INCHES; HOWEVER, THE ELEVATIONS INDICATE | | | THAT THE MEAN ROOF HEIGHT IS 42 FEET 1/2 INCHES. PLEASE | | | ENSURE THAT ALL PLANS ARE CONSISTENT. | | | | | | ___________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE | | | PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X | | | 17IN), AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-05-2014 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
08-05-2014 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
08-05-2014 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2014-08-05 14:44:05 | ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.05.2014 | | | PROJECT NO.: Z14070022 | | | CASE NO.: PB 1259C | | | ADDRESS: 5483 LEEPER DRIVE | | | APPLICANT/CONTACT: CHRIS TRAIKOFF | | | TELEPHONE NO.: 561.684.6141 | | | SCOPE OF REVIEW: NEW 30,000 SQUARE FOOT WAREHOUSE | | | FACILITY. | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. AN APPROVED TRAFFIC CONCURRENCY LETTER FROM PALM | | | BEACH COUNTY SHALL BE PROVIDED. | | | | | | 2. ARE ANY EXISTING TREES PROPOSED TO BE | | | REMOVED/RELOCATED? IF SO, AN APPLICATION FOR A TREE | | | ALTERATION PERMIT SHALL BE SUBMITTED. | | | | | | 3. A SURVEY SHALL BE PROVIDED. | | | | | | 4. UTILITY LETTERS SHALL BE PROVIDED. | | | | | | 5. AS REQUIRED BY SECTION 5, PARAGRAPH 4 OF ORDINANCE | | | NO. 3198-98, "PRIOR TO THE ISSUANCE OF ANY PERMITS FOR | | | ANY SITE PREPARATION OR IMPROVEMENTS, THE | | | APPLICANT/OWNER SHALL PROVIDE DOCUMENTATION FROM A | | | CERTIFIED ENGINEER, DEMONSTRATING COMPLIANCE WITH | | | POLICY 1.9.5 OF THE FUTURE LAND USE ELEMENT OF THE | | | CITY'S COMPREHENSIVE PLAN." | | | | | | 6. ALL PLANS SHALL BE APPROVED BY THE HAVERHILL | | | COMMERCE PARK ARCHITECTURAL REVIEW COMMITTEE, AS | | | SPECIFIED IN THE "DESIGN CRITERIA FOR HAVERHILL | | | COMMERCE PARK". | | | | | | 7. ALL LANDSCAPING MISSING IN THE MEDIAN OF LEAPER | | | DRIVE SHALL BE REPLACED. | | | | | | 8. ARE ANY WALL-MOUNTED SIGNS PROPOSED? IF SO, THEY | | | SHALL CONFORM TO THE REQUIREMENTS OUTLINED IN THE | | | DESIGN CRITERIA. | | | | | | 9. AS REQUIRED BY THE DESIGN CRITERIA, PLEASE PROVIDE A | | | TABLE OF ALL THE USES (EXISTING + PROPOSED) WITHIN THE | | | HAVERHILL COMMERCE PARK IPD, THEIR SQUARE FOOTAGE, AND | | | THEIR APPLICABLE TRAFFIC COUNT. THE MAXIMUM DEVELOPMENT | | | WITHIN THE HAVERHILL COMMERCE PARK IPD SHALL NOT EXCEED | | | 220,000 SQUARE FEET (2,420 DAILY VEHICULAR TRIPS) | | | UNLESS CITY COMMISSION APPROVAL IS OBTAINED. | | | | | | 10. SITE DATA TABLE INDICATES THAT THIS IS A 2-STORY | | | BUILDING; PLEASE CLARIFY. | | | | | | 11. SITE DATA TABLE INDICATES THAT THE BUILDING HEIGHT | | | IS 28 FEET; HOWEVER, THE ELEVATIONS INDICATE THAT THE | | | MEAN ROOF HEIGHT IS 35 FEET 7.5 INCHES. PLEASE ENSURE | | | THAT ALL PLANS ARE CONSISTENT. | | | | | | 12. THE DEVELOPMENT REGULATIONS TABLE INDICATES THAT | | | THE REQUIRED LANDSCAPE AREA IS 20%; PER SECTION 94-173, | | | THE REQUIRED LANDSCAPE AREA IS ONLY 15%. | | | | | | 13. IS IS RECOMMENDED THAT THE PARKING SPACES ALONG THE | | | NORTH SIDE OF THE PROPERTY BE ONLY 16 FEET IN LENGTH | | | AND PROVIDE FOR A 2-FOOT OVERHANG THAT CONSISTS OF | | | GRASS OR OTHER GROUNDCOVER (6 INCHES OR LESS IN | | | HEIGHT). THIS ELIMINATES THE NEED FOR WHEEL STOPS AND | | | INCREASES THE PLANTING AREA FOR SHADE TREES. THE SPACES | | | IN FRONT OF THE BUILDING MAY ALSO BE SHORTENED SO LONG | | | AS THE CONCRETE WALK MAINTAINS SUFFICIENT CLEAR WIDTH | | | OUTSIDE OF THE 2-FOOT OVERHANG. | | | | | | 14. NO WALLS OR FENCES ARE BEING PROPOSED? | | | | | | 15. PLEASE PROVIDE THE PROPOSED SETBACK FOR THE | | | FREESTANDING MONUMENT SIGN (5 FEET MINIMUM). | | | | | | 16. PER SECTION 94-408(E)(2)B., THE MAXIMUM SIGN AREA | | | FOR FREESTANDING MONUMENT SIGNS SHALL BE ONE (1) SQUARE | | | FOOT FOR EACH ONE (1) LINEAR FOOT OF STREET FRONTAGE. | | | THEREFORE, IF THE LOT WIDTH IS 55 FEET, THE MAXIMUM | | | SIGN AREA IS 55 FEET (PLEASE NOTE THAT BOTH SIDE OF THE | | | SIGN COUNT TOWARD THIS ALLOWANCE). | | | | | | 17. PER SECTION 94-408(E)(2)E.1., FREESTANDING MONUMENT | | | SIGNS SHALL BE A MINIMUM OF 24 FEET FROM ANOTHER LOT. | | | | | | 18. ACCORDING TO THE PLAT OF HAVERHILL COMMERCE PARK, | | | THE ENTIRE 50 FOOT WIDE PORTION OF THE LOT THAT EXTENDS | | | WEST FROM LEEPER DRIVE CONSISTS OF A UTILITY EASEMENT. | | | LANDSCAPING SHALL NOT BE INSTALLED WITHIN A UTILITY | | | EASEMENT UNLESS WRITTEN CONSENT IS OBTAINED FROM ALL | | | UTILITY HOLDERS, OR THE EASEMENT IS ABANDONED. | | | | | | 19. PLEASE GROUP THE PLANT LIST INTO SHADE TREES, | | | FLOWERING TREES, AND PALMS. | | | | | | 20. PURSUANT TO SECTION 94-445G.3.II., IRRIGATION SHALL | | | PROVIDE 120% COVERAGE TO CULTIVATED LANDSCAPE AREAS. | | | | | | 21. BICYCLE PARKING SHALL BE PROVIDED AT A RATIO OF ONE | | | (1) SPACE PER 20 AUTOMOBILE SPACES. PLEASE IDENTIFY THE | | | LOCATION OF THE BIKE RACK, AS WELL AS A DETAIL OF THE | | | PROPOSED RACK TO BE INSTALLED. PLEASE CONTACT ME FOR A | | | LIST OF ACCEPTABLE BIKE RACK STYLES. | | | | | | 22. PLEASE PROVIDE A COPY OF THE LATEST DECLARATION OF | | | RESTRICTIONS PROTECTIVE COVENANTS FOR HAVERHILL | | | COMMERCE PARK, AS OUTLINED AND REFERENCED IN THE DESIGN | | | CRITERIA. | | | ___________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE | | | PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X | | | 17IN), AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|
| |