| Plan Review Stops For Project Z14030060 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
04-04-2014 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
04-04-2014 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
04-09-2014 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2014-04-09 11:21:47 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. NO ACCESSIBLE PARKING SPACES ARE CURRENTLY SHOWN. | | | PER THE FAIR HOUSING ACT, AT LEAST 2% OF THE PARKING | | | SPACES PROVIDED FOR THE DWELLING UNITS MUST BE | | | ACCESSIBLE. ALSO, ACCESSIBLE PARKING SPACES SERVING THE | | | NON-RESIDENTIAL AREAS OF THE BUILDINGS SHALL BE | | | PROVIDED IN NUMBERS SUFFICIENT TO COMPLY WITH SECTION | | | 208.2 OF FLORIDA ACCESSIBILITY CODE, | | | | | | 3. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE | | | ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE | | | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING | | | TO AN ACCESSIBLE ENTRANCE FOR EACH | | | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE | | | | | | 4. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, | | | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A | | | PARKING STRUCTURE, SHALL BE VAN ACCESSIBLE AND DESIGNED | | | IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA | | | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 | | | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) | | | | | | 5. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL | | | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS | | | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND | | | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA | | | BUILDING CODE | | | | | | 6. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH | | | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND | | | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF | | | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. | | | | | | 7. ENCLOSED PARKING GARAGES MUST HAVE EXHAUST SYSTEMS | | | DESIGNED TO MINIMIZE NOISE LEVELS USING INLINE FAN | | | SILENCERS OR OTHER APPROVED METHODS. | | | | | | 8. THE NEW BUILDINGS SHALL BE SEPARATED FROM THE | | | EXISTING BUILDINGS BY FIRE WALLS DESIGNED IN ACCORDANCE | | | WITH SECTION 706 OF FLORIDA BUILDING CODE, OR THEY MUST | | | BE CONSIDERED AS ADDITIONS AS COVERED BY CHAPTER 10 OF | | | THE FLORIDA EXISTING BUILDING CODE. | | | | | | 9. THE BRIDGES BETWEEN THE BUILDINGS AT LEVEL 5 AND | | | LEVEL 6 SHALL BE DESIGNED IN ACCORDANCE WITH SECTION | | | 3104 OF FLORIDA BUILDING CODE SUCH THAT THE BUILDINGS | | | ARE CONSIDERED SEPARATE. | | | | | | 10. SHEET A-4 SHOWS A LONG DEAD END CORRIDOR FROM THE | | | RESIDENTIAL UNITS TO THE CLOSEST EXIT STAIR. PER | | | SECTION 1018.4 OF FLORIDA BUILDING CODE, THE DEAD END | | | CORRIDOR SHALL NOT EXCEED 50 FEET. | | | | | | 11. IT IS NOTED THAT ELEVATOR LOBBIES ARE NOT SHOWN. | | | THE BUILDING AND BUILDING SYSTEMS MUST MEET ONE OF THE | | | EXCEPTIONS GIVEN IN SECTION 1018.4.1 OF FLORIDA | | | BUILDING CODE (SUCH AS ELEVATOR HOISTWAY | | | PRESSURIZATION), IF ELEVATOR LOBBIES ARE NOT PROPOSED. | | | | | | 12. IT IS NOTED THAT WIDENING OF THE ALLEY IS PROPOSED | | | TO ACCOMODATE TWO-WAY VEHICULAR TRAFFIC. ON SHEET A-2, | | | NO EXIT DISCHARGE DOOR IS YET SHOWN FOR THE STAIRWAY | | | ADJACENT TO THE ALLEY, AND WHEN IT IS SHOWN THE EXIT | | | DISCHARGE DOOR SHALL BE RECESSED SUCH THAT IT DOES NOT | | | SWING INTO THE VEHICULAR TRAVEL LANE. | | | | | | 13. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE | | | OBTAINED BEFORE COMMENCING THE WORK. | | | | | | 14. FOR STREET ADDRESSING CONTACT SCOTT ALEF, GIS | | | SUPPORT SPECIALIST, AT (561) 494 1094, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
11-10-2014 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
11-10-2014 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
11-10-2014 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2014-11-10 08:58:24 | ENGINEERING/PULBLIX WORKS DEPT. | | | LAND DEVELOPMENT | | | | | | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION DETAILS | | | WILL BE REVIEWED AS PART OF THE ENGINEERING DEVELOPMENT | | | APPROVAL AND BUILDING PERMIT APPLICATION PROCESSES. | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL. | | | | | | 1. ON SHEETS C1 AND C2, CHANGE NOTES 4 AND 1 TO READ | | | "ALLEYWAY SHALL BE RECONSTRUCTED TO MEET CITY OF WEST | | | PALM BEACH STANDARDS." | | | | | | 2. AFTER INSPECTING THE EXISITING SANITARY LINES, WE | | | HAVE FOUND THE SANITARY LINE IN THE ALLEY TO BE IN POOR | | | CONDITION. PLEASE REVISE THE DESIGN TO TIE INTO THE | | | MAIN ALONG ROSEMARY. | | | | | | 3.VERIFY THE SOUTHERN PARKING GARAGE RAMP SLOPE BETWEEN | | | THE GROUND AND 2ND FLOORS. THE RAMP IS MARKED WITH A 6% | | | SLOPE, BUT THE ELEVATIONS INDICATE THE RAMP CLIMBS FROM | | | 3 TO 14 FEET OVER THE 84 FT LENGTH OF THE RAMP. | | | | | | 4. THE PROPOSED FLOOD PROTECTION FOR THE SOUTHERN | | | PARKING GARAGE IS A PUMP. SHOW HOW THE ANY WATER | | | COLLECTED IN THIS AREA IS GOING TO BE TREATED PRIOR TO | | | DISCHARGE AND WHERE THE TREATED WATER WILL BE | | | DISCHARGED. | | | | | | 5. THE PROPOSED LAYOUT IS NOT ACCESSIBLE TO THE SOLID | | | WASTE TRUCKS (35 FT LONG, 15 FT HIGH). THE PROPOSAL TO | | | ROLL THE TRASH BINS INTO THE ALLEY WILL IMPEDE TRAFFIC | | | FLOW WHILE THE BINS ARE IN THE ALLEY AND COMPLETELY | | | BLOCK TRAFFIC WHEN THE SOLID WASTE TRUCKS ARE | | | COLLECTING THE GARBAGE. REVISE THE DESIGN TO | | | ACCOMMODATE THE TRUCKS WITHOUT REQUIRING THEM TO BACK | | | AROUND CORNERS OR DOWN THE ALLEY AND TO COMPLY WITH | | | SECTION 74-35(A)(9) OF THE CODE OF ORDINANCES. | | | | | | 6. VERIFY THAT THE PROPOSED SIZE AND QUANTITY OF TRASH | | | BINS IS APPROPRIATE FOR THE WASTE YARDAGE ANTICIPATED | | | TO BE GENERATED BY THE COMPLEX. CONSIDER USING A | | | COMPACTOR TO REDUCE THE YARDAGE OF WASTE THAT WILL NEED | | | TO BE COLLECTED. | | | | | | 7. PROVIDE VERTICAL PROFILES FOR THE PARKING GARAGE | | | RAMPS INCLUDING THE TRANSITION AREA GEOMETRY. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | [email protected] | | | 561-494-1098 (OFFICE) | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
11-10-2014 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
08-20-2014 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
11-10-2014 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2014-08-20 14:30:23 | ENGINEERING/PULBLIX WORKS DEPT. | | | LAND DEVELOPMENT AND STORMWATER | | | | | | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION DETAILS | | | WILL BE REVIEWED AS PART OF THE ENGINEERING DEVELOPMENT | | | APPROVAL AND BUILDING PERMIT APPLICATION PROCESSES. | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL. | | | | | | 1. INCLUDE PARKING PLANS FOR ALL LEVELS OF THE PARKING | | | GARAGE AND ENSURE THAT THE ELEVATION VIEW OF THE GARAGE | | | MATCHES THE PLAN VIEW. THE SUBMITTED PLANS DID NOT | | | INCLUDE PARKING LAYOUTS FOR UNDERGROUND LEVELS 1B, 1D, | | | OR 1E. | | | | | | 2. THE PARKING LAYOUT CONTAINS SEVERAL DEAD-ENDS, | | | INACCESSIBLE PARKING SPACES, PARKING SPACES AND DRIVE | | | AISLES WHICH DO NOT MEET CODE REQUIREMENTS. TURN AROUND | | | SPACES MUST BE PROVIDED AT THE DEAD ENDS. SHOW PROFILE | | | DETAILS FOR THE PARKING SPOTS PROPOSED UNDER RAMPS. | | | REVISE THE PARKING LAYOUT TO COMPLY WITH SECTION 94-485 | | | OF THE CODE OF ORDINANCES. ALSO , RESPOND TO THE | | | RELATED ZONING, PARKING AND TRAFFIC ENGINEERING | | | COMMENTS. | | | | | | 3. THE PROPOSED FLOOD PROTECTION FOR THE SOUTHERN | | | PARKING GARAGE, WHICH IS PROPOSED WITH A BOTTOM | | | ELEVATION OF APPROXIMATELY 7.8 FT NGVD, IS A PUMP. SHOW | | | HOW THE ANY WATER COLLECTED IN THIS AREA IS GOING TO BE | | | TREATED PRIOR TO DISCHARGE AND WHERE THE TREATED WATER | | | WILL BE DISCHARGED. | | | | | | 4. THE PROPOSED LAYOUT IS NOT ACCESSIBLE TO THE SOLID | | | WASTE TRUCKS (35 FT LONG, 15 FT HIGH). THE PROPOSAL TO | | | ROLL THE TRASH BINS INTO THE ALLEY WILL IMPEDE TRAFFIC | | | FLOW WHILE THE BINS ARE IN THE ALLEY AND COMPLETELY | | | BLOCK TRAFFIC WHEN THE SOLID WASTE TRUCKS ARE | | | COLLECTING THE GARBAGE. REVISE THE DESIGN TO | | | ACCOMMODATE THE TRUCKS WITHOUT REQUIRING THEM TO BACK | | | AROUND CORNERS OR DOWN THE ALLEY AND TO COMPLY WITH | | | SECTION 74-35(A)(9) OF THE CODE OF ORDINANCES. | | | | | | 5. VERIFY THAT THE PROPOSED SIZE AND QUANTITY OF TRASH | | | BINS IS APPROPRIATE FOR THE WASTE YARDAGE ANTICIPATED | | | TO BE GENERATED BY THE COMPLEX. CONSIDER USING A | | | COMPACTOR TO REDUCE THE YARDAGE OF WASTE THAT WILL NEED | | | TO BE COLLECTED. | | | | | | 6. THE PROJECT MUST PROVIDE ADEQUATE STORMWATER | | | MANAGEMENT, INCLUDING NOT MODIFYING THE VELOCITY OR | | | VOLUME OF OFF-SITE STORMWATER DISCHARGE. DESCRIBE HOW | | | THIS WILL BE ACHIEVED. COMPLIANCE WITH CHAPTER 40E-4 | | | FAC WILL DEMONSTRATE COMPLIANCE WITH THIS PROVISION. | | | [CODE OF ORDINANCES SECTIONS 90-201, 94-35(C )(11), | | | 94-307, AND 94-580] | | | | | | 7. PROVIDE VERTICAL PROFILES FOR THE PARKING GARAGE | | | RAMPS INCLUDING THE TRANSITION AREA GEOMETRY. | | | | | | 8. PROVIDE DETAILS AND ELEVATION VIEWS OF THE LOADING | | | AREA AND ADJACENT PARKING GARAGE RAMPS. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED IN THE | | | CONSTRUCTION PLANS SUBMITTED FOR DEVELOPMENT APPROVAL | | | FROM THE ENGINEERING DEPARTMENT. | | | | | | 1. THE EXISTING WATER MAIN WITHIN THE ALLEY ALSO SERVES | | | THE METER AT 522 CLEMATIS STREET. WATER SERVICE MUST | | | CONTINUE TO BE PROVIDED FOR THIS ADDRESS. | | | | | | 2. SEWAGE DEMAND CALCULATIONS WILL NEED TO BE PROVIDED | | | AS PART OF THE FINAL DESIGN. THE 8-INCH GRAVITY SEWER | | | LINE MAY NOT BE SUFFICIENT FOR THE PROPOSED DEMAND AND | | | MAY NEED TO BE UPGRADED. RECENT INSPECTIONS OF THE | | | 8-INCH LINE INDICATE THAT IT IS NOT IN ACCEPTABLE | | | CONDITION TO CONVEY ADDITIONAL FLOWS AND POSSIBLY MAY | | | NOT WITHSTAND THE PROPOSED NEARBY SUBSURFACE | | | CONSTRUCTION. | | | | | | 3. THE AVAILABLE WATER PRESSURE WITHIN THE CITY MAY NOT | | | BE ACCEPTABLE AT ELEVATIONS HIGHER THAN THE 2ND FLOOR. | | | WE RECOMMEND THAT A LONG-TERM PRESSURE STUDY BE | | | PERFORMED ON THE POTABLE WATER LINES PRIOR TO | | | FINALIZATION OF THE DESIGN. | | | | | | 4. SOLID WASTE YARDAGE WILL NEED TO BE ESTIMATED AS | | | PART OF THE FINAL DESIGN TO VERIFY THAT THE DESIGN | | | INCLUDES APPROPRIATE NUMBER AND SIZE OF TRASH BINS. | | | | | | 5. AN EXISTING SOLID WASTE CUSTOMER IS LOCATED ON THE | | | ALLEY EAST OF THE PROPOSED PROJECT. THE FINAL PLANS | | | WILL NEED TO INCLUDE A PROPOSAL FOR CONTINUING THEIR | | | SOLID WASTE SERVICE DURING CONSTRUCTION. THE ALLEY END | | | WEST OF THE RAILROAD LINE AND THERE IS NOT CURRENTLY A | | | PAVED OR STABILIZED TURNAROUND. | | | | | | 6. STORMWATER CALCULATIONS WILL NEED TO BE SUBMITTED AS | | | PART OF THE ENGINEERING DEVELOPMENT APPROVAL. IN | | | ADDITION TO DEMONSTRATING THAT THE REQUIRED FLOOD | | | PROTECTION AND WATER QUALITY TREATMENT IS PROVIDED, THE | | | CALCULATION SHOULD INCLUDE THE PROPOSED PUMPED | | | DISCHARGE FROM THE GARAGE, MOUNDING ANALYSIS FOR THE | | | EXFILTRATION TRENCH, EVALUATION OF THE IMPACT (IF ANY) | | | OF THE ROOF DRAIN VELOCITY INTO THE STORMWATER SYSTEM. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | ENGINEERING & PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | [email protected] | | | 561-494-1098 (OFFICE) | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
06-03-2014 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
06-03-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-06-03 11:23:16 | 2ND REVIEW RESPONSE | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED MAY | | | 23, 2014, FROM JON E. SCHMIDT AND ASSOCIATES TO ANA | | | MARIA APONTE, PLANNER, THE PREVIOUSLY SUBMITTED FIRE | | | PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
03-31-2014 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
03-31-2014 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
03-31-2014 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2014-03-31 12:15:37 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE | | | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF | | | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE | | | FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE | | | SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY, | | | CHAPTER 30, NEW APARTMENTS. | | | | | | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, | | | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, | | | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE | | | OCCUPANCIES (PARKING STRUCTURES) | | | | | | 7. THE SEPARATION AND OPENING PROTECTION BETWEEN THE | | | PARKING GARAGE AND HOTEL SHALL BE IN ACCORDANCE AND | | | COMPLIANCE WITH THE SPECIFIC AND MOST STRINGENT | | | PROVISION REQUIREMENT OF EITHER CHAPTER. | | | | | | 8. SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND | | | OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE | | | DWELLING UNITS. THESE DETECTORS SHALL BE HARD WIRED AND | | | SHALL BE INTERCONNECTED TO ONE ANOTHER. | | | | | | 9. INTERIOR FINISH CLASSIFICATIONS FOR ALL WALLS AND | | | CEILINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTED | | | BUILDING PERMIT PLAN. | | | | | | 10. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA | | | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE | | | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED | | | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE | | | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 11. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS | | | STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION | | | BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 12. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR | | | THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND INDICATED | | | ON THE PLANS. | | | | | | 13. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND | | | HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN | | | THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS | | | CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE | | | EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR | | | TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL | | | BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR | | | SCHEDULE. | | | | | | 14. PRESCRIPTIVE STRENGTH REQUIREMENTS FOR ALL | | | HANDRAILS AND GUARDRAILS FOR THE BUILDING SHALL BE | | | PROVIDED AND CLEARLY INDICATED ON THE PLANS. | | | | | | 15. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY | | | ILLUSTRATED ON THE PLAN. | | | | | | 16. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING | | | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. | | | | | | 17. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE | | | CLEARLY IDENTIFIED AND INDICATED ON THE PLAN. | | | | | | 18. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM | | | RISE, RUN, AND TREAD DEPTH. | | | | | | 19. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | 20. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 | | | KEYWAY SYSTEM. | | | | | | 21. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT | | | DOORS. | | | | | | 22. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY | | | EQUIPMENT. | | | | | | 23. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED | | | AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED | | | THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE. | | | | | | 24. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY | | | INDICATED ON THE BUILDING PLAN. | | | | | | 25. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT | | | AND/OR TENANT SHALL BE CLEARLY INDICATED AND | | | ILLUSTRATED ON THE BUILDING PLAN. | | | | | | 26. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY | | | INDICATED AND ILLUSTRATED ON THE BUILDING PLAN. | | | | | | 27. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | 28. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS | | | (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND | | | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 29. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE | | | ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED | | | ON THE PLAN. | | | | | | 30. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED | | | TO EACH APARTMENT AND/OR TENANT. THESE INSTRUCTIONS ARE | | | TO INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND | | | ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR ALARM | | | ACTIVATION. | | | | | | 31. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR | | | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR | | | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE | | | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY | | | DOOR. | | | | | | 32. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 33. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS IN ACCORDANCE WITH THE REQUIREMENTS OF ALL | | | APPLICABLE CODES AND STANDARDS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
3 |
Status |
F |
Date |
11-06-2014 |
|
|
Cont ID |
|
| Sent By |
ssamuels |
Date |
11-06-2014 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
ssamuels |
Date |
11-06-2014 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2014-11-06 16:49:24 | PARKING DEPARTMENT | | | Z - 14030060 | | | | | | AFTER REVIEWING THE FINAL PLANS FOR CLEMATIS PLACE, WE | | | NOTICED THAT DATURA CURRENTLY HAS FOUR PARKING SPACES. | | | THE PLANS ONLY SHOW TWO PARKING SPACES. I WOULD | | | CONCLUDE THAT THEY ARE ELIMINATING TWO METER SPACES. WE | | | WOULD REQUEST A PAYMENT IN ADVANCE OF $33,600 FOR THE | | | REMOVAL OF THOSE METERS. CAN YOU PLEASE SUBMIT THIS | | | BEFORE THE NOVEMBER 7 DEADLINE? THANKS FOR YOUR | | | ASSISTANCE. | | | | | | PERMANENT REMOVAL | | | | | | CITY OF WEST PALM BEACH | | | ZONING AND LAND DEVELOPMENT REGULATIONS | | | SECTION94- I LL SUBSECTION (H) PAYMENT-IN-LIEU | | | | | | PAYMENT-IN-LIEU | | | PROPOSED DEVELOPMENTS WITHIN THE DOWNTOWN MASTER PLAN | | | (DMP) MAY ACCOMMODATE THEIR | | | REQUIRED PARKING BY MAKING PAYMENT FOR EACH REQUIRED | | | PARKING SPACE INTO THE DOWNTOWN PARKING | | | TRUST FUND. THE FEE PER PARKING SPACE IS BASED UPON THE | | | CURRENT CONSTRUCTION COST OF STRUCTURED | | | PARKING, AS DETERMINED BY THE CITY PARKING | | | ADMINISTRATOR, AND PAID AT THE TIME OF BUILDING PERMIT | | | APPLICATION. PAYMENT INTO THE DOWNTOWN PARKING TRUST | | | FUND IS NOT PAYMENT FOR AND DOES NOT | | | PROVIDE THE RIGHT TO ANY PARKING SPACE IN ANY CITY | | | FACILITY. | | | A. PERMANENT REMOVAL OF A METER PARKING SPACE IS | | | SIXTEEN THOUSAND EIGHT | | | HUNDRED DOLLARS ($ 16,800.00). | | | | | | OTHER FEES | | | THERE IS A ONE TIME $100.00 FEE PER METER FOR TEMPORARY | | | REMOVAL AND REPLACEMENT. | | | | | | SEAN SAMUELS | | | PARKING FACILITY SUPERVISOR | | | PARKING ADMINSTRATION | | | TEL : 561-822-1507 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
2 |
Status |
F |
Date |
08-20-2014 |
|
|
Cont ID |
|
| Sent By |
ssamuels |
Date |
08-20-2014 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
ssamuels |
Date |
08-20-2014 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2014-08-20 17:33:16 | PARKING DEPT COMMENTS | | | | | | PLAN Z 14030060 | | | | | | REMOVAL OF ON - STREET METERED PARKING SPACES WILL | | | REQUIRED PAYMENT OF A FEE AS ESTABLISH BY THE PARKING | | | ADMINSTRATOR. | | | | | | FEE: PERMANENT METER REMOVAL - $16,800 PER METER | | | TEMPORARY METER REMOVAL - $100 PER METER | | | METER HOOD RENTAL - $350 PER MONTH / PER METER | | | $20 PER DAY INCLUDED HOLIDAY AND SUNDAY | | | | | | CONCERN ABOUT THE NUMBER PROVIDED FOR THE GARAGE FIRST | | | LEVEL SLOPE PLEASE REFER TO THE CITY OF WEST PALM BEACH | | | ZONING AND LAND DEVELOPMENT REGULATIONS CODE. | | | | | | PLEASE PROVIDE BICYCLE RACK SPECIFICATION BY CITY OF | | | WEST PALM BEACH CODE SPECIFICATION | | | | | | PARKING DETAIL IS REQUIRED PER CITY OF WEST PALM BEACH | | | INCLUDED ANGLE PARKING SPACES. H.C SYMBOL | | | | | | 3RD LEVEL NO DIMENSION FOR SPACES IS PROVIDED. | | | | | | PLAN LACK FULL LAYOUT OF PARKING SPACES FOR ALL LEVELS | | | OF GARAGES - UNDERGROUND LEVELS - 1B - 1D - 1 E | | | | | | | | | SEAN SAMUELS | | | | | | TEL - 561-822-1507 | | | [email protected] | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
F |
Date |
04-09-2014 |
|
|
Cont ID |
|
| Sent By |
ssamuels |
Date |
04-09-2014 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
ssamuels |
Date |
04-09-2014 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2014-04-09 12:12:53 | PARKING DEPARTMENT | | | Z 14030060 | | | | | | REMOVAL OF ON - STREET METERED PARKING SPACES WILL | | | REQUIRED PAYMENT OF A FEE AS ESTABLISH BY THE PARKING | | | ADMINSTRATOR. | | | | | | FEE : | | | PERMANENT METER REMOVAL - $16,800 PER METER. | | | TEMPORARY METER REMOVAL - $100 PER METER | | | METER HOOD RENTAL $350 PER MONTH/ PER METER | | | METER HOOD RENTAL $20 PER DAY ( INCLUDED SUNDAY AND | | | HOLIDAY) | | | | | | NO DIMENSION OF PARKING WAS PROVIDED FOR REGULAR AND | | | HANDICAP SPACES. | | | NO HANDICAP SPACE SHOW ON THE PLAN | | | NO BIKE PARKING SPACE SHOW | | | | | | | | | SEAN SAMUELS CPP | | | PARKING ADMINSTRATION | | | 561-822-1507 | | | [email protected] | | | | | | |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
Jackson |
Date |
06-18-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-06-18 16:07:17 | SANITARY SEWER | | | | | | WE DO NOT RECOMMEND THE POINT OF TIE TO BE AT THE 24? | | | CLAY GRAVITY LINE ON ROSEMARY. A TIE-IN TO THE EXISTING | | | 24? (VCP) CLAY LINE WOULD BE DISRUPTIVE AND EXPENSIVE. | | | AFTER REVIEWING THE PLANS WITH JOSH MCDERMOTT, | | | SUPERINTENDENT, WE?VE CONCLUDED THAT THE PREFERRED | | | TIE-IN FOR THE SANITARY SEWER SHOULD THE 8? GRAVITY | | | LINE THAT RUNS DOWN THE ALLEY BETWEEN THE TWO (2) | | | PROPERTIES. | | | ALTHOUGH THIS 8? CLAY LINE IS IN ?FAIR? CONDITION, IT | | | IS REASONABLE TO EXPECT THAT THIS IS LESS COSTLY TO THE | | | DEVELOPER AND LESSENS THE IMPACT TO THE EXISTING | | | INFRASTRUCTURE ALONG ROSEMARY . | | | | | | | | | JACKSON LOEBIG | | | O&M SUPERINTENDENT | | | PUBLIC UTILITIES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | | | | TEL: 561 494-1067 | | | CELL: 561 951-7656 | | | | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
06-02-2014 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-02-2014 |
Time |
18:51 |
Rev Time |
0.50 |
| Received By |
cranford |
Date |
08-20-2014 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2014-08-20 14:32:49 | SEE ENGINEERING COMMENTS | | 2014-06-02 19:32:59 | 1. DRAINAGE STRUCTURE S-202 APPEARS TO BE NEW. PROPOSED | | | PIPE BETWEEN S-202 AND CS-2 WILL BE IN CONFLICT WITH | | | EXISTING 6" WATER MAIN TO BE ABANDONED. CAN CS-2 | | | CONNECT TO EXISTING CURB INLET TO THE SOUTH OF CS-2 | | | INSTEAD? IT APPEARS IT WOULD CLEAR THE SANITARY MAIN IN | | | THE ALLEY. | | | 2. SURVEY SHOWS THE GRATE ELEVATION OF THE EXISTING | | | CURB INLET IN THE ALLEY TO BE 23.13 FT NGVD. THE PAVING | | | AND DRAINAGE PLAN CALLS OUT A GRATE ELEVATION OF 22.0 | | | FT NGVD. LIKEWISE, THE GRATE ELEVATIONS FOR PROPOSED | | | DRAINAGE STRUCTURES S-201, CS-2, CS-1 AND S-301 ON THE | | | PAVING AND DRAINAGE PLAN ARE SHOWN TO BE MORE THAN 1 | | | FOOT BELOW EXISTING GRADES OF THE ALLEY AND ROSEMARY | | | AVENUE. | | | 3. VERIFY THE WIDTH OF THE CONTROL STRUCTURES CAN "FIT" | | | BOTH A WEIR BOX AND BAFFLE AND HAVE SUFFICIENT SPACE TO | | | INSTALL BOTH. | | | 4. ON THE BAFFLE DETAIL, INDICATE MINIMUM DISTANCE | | | BETWEEN BOTTOM OF BAFFLE AND INVERT OF EXFILTRATION | | | TRENCH PIPE. | | | 5. DRAINAGE CALCULATIONS ON SHEET C3 INDICATE THE | | | 3-YEAR 1-HOUR DESIGN STORM TO BE 1 INCH. PER FDOT IDF | | | CURVES, 3-YEAR 1 HOUR STORM IS CLOSER TO 2.8 INCHES. | | | 6. VALIDATE THE USE OF THE SFWMD EXFILTRATION TRENCH | | | STANDARD FORMULA WITHOUT MODIFICATION WITH ONE SIDE OF | | | THE TRENCH NEARLY ADJACENT TO THE WALL OF THE | | | UNDERGROUND PARKING STRUCTURE. | | | 7. INDICATE HOW THE DRAINAGE OF THE UNDERGOUND PARKING | | | STRUCTURES WILL BE MANAGED. | | | 8. TIE ROOF DRAINS INTO THE ONSITE DRAINAGE SYSTEM OR | | | DISCAHRGE TO PERVIOUS AREAS WHERE POSSIBLE. | | | 9. WITH THE ENGINEERING PERMIT APPLICATION SUBMIT A | | | STORMWATER POLLUTION PROTECTION PLAN. | | | 10. PRIOR TO CONSTRUCTION OR DEMOLITION, SUBMIT A COPY | | | OF THE FDEP GENERAL PERMIT FOR STORMWATER DISCHARGES | | | ASSOCIATION WITH CONSTRUCTION SITES (NPDES PERMIT). | | | 11. WATER MAIN VALVES AND SANITARY LATERALS SHOULD NOT | | | BE LOCATED NEAR OR UNDER TREE PLANTERS. | | | 12. ON THE ARCHITECTURAL VIEWS, SETBACK LINES AND | | | PROPERTY LINES ARE MISLABELED. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | 561-494-1120 | | | | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
04-04-2014 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-04-2014 |
Time |
13:47 |
Rev Time |
|
| Received By |
tward |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-04-04 13:57:14 | 1. INCLUDE WITH THE ENGINEERING PERMIT APPLICATION THE | | | FOLLOWING: | | | - SIGNED AND SEALED DRAINAGE CALCULATIONS AND LAND USE | | | BREAKDOWN (PERVIOUS/IMPERVIOUS/BUILDING/ETC.) | | | - SIGNED AND SEALED ENGINEERING PLANS INCLUDING PAVING, | | | GRADING AND DRAINAGE PLAN AND AN EROSION CONTROL PLAN | | | 2. BEFORE START OF CONSTRUCTION, PROVIDE FDEP NPDES | | | PERMIT | | | 3. WEIR BOX DETAIL SHOWS HEIGHT TO BE PIPE DIAMETER + | | | 6". BASED ON EXFILTRATION TRENCH DESIGN, THE HEIGHT | | | SHOULD BE PIPE DIAMETER + 18" (6" BELOW AND 12" ABOVE | | | THE PIPE). | | | 4. INCLUDE BAFFLES IN INLETS CONNECTED TO EXFILTRATION | | | TRENCHES. | | | 5. WILL THE OVERHEAD ELECTRIC LINES IN THE ALLEY BE | | | AFFECTED? | | | 6. SHOW PROPERTY LINES ON THE BUILDING SECTION SHEET | | | A-6. | | | 7. WHERE IS THE ALLEY EXFILTRATION TRENCH IN RELATION | | | TO THE SUBTERRANEAN PARKING AREAS? | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING AND PUBLIC WORKS DEPARTMENT | | | 561-494-1120 |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-08-27 10:24:24 | 1. PREVIOUS COMMENTS FROM REVIEW #2 STILL PERTAIN. | | | 2. RESPONSE FROM APPLICANT WAS THAT SANITATION HAD | | | APPROVED AT PPRC. THAT IS INCORRECT. APPLICANT | | | NEEDS TO CONTACT FERDINAND RIVERA AS PROPOSED | | | COLLECTION IS NOT APPROVED. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
06-12-2014 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
06-12-2014 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-06-12 07:22:46 | 1. ORIGINAL COMMENTS CONCERNING REPLAT AND BRIDGE | | | CROSSING STILL PERTAIN. | | | 2. AN ACCESS EASEMENT OVER THE EXPANDED ALLEY WILL BE | | | REQUIRED. | | | 3. DEVELOPER'S AGREEMENT WILL BE REQUIRED FOR | | | MAINTENANCE OF EXISTING AND PROPOSED PAVERS IN ALLEY | | | AND ALONG DATURA, ROSEMARY AND CLEMATIS. | | | 4. SANITATION HAS NOT BEEN CONTACTED FOR APPROVAL. | | | PROJECT WILL NOT BE APPROVED WITHOUT THEIR CONSENT. | | | 5. METER ASSEMBLIES NEED TO BE LOCATED OUTSIDE OF | | | RIGHT-OF-WAY. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
04-04-2014 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-04-2014 |
Time |
09:45 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-04-04 10:34:13 | 1. REPLAT WIL BE REQUIRED. APPLICATION IS MADE THROUGH | | | ENGINEERING SERVICES FOR TECHNICAL REVIEW. | | | 2. REVISE SURVEY TO INCLUDE WEST ONE-HALF OF LOT 5. | | | 3. RIGHT-OF-WAY DEDICATION WILL BE REQUIRED FOR A | | | PORTION OF DATURA ST. | | | 4. PRIVATE DRAINAGE CROSSING ALLEY WILL REQUIRE | | | AGREEMENT. | | | 5. KEEP SANITARY CONNECTIONS OUT OF ALLEY. | | | 6. PROVIDE JUSTIFICATION FOR ABANDONMENT OF 6" WATER | | | MAIN. | | | 7. SITE/CIVIL PLANS REQUIRE SEPARATE SUBMITTAL TO | | | ENGINEERING SERVICES. | | | 8. BRIDGE CROSSING ALLEY WILL REQUIRE A SEPARATE | | | AGREEMENT/PERMIT. | | | 9. SITE PLAN DOES NOT SHOW ADDITIONAL R/W PER | | | MAINTENANCE MAP FOR WEST 1/2 OF LOT 5. DOORS CANNOT | | | OPEN INTO RIGHT-OF-WAY. | | | 10. IS ADDITIONAL ALLYE WIDTH TO BE DEDICATED AS R/W? | | | 11. BRIDGE NOT SHOWN ON SHEET A-6, BUILDING SECTION. | | | ADD RIGHT-OF-WAY LINES TOSECTION AND ELEVATIONS. | | | 12. APPROVAL OF SANITATION SUPERVISOR, FERDINAND | | | RIVERA, WILL BE REQUIRED. | | | 13 PROPERTY CORNERS MISSING ALONG EAST LINE OF LOT 4. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
04-08-2014 |
Time |
|
Rev Time |
0.00 |
| Received By |
bcollins |
Date |
04-08-2014 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2014-04-08 15:08:04 | 1. TRAFFIC MOVEMENTS SHALL BE SHOWN, USING AUTOTURN, TO | | | DEPICT HOW ACCESS AND EGRESS FROM THE LOADING AREAS ARE | | | ACHIEVED. | | | 2. TRAFFIC MOVEMENTS SHALL BE SHOWN, USING AUTOTURN, TO | | | DEPICT HOW ACCESS AND EGRESS FROM THE PARKING AREAS ARE | | | ACHIEVED. | | | 3. WILL THE ADDITIONAL PAVED WIDTH OF THE ALLEY BE | | | DEDICATED AS ALLEY RIGHT OF WAY? | | | 4. ALL TRAFFIC LEAVING THE SITE ONTO THE ALLEY SHALL BE | | | DIRECTED BY SIGNAGE TO ROSEMARY AVENUE. | | | 5. THE PROPOSED PATHWAY IS TOO CLOSE (2 FT.) TO THE | | | ENTRANCE TO THE GARAGE. THIS PATHWAY SHOULD BE | | | RESTRICTED TO ONE-WAY TRAFFIC WITH A MINIMUM 6FT. | | | SEPARATION FROM THE GARAGE ACCESS. | | | 6. THE RAMP UP TO PARKING IN THE 5 STORY BUILDING IS | | | NOT SHOWN ON THE SITE PLAN. | | | 7. REMOVAL OF ON STREET METERED PARKING SPACES WILL | | | REQUIRE PAYMENT OF A FEE AS ESTABLISHED BY THE PARKING | | | DEPARTMENT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
11-17-2014 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
11-17-2014 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
11-17-2014 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2014-11-17 16:29:08 | 1. FITNESS ROOM CANNOT GO IN THE ROOFTOP TERRACE. | | | PLEASE LOOK AT DEFINITION FOR ROOFTOP GARDENS AND | | | ELEMENTS ALLOWED TO ENCROACH INTO THE MAXIMUM BUILDING | | | HEIGHT. | | | 2. PLEASE IDENTIFY THE LOCATION OF THE EXISTING WINDOWS | | | ON ADJACENT PROPERTY TO THE EAST. | | | 3.PLEASE CHECK THE SPACES EXCLUDED FROM THE FAR | | | CALCULATION ( JANITOR ROOMS, TOILET NEXT TO ELEVATOR ON | | | FIRST FLOOR, AREA ADJACENT TO ELEVATOR ON FLOORS 2 TO 5 | | | ON SOUTH TOWER). | | | 4. DRIVE AISLE IN SOUTH PARKING GARAGE IS ONLY 20' IN | | | WIDTH WHILE 24' IS REQUIRED FOR 90 DEGREE PARKING. | | | 5. PLEASE INCLUDE IN THE PROPERTY DEVELOPMENT TABLE IN | | | SHEET A-1 THE INFORMATION REGARDING COMPLIANCE WITH | | | MAXIMUM BUILDING FOOTPRINT FOR EACH PARCEL. | | | 6. FAR TABLE IN SHEET A-1 SHOWS MAX FAR PERMITTED AS | | | 180,173.95 SF. THE CORRECT NUMBER IS 180,153.75 SF. | | | 7. GARAGE RAMP TO 2ND LEVEL HAS A SLOPE OF 8%. MAXIMUM | | | ALLOWED IS 6% FOR A RAMP WITH PARKING. | | | 8. BALCONIES SHOWN ON THE DATURA ELEVATION FOR FLOORS 2 | | | TO 5 ARE NOT DEPICTED ON FLOOR PLANS. | | | 9. AT RETAIL FRONTAGE, DETAILS CALL FOR A "FABRIC | | | CANOPY WITH METAL FRAMEWORK". PLEASE INCLUDE ADDITIONAL | | | REFERENCE PICTURES FOR THIS TYPE OF AWNING TO | | | DEMONSTRATE COMPATIBILITY WITH PROPOSED STYLE. | | | 10. PLEASE INCLUDE CALCULATION FOR THE PRIVATE OPEN | | | SPACE ON THE SOUTH PARCEL, AND ADD A SUMMARY WITH THE | | | OVERALL PRIVATE AND PUBLIC OPEN SPACE REQUIRED IF THE | | | TWO PARCELS ARE PUT TOGETHER. INCLUDE A NOTE EXPLAINING | | | HOW THE CALCULATION WAS DONE. | | | 11. SANITATION APPROVAL FOR PROPOSED GARBAGE DISPOSAL | | | AND COLLECTION WILL BE REQUIRED. PLEASE CONTACT | | | FERDINAND RIVERA AT 822-2076. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
07-14-2014 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
07-14-2014 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
07-14-2014 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2014-07-14 16:29:22 | RESPONSES TO COMMENTS FROM PREVIOUS REVIEW: | | | 3. INFORMATION REGADING COMPLIANCE WITH PRIVATE OPEN | | | SPACE REQUIREMENTS PROVIDED IN LA DRAWINGS IS NOT | | | SUFFICIENT. PLEASE INDICATE COMPLIANCE FOR EACH OF THE | | | PARCELS REGARDING THE AMOUNT OF PUBLIC OPEN SPACE | | | REQUIRED, PRIVATE OPEN SPACE REQUIRED, PERCENTAGE OF | | | VEGETATED AREA REQUIRED, AND PERCENTAGE OF TREE CANOPY | | | ACCORDING TO TABLE IV-7 AND IV-8. TABLE SHALL ALSO | | | INCLUDE CALCULATIONS FOR THE PUBLIC OPEN SPACE | | | REQUIRED. | | | 4. ADDITIONAL INFORMATION REGARDING PROPOSED BRIDGE IS | | | MISSING. FLOOR PLANS FOR 3RD, 4RD AND 5TH FLOOR MISSING | | | FROM PACKET. IS THE BRIDGE IS ONLYY CONNECTING THE TWO | | | ROOFTOP GARDENS? SECTION ON SHEET A8 SHOWS A PORTION OF | | | A BRIDGE ALSO ON 5TH FLOOR. | | | 8. GROSS SQUARE FOOTAGE CALCULATIONS PROVIDED SEEM NOT | | | TO INCLUDE A PORTION OF THE LOBBLY ON CLEMATIS STREET. | | | PLEASE CLARIFY THE USE OF AREA EXCLUDED AROUND THE | | | ELEVATOR ON THE 11TH FOOR, CORRIDORS LEADING TO | | | MECHANICAL ROOMS SHALL BE INCLUDED IN THE FAR. IN | | | GENERAL, PLEASE CONFIRM THE GROSS BUILDING AREA FOR ALL | | | THE FLOOR. A ROUGH ESTIMATE OF THE FIRST FLOOR | | | CALCULATED BY STAF FRESULTS IN 14,830SF VS 12,690SF | | | INDICATED IN SHEET A-14 FOR THE CLEMATIS STREET | | | BUILDING. | | | SCHOOL BOARD APPROVAL IS FOR 166 UNITS, AND THE PROJECT | | | CURRENTLY PROPOSED 168, PLEASE OBTAIN REVISED APPROVAL. | | | 10. ELEVATIONS PROVIDED AR BLACK AND WHITE AND IT IS | | | VERY DIFFICULT TO READ THE ARCHITECTURAL DESIGN. PLEASE | | | PROVIDE COLORED ELEVATIONS WITH SHADOWS TO BETTER ALLOW | | | THE BUILDING ELEVATION REVIEW. THEY COULD BE RPOVIDED | | | AT 11 BY 17 SIZE. | | | 13. PLEASE PROVIDE BACK UP INFORMATION TO CONFIRM | | | COMPLIANCE WITH TABLE IV-4: FACADE ARTICULATION | | | REQUIREMENTS. COMPLIANCE WITH PLANAR BREAK AND BLANK | | | WALL WILL BE REQUIRED BETWEEN OTHERS INCLUDED IN | | | TABLE.WHAT IS THE PROPOSED TREATMENT FOR THE WALL | | | ADJACENT TO FPL? | | | 14. AUTO TURN ANALYSIS WAS NOT INCLUDED WITH | | | RESUBMITTAL. | | | 17. FOUNTAIN INDICATED AS REMOVED IN RESPONSE LETTER IS | | | STILL SHOWN IN LA AND SITE PLAN DRAWINGS. IT SHALL BE | | | REMOVED OR MOVED CLOSER TO THE BUILDING AS IT BLOCKS | | | PEDESTRIAN TRAFFIC. | | | 18. TREE GRATES ALONG DATURA SHALL BE LOCATED ADJACENT | | | TO THE CURB. | | | 25. PLEASE INCLUDE DIMENSIONS IN ALL PARKING SPACES TO | | | DEMONSTRATE COMPLIANCE. | | | | | | ADDITIONAL COMMENTS FRO 2ND REVIEW | | | 1. PARKING ON NORTH SIDE OF ALLEY REQUIRES A 5 FEET | | | LANDSCAPE BUFFER. ONE ALTERNATIVE IS TO RELOCATE THE | | | PARKING AS 90 DEGREE BACKING UP ON THE ALLEY (BACK UP | | | WIDTH SHALL BE MIN. 24'). | | | 2. TREE GRATES ALONG DATURA STREET SHALL BE LOCATED | | | ADJACENT TO THE BACK OF CURB. | | | 3. ENTIRE SIDEWALK WIDTH ALONG DATURA STREET SHALL BE | | | CONCRETE. | | | 4. A TRANSITIONAL PAVER DESIGN SHALL BE DONE AT | | | CLEMATIS AND ROSEMARY, AND ROSEMARY AND DATURA. FURTHER | | | DISCUSSION NEEDED. | | | 5. PROPOSED CURB CUT ON DATURA ST. EXCEED MAXIMUM CURB | | | CUT ALLOWED. MAXIMUM PERMITTED IS 25'. | | | 6. DUE TO THE PROPOSED RAMP SLOPE A BREAK OVER | | | TRANSITION IS REQUIRED. | | | 7. PARKING RAMP CANNOT START WITHIN THE MINIMUM | | | REQUIRED SETBACK. | | | 8. BIKE RACK SHALL FOLLOW CITY STANDARD. | | | 9. ALL MECHANICAL EQUIPMENT IN ROOF SHALL BE ENCLOSED | | | AND SCREENED. | | | 10. PLEASE DIMENSION ALL PARKING SPACES INSIDE GARAGE. | | | 11. ALL SETBACKS ARE MEASURED FROM THE BACK OF CURB, | | | NOT THE FACE OF CURB. | | | 12. PLEASE PROVIDE COLORED ELEVATIONS, PREFERABLY WITH | | | SHADOWS. BLACK AND WHITE COPIES ARE REALLY DIFFICULT TO | | | READ. PRINTED COLORED ELEVATIONS CAN BE 11 BY 17. | | | 13.PLEASE INCLUDE A STRUCTURAL SOIL DETAIL FOR ALL | | | AREAS AROUND TREE GRATES (10' AROUND TREE UNDER | | | SIDEWALK). | | | 14. PLEASE STUDY THE POSIBILITY TO RELOCATE THE WATER | | | METER AND RPZ TO THE ALLEY FRONTAGE. | | | 15. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE | | | WITH ALL BUILDING REQUIREMENT ELEMENTS FOR EACH PARCEL | | | (FOOTPRINT). | | | 16. DROP-OFF AREA ON CLEMATIS STREET IS NOT PERMITTED, | | | SPACE SHALL BE MAINTAINED AS ON-STREET PARKING. | | | 17. PLEASE PROVIDE DOCUMENTATION FOR SANITATION | | | APPROVAL ON TRASH COLECTION LOCATION. | | | 18. PLEASE PROVIDE A TABLE WITH ALL UNIT SIZE TO | | | CONFIRM COMPLIANCE WITH MINIMUM UNIT SIZE AND AVERAGE | | | UNIT SIZE REQUIRED. | | | 19. FLOOR PLANS FOR LEVEL 3, 4, AND 5 ARE MISSING FROM | | | DRAWING SET. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
04-07-2014 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
04-07-2014 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
04-04-2014 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2014-04-04 11:44:09 | 1. PROPOSED COURTYARD IS NOT CURRENTLY PERMITTED IN THE | | | CWD-CD. STAFF SUGGEST A CODE AMENDMENT TO ALLOW THE | | | PROPOSED COURTYARD. | | | 2. A PASSGEWAY IS REQUIRED FOR THE CWD-10. PROPOSED | | | PASSAGEWAY DOES NOT COMPLY WITH CODE REQUIREMENTS FOR | | | PASSAGEWAY INTENDED FOR PEDESTRIAN CIRCULATION. | | | ADDITIONAL DISCUSSION WILL BE NECESSARY TO DETERMINE | | | ALTENATIVE OPEN SPACES. | | | 3.PLEASE PROVIDE INFORMATION REGARDING COMPLIANCE WITH | | | PRIVATE OPEN SPACE REQUIREMENT (LA AND HARDSCAPE | | | DRAWINGS REQUIRED). TABLE INDICATING AMOUNT OF | | | VEGETATED AREA, AND TREE CANOPY REQUIRED VS PROVIDED. | | | 20% OF SITE AS TERRACE ON TOP OF 2ND STORY. | | | 4.PLEASE PROVIDE DETAIL INFORMATION ABOUT THE PROPOSED | | | BRIDGE OVER THE ALLEY ROW. | | | 5. PROPOSED BULB OUT ON CLEMATIS STREET SHALL BE | | | REMOVED. CLEMATIS STREETSCAPE SHALL BE MAINTAINED | | | CONSISTENT WITH THE EXISTING. REMOVED PROPOSED GREEN | | | ISLAND FICUS. | | | 6. PLEASE INDICATE THE DIMENSION OF SETBACK ON DATURA | | | STREET. | | | 7. PLEASE INDICATE THE PROPERTY LINE AND SETBACK LINE | | | ON ALL FLOOR PLANS AND ELEVATIONS. | | | 8. PLEASE PROVIDE A GROSS BUILDING AREA TABLE AND AN | | | ASSOCIATED GRAPHIC FOR EACH FLOOR INDICATING THE AREA | | | CALCULATED FOR FAR AND EXCLUDED ON EACH FLOOR. USE | | | DEFINITION OF GROSS BUILDING AREA IN SECTION 94-109. | | | 9. PLEASE PROVIDE A DEVELOPEMENT CAPACITY VS PROPOSED | | | DEVELOPEMENT TABLE INDICATING THE AREA AND FAR OF EACH | | | PARCEL. | | | 10.PLEASE PROVIDE COLORED ELEVATIONS (ASSIGN | | | TRANSPARENCY TO STREET TREES), AND INDICATE MAIN | | | MATERIALS, BUILDING HEIGHTS, SETBACK AND PROPERTY | | | LINES. | | | 11. PLEASE INSERT COLOR ELEVATION IN THE STREET CONTEXT | | | FOR EACH STREET FRONTAGE. | | | 12. WHAT ARE THE POSSIBILITIES TO BURY THE OVERHEAD | | | ELECTRIC LINES ON DATURA STREET? PROPOSAL RELOCATES THE | | | EXISTING POLES TO THE CITY ROW. FURTHER DISCUSSION ON | | | ALTERNATIVES IS NECESSARY. | | | 13. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE | | | WITH TABLE IV-4: FACADE ARTICULATION REQUIREMENTS. | | | 14. PLEASE PROVIDE AUTO-TURN TO DEMONSTRATE LOADING | | | AREA OPERATION. | | | 15. PLEASE STUDY THE OPTION TO NARROW THE ALLEY EXIT | | | INTO ROSEMARY AVE TO REDUCE THE NEGATIVE IMPACT ON | | | PEDESTRIAN CIRCULATION. | | | 16. PLEASE DISCUSS THE POSSIBILITY TO RELOCATE THE BACK | | | FLOW PREVENTORS TO THE ALLEY. THEY SHALL NOT BE LOCATED | | | ON THE PRIMARY STREET IF THERE ARE OTHER OPTIONS. | | | 17. LP-1 SHOWS AN OAK AT THE ROSEMARY AVE/DATURA STREET | | | CORNER, A-1 SHOWS A FOUNTAIN. | | | 18. DATURA STREETSCAPE SHALL BE CONSISTENT. SHADE TREES | | | SHALL BE PROVIDED (OAKS ARE PLANTED ALONG 610 CLEMATIS | | | BUILDING). TREE GRATES SHALL BE INSTALLED ADJACENT TO | | | THE CURB. | | | 19. EXISTING TREES ALONG ROSEMARY AVENUE SHALL BE | | | EVALUATED TO DETERMINE IF REPLACEMENT IS NEEDED. | | | 20. ROSEMARY AVENUE PAVERS SHALL NOT CONTINUE ALONG | | | DATURA STREET. | | | 21. PLEASE CLARIFY WHAT ARE THE ARCHITECTURAL COLUMNS | | | INDICATED IN HP-1. | | | 22. CLEMATIS PLAZA SHALL HAVE THE SAME PAVERS CURRENTLY | | | INSTALLED ALONG CLEMATIS STREET. | | | 23. PLEASE CORRECT PARKING TABLE (MAX PARKIGN ALLOWED | | | FOR RETAIL). | | | 24. PLEASE INDICATE PARKING DIMENSIONS (AISLE+SPACES). | | | CONSIDER WIDER STALL REQUIRED WHEN COLUMNS PRESENT. | | | 25. PLEASE INDICATE CIRCULATION PATTER IN GARAGE. | | | 26. PLEASE INDICATE LOCATION OF HANDICAP SPACES AND | | | GUEST PARKING. | | | 27. TANDEM SPACES FOR RESIDENTIAL USES SHALL BE | | | ASSIGNED TO UNE SINGLE UNIT AND RESTRICTIVE COVENANT | | | WILL BE REQUIRED. TANDEM FOR COMMERCIAL WILL COUNT AS 1 | | | SPACE UNLESS VALET PARKING IS PROVIDED, AND RESTRICTIVE | | | COVENANT WILL BE REQUIRED. | | | 28.PLEASE PROVIDE REQUIRED BIKE PARKING FOR COMMERCIAL | | | AND RESIDENTIAL USES. COMMERCIAL (5 SPACES + ONE | | | SHOWER/CHANGING FACILITY) RESIDENTIAL (12 SPACES). | | | 29. PLEASE INDICATE LOCATION OF DUMPSTER FOR GARBAGE. | | | 30.PLEASE PROVIDE INFORMATION ABOUT PROPOSED STRUCTURES | | | ON ROOF TOP (HEIGHT, USES) COMPLIANCE WITH TABLE IV-5. | | | 31. PLEASE PROVIDE INFORMATION ON COMPLIANCE WITH BLANK | | | WALL REGULATIONS. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439 |
|
|
| |
Print |