Plan Review Details - Project Z14030050
Plan Review Stops For Project Z14030050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 04-09-2014 Cont ID  
Sent By rbrown Date 04-09-2014 Time 10:04 Rev Time 0.00
Received By rbrown Date 04-09-2014 Time 10:04 Sent To  
Notes
2014-04-09 10:39:01DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE PROPOSED LOT LINE LOCATION WOULD LEAVE THE 2
 STORY BUILDING OUT OF COMPLIANCE WITH BUILDING
 SEPARATION, PERCENTAGE OF OPENINGS AND OPENING
 PROTECTIVE REQUIREMENTS OF SECTION R302 OF FLORIDA
 BUILDING CODE (RESIDENTIAL). THE FIRE RESISTANCE RATING
 OF EXTERIOR WALLS, OPENINGS AND PENETRATIONS, AND THEIR
 SEPARATION DISTANCE TO THE NEAREST LOT LINE, SHALL
 COMPLY WITH TABLE R302.1. THE CODE WILL ONLY ALLOW THE
 EXTERIOR WALL TO BE ON THE LOT LINE (OR LESS THAN 3
 FEET FROM THE LOT LINE) IF THE WALL HAS A 1 HOUR
 FIRE-RESISTANCE RATING AGAINST FIRE EXPOSURE FROM BOTH
 SIDES, ANY PROJECTIONS (SUCH AS ROOF OVERHANG) HAVE A 1
 HOUR FIRE-RESISTANCE RATING ON THE UNDERSIDE, THERE ARE
 NO OPENINGS (WINDOWS, DOORS, VENTS, ETC.) IN THE WALL,
 AND ANY PENETRATIONS FOR PIPES, CONDUIT, ETC., ARE
 FIRESTOPPED IN ACCORDANCE WITH SECTION R302.4 OF
 FLORIDA BUILDING CODE (RESIDENTIAL). ALSO, THE EXISTING
 COVERED WALKWAY APPEARS TO BE ATTACHED TO BOTH
 BUILDINGS AND IS NOT PERMITTED BECAUSE IT WOULD BE
 UNITING TWO SEPARATE BUILDINGS ON SEPARATE LOTS.
  
 3. FOR STREET ADDRESSING CONTACT SCOTT ALEF, GIS
 SUPPORT SPECIALIST, AT (561) 494 1094, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status P Date 04-04-2014 Cont ID  
Sent By tward Date 04-04-2014 Time 12:00 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2014-04-04 12:01:551. ANY DRAINAGE SYSTEM CROSSING THE COMMON PARCEL
 LINE(S) WILL REQUIRE CROSS- DRAINAGE EASEMENT.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-04-04 09:23:101. REPLAT PER CHAPTER 177 WILL BE REQUIRED PRIOR TO
 BUILDING PERMITS BEING ISSUED.
 2. CROSS ACCESS/PARKING/UTILITY AGREEMENT MAY BE
 REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 04-09-2014 Cont ID  
Sent By aaponte Date 04-09-2014 Time 11:03 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
2014-04-09 12:29:221. EXISTING DOOR ON NEW PROPERTY LINE SHALL BE CLOSED.
 2. EXISTING PARKIGN DRIVEWAYS SEEMS TO CROSS THE NEW
 PROPERTY LINE. PARKING LAYOUT SHALL BE REDESIGN OR A
 CROSS ACCESS AGREEMENT SHALL BE APPROVED.
 3. PROPERTY RE-PLAT WILL BE REQUIRED BEFORE ANY
 BUILDING PERMIT FOR RENOVATIONS OF EXISTING BUILDING
 CAN BE APPROVED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.