Plan Review Details - Project Z14020011
Plan Review Stops For Project Z14020011
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pleduc Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date 03-07-2014 Cont ID  
Sent By pleduc Date 03-07-2014 Time 16:45 Rev Time 0.00
Received By pleduc Date 03-07-2014 Time 16:05 Sent To  
Notes
2014-03-07 16:24:59THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. IT WOULD APPEAR THAT THE PROPOSED PROJECT WOULD NEED
 TO MEET THE REQUIRMENTS OF CHAPTER 27, HOTELS AND
 DORMITORIES, NFPA 101, LIFE SAFETY CODE, FLORIDA 2010
 EDITION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. A MONITORED FIRE ALARM AND SPRINKLER SYSTEM IS
 REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 6. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE.
  
 7. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN.
  
 8. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 9. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 10. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 11. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 12. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
 13. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 14. THE FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 16. NOTICE REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 04-08-2014 Cont ID  
Sent By tward Date 04-08-2014 Time 15:11 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2014-04-08 15:16:451. WEIR TO BE ADJUSTED IN EXISTING STRUCTURE SHOULD BE
 ON THE SOUTH WALL OF THE CATCH BASIN.
 2. RECOMMEND MINIMUM 15" DIAMETER DRAINAGE PIPE TO
 REDUCE THE POSSIBILITY OF PIPE BLOCKAGE FROM LEAVES AND
 SEDIMENT GETTING INTO THE SYSTEM.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-01-2014 Cont ID  
Sent By tward Date 03-01-2014 Time 16:08 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2014-03-01 16:17:421. PROVIDE COPY OF SFWMD ERP PRIOR TO START OF
 CONSTRUCTION.
 2. PROVIDE COPY OF NPDES CGP PERMIT PRIOR TO START OF
 CONSTRUCTION.
 3. PROVIDE DRAINAGE CALCULATIONS, INCLUDING LAND USE
 BREAKDOWN (PERVIOUS, IMPERVIOUS, BUILDING, ETC), WATER
 QUALITY TREATMENT, ETC., WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 4. PROVIDE SWPPP PLAN WITH THE CITY'S ENGINEERING
 PERMIT APPLICATION.
 5. NO ENGINEERING PLANS OR CALCULATIONS PROVIDED.
 6. IDENTIFY WHICH DRAINAGE STRUCTURES WILL HAVE WEIR(S)
 AND/OR BAFFLES.
 7. SURVEY VERTICAL DATUM LISTED AS NAVD 1988. VERTICAL
 DATUM NEEDS TO BE NGVD 1929 PER CITY CODE.
 8. GENERAL NOTE 1 ON UTILITY PLAN C-1 INDICATES
 ELEVATIONS ARE REFERENCED TO NGVD 1929. ELEVATION DATA
 PROVIDED FOR EXISTING CATCH BASIN ON SHEET C-2 MATCHES
 DATA PROVIDED ON SURVEY (NAVD 1988 DATUM).
 9. PROVIDE WEIR ELEVATION FOR EXISTING DRAINAGE CONTROL
 STRUCTURE.
 10. SHOW EXISTING AND PROPOSED UTILITIES ON THE
 LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 04-07-2014 Time   Rev Time 0.00
Received By bcollins Date 04-07-2014 Time 16:54 Sent To  
Notes
2014-04-07 16:56:14STOP SIGNS AT MAIN (3 LEG) INTERSECTION SHOULD HAVE ALL
 WAY PLAQUE ADDED. SHOULD ADD PED. CROSSING SIGNS AT
 CROSSWALKS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date 03-11-2014 Time   Rev Time 0.00
Received By bcollins Date 03-11-2014 Time 16:32 Sent To  
Notes
2014-03-11 16:34:45NO TRAFFIC SIGNAGE OR MARKINGS ON SITE PLAN. WHAT IS
 THE ACCESSS TO THE NEW AREA? IS "FUTURE ACCESS ROUTE"
 IN PLACE?

Review Stop Z ZONING
Rev No 2 Status F Date 04-08-2014 Cont ID  
Sent By dkittred Date 04-08-2014 Time 11:10 Rev Time 0.00
Received By dkittred Date 03-25-2014 Time 11:09 Sent To  
Notes
2014-04-08 11:10:19PLANNING AND ZONING COMMENTS:
  
 4/8/2014
  
 COMMENTS TO BE ADDRESSED:
  
 1. THE EMAIL PROVIDED AS SUPPORT FOR THE COMMENT
 REGARDING THE SIDEWALK/PATHWAY BEING OUTSIDE THE LEASE
 AREA DOES NOT SPECIFICALLY ACKNOWLEDGE THE SIDEWALK
 WALK AND IT IS UNCLEAR IF THE VERSION OF THE SITE PLAN
 REVIEWED AND COMMENTED ON IN THE EMAIL CONTAINED THE
 SIDEWALK OUTSIDE THE LEASE AREA AT THAT TIME. PLEASE
 PROVIDE A RESPONSE FROM ST. MARY'S SPECIFICALLY
 INDICATING THIS WORK OUTSIDE THE LEASE AREA IS
 PERMITTED. (PREVIOUS COMMENT 9)
  
 2. PRELIMINARY LIGHTING HAS BEEN REVIEWED VIA EMAIL AND
 WAITING FOR FINAL PAPER SUBMITTAL. (PREVIOUS COMMENT
 16)
  
 3. DESIGN GUIDELINES (SECTION 2(G)) FOR THE ST. MARY'S
 CSPD REQUIRED THAT A MINIMUM OF 50% OF THE REQUIRED
 SHRUBS BE NATIVE TO PALM BEACH COUNTY OR DESIGNATED AS
 VERY DROUGHT TOLERANT. LANDSCAPE SHEET 1 OF 2 INDICATES
 THAT 100% OF THE REQUIRED SHRUBS ARE NATIVE, HOWEVER,
 LANDSCAPE SHEET 2 OF 2 DOES NOT INDICATE IN THE CHART
 THAT ANY OF THE SHRUBS ARE NATIVE. PLEASE CLARIFY THIS
 REFERENCE TO THE SHRUBS BEING NATIVE. OR WAS THE ITEM
 INTENDED TO MEAN THAT 100% OF THE REQUIRED SHRUBS ARE
 DROUGHT TOLERANT? IF CHANGES ARE REQUIRED BASED ON THE
 RESPONSE TO THIS ITEM PLEASE CONTACT ME TO DETERMINE IF
 THE CHANGE CAN BE ADDRESSED AT THE TIME OF SUBMITTAL OF
 THE LANDSCAPE PERMIT FOR THE SITE. (PREVIOUS COMMENT
 19)
  
 4. COMMENTS ON THE TREE ALTERATION PERMIT ARE UNDER
 PROJECT NUMBER Z14020013.
  
  
 CORRECTIONS THAT CAN BE MADE AT THE TIME OF SUBMITTAL
 OF A BUILDING/LANDSCAPE PERMIT:
  
 5. DISTANCE BETWEEN DOUBLE STRIPES ON THE PARKING
 DETAIL ON SHEET C-3 SHOULD BE 12" RATHER THAN 16". THE
 PLAN PACKET INCLUDES TWO STRIPING DETAILS IN THE
 PACKET. YOU MAY WANT TO OMIT ONE.
  
 6. BICYCLE PARKING SPACES PROVIDED IS 2 RATHER THAN 4.
 RACKS HOLD 1 BICYCLE EACH.
  
 7. CALCULATION FOR HANDICAP SPACES IS BASED ON THE
 TOTAL NUMBER OF SPACES PROVIDED, NOT THE MINIMUM
 PARKING REQUIRED BY CODE. AS A RESULT, 2 HANDICAP
 SPACES ARE REQUIRED AND 2 HAVE BEEN PROVIDED.
  
 8. THE LIVE OAK PROPOSED ON THE SOUTHEAST CORNER OF THE
 SITE NEEDS TO BE LOCATED ON THE NORTH SIDE OF THE
 SIDEWALK WITHIN THE LANDSCAPE PARKING ISLAND UNLESS
 JUSTIFICATION IS PROVIDED FOR ITS LOCATION.
 ADDITIONALLY, MOVING THE TREE MORE NORTHWARD WILL AVOID
 ANY VISUAL OBSTRUCTIONS AT THE TIME THE FUTURE
 CONNECTION ROAD IS CONSTRUCTED.
  
 9. IT APPEARS THAT LOCATIONS FOR THE AC UNITS HAVE BEEN
 IDENTIFIED ON THE PLANS WITH SQUARES, BUT THEY ARE NOT
 LABELED. SOME OF THESE 'SQUARES' HAVE LANDSCAPING
 PROPOSED OVER TOP OF THESE AREAS. PLEASE IDENTIFY THESE
 SQUARES AND CONFLICTS WITH THE LANDSCAPING. (PREVIOUS
 COMMENT 13)
  
 10. PER THE FIRE DEPT., THE FDC SHOULD BE MOVED TO THE
 SAME LOCATION AS THE PROPOSED FIRE HYDRANT NEAR THE
 DUMPSTER ENCLOSURE. (PLEASE CONTACT PETER LEDUC, FIRE
 MARSHAL WITH ANY QUESTIONS - (561)804-4709
 [email protected].)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 03-05-2014 Cont ID  
Sent By dkittred Date 03-05-2014 Time   Rev Time  
Received By dkittred Date   Time   Sent To  
Notes
2014-03-05 15:18:11PLANNING AND ZONING COMMENTS:
  
 3/5/14
  
 SITE PLAN:
  
 1. PARKING STRIPING DETAIL NEEDS TO BE UPDATED (GRAPHIC
 WILL BE PROVIDED FOR REFERENCE).
  
 2. PROVIDE BICYCLE PARKING IN ACCORDANCE WITH ZLDR SEC.
 94-485(Q).
  
 3. PROVIDE LOADING AREA IN ACCORDANCE WITH ZLDR SEC.
 94-485(P).
  
 4. INCLUDE PARKING CALCULATION FOR HANDICAP ACCESSIBLE
 SPACES.
  
 5. THE LOT COVERAGE CALCULATION ON SHEET SP1.0 APPEARS
 TO BE THE LOT SIZE RATHER THAN LOT COVERAGE
 CALCULATION. PLEASE VERIFY.
  
 6. TRAFFIC CONCURRENCY LETTER FROM PALM BEACH COUNTY
 WILL BE REQUIRED BEFORE FINAL APPROVAL.
  
 7. MINIMUM HEIGHT OF DUMPSTER ENCLOSURE WALL IS SIX (6)
 FEET (ZLDR SEC. 94-444(B) FIGURE XIV-3). PLEASE CLARIFY
 PROPOSED HEIGHT OF DUMPSTER ON THE PLAN.
  
 8. PLEASE CLARIFY LEASE AREA VERSUS PROPERTY LINE.
  
 9. PLEASE CLARIFY THE EASTERN SIDEWALK LOCATION. IT
 APPEARS TO BE OUTSIDE THE LEASE AREA.
  
 10. THERE IS A SIDEWALK ON THE EAST SIDE OF THE
 HANDICAP PARKING SPACES PROVIDING A CONNECTION TO THE
 SOUTH. THIS CONNECTION IS ONLY SHOWN ON THE SITE PLAN
 (SP1.0) AND NOT CARRIED THROUGH TO THE OTHER SHEETS.
 PLEASE CORRECT.
  
 11. HOW WILL PEDESTRIANS USING THE SIDEWALK AROUND THE
 ROUNDABOUT BE PROTECTED FROM VEHICLES IN THE
 ROUNDABOUT? IS THE SIDEWALK RAISED?
  
 12. THE SIDEWALK ALIGNMENT IN THE LANDSCAPE ISLAND ON
 THE SOUTHEAST CORNER OF THE ROUNDABOUT IS NOT
 CONSISTENT BETWEEN THE SITE PLAN AND LANDSCAPE PLAN.
 ADDITIONALLY, A FIRE HYDRANT IS BEING PROPOSED ON THE
 UTILITY PLAN WITHIN THIS LANDSCAPE ISLAND WHICH WILL
 AFFECT THE PROPOSED PLANTINGS.
  
 13. WILL THERE BE ANY OTHER OUTDOOR MECHANICAL
 EQUIPMENT OR UTILITIES IN ADDITION TO THE GENERATOR AND
 TRANSFORMER SHOWN ON THE SITE PLAN SUCH AS POOL
 EQUIPMENT, AIR CONDITIONING UNITS, BACKFLOW PREVENTERS?
 IF SO, PLEASE INDICATE AND PROVIDE PROPER SCREENING.
 ADDITIONAL SCREENING SHOULD ALSO BE PROPOSED AROUND THE
 TRANSFORMER.
  
 14. WHAT IS THE TRAFFIC CONTROL PROPOSED FOR THE
 ALIGNMENT OF THE NEW DRIVEWAYS ON THE PLAN? HAS ANY
 CONSIDERATION BEEN MADE FOR THE TRAFFIC FLOW WITH THE
 FUTURE ENTRY ROAD ON THE MASTER PLAN?
  
 15. SITE PLAN INDICATES THE EXISTING FREESTANDING SIGN
 TO BE RELOCATED. PLEASE INCLUDE ON THE SITE PLAN WHERE
 THE FREESTANDING SIGN WILL BE RELOCATED TO SO IT CAN BE
 ACCOUNTED FOR IN THE MINOR PD AMENDMENT. IF A NEW
 FREESTANDING SIGN WILL BE CONSTRUCTED RATHER THAN
 RELOCATED, COMPLIANCE WITH THE ST. MARY'S CSPD MASTER
 SIGNAGE PROGRAM WILL NEED TO BE DEMONSTRATED.
 A NEW 3' X 2' DIRECTIONAL PARKING SIGN IS BEING
 PROPOSED ON THE SOUTH PORTION OF THE SITE. ADDITIONAL
 DESIGN INFORMATION IS NEEDED ON THIS SIGN TO EVALUATE
 CONSISTENCY OF THIS SIGN WITH THE MASTER SIGNAGE PLAN
 FOR ST. MARY'S CSPD.
  
 16. PLEASE REVIEW LIGHTING GUIDELINES OF THE ST. MARY'S
 CSPD AND DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS
 OR NOTATE WHERE THE PLAN DEVIATES FROM THE GUIDELINES.
 IT WILL BE IMPORTANT THAT THE PROPOSED LIGHTING
 FIXTURES ARE AESTHETICALLY COMPATIBLE WITH WHAT IS
 EXISTING ON THE ST. MARY'S CAMPUS.
  
 17. TREE ALTERATION PERMIT WAS RECEIVED BUT IT ONLY
 CONTAINED A LIST OF TREES TO BE REMOVED. A SITE PLAN
 INDICATING THE LOCATION OF THE TREES TO BE REMOVED AND
 CALCULATION FOR REPLACEMENT WILL NEED TO BE SUBMITTED
 PER ZLDR SEC. 94-448.
  
 LANDSCAPING:
  
 18. 75% OF REQUIRED TREES ARE TO BE SHADE TREES. SHEET
 1 OF 2 OF THE LANDSCAPE PLAN INDICATES ONLY 63% IS
 PROVIDED. IS THERE A REASON THE 75% CANNOT BE MET?
  
 19. THE DESIGN GUIDELINES (SECTION 2(G)) FOR THE ST.
 MARY'S CSPD REQUIRE THAT A MINIMUM OF 75% OF THE TREES
 AND PALMS REQUIRED BY CODE AND THE GUIDELINES BE NATIVE
 TO PALM BEACH COUNTY. SIMILARLY A MINIMUM OF 50% OF THE
 SHRUBS REQUIRED TO BE INSTALLED SHALL BE NATIVE TO PALM
 BEACH COUNTY.
  
 20. LOCATION OF UTILITIES THAT MAY IMPACT THE PLANTINGS
 SHOULD BE DEPICTED ON THE LANDSCAPE PLAN WHICH INCLUDES
 BUT IS NOT LIMITED TO LOCATION OF UTILITY AND DRAINAGE
 EASEMENTS, OVERHEAD LINES, WATER METERS, TRANSFORMERS
 CHECK VALVES, CLEAN-OUTS, FIRE HYDRANTS, LIGHT POLES,
 ETC.
  
 21. THE DIVIDER MEDIAN LANDSCAPE AREA ON THE WESTERN
 SIDE OF THE PARKING LOT SHALL BE A MINIMUM OF 5' IN
 WIDTH EXCLUDING THE CURBING.
  
 22. PLEASE REVIEW AND VERIFY COMPLIANCE WITH SECTION
 6(D) REQUIRED PLANT MATERIAL SPECIFICATIONS OF THE ST.
 MARY'S CSPD REGARDING PLANT HEIGHT, CLEAR TRUNK, AND
 SPREAD REQUIREMENTS.
  
 GENERAL COMMENTS FOR RESUBMITTING:
  
 A. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 DEPARTMENTS IN A WRITTEN FORMAT WHEN RESUBMITTING.
  
 B. 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE REDUCED COPY AND AN ELECTRONIC
 COPY OF ALL PLANS. YOU MAY VERIFY PRIOR TO RESUBMITTAL
 IF A REDUCED NUMBER PLANS CAN BE SUBMITTED.
  
 C. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 D. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  