Plan Review Details - Project Z14010020
Plan Review Stops For Project Z14010020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 02-12-2014 Cont ID  
Sent By rbrown Date 02-12-2014 Time 11:08 Rev Time 0.00
Received By rbrown Date 02-12-2014 Time 11:07 Sent To  
Notes
2014-02-12 11:08:40DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE PLAN AMENDMENT. IT IS NOT A REVIEW FOR FULL
 COMPLIANCE WITH FLORIDA BUILDING CODE. THE FOLLOWING
 COMMENTS ARE TO BE ADDRESSED FOR PERMITTING.
  
 2. SHEET A1.0 SITE PLAN. THE SWING OF THE PARKING LOBBY
 ENTRANCE DOORS IS TOO CLOSE TO THE STEPS WHICH IMPEDES
 ACCESS TO AND FROM THE ACCESSIBLE PARKING SPACES. PER
 SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE
 PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST
 POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN OF
 ACCESSIBLE PARKING
 SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
 3. SHEET A1.0 SITE PLAN. NEITHER OF THE ACCESSIBLE
 PARKING SPACES IS CALLED OUT AS VAN ACCESSIBLE. PER
 SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN
 EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. SHEET A1.0 SITE PLAN. THE EXIT DISCHARGE DOOR FROM
 THE WEST STAIR DISCHARGES INSIDE THE BUILDING. PER
 SECTION 1027.1 OF FLORIDA BUILDING CODE, THE EXIT
 DISCHARGE DOOR SHALL DISCHARGE DIRECTLY TO THE OUTSIDE
 SO THAT USERS DO NOT RE-ENTER A FIRE RISK AREA WHEN
 LEAVING THE STAIR ENCLOSURE.
  
 5. SHEET A2.5 LEVEL 6 ROOF PLAN. ONLY ONE EXIT STAIR IS
 SHOWN SERVING THE ROOF GARDEN/DECK. PER SECTION 1021.1
 OF FLORIDA BUILDING CODE, TWO EXITS ARE REQUIRED.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-02-11 15:09:34CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
 ENTRY GATES INTO THE COMPLEX WILL BE ACCESS CONTROLLED?
 WILL THE LOBBY BE MANNED?
  
 A. ENTRY INTO THE POOL AREA FROM PUBLIC ACCESS AREAS
 (GATES) NEED ACCESS CONTROL AND SHALL BE RESTRICTED, BY
 KEY, KEY FOB, OR CARD ACCESS.
 B. BICYCLE SPACES SHALL BE LOCATED IN CLOSE PROXIMITY
 TO THE FRONT OF BUILDINGS AND NOT IN PARKING LOTS.
 C. MAILBOX LOCATIONS SHALL BE VISIBLE HIGH TRAFFIC
 LOCATION
 D. CAMERAS WILL BE NEEDED IN THE LOBBY, ALL LOBBY
 ELEVATOR STOPS, CAMERA COVERING THE ENTRY FROM THE
 PARKING GARAGE INTO THE BUILDING AND ENTRY INTO THE
 SPA.
 E. CAMERAS WILL BE NEEDED TO COVER THE POOL AREA AND
 PUBLIC ACCESS ENTRIES INTO THE POOL AREA WHICH SHOULD
 ALSO BE ACCESS CONTROLLED.
 F. DOOR LEADING INTO A RESIDENTIAL UNIT SHALL BE SOLID
 CORE.
 G. EXTERIOR DOORS SHALL BE EQUIPPED WITH A 180-DEGREE
 PEEPHOLE AND NON-REMOVABLE SECURITY HINGES.
 H. ANTI-LIFTING AUXILIARY LOCKS SHALL BE INSTALLED ON
 SLIDING DOORS AND WINDOWS.
 I. ALL DOORS SHALL BE EQUIPPED WITH SINGLE CYLINDER
 DEAD BOLT LOCK WITH A MINIMUM THROW OF ONE INCH AND AN
 EMBEDMENT OF NOT LESS 5/8 INCH INTO THE HOLDING DEVICE.
 PICK PLATES SHOULD ALSO BE PLACED ALL EXTERIOR DOORS.
 J. CONVEX MIRRORS SHALL BE INSTALLED IN STAIRWELL
 ENABLING VIEWS OF UPPER AND LOWER STAIRWAYS.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 02-05-2014 Time 1620 Rev Time  
Received By   Date 02-05-2014 Time 1450 Sent To  
Notes
2014-02-05 16:17:30THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 4. ALL APARTMENT BUILDINGS SHALL COMPLY WITH NFPA 101,
 LIFE SAFETY CODE, FLORIDA 2010 EDITION, INCLUDING MORE
 SPECIFICALLY, CHAPTER 30, NEW APARTMENTS BUILDINGS.
  
 5. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 6. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 7. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR
 THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND
 INDICATED.
  
 8. ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE.
  
 9. PRESCRIPTIVE STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS FOR THE BUILDING SHALL BE PROVIDED AND
 CLEARLY INDICATED.
  
 10. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN.
  
 11. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 12. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING.
 THE ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND
 CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED.
  
 13. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 14. STAIR DETAIL SHALL BE PROVIDED INCLUDING MINIMUM
 RISE, RUN, AND TREAD DEPTH.
  
 15. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 16. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
 17. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 18. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY
 INDICATED ON THE BUILDING PLAN.
  
 19. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT
 AND/OR TENANT SHALL BE CLEARLY INDICATED AND
 ILLUSTRATED ON THE BUILDING PLAN.
  
 20. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY
 INDICATED AND ILLUSTRATED ON THE BUILDING PLAN.
  
 21. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 22. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 23. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 24. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED
 TO EACH APARTMENT AND/OR TENANT. THESE INSTRUCTIONS ARE
 TO INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND
 ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR ALARM
 ACTIVATION.
  
 25. ALL DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS
 SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE EQUIPPED
 WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR TO
 POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL BE
 CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR SCHEDULE.
  
 26. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING
 REACHES THREE LEVELS OR THIRTY FEET WHILE BEING
 CONSTRUCTED.
  
  
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date 02-11-2014 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ktucker Date 02-11-2014 Time 15:08 Sent To  
Notes
2014-02-12 11:22:44CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
 ENTRY GATES INTO THE COMPLEX WILL BE ACCESS CONTROLLED?
 WILL THE LOBBY BE MANNED?
  
 A. ENTRY INTO THE POOL AREA FROM PUBLIC ACCESS AREAS
 (GATES) NEED ACCESS CONTROL AND SHALL BE RESTRICTED, BY
 KEY, KEY FOB, OR CARD ACCESS.
 B. BICYCLE SPACES SHALL BE LOCATED IN CLOSE PROXIMITY
 TO THE FRONT OF BUILDINGS AND NOT IN PARKING LOTS.
 C. MAILBOX LOCATIONS SHALL BE VISIBLE HIGH TRAFFIC
 LOCATION
 D. CAMERAS WILL BE NEEDED IN THE LOBBY, ALL LOBBY
 ELEVATOR STOPS, CAMERA COVERING THE ENTRY FROM THE
 PARKING GARAGE INTO THE BUILDING AND ENTRY INTO THE
 SPA.
 E. CAMERAS WILL BE NEEDED TO COVER THE POOL AREA AND
 PUBLIC ACCESS ENTRIES INTO THE POOL AREA WHICH SHOULD
 ALSO BE ACCESS CONTROLLED.
 F. DOOR LEADING INTO A RESIDENTIAL UNIT SHALL BE SOLID
 CORE.
 G. EXTERIOR DOORS SHALL BE EQUIPPED WITH A 180-DEGREE
 PEEPHOLE AND NON-REMOVABLE SECURITY HINGES.
 H. ANTI-LIFTING AUXILIARY LOCKS SHALL BE INSTALLED ON
 SLIDING DOORS AND WINDOWS.
 I. ALL DOORS SHALL BE EQUIPPED WITH SINGLE CYLINDER
 DEAD BOLT LOCK WITH A MINIMUM THROW OF ONE INCH AND AN
 EMBEDMENT OF NOT LESS 5/8 INCH INTO THE HOLDING DEVICE.
 PICK PLATES SHOULD ALSO BE PLACED ALL EXTERIOR DOORS.
 J. CONVEX MIRRORS SHALL BE INSTALLED IN STAIRWELL
 ENABLING VIEWS OF UPPER AND LOWER STAIRWAYS.
  

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date   Cont ID  
Sent By   Date 02-11-2014 Time   Rev Time 0.00
Received By   Date 02-11-2014 Time   Sent To  
Notes
2014-02-11 16:12:55JLOEBIG
  
 THE NUMBER OF SANITARY SEWER LATERALS IS STILL THREE
 (3). THE 4" SANITARY LINE SHOULD BE CUT AND CAPPED IF
 THE LARGER 6" LINE IS PREFERRED (PALM BEACH LAKES
 FACING BUILDING) AND THE LOCATION OF SANITARY
 CLEAN-OUTS SHOULD BE INDICATED.
  
 THERE ARE TWO (2) 2" WATER METERS AVAILABLE, WILL THE
 TWO BUILDINGS CONTINUE TO BE SERVICED BY BOTH METERS?
 PLANS SHOW EXISTING UTILITES, HOWEVER THERE WAS NO
 INDICATION WHICH WOULD ACTUALLY BE UTILIZED.
  
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-30-2014 Cont ID  
Sent By tward Date 01-30-2014 Time 18:51 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2014-01-30 18:51:271. SITE IS TO RETAIN STORMWATER RUNOFF MEETING SFWMD
 CRITERIA AND OBTAIN PERMITS FROM THE PROPER DRAINAGE
 DISTRICT TO DISCHARGE STORMWATER INTO THEIR SYSTEM.
 2. REMOVE DRIVEWAY CONNECTION WHERE THE POOL IS
 LOCATED. REPLACE WITH TYPE' F; CURB AND CONCRETE
 SIDEWALK.
 3. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
 4. PROVIDE COPY OF FDEP CONSTRUCTION NPDES PERMIT
 BEFORE START OF CONSTRUCTION.
 5. PROVIDE STORMWATER MANAGEMENT CALCULATIONS AND
 PERVIOUS/IMPERVIOUS INFORMATION WITH ENGINEERING PERMIT
 APPLICATION.
 6. IF PAVERS ARE ALLOWED IN THE ALLEY AND IN N. OLIVE
 AVE RIGHT-OF-WAY, PROPERTY OWNER TO BE RESPONSIBLE TO
 MAINTAIN THE PAVERS AND HEADER CURBS.
 7. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 02-05-2014 Cont ID  
Sent By vnoel Date 02-05-2014 Time 09:10 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2014-02-05 09:24:501. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING SERVICES.
 2. SURVEY SHOULD BE SIGNED AND SEALED.
 3. SITE/CIVIL PLANS WILL REQUIRE A SEPARATE APPLICATION
 TO ENGINEERING SERVICES.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 02-07-2014 Time   Rev Time 0.00
Received By bcollins Date 02-07-2014 Time 10:36 Sent To  
Notes
2014-02-07 10:37:16NEED TURNAROUND FOR HANDICAPPED SPACE

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 01-28-2014 Time   Rev Time 0.00
Received By aaponte Date 01-28-2014 Time 10:39 Sent To  
Notes
2014-01-28 10:39:271. PROPOSED POOL TRELLIS IS CONSIDERED A STRUCTURE AND
 THEREFORE CANNOT ENCROACH INTO THE 10' REQUIRED
 SETBACK. THE TRELLIS IS ALSO ACTING AS A FENCE, AND AS
 SUCH EXCEEDS THE MAXIMUM 4 FEET ALLOWED WITHIN THE
 SETBACK. TRELLIS/FENCE SHALL BE MOVED BACK OR A
 VARIANCE SHALL BE REQUESTED FROM THE DAC BOARD.
 2. FENCE DETAIL ON SHEET L-2 SHALL INDICATE MAXIMUM 4'
 HEIGHT FOR FENCE.
 3. SHADE TREES ARE REQUIRED EVERY 30' ALONG THE PARKING
 LANDSCAPE BUFFER. THE WEST BUFFER NEEDS ONE ADDITIONAL
 TREE WHICH CAN BE LOCATED ON THE WEST SIDE OF THE
 PARKING ACCESS. ANOTHER TREE IS NEEDED ON THE EAST SIDE
 OF THE ENTRANCE. SHADE TREES CANNOT BE SUBSTITUTED BY
 PALMS.
 4. SHADE TREE IS MISSING FROM SOME INTERIOR ISLANDS.
 SHADE TREES CANNOT BE SUBSTITUTED BY PALMS.
 5. ALL MECHANICAL EQUIPMENT SHALL ENCLOSED WITH AN
 OPAQUE FENCE OR WALL AND SHALL BE SCREENED WITH
 LANDSCAPE IN ALL SIDES.
 6. PLEASE INDICATE IF THE PARKING SPACES WILL BE
 ASSIGNED TO EACH UNIT. IF UN-ASSIGNED, A TURN- AROUND
 SHALL BE PROVIDED FOR THE PARKING AREA UNDER THE WEST
 BUILDING. THE PROPOSED TURN AROUND SHALL BE WIDENED AS
 MUCH AS POSSIBLE, THE BIKE PARKING MAY NEED TO BE
 RELOCATED.
 7. MAXIMUM CURB CUT WIDTH IS 25' AS MEASURED PARALLEL
 TO THE STREET AT THE CURB. PLEASE CONFIRM COMPLIANCE IF
 THE CURB CUT IS NEW OR MODIFIED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-8221439
  