Plan Review Details - Project Z14010014
Plan Review Stops For Project Z14010014
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 02-11-2014 Cont ID  
Sent By rbrown Date 02-11-2014 Time 17:41 Rev Time 0.00
Received By rbrown Date 02-11-2014 Time 17:41 Sent To  
Notes
2014-02-11 17:50:37DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBLE ROUTE. AT LEAST ONE ACCESSIBLE ROUTE,
 COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA
 ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL
 ACCESSIBLE BUILDING OR FACILITY ENTRANCES. THE NEW 5
 FOOT WIDE SIDEWALK FROM LAKE AVE TO THE STORE IS RAISED
 ABOVE THE PARKING LOT BUT IT CONNECTS TO THE ACCESS
 AISLE FOR THE ACCESSIBLE PARKING SPACE WHICH IS AT
 PARKING LOT LEVEL. THERE WILL BE A CONFLICT AT THAT
 LOCATION BECAUSE ACCESS AISLE FOR THE ACCESSIBLE
 PARKING SPACE IS REQUIRED TO BE THE ENTIRE LENGTH OF
 THE PARKING SPACE AND MUST COMPLY WITH ALL PROVISIONS
 OF SECTION OF 502.3 OF FLORIDA ACCESSIBILITY CODE.
  
 3. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-02-11 17:40:39POLICE DEPARTMENT CPTED COMMENTS WERE ENTERED UNDER
 BUILDING REVIEW STOP IN ERROR. PLEASE SEE
 REVISION/SEQUENCE 2 FOR BUILDING REVIEW COMMETS.
2014-02-11 14:07:23SHOW LIGHTING FOR THE SITE. AN INSPECTION OF THE STORE
 FOR COMPLIANCE OF CITY ORDINANCES ON CONVENIENCE STORES
 MUST BE COMPLETED BEFORE OPENING. CONTACT THE CRIME
 PREVENTION OFFICE AT 822-1620; ORDINANCE IS AS FOLLOWS
  
 LIGHTING
 A. PARKING LOT AND PEDESTRIAN LIGHTING SHALL BE:
 A) HIGH EFFICACY OF GREATER THAN 70 LUMENS PER WATT
 B. LIGHT POLES 10 ? 15 FOOT HIGH FOR PEDESTRIAN-SCALE
 LIGHTING SHALL BE USED FOR ALL PEDESTRIAN WALKWAYS.
 C. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 D. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND
 WALKWAYS.
 E. PROVIDE TIMER CLOCK OR PHOTOCELL SENSOR ENGAGED
 LIGHTING FOR ABOVE OR NEAR ENTRYWAYS AND ALL PEDESTRIAN
 SIDEWALKS FOR DUSK TO DAWN OPERATION.
 F. PROVIDE LIGHTING FOR ENTRANCE SIGN.
 G. LIGHTING ON BUILDINGS SHALL BE AROUND PERIMETER OF
 ALL SIDES AND ON PEDESTRIAN WALKWAY SURROUNDING THE
 BUILDINGS.
 NUMERICAL ADDRESS
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 B. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 C. ADDRESS NUMBERS ON DOORS SHALL BE A MINIMUM OF 6
 INCHES HIGH.
 DESIGN
 A. CONVEX MIRRORS SHALL BE INSTALLED AND SIGNS AND
 SHELVES SHALL BE KEPT LOW, WHERE THEY DON?T OBSTRUCT
 EMPLOYEE VIEW.
 B. DROP SAFE SHALL BE INSTALLED.
 C. SIGNAGE INDICATING THAT LITTLE CASH IS KEPT ON HAND
 SHALL BE VISIBLE.
 D. VIDEO SURVEILLANCE EQUIPMENT AND CCTV TO DETER
 ROBBERIES SHALL BE INSTALLED, THEREBY INCREASING THE
 RISK OF IDENTIFICATION. CCTV SHOULD BE INSTALLED TO
 OBSERVE THE PUMP TRANSACTIONS, RECORD ACTIVITIES AND
 TRANSACTIONS OF A CLERK, FRONT AND REAR DOOR, COVER
 HARD TO SEE AREAS, CAR WASH, BATHROOMS, TIRE/WATER
 PUMPS, TELEPHONES AND ATMS. SYSTEM SHALL BE CAPABLE OF
 RETRIEVING AN IMAGE ON DEMAND.
 E. SILENT ALARMS TO NOTIFY POLICE IN THE EVENT OF A
 PROBLEM SHALL BE INSTALLED.
 F. DOORS NOT IN USE SHALL BE KEPT LOCKED.
 G. REAR DELIVERY DOORS SHALL HAVE A PEEPHOLE, DOOR
 CHIME DETECTOR AND LOCKING MECHANISM ON THE DOOR THAT
 ONLY FUNCTIONS WITH A KEY.
 H. STORE ACCESS DURING LATE NIGHT HOURS SHALL BE
 LIMITED BY INSTALLING BULLET-RESISTANT ENCLOSURES WITH
 PASS-THROUGH WINDOWS.
 I. EXIT DOORS SHALL HAVE HEIGHT MARKERS TO HELP
 WITNESSES PROVIDE MORE COMPLETE DESCRIPTIONS OF
 ASSAILANTS.
 J. DOOR CHIME DETECTORS TO ALERT EMPLOYEES WHEN PERSONS
 ENTER THE STORE SHALL BE INSTALLED.
 K. STORE ACCESS SHALL BE CONTROLLED WITH DOOR BUZZERS
 FOR NIGHTTIME USE OR CLOSING HOURS.
 L. BATHROOMS SHALL BE LOCATED IN A CONSPICUOUS LOCATION
 WHERE THERE WILL BE A HIGH VOLUME OF PEDESTRIAN
 TRAFFIC. KEY CONTROL SHOULD BE USED FOR ACCESS.
 M. CASHIER STATION AREA SHALL BE PLACED AT THE FRONT OF
 THE STORE FOR GOOD VISIBILITY AND ENHANCED NATURAL
 SURVEILLANCE.
 N. STORAGE AREAS WITH EXTERIOR ROLL-UP DOORS SHALL BE
 TARGET HARDENED (I.E., SECURED LOCKS CONNECTED TO ALARM
 SYSTEM).
 O. FUEL TANKS AND FUEL PUMPS SHALL BE PLACED IN AN
 ISOLATED AREA OF THE PARKING LOT AWAY FROM BUILDINGS
 AND FLOW OF PARKING LOT TRAFFIC. FUEL TANKS AND FUELS
 PUMPS SHALL BE SECURED AREAS (NOT EASILY ACCESSIBLE).
 P. ATM INSTALLATION SHALL MEET FSS 655-965
 REQUIREMENTS.
 Q. ATM SHOULD BE LOCATED WITHIN SIGHT OF CASHIER.
 R. AVOID PLACEMENT OF ATM BY THE ENTRANCE OF THE STORE.
 S. THE INSTALLATION OF THE ATM SHOULD BE PHYSICALLY
 ATTACHED TO THE FLOOR.
  
  
 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 03-10-2014 Cont ID  
Sent By pleduc Date 03-10-2014 Time 12:17 Rev Time 0.00
Received By pleduc Date 03-10-2014 Time 12:16 Sent To  
Notes
2014-03-10 12:17:102ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE RESPONSE LETTER FROM NEXUS DESIGN
 GROUP, ATTACHED TO A MEMORANDUM FROM DANIELLE
 KITTREDGE, SENIOR PLANNER, DATED MARCH 2, 2014, THE
 PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS
 HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 02-05-2014 Cont ID  
Sent By   Date   Time 1435 Rev Time 0.00
Received By pleduc Date 03-10-2014 Time 11:31 Sent To  
Notes
2014-03-10 11:36:502ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE RESPONSE LETTER FROM NEXUS DESIGN
 GROUP, ATTACHED TO MEMORANDUM FROM DANIELLE KITTREDGE,
 SENIOR PLANNER, DATED MARCH 2, 2014, THE PREVIOUSLY
 SUBMITTED FIRE PREVENTION BUREAU COMMENTS HAVE BEEN
 ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
2014-02-05 14:33:25THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. BUILDING PLANS, FLOOR PLANS, ELEVATIONS AND/OR
 DETAILED DRAWINGS WERE NOT CONTAINED IN THE SUBMITTAL
 AND CANNOT BE COMMENTED ON.
  
 2. ALL LIFE SAFETY ASPECTS OF THE PROPOSED PROJECT
 SHALL COMPLY AS A NEW OCCUPANCY UNDER THE CURRENT
 EDITION OF THE 2010 FLORIDA FIRE PREVENTION CODE AND
 ALL APPLICABLE CODES CONTAINED THEREIN.
  
 3. APPROVAL OF THIS PROJECT BY THE FIRE PREVENTION
 BUREAU IS PENDING THE SUBMITTAL OF MORE DETAILED
 INFORMATION WITH THE ACKNOWLEDGEMENT OF # 2.

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status P Date 02-12-2014 Cont ID  
Sent By ssamuels Date 02-12-2014 Time 12:04 Rev Time  
Received By ssamuels Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date 02-11-2014 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ktucker Date 02-11-2014 Time 14:04 Sent To  
Notes
2014-02-12 09:45:42SHOW LIGHTING FOR THE SITE. AN INSPECTION OF THE STORE
 FOR COMPLIANCE OF CITY ORDINANCES ON CONVENIENCE STORES
 MUST BE COMPLETED BEFORE OPENING. CONTACT THE CRIME
 PREVENTION OFFICE AT 822-1620; ORDINANCE IS AS FOLLOWS
  
 LIGHTING
 A. PARKING LOT AND PEDESTRIAN LIGHTING SHALL BE:
 A) HIGH EFFICACY OF GREATER THAN 70 LUMENS PER WATT
 B. LIGHT POLES 10 ? 15 FOOT HIGH FOR PEDESTRIAN-SCALE
 LIGHTING SHALL BE USED FOR ALL PEDESTRIAN WALKWAYS.
 C. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 D. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND
 WALKWAYS.
 E. PROVIDE TIMER CLOCK OR PHOTOCELL SENSOR ENGAGED
 LIGHTING FOR ABOVE OR NEAR ENTRYWAYS AND ALL PEDESTRIAN
 SIDEWALKS FOR DUSK TO DAWN OPERATION.
 F. PROVIDE LIGHTING FOR ENTRANCE SIGN.
 G. LIGHTING ON BUILDINGS SHALL BE AROUND PERIMETER OF
 ALL SIDES AND ON PEDESTRIAN WALKWAY SURROUNDING THE
 BUILDINGS.
 NUMERICAL ADDRESS
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 B. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 C. ADDRESS NUMBERS ON DOORS SHALL BE A MINIMUM OF 6
 INCHES HIGH.
 DESIGN
 A. CONVEX MIRRORS SHALL BE INSTALLED AND SIGNS AND
 SHELVES SHALL BE KEPT LOW, WHERE THEY DON'T OBSTRUCT
 EMPLOYEE VIEW.
 B. DROP SAFE SHALL BE INSTALLED.
 C. SIGNAGE INDICATING THAT LITTLE CASH IS KEPT ON HAND
 SHALL BE VISIBLE.
 D. VIDEO SURVEILLANCE EQUIPMENT AND CCTV TO DETER
 ROBBERIES SHALL BE INSTALLED, THEREBY INCREASING THE
 RISK OF IDENTIFICATION. CCTV SHOULD BE INSTALLED TO
 OBSERVE THE PUMP TRANSACTIONS, RECORD ACTIVITIES AND
 TRANSACTIONS OF A CLERK, FRONT AND REAR DOOR, COVER
 HARD TO SEE AREAS, CAR WASH, BATHROOMS, TIRE/WATER
 PUMPS, TELEPHONES AND ATMS. SYSTEM SHALL BE CAPABLE OF
 RETRIEVING AN IMAGE ON DEMAND.
 E. SILENT ALARMS TO NOTIFY POLICE IN THE EVENT OF A
 PROBLEM SHALL BE INSTALLED.
 F. DOORS NOT IN USE SHALL BE KEPT LOCKED.
 G. REAR DELIVERY DOORS SHALL HAVE A PEEPHOLE, DOOR
 CHIME DETECTOR AND LOCKING MECHANISM ON THE DOOR THAT
 ONLY FUNCTIONS WITH A KEY.
 H. STORE ACCESS DURING LATE NIGHT HOURS SHALL BE
 LIMITED BY INSTALLING BULLET-RESISTANT ENCLOSURES WITH
 PASS-THROUGH WINDOWS.
 I. EXIT DOORS SHALL HAVE HEIGHT MARKERS TO HELP
 WITNESSES PROVIDE MORE COMPLETE DESCRIPTIONS OF
 ASSAILANTS.
 J. DOOR CHIME DETECTORS TO ALERT EMPLOYEES WHEN PERSONS
 ENTER THE STORE SHALL BE INSTALLED.
 K. STORE ACCESS SHALL BE CONTROLLED WITH DOOR BUZZERS
 FOR NIGHTTIME USE OR CLOSING HOURS.
 L. BATHROOMS SHALL BE LOCATED IN A CONSPICUOUS LOCATION
 WHERE THERE WILL BE A HIGH VOLUME OF PEDESTRIAN
 TRAFFIC. KEY CONTROL SHOULD BE USED FOR ACCESS.
 M. CASHIER STATION AREA SHALL BE PLACED AT THE FRONT OF
 THE STORE FOR GOOD VISIBILITY AND ENHANCED NATURAL
 SURVEILLANCE.
 N. STORAGE AREAS WITH EXTERIOR ROLL-UP DOORS SHALL BE
 TARGET HARDENED (I.E., SECURED LOCKS CONNECTED TO ALARM
 SYSTEM).
 O. FUEL TANKS AND FUEL PUMPS SHALL BE PLACED IN AN
 ISOLATED AREA OF THE PARKING LOT AWAY FROM BUILDINGS
 AND FLOW OF PARKING LOT TRAFFIC. FUEL TANKS AND FUELS
 PUMPS SHALL BE SECURED AREAS (NOT EASILY ACCESSIBLE).
 P. ATM INSTALLATION SHALL MEET FSS 655-965
 REQUIREMENTS.
 Q. ATM SHOULD BE LOCATED WITHIN SIGHT OF CASHIER.
 R. AVOID PLACEMENT OF ATM BY THE ENTRANCE OF THE STORE.
 S. THE INSTALLATION OF THE ATM SHOULD BE PHYSICALLY
 ATTACHED TO THE FLOOR.
  
  
 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status F Date   Cont ID  
Sent By JLoebig Date 03-25-2014 Time   Rev Time 0.00
Received By   Date   Time   Sent To PU
Notes
2014-03-25 14:52:47 
 3/25/2014
  
  
 DURING OUR FIRST REVIEW WE ASKED THAT ALL OF THE
 EXISTING AND ANY NEW WATER/SANITARY SEWER UTILITIES BE
 IDENTIFIED ON THE PLANS SUBMITTED FOR REVIEW. THE WATER
 WAS IDENTIFIED IN THE FIRST REVIEW HOWEVER, THE
 SANITARY SEWER WAS NOT.
  
 THIS CONCERN HAS NOT BEEN REMEDIED WITH THIS LATEST
 SUBMISSION FOR PLAN REVIEW.
  
 ALTHOUGH THE BUILDING LOCATION HAS NOT CHANGED, WE
 WOULD LIKE THE OPPORTUNITY TO REVIEW THE PLACEMENT OF
 LANDSCAPING, OVERHEAD UTILITIES RELATIVE TO THE
 LOCATION OF THE SITES' SANITARY CLEAN-OUT AND THE
 GRAVITY SEWER LATERAL.
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 02-11-2014 Cont ID  
Sent By   Date 02-11-2014 Time   Rev Time 0.00
Received By   Date 02-11-2014 Time   Sent To  
Notes
2014-02-11 14:32:47JLOEBIG
  
 THE PUBLIC UTILITIES DEPARTMENT REQUIRES THE REVIEW AND
 APPROVAL OF THE PLANS FOR THE ACTUAL SERVICE
 CONNECTIONS; NO CIVIL DRAWINGS WERE INCLUDED IN
 APPLICATION.
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  
  
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-30-2014 Cont ID  
Sent By tward Date 01-30-2014 Time 18:19 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2014-01-30 18:19:391. NO ENGINEERING PLANS SUBMITTED.
 2. SITE IS TO RETAIN STORMWATER RUNOFF MEETING SFWMD
 CRITERIA AND OBTAIN PERMITS FROM THE PROPER DRAINAGE
 DISTRICT TO DISCHARGE STORMWATER INTO THEIR SYSTEM.
 3. HANDICAP PARKING SPACE DETAIL - SIDEWALK AND CURB TO
 BE FLUSH WITH ACCESS AISLE.
 4. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 03-10-2014 Cont ID  
Sent By vnoel Date 03-10-2014 Time 11:02 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2014-03-10 11:02:57UNITY OF TITLE APPLICATION WAS RECEIVED.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 02-05-2014 Cont ID  
Sent By vnoel Date 02-05-2014 Time 08:48 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2014-02-05 09:05:361. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING SERVICES.
 2. DUMPSTER DOES NOT MEET CITY STANDARDS. SEE
 ENGINEERING WEBSITE FOR STANDARD DETAIL.
 3. NO ENGINEERING PLANS PROVIDED. EXISTING
 CONCRETE/ASPHALT SHOULD BE OVERLAYED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 02-07-2014 Time   Rev Time 0.00
Received By bcollins Date 02-07-2014 Time 10:30 Sent To  
Notes
2014-02-07 10:30:41NO COMMENTS

Review Stop Z ZONING
Rev No 2 Status P Date 03-06-2014 Cont ID  
Sent By dkittred Date 03-06-2014 Time 14:44 Rev Time 0.00
Received By dkittred Date 03-04-2014 Time 14:03 Sent To  
Notes
2014-03-06 14:40:38PLANNING AND ZONING COMMENTS:
  
 3/6/14
  
 UPON REVIEW OF THE REVISED PLANS, THE FOLLOWING ARE
 OUTSTANDING COMMENTS THAT WILL BE MADE CONDITIONS OF
 APPROVAL:
  
 1. PARKING STRIPING DETAIL WAS ONLY PARTIALLY UPDATED.
 PLAN DOES NOT INCLUDE DOUBLE STRIP IN BOTH SIDES OF THE
 HANDICAP PARKING SPACE AND INSIDE LINES OF THE HANDICAP
 PARKING SPACE SHALL BE BLUE. A PDF OF THE STANDARD
 PARKING STRIPING CAN BE SENT UPON REQUEST WHICH CAN BE
 INCORPORATED INTO THE PLAN.
  
 2. PLAN DID NOT INCLUDE REQUIRED BICYCLE PARKING [ZLDR
 SEC. 94-485(Q)].
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 02-13-2014 Cont ID  
Sent By dkittred Date 01-28-2014 Time 14:47 Rev Time  
Received By dkittred Date   Time   Sent To  
Notes
2014-02-13 08:58:28PLANNING AND ZONING ADDITIONAL COMMENT (ADDED 2/13/14):
  
 1. PROVIDE A BICYCLE PARKING SPACE ON THE SITE IN
 COMPLIANCE WITH ZLDR SEC. 94-485(Q).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-01-28 14:45:09PLANNING AND ZONING COMMENTS
  
 1/28/14
  
 1. STRIPING DETAIL FOR PARKING SHALL BE UPDATED TO
 REFLECT A DOUBLE LINE DETAIL PER 'STALL PAINTING
 DETAIL' IN ZLDR SEC. 94-485.
  
 2. ADDITIONAL INFORMATION IS REQUIRED FOR THE DUMPSTER
 DETAIL TO DEMONSTRATE COMPLIANCE WITH ZLDR SEC. 94-444,
 FIGURE XIV-3. IF YOU ARE PROPOSING WIDTH OR DEPTH
 DIMENSION DIFFERENT FROM THE STANDARD DETAIL, PLEASE
 CONTACT MANNY GONZALEZ IN THE ENGINEERING DEPT.
 (561-494-1085) TO DISCUSS IF A DIFFERENT WIDTH OR DEPTH
 WOULD BE PERMITTED.
  
 3. THE CITY OF WEST PALM BEACH USES 'GC' AS THE
 ABBREVIATION FOR GENERAL COMMERCIAL RATHER THAN 'CG'.
 PLEASE CORRECT.
  
 4. PLEASE PROVIDE A CALCULATION DEMONSTRATING
 COMPLIANCE WITH MINIMUM OPEN SPACE REQUIREMENT IN ZLDR
 SEC. 94-145(5)A. (OPEN SPACE MEANS AN OPEN UNENCLOSED
 ARE CONSISTING OF SETBACKS, LANDSCAPING, BUFFERS,
 VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES AND
 SURFACE PARKING.)
  
 5. THE REAR SETBACK FOR THE SUBJECT PROPERTY IS 5'
 RATHER THAN 15' AS THIS PORTION OF THE PROPERTY DOES
 NOT ABUT A RESIDENTIAL ZONING DISTRICT. PLEASE CORRECT
 ON PLANS. ADDITIONALLY, THE REQUESTED WAIVER FOR THE
 REAR BUILDING SETBACK WILL NOT BE REQUIRED. PLEASE
 REMOVE FROM YOUR REQUEST.
  
 6. PLEASE CLARIFY HOW THE DISTANCE WAS DERIVED FOR THE
 'DISTANCE FROM A RESIDENTIAL DISTRICT' WAIVER. WHEN TWO
 DIFFERENT ZONING DISTRICT ABUT, THE CENTERLINE OF THE
 STREET IS WHERE ONE ZONING DISTRICT BEGINS AND THE
 OTHER ENDS. BASED ON THE SURVEY SUBMITTED, THE WAIVER
 REQUEST WOULD NEED TO BE FOR 30 FEET RATHER THAN 27.5
 FEET.
  
 7. UNDER WAIVER REQUESTS, PLEASE VERIFY THE SETBACKS
 AND PROPOSED WAIVERS FOR THE SETBACK OF THE CANOPY,
 SIGN, AND TANKS. BASED ON THE PLAN AND SURVEY SUBMITTED
 THE CANOPY SETBACK IS 15', SIGN IS APPROXIMATELY 5',
 AND IT IS UNCLEAR WHAT THE SETBACK OF THE TANKS ARE.
  
 LANDSCAPING:
  
 8. CONTINUE SHRUBS AROUND SOUTHERN PORTION OF THE
 DUMPSTER ENCLOSURE.
  
 9. THERE ARE OVERHEAD POWER LINES ALONG LAKE AVENUE AND
 ALLEY TO THE NORTH. PLEASE REVIEW FPL 'RIGHT TREE,
 RIGHT PLACE' GUIDELINES FOR TREE PLACEMENT.
  
 10. PLEASE VERIFY THE MINIMUM TREE (SHADE AND
 FLOWERING) AND SHRUB REQUIREMENT CALCULATION PROVIDED
 (ZLDR SEC. 94-442(B)(2)B.). THE TOTAL OPEN SPACE
 REQUIRED SHALL BE USED TO DETERMINE THE MINIMUM
 PLANTING REQUIREMENTS (ZLDR SEC. 94-442((B)(3). TREES
 PROVIDED IN THIS CALCULATION MAY INCLUDE THOSE USED FOR
 BUFFERING, SCREENING, OR TO IMPROVE THE AESTHETICS OF
 THE SITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  