Plan Review Details - Project Z13120013
Plan Review Stops For Project Z13120013
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 01-07-2014 Cont ID  
Sent By rbrown Date 01-07-2014 Time 20:15 Rev Time 0.00
Received By rbrown Date 01-07-2014 Time 20:14 Sent To  
Notes
2014-01-07 20:26:00DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. RELOCATE THE ACCESSIBLE PARKING SPACES SO THAT THEY
 ARE THE CLOSEST TO THE BUILDING ENTRANCE. PER SECTION
 208.3 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE PARKING
 SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE FOR EACH BUILDING. THE DESIGN OF ACCESSIBLE
 PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE.
  
 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE.
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 5. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-01-03 11:53:52 
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-01-06 12:26:50THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. ALL CONSTRUCTION SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2010 EDITION, INCLUDING BUT NOT
 LIMITED TO, CHAPTER 36, NEW MERCANTILE OCCUPANCIES.
  
 2. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING. THE
 ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND
 CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED.
  
 3. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE SUBMITTED PLAN.
  
 4. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 5. NOTICE REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 6. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 7. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE
 CODES AND STANDARDS.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ssamuels Date 01-07-2014 Time 17:48 Sent To  
Notes
2014-01-07 17:50:31PLEASE CORRECT LOADING ZONE REQUIREMENT BY THE CITY OF
 WEST PALM BEACH ZLDR
 MIN 10' X 25'

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date   Cont ID  
Sent By jloebig Date 01-03-2014 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-01-03 16:40:38 
 PROJECT IS PASSED AS PROPOSED.
  
 THERE ARE ADEQUATE UTILITIES CURRENTLY LOCATED IN THE
 VICINITY OF THIS PROJECT: 12" WATER MAIN FOR POTABLE
 AND FIRE PROTECTION, 8" PVC FOR SANITARY SEWER
 COLLECTIONS.
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 06-02-2014 Cont ID  
Sent By tward Date 06-02-2014 Time 20:40 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2014-06-02 20:59:25SITE PLAN APPROVED WITH THE FOLLOWING CONDITIONS:
 1. VERTICAL DATUM ON SITE PLAN SHEET C1.0 INDICATED AS
 NAVD 1988. PER CITY CODE, VERTICAL DATUM IS TO
 REFERENCE NGVD 1929.
 2. COMPLETE THE FINISHED FLOOR ELEVATION STATEMENT ON
 SHEET C1.0.
 3. INDICATE VERTICAL DATUM ON GRADING AND DRAINAGE PLAN
 SHEET C1.1.
 4. RECOMMEND 15" DIAMETER AS MINIMUM MAINLINE STORM
 PIPE SIZE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-03-2014 Cont ID  
Sent By tward Date 01-03-2014 Time 16:58 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2014-01-03 17:11:391. DRAINAGE DESIGN TO MEET SFWMD CRITERIA.
 2. PROVIDE COPY OF FDOT PERMIT BEFORE START OF
 CONSTRUCTION.
 3. PROVIDE COPY OF PALM BEACH COUNTY RIGHT-OF-WAY
 PERMIT BEFORE START OF CONSTRUCTION.
 4. PROVIDE SIGNED AND SEALED SWPPP AND FINAL PGD PLANS
 WITH ENGINEERING PERMIT APPLICATION.
 5. PROVIDE SIGNED AND SEALED DRAINAGE CALCULATIONS WITH
 ENGINEERING PERMIT APPLICATION.
 6. VERTICAL DATUM ON SURVEY AND ENGINEERING PLANS NEEDS
 TO BE NGVD 1929.
 7. INDICATE CONTROL STRUCTURE LOCATION FOR DRAINAGE
 SYSTEM.
 8. SHOW LOCATIONS OF DOWN SPOUTS CONNECTING INTO
 DRAINAGE SYSTEM. DOWN SPOUTS SHOULD CONNECT DIRECTLY
 INTO CATCH BASINS OR DRAINAGE MANHOLES WHERE EVER
 POSSIBLE.
 9. SHOW ALL PROPOSED AND EXISTING UTILITIES ON
 LANDSCAPE PLANS. DRAINAGE IS NOT SHOWN.
 10. VERIFY OWNERSHIP OF EXISTING SANITARY SEWER SYSTEM
 THAT IS BEING CONNECTED TO. WILL EASEMENT BE NEEDED FOR
 LATERAL CONNECTION OUTSIDE THE APPLICANT'S PROPERTY?
 11. AVOID PLANTING TREES WITHIN 5 FEET OF UNDERGROUND
 UTILITIES.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 05-30-2014 Cont ID  
Sent By vnoel Date 05-30-2014 Time 08:41 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-31-2013 Cont ID  
Sent By vnoel Date 12-31-2013 Time 09:15 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2013-12-31 10:27:311. SURVEY NEEDS TO BE SIGNED AND SEALED.
 2. VERTICAL DATUM IS NGVD-29 PER CITY CODE. REVISE
 SURVEY AND OTHER PLANS ACCORDINGLY.
 3. SITE/CIVIL PLANS WILL NEED A SEPARATE SUBMITTAL TO
 ENGINEERING SERVICES.
 4. ENTRANCE OFF 45TH WILL REQUIRE PB COUNTY PERMIT.
 MILITARY TRAIL WILL REQUIRE FDOT PERMIT. BOTH WILL BE
 REQUIRED PRIOR TO ANY CITY PERMITS.
 5. DUMPSTER ENCLOSURE AND LOCATION WILL REQUIRE
 APPROVAL OF FERDINAND RIVERA, SANITATION SUPERVISOR.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 06-02-2014 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date 01-07-2014 Time   Rev Time 0.00
Received By bcollins Date 01-07-2014 Time 08:26 Sent To  
Notes
2014-01-07 16:31:17SITE DRIVEWAYS NEED TO BE APPROVED BY PALM BEACH COUNTY
 (45TH STREET) AND FDOT (MILITARY TRAIL).

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 08-15-2014 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-08-15 13:59:33SITE PLAN APPROVAL IS CONTIGENT ON THE PROJECT
 RECEIVING ROW PERMITS FROM FDOT AND THE COUNTY FOR THE
 ACCESS POINTS ON MILITARY TRAIL AND 45TH STREET. COPIES
 OF THESE PERMITS WILL NEED TO BE SUBMITTED TO THE
 PLANNING DIVISION PRIOR TO BUILDING PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 05-28-2014 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-05-28 17:46:42ZONING COMMENTS
  
 *PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 *WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TEN
 (10) COPIES, ONE (1) REDUCED COPY (8 ? BY 11), AND AN
 ELECTRONIC COPY IN .PNG FORMAT OF ALL PLANS. PLEASE
 NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 *PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% ($200) OF THE ORIGINAL APPLICATION FEE.
  
  
 GENERAL COMMENTS:
  
 1.) EVIDENCE (I.E. WRITTEN STATEMENT) THAT THE PROPOSED
 INGRESS/EGRESS ON 45TH STREET HAS BEEN REVIEWED BY THE
 COUNTY AND THERE ARE NO ISSUES WITH THE DESIGN AND THE
 LOCATION OF THE PROPOSED ACCESS POINT.
  
 2.) EVIDENCE (I.E. WRITTEN STATEMENT) THAT THE PROPOSED
 INGRESS/EGRESS ON MILITARY TRAIL HAS BEEN REVIEWED BY
 FDOT AND THERE ARE NO ISSUES WITH THE DESIGN AND THE
 LOCATION OF THE ACCESS POINT.
  
  
 SITE PLAN:
  
 1.) THE HANDICAP PARKING STALL DETAIL IN SHEET C1.A
 DOES NOT COMPLY WITH CITY STANDARDS. PLEASE ADDRESS.
 (SEE ATTACHED DETAIL)
  
 2.) PROVIDE A DETAIL OF THE BICYCLE RACK IN SHEET C1.A.
  
 3.) THERE ARE TWO (2) DUMPSTER DETAILS IN SHEET C1.A.
 DETAIL 8 DOES NOT COMPLY WITH THE STANDARDS PROVIDED IN
 ZLDR S.94-444, FIGURE XIV-3. PLEASE ADDRESS IN SHEETS
 C1.0 (KEYNOTES) AND SHEET C1.A.
  
 4.) PLEASE ADDRESS THE WALL MOUNTED LIGHT FIXTURES IN
 SHEET C1.0. DO THE FIXTURES PROJECT 3 FT. FROM THE WALL
 (AS MEASURED IN THE SITE PLAN)? A NOTATION IN THE
 KEYNOTES WOULD BE REQUIRED.
  
 5.) WILL THE PARKING SPACES ADJACENT TO THE BUILDING
 HAVE WHEEL STOPS OR WILL THE PEDESTRIAN WALKWAY BE
 CURBED TO PREVENT VEHICULAR ACCESS? PLEASE CLARIFY AND
 ILLUSTRATE.
  
 6.) IDENTIFY THE CORRECT LOCATION OF THE PROJECT IN THE
 VICINITY MAP IN SHEET C1.0
  
 7.) PLEASE CORRECT THE FOLLOWING IN THE SITE DATA
 TABULAR: BUILDING HEIGHT PROVIDED = 23?, LOADING SPACE:
 MINIMUM AND PROVIDED = 10? X 25?.
  
  
 LANDSCAPE PLAN:
  
 1.) THE TRANSFORMER, LOCATED ON THE NORTH SIDE OF THE
 PROPERTY, SHALL BE SCREENED IN ACCORDANCE WITH ZLDR
 S.94-444(B)). PLEASE ADDRESS AND PROVIDE A DETAIL.
  
 2.) THE VISIBILITY TRIANGLES IN SHEET L1.0 ARE NOT IN
 COMPLIANCE WITH ZLDR S.94-305(E). (SEE ATTACHED DETAIL)
  
  
 PHOTOMETRIC PLAN:
  
 1.) THE LIGHTING NOTES (SHEET P1.0) REFERENCES THE CITY
 OF NORTH LAUDERDALE?S LIGHTING STANDARDS. PLEASE
 CORRECT. (REPEAT COMMENT)
  
  
 SIGNAGE PLAN:
  
 1.) THE SIGN AREA SHALL BE CALCULATED AS THE AREA WITH
 THE SMALLEST RECTANGLE THAT ENCOMPASSES ALL ELEMENTS OF
 THE SIGN. (ZLDR S.94-405)
  
 2.) THE SCALE SEEMS TO BE INCORRECT. PLEASE ADDRESS.
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 01-03-2014 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2014-01-03 11:57:07CASE NO. ISPR 13-12 (Z13120013)
 PROJECT: AUTOZONE STORE #4938
 ADDRESS: 5660 NORTH MILITARY TRAIL
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX (6)
 PAPER COPIES, ONE (1) REDUCED COPY IN 8 ? INCHES X 11
 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT CHANGES
 ON THE RESUBMITTED PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
  
 GENERAL NOTES
  
 1.) A RIGHT-OF-WAY PERMIT FROM THE COUNTY FOR THE
 PROPOSED INGRESS/EGRESS ON 45TH STREET SHALL BE
 SUBMITTED PRIOR TO SITE PLAN APPROVAL.
  
 2.) A RIGHT-OF-WAY PERMIT FROM FDOT FOR THE PROPOSED
 INGRESS/EGRESS ON MILITARY TRAIL SHALL BE SUBMITTED
 PRIOR TO SITE PLAN APPROVAL.
  
 3.) THE SURVEY DOES NOT SHOW ANY EASEMENTS ON THE
 PROPERTY; HOWEVER, THE UTILITY LETTERS STATE OTHERWISE.
 PLEASE VERIFY. ALL EXISTING AND PROPOSED EASEMENTS MUST
 BE SHOWN IN THE PLANS.
  
  
 SITE PLAN:
  
 1.) TRAFFIC CIRCULATION MOVEMENTS SHALL BE PROVIDED ON
 THE PAVEMENT TO ENSURE SAFE AND EFFICIENT TRAFFIC
 MOVEMENT WITHIN THE PROJECT. PLEASE ILLUSTRATE IN THE
 PLANS. (ZLDR S.94-485(G))
  
 2.) THE PROPOSED TURNAROUND IN THE PARKING AREA SEEMS
 SHORT AND MAY BE INADEQUATE FOR VEHICLES TO BACK OUT. A
 DETERMINATION BY THE ENGINEERING SERVICES DEPARTMENT IS
 REQUIRED.
  
 3.) THE SURVEY SHOWS AN EXISTING CONCRETE PAD AT THE
 SOUTHEAST CORNER OF THE PROPERTY. PLEASE CLARIFY WHAT
 THIS PAD IS UTILIZED FOR. APPROPRIATE SCREENING MAY BE
 REQUIRED.
  
 4.) THE SITE PLAN SHOWS A NEW 5 FT. X 5 FT. CONCRETE
 PAD AT THE NORTH SIDE OF THE PROPERTY (LABELED AS #18
 ON SHEET C1.0). CLARIFY IN THE PLANS TO WHAT THIS
 CONCRETE PAD WILL BE UTILIZED FOR. APPROPRIATE
 SCREENING MAY BE REQUIRED.
  
  
 PARKING AND LOADING:
  
 1.) PARKING STALL PAINTING DETAIL SHALL COMPLY WITH THE
 DIMENSIONS ILLUSTRATED IN ZLDR S.94-485(J), STALL
 PAINTING DETAIL. A STANDARD PARKING STALL PAINTING
 DETAIL SHALL BE PROVIDED ON SHEET C1.A (SITE DETAILS)
 FOR CONSISTENCY.
  
 2.) THE PROPOSED 20 FT. X 16 FT. LOADING ZONE DOES NOT
 MEET CODE. A MINIMUM 10 FT. X 25 FT. LOADING ZONE IS
 REQUIRED. (ZLDR S.94-485(P), TABLE XV-4)
  
 3.) PROVIDE BICYCLE PARKING. AT LEAST ONE (1) BICYCLE
 PARKING IS REQUIRED FOR THIS PROJECT PER ZLDR
 S.94-485(Q)(1). THE DESIGN OF THE BICYCLE PARKING SHALL
 COMPLY WITH THE REQUIREMENTS OF ZLDR S.94-485(Q)(2).
  
 4.) DIMENSIONS FOR A WHEEL STOP SHALL COMPLY WITH ZLDR
 S.94-443(C)(5), FIGURE XIV. THE DETAIL IN SHEET C1.A,
 SITE DETAILS, DOES REFLECT THE MINIMUM REQUIRED
 DIMENSIONS FOR A WHEEL STOP.
  
  
 LANDSCAPING:
  
 1.) VERIFY WITH FLORIDA POWER & LIGHT (FP&L) THAT THE
 PROPOSED 5 FT. WIDE LANDSCAPE BUFFER IS NOT IN CONFLICT
 WITH ITS OVERHEAD AND UNDERGROUND FACILITIES TO THE
 NORTH AND EAST SIDES OF THE PROPERTY.
  
 2.) VERIFY THAT THAT THE 5 FT. WIDE LANDSCAPE BUFFER IS
 NOT IN CONFLICT WITH THE PROPOSED DRAINAGE SYSTEM. THE
 LANDSCAPE PLAN SHOWS A PROPOSED OAK TREE IN THE 5 FT.
 BUFFER THAT MAY BE IN CONFLICT WITH THE DRAINAGE
 SYSTEM. A DETERMINATION BY THE PUBLIC WORKS AND
 ENGINEERING SERVICES DIVISION IS REQUIRED.
  
 3.) ALL TREES SHALL HAVE A MINIMUM OF 5 FT. OF CLEAR
 TRUNK SPACE. PLEASE INCLUDE THIS NOTATION IN THE PLANT
 SCHEDULE. (ZLDR S.94-445(4) A.)
  
 4.) THE REQUIRED LANDSCAPE BUFFER STRIP MAY NOT BE
 INTERRUPTED BY MORE THAN 25 PERCENT OF ITS REQUIRED
 LENGTH FOR SIGNS OR VEHICULAR INGRESS AND EGRESS. THE
 PROPOSED CURB CUT ON MILITARY TRAIL EXCEEDS THE 25
 PERCENT. (ZLDR S.94-443(B)(2))
  
 5.) AT LEAST 30 PERCENT OF THE LINEAR FEET AROUND THE
 EXTERIOR OF ALL COMMERCIAL STRUCTURES SHALL BE PLANTED
 WITH TREES, SHRUBS OR HEDGES. (ZLDR S.94-443(E)(1))
  
 6.) THE LANDSCAPED TERMINAL ISLANDS AT THE END OF EACH
 ROW OF PARKING SPACES SHALL NOT BE LESS THAN 5 FT. IN
 WIDTH AND NOT LESS THAN THE LENGTH OF THE ADJACENT
 PARKING STALL. PROVIDE DIMENSIONS FOR THE TERMINAL
 ISLANDS. MOST OF THE TERMINAL ISLANDS SEEM TO FALL
 SHORT OF THIS REQUIREMENT. (ZLDR S.94-443(C)(3)A.)
  
 7.) THE WALLS OF THE DUMPSTER ENCLOSURE SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT 2 FT.
 INTERVALS. THERE DOES NOT SEEM TO BE ADEQUATE
 LANDSCAPING AROUND THE DUMPSTER ENCLOSURE TO MEET THIS
 REQUIREMENT. (ZLDR S.94-444(B))
  
 8.) THE SITE PLAN INDICATES THAT TREES/PALMS WILL BE
 REMOVED FROM THE PROPERTY. NO TREE OR PALM SHALL BE
 REMOVED FROM THE PROPERTY WITHOUT FIRST OBTAINING A
 TREE ALTERATION PERMIT FROM THE CITY. PLEASE SUBMIT AN
 APPLICATION FOR A TREE ALTERATION PERMIT. (ZLDR
 S.94-448(D))
  
 9.) ILLUSTRATE THAT THE PROPOSED LANDSCAPING AT THE
 ROADWAY INTERSECTIONS FOR THE PROJECT, WILL NOT OBSCURE
 VISIBILITY BY PROVIDING 20 FT. X 20 FT. VISIBILITY
 TRIANGLES. THE VISIBILITY TRIANGLE MUST COMPLY WITH THE
 REQUIREMENTS OF ZLDR S. 94-305(E), FIGURE X-1.
  
 10.) THE STATEMENT THAT THE PROJECT IS EXEMPTED FROM
 ZLDR S.94-443(C)(3) FOR INTERIOR LANDSCAPED AREAS IN
 SHEET L1.0, LANDSCAPE PLAN, UNDER THE LANDSCAPE
 REQUIREMENTS, DOES NOT APPLY FOR THIS PROJECT. THE
 PROJECT MUST MEET ALL INTERIOR LANDSCAPING
 REQUIREMENTS.
  
 11.) LANDSCAPE PLAN NOTE 32 SPECIFIES ?PERMANENT
 AUTOMATIC IRRIGATION, INCLUDING ADJACENT RIGHT-OF-WAY?;
 HOWEVER, NO IRRIGATION PLANS WERE SUBMITTED. SUBMIT AN
 IRRIGATION PLAN.
  
 12.) IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE. (ZLDR S.94-445(4)(G))
  
 13.) THE QUANTITY OF HAMELIA PATENS/FIRE BUSH (HAM) IN
 THE LANDSCAPE PLAN DOES NOT MATCH THE QUANTITY PROVIDED
 IN THE PLANT SCHEDULE.
  
 14.) THERE IS A FLOATING "SP/2" SYMBOL IN THE LANDSCAPE
 PLAN. PLEASE CORRECT.
  
  
 ARCHITECTURAL:
  
 1.) THE EAST AND WEST ELEVATIONS ON SHEET A-2 ARE
 LABELED INCORRECTLY. PLEASE CORRECT.
  
  
 LIGHTING:
  
 1.) THE LIGHTING NOTES IN THE PHOTOMETRIC PLAN (SHEET
 P1.0) REFERENCES THE CITY OF NORTH LAUDERDALE'S
 LIGHTING STANDARDS. PLEASE CORRECT.
  
  
 SIGNAGE:
  
 1.) PROVIDE SETBACK DIMENSIONS FOR THE PROPOSED 30 FT.
 HIGH PYLON SIGN AT THE SOUTHWEST CORNER OF THE
 PROPERTY.
  
 2.) THE WALL SIGN ON THE SOUTH ELEVATION SHALL NOT
 EXCEED 102.13 SQ. FT. THE PROPOSED WALL SIGN ON THE
 SOUTH FACADE HAS BEEN CALCULATED AT 127.26 SQ. FT.
 (ZLDR S.94-408(D) C.)
  
 3.) PLEASE LABEL THE ELEVATIONS WITH DIRECTIONS IN THE
 SIGN PLAN.
  
  
 RECOMMENDED SITE PLAN IMPROVEMENTS:
  
 1.) HAVE OTHER ALTERNATIVES FOR BUILDING PLACEMENT BEEN
 EXPLORED, SUCH AS PLACING THE BUILDING CLOSER TO THE
 STREET FRONTAGES?
  
 2.) IT IS STRONGLY ENCOURAGED THE ARCHITECT WORKS WITH
 STAFF TO PROVIDE ARCHITECTURAL ENHANCEMENTS (I.E.
 WINDOWS, FENESTRATIONS, RECESSES, ETC.) TO THE
 BUILDINGS STREET FACADES.
  
 3.) WHY IS THE PEDESTRIAN CONNECTION LOCATED ON THE
 WEST SIDE OF THE BUILDING NEXT TO THE LOADING ZONE
 (FROM MILITARY TRAIL), AND NOT FROM 45TH STREET WHICH
 WOULD PROVIDE PEDESTRIAN ACCESS FROM THE STREET TO THE
 MAIN ENTRANCE OF THE BUILDING?
  
 4.) HAVE OTHER ALTERNATIVES FOR THE FREE-STANDING SIGN
 BEEN EXPLORED? THE 30 FT. PYLON SIGN SEEMS OUT OF SCALE
 WITH THE PROJECT.
  