Plan Review Details - Project Z13120012
Plan Review Stops For Project Z13120012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 01-07-2014 Cont ID  
Sent By rbrown Date 01-07-2014 Time 20:02 Rev Time 0.00
Received By rbrown Date 01-07-2014 Time 20:02 Sent To  
Notes
2014-01-07 20:08:40DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW THAT
 THE TYPE OF CONSTRUCTION FOR THE BUILDINGS WILL BE IN
 ACCORDANCE WITH THE HEIGHT, AREA AND OCCUPANCY
 LIMITATIONS IN CHAPTER 5 OF THE FLORIDA BUILDING CODE
  
 3. WHEN SUBMITTED FOR PERMIT, COMPLIANCE WITH ALL
 BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND OPENING
 PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF THE
 FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 4. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 10 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 5. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 01-06-2014 Time 12:00 Rev Time  
Received By   Date 01-06-2014 Time 11:40 Sent To  
Notes
2014-01-06 11:48:43THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1. ALL CONSTRUCTION SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2010 EDITION, INCLUDING BUT NOT
 LIMITED TO, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES.
  
 2. ALL ADDITIONS OR DELETIONS TO THE EXISTING FIRE
 ALARM AND SPRINKLER SYSTEMS SHALL BE DONE BY A SYSTEM
 CERTIFIED LICENSED CONTRACTOR. THOSE PERMITS SHALL BE
 SHOP DRAWING APPLIED FOR SEPARATELY.
  
 3. COMPLETE LIFE SAFETY PLANS FOR THE PROJECT SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 4. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 5. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 6. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE
 CODES AND STANDARDS.
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status P Date 01-07-2014 Cont ID  
Sent By ssamuels Date 01-07-2014 Time 17:43 Rev Time 0.00
Received By ssamuels Date 01-07-2014 Time 17:43 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 01-06-2014 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-01-06 14:13:07PROJECT IS PASSED AS PROPOSED.
  
  
 UTILITIES (WATER/SEWER) ARE CURENTLY AVAILABLE FOR THIS
 PROJECT DUE TO PRIOR TENANT.
  
  
  
 JACKSON LOEBIG
 O&M SUPERINTENDENT
 PUBLIC UTILITIES DEPARTMENT
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 TEL: 561 494-1067
 CELL: 561 951-7656
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 01-22-2014 Cont ID  
Sent By tward Date 01-22-2014 Time 23:08 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2014-01-22 23:08:481. SHOULD THE YELLOW STRIPING NEXT TO THE LANDSCAPE
 ISLAND BY THE DUMPSTER BE WHITE INSTEAD OF YELLOW. IT
 IS PAVEMENT MARKINGS TO THE RIGHT OF THE TRAFFIC LANE.
 2. STOP SIGN AT BYPASS EXIT TO NORTH PARKING LOT SHOULD
 BE ON THE RIGHT SIDE OF THE EXIT. IS A STOP BAR NEEDED
 HERE?
 3. ON THE SITE PLAN, IS THERE PROPER SIDEWALK CLEARANCE
 AROUND THE STOP SIGN LOCATED IN THE REAR SIDEWALK
 LEADING TO THE SOUTH END OF THE THE DRIVE-THRU LOOP?
 4. INDICATE VERTICAL DATUM ON ENGINEERING PLAN, SHEET
 C-06. DATUM SHOULD BE NGVD 1929 PER CITY CODE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 1 Status P Date 01-03-2014 Cont ID  
Sent By tward Date 01-03-2014 Time 16:02 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2014-01-03 16:39:221. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE
 START OF CONSTRUCTION.
 2. PROVIDE SWPPP AND FINAL PGD PLANS WITH ENGINEERING
 PERMIT APPLICATION.
 3. AVOID PLANTING OF TREES WITHIN 5 FEET OF UNDERGROUND
 UTILITIES.
 4. C-SHEETS TITLE BLOCK READS CITY OF PLAM BEACH, WEST
 PALM BEACH COUNTY.
 5. SHEET C-02 - NOTE 25 - "... RECONSTRUCTION
 CONFERENCE ..."
 6. SHEET C-02 - NOTE 30 - PALM BEACH COUNTY INSTEAD OF
 DADE COUNTY
 7. SHEET C-05 - ADA SIDEWALK RAMP DETAIL DOESN'T MATCH
 THE RAMPS SHOWN ON SHEET C-03.
 8. EXISTING CONCRETE FLUME ALONG WESTERN PARKING SPACES
 SOUTH OF PROPOSED DRIVE-THRU LANE IS NOT SHOWN ON THE
 LANDSCAPE PLANS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 12-31-2013 Cont ID  
Sent By vnoel Date 12-31-2013 Time 09:10 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2013-12-31 09:11:02NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 01-24-2014 Time   Rev Time 0.00
Received By bcollins Date 01-24-2014 Time 10:12 Sent To  
Notes
2014-01-24 10:15:12STOP SIGN (ON RIGHT SIDE) AND STOP BAR SHALL BE
 INSTALLED AT EXIT TO MAIN SHOPPING CENTER DRIVEWAY.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 01-03-2014 Time   Rev Time 0.00
Received By bcollins Date 01-03-2014 Time 13:57 Sent To  
Notes
2014-01-03 14:06:471.THE TURNING RADIUS FROM THE DRIVE THRU TO THE PICKUP
 WINDOW APPEARS TO BE TIGHT. AUTOTURN SHOULD BE USED TO
 VERIFY THAT THE TURNING RADIUS IS ADEQUATE.
 2. THE ACCESS AND EGRESS AT THE SOUTH END IS
 PROBLEMMATIC. VEHICLES ENTERING AND LEAVING IN AN
 "ENGLISH" FLOW DIRECTION THAT WILL CONFUSE DRIVERS AND
 CREATE CROSSING CONFLICTS. IT IS SUGGESTED THAT THIS
 COULD BE REMEDIED BY EXTENDING THE CENTER ISLAND TO THE
 SOUTH SUCH THAT THE ACCESS AND EGRESS ARE COMPLETELY
 SEPARATED.

Review Stop Z ZONING
Rev No 2 Status P Date 01-28-2014 Cont ID  
Sent By dkittred Date 01-28-2014 Time 16:36 Rev Time 0.00
Received By dkittred Date 01-21-2014 Time 16:35 Sent To  
Notes
2014-01-28 16:37:53PLANNING AND ZONING COMMENTS:
  
 1/28/14
  
 NOTATION ADDED TO SHEET C-05 TO INDICATE MINIMUM
 DIMENSIONS OF THE CONCRETE PAD FOR THE BICYCLE PARKING.
 CONCRETE PAD MUST HAVE A MINIMUM LENGTH OF SIX (6) FEET
 AND EXTEND A MINIMUM OF TWO (2) FEET ON EITHER SIDE OF
 THE BICYCLE RACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 01-03-2014 Cont ID  
Sent By dkittred Date 01-03-2014 Time 14:51 Rev Time  
Received By dkittred Date   Time   Sent To  
Notes
2014-01-03 14:52:58PLANNING AND ZONING COMMENTS:
  
 1/3/14
 1. CORRECT PARKING SPACE STRIPING DETAIL TO SHOW ALL
 LINES DOUBLE STRIPED AND CONNECTED ON THE BOTTOM PER
 ZLDR SECTION 94-485.
  
 2. WHEEL STOPS SHALL BE PROVIDED FOR NEW HANDICAP
 PARKING SPACES CONSISTENT WITH THE REST OF THE PARKING
 LOT.
  
 3. PLEASE SUBMIT A SEPARATE TREE ALTERATION PERMIT
 APPLICATION FOR THE TREES REQUESTED TO BE REMOVED AND
 RELOCATED.
  
 4. VERIFY AMOUNT OF NEW SQUARE FOOTAGE BEING ADDED TO
 THE PROJECT. THE MAJOR PD AMENDMENT CURRENTLY PENDING
 PUBLIC HEARING APPROVAL ONLY ALLOWS FOR A MAXIMUM OF
 400 NEW SQUARE FEET FOR THE PROJECT.
  
 5. TRAFFIC CONCURRENCY LETTER IS REQUIRED FROM PALM
 BEACH COUNTY.
  
 6. ON PAGE C-02 UNDER GENERAL NOTES #30, THERE IS A
 REFERENCE TO DADE COUNTY, THE SUBJECT PROJECT IS IN
 PALM BEACH COUNTY. PLEASE CORRECT OR CLARIFY.
  
 7. THE PLANS SHOW THAT PART OF THE WALK-IN
 COOLER/FREEZER WILL BE VISIBLE. PLEASE CLARIFY WHAT THE
 EXTERIOR MATERIAL OF THE WALK-IN COOLER/FREEZER WILL BE
 CONSTRUCTED OF.
  
 8.ADDITIONAL LANDSCAPING IS RECOMMENDED FOR THE CENTRAL
 DRIVE-THRU ISLAND.
  
 9. DESIGN OF WESTWARD CROSSWALK FROM HANDICAP PARKING
 SPACES TO BUILDING IS NOT IDEAL. CROSSWALK SHOULD BE
 MOVED SLIGHTLY FURTHER WESTWARD TO MAINTAIN THE END OF
 THE LANDSCAPE ISLAND.
  
 10. THE PLANS DEPICT THAT THE LENGTH OF AN EXISTING
 LANDSCAPE ISLAND WILL BE REDUCED FOR THE PROPOSED
 ENTRANCE TO THE DRIVE-THRU. PLEASE DEMONSTRATE THAT BY
 REDUCING THE LENGTH OF THIS LANDSCAPE ISLAND THERE WILL
 NOT BE A CONFLICT BETWEEN VEHICLES ENTERING THE
 DRIVE-THRU AND A VEHICLE PARKED IN THE SPACE DIRECTLY
 TO THE SOUTH OF THE LANDSCAPE ISLAND.
  
 11. BICYCLE PARKING SHALL BE PROVIDED (MINIMUM ONE
 BICYCLE PARKING SPACE OR DEMONSTRATE AMPLE BICYCLE
 PARKING IS ALREADY PROVIDED FOR THE ENTIRE SHOPPING
 CENTER). INCLUDE BICYCLE PARKING DETAIL ON THE PLAN.
  
 12. PLAN ELIMINATES THE SIDEWALK CONNECTION FROM ALONG
 THE WESTERN SIDE OF THE BUILDING. PLEASE PROVIDE AN
 ALTERNATIVE CONNECTION GIVING PEDESTRIAN ACCESS BETWEEN
 THE AREA SOUTH OF THE DRIVE-THRU TO THE AREA NORTH OF
 THE DRIVE-THRU.
  