| 2013-12-06 12:07:15 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. 561-804-4709 |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 4. THE HOTEL STRUCTURE SHALL COMPLY WITH THE FLORIDA |
| | FIRE PREVENTION CODE, 2010 EDITION, INCLUDING BUT NOT |
| | LIMITED TO, CHAPTER 28, NEW HOTELS AND DORMITORIES. |
| | |
| | 5. THE PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, |
| | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, |
| | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE |
| | OCCUPANCIES (PARKING STRUCTURES) |
| | |
| | 6. THE SEPARATION AND OPENING PROTECTION BETWEEN THE |
| | PARKING GARAGE AND HOTEL SHALL BE IN ACCORDANCE AND |
| | COMPLIANCE WITH THE SPECIFIC AND MOST STRINGENT |
| | PROVISION REQUIREMENT OF EITHER CHAPTER. |
| | |
| | 7. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR |
| | THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND |
| | INDICATED. ALL FIRE RATED OPENING PROTECTIONS (FIRE |
| | DOORS AND HARDWARE) SHALL BE CLEARLY IDENTIFIED AND |
| | INDICATED IN THE DOOR SCHEDULE. |
| | |
| | 8. AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE |
| | INSTALLED IN EVERY GUEST ROOM AND EVERY LIVING AREA AND |
| | SLEEPING ROOM WITHIN A GUEST SUITE. |
| | |
| | 9. INTERIOR FINISH CLASSIFICATIONS FOR ALL WALLS AND |
| | CEILINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTED |
| | BUILDING PERMIT PLAN. |
| | |
| | 10. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA |
| | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THE |
| | HOTEL AND PARKING GARAGE. SEPARATE SHOP DRAWINGS, ARE |
| | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE |
| | FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 11. THE LOCATION OF THE FDC'S, FIRE DEPARTMENT CONTROL |
| | ROOM, ANNUNCIATOR PANEL, FIRE PUMP ROOM, AND FIRE |
| | LANES, SHALL BE DISCUSSED, REVIEWED AND APPROVED |
| | THROUGH THE COORDINATED EFFORTS AND MEETINGS WITH THE |
| | FIRE MARSHAL AND THE STAFF OF THE BUREAU OF FIRE |
| | PREVENTION. |
| | |
| | 12. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS |
| | STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 13. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY |
| | ILLUSTRATED ON THE PLAN. TACTILE SIGN SHALL BE |
| | INSTALLED AT ALL EXIT DOORS. ALL DOORS THAT OPEN ONTO |
| | EXIT ACCESS CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE |
| | RATED AND BE EQUIPPED WITH SELF-CLOSING DEVICES THAT |
| | CAUSE THE DOOR TO POSITIVELY LATCH WHEN CLOSED. THIS |
| | REQUIREMENT SHALL BE CLEARLY INDICATED AND ILLUSTRATED |
| | ON THE DOOR SCHEDULE. |
| | |
| | 14. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING |
| | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. |
| | |
| | 15. IN THE PARKING GARAGE, THE EXIT DOORS OF THE EAST |
| | STAIRWELL ON THE 2ND AND 3RD LEVEL SHALL SWING IN THE |
| | DIRECTION OF EGRESS. |
| | |
| | 16. IN THE HOTEL ON THE 2ND FLOOR, AT THE END OF THE NE |
| | CORRIDOR, AT THE TOP OF THE STAIRS, THE EXIT DOOR SHALL |
| | SWING IN THE DIRECTION OF EGRESS. |
| | |
| | 17. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL BE |
| | INDICATED AND LOCATED ON THE SUBMITTED PLAN AND COMPLY |
| | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | |
| | 18. ALL BACK OF HOUSE EQUIPMENT AND OPERATIONS SHALL BE |
| | INDICATED ON THE SUBMITTED PLANS. |
| | |
| | 19. ALL EXERCISE EQUIPMENT CONTAINED WITHIN THE FITNESS |
| | CENTER SHALL BE INDICATED ON THE SUBMITTED PLANS. |
| | |
| | 20. BUILDING ADDRESSES ARE REQUIRED ON THE BUILDING. |
| | THE ADDRESS IS TO BE A MINIMUM OF AT LEAST 6" HIGH AND |
| | CONTRAST TO THE BACKGROUND THAT THEY ARE AFFIXED. |
| | |
| | 21. FLAME SPREAD DETAILS ON ALL FOAM BACKED STUCCO TRIM |
| | PLANNED FOR BUILDING SHALL BE PROVIDED FOR AND/OR |
| | IDENTIFIED AND INDICATED ON THE PLAN. |
| | |
| | 22. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE |
| | CLEARLY IDENTIFIED AND INDICATED ON THE PLAN. |
| | |
| | 23. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY |
| | EQUIPMENT. |
| | |
| | 24. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY |
| | INDICATED ON THE BUILDING PLAN. |
| | |
| | 25. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT |
| | AND/OR TENANT SHALL BE CLEARLY INDICATED AND |
| | ILLUSTRATED ON THE BUILDING PLAN. |
| | |
| | 26. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY |
| | INDICATED AND ILLUSTRATED ON THE BUILDING PLAN. |
| | |
| | 27. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING |
| | REACHES THREE LEVELS OR THIRTY FEET WHILE BEING |
| | CONSTRUCTED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |