Plan Review Details - Project Z13020021
Plan Review Stops For Project Z13020021
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 03-13-2013 Cont ID  
Sent By lmartine Date 03-13-2013 Time 08:34 Rev Time 0.00
Received By mdekle Date 03-13-2013 Time 08:34 Sent To  
Notes
2013-03-13 08:59:01BUILDING REVIEW COMMENTS
 2010 FLORIDA BUILDING CODE
  
  
 SEE SEPARATION FROM BUILDING WALL TO PROPERTY LINE WEST
 ELEVATION. THE SURVEY CALLS FOR 1.2 ' AND YOUR SITE
 PLAN SHOWS 3 '. TABLE 602 REQUIRES A FIRE RESISTANCE
 RATING OF 1 HOUR.
  
 WILL THIS PROJECT BE A MANUFACTURED BUILDING OR OF HAND
 FRAMED CONSTRUCTION.
  
 A MINIMUM OF ONE ACCESSIBLE TOILET ROOM AND DRINKING
 FOUNTAIN WILL BE REQUIRED.
  
 THE BUILDING ENTRANCE DOOR SHALL NOT SWING INTO YOUR
 PARKING ACCESS ISLE.
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-11-2013 Cont ID  
Sent By bmoree Date 03-11-2013 Time 11:04 Rev Time 0.00
Received By bmoree Date 03-11-2013 Time 10:43 Sent To  
Notes
2013-03-11 11:04:441. DUMPSTER DETAIL REQUIRED ON PLANS.
 2. PLEASE PROVIDE DUMPSTER ACCESSIBILITY PLAN. HOW WILL
 THE CITY ACCESS THE DUMPSTER FOR COLLECTION? WILL THE
 GATE BE OPENED? WILL THE DUMPSTER BE PUSHED OUT? ETC.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 04-16-2013 Cont ID  
Sent By ddaniels Date 04-16-2013 Time 15:26 Rev Time 0.00
Received By ddaniels Date 04-16-2013 Time 15:26 Sent To  
Notes
2013-04-16 15:27:46FIRE PLAN REVIEW
 PERMIT # Z13020021
 ADDRESS: 1141 OLD OKEECHOBEE ROAD
 CONTRACTOR: GRUBER CONSULTING ENGINEERS, INC
 ACTION: DENIED
  
 FLORIDA FIRE PREVENTION CODE 2010 EDITION
  
  
  
 2ND SUBMITTAL FIRE COMMENTS NOT ADDRESSED
  
  
 1. SHOW SCOPE OF WORK ON PLANS.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 6. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 7. PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 8. DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 9. PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 10. PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 03-03-2013 Cont ID  
Sent By ddaniels Date 03-03-2013 Time 13:32 Rev Time 0.00
Received By ddaniels Date 03-03-2013 Time 13:32 Sent To  
Notes
2013-03-03 14:04:57FIRE PLAN REVIEW
 PERMIT # Z13020021
 ADDRESS: 1141 OLD OKEECHOBEE ROAD
 CONTRACTOR: GRUBER CONSULTING ENGINEERS, INC
 ACTION: DENIED
  
 FLORIDA FIRE PREVENTION CODE 2010 EDITION
  
 1. SHOW SCOPE OF WORK ON PLANS.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 6. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 7. PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 8. DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 9. PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 10. PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-13-2013 Cont ID  
Sent By   Date 03-13-2013 Time   Rev Time 0.00
Received By mdekle Date 03-13-2013 Time 11:37 Sent To  
Notes
2013-03-13 11:36:47SEE ZONING NOTES

Review Stop PARK PARKING
Rev No 1 Status P Date 03-12-2013 Cont ID  
Sent By ssamuels Date 03-12-2013 Time 18:22 Rev Time 0.00
Received By ssamuels Date 03-12-2013 Time 18:22 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status P Date 04-12-2013 Cont ID  
Sent By   Date 04-12-2013 Time   Rev Time  
Received By   Date 04-12-2013 Time   Sent To  
Notes
2013-04-12 16:19:50PASSED PER K.C. - POLICE HAVE NO COMMENTS - MD

Review Stop STORM STORMWATER
Rev No 2 Status P Date 04-15-2013 Cont ID  
Sent By tward Date 04-15-2013 Time 15:33 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2013-04-15 15:56:391. RETENTION AREA ON LANDSCAPE PLAN DOES NOT MATCH WHAT
 IS SHOWN ON SHEET C-1.
 2. SEWER CLEANOUT SHOULD BE EAST OF THE BACK OF
 SIDEWALK.
 3. GENERAL NOTES AND SPECIFICATIONS REFERENCE 1986 FDOT
 SPECIFICATIONS.
 4. SHEET C-1 DIMENSIONS PARKING STALLS AS 10' X 20'.
 PARKING STALL LAYOUT DETAIL ON LANDSCAPE PLAN AND ON
 SHEE C-2 SHOW 8.5' X 18' PARKING SPACES.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-11-2013 Cont ID  
Sent By tward Date 03-11-2013 Time 12:24 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2013-03-11 12:42:241. PROJECT DESCRIPTION DESCRIBED A 6' WALL SURROUNDING
 THE PROPERTY. SURVEY CALLS OUT EXISTING 8' WALL.
 2. CITY CONSIDERS GRAVEL COVERED AREAS AS IMPERVIOUS
 SURFACE. REVISE THE DRAINAGE CALCULATIONS ACCORDINGLY.
 3. LABEL DIMENSIONS OF DETENTION AREA.
 4. STORMWATER DETENTION AREA SHOULD BE SODDED.
 5. SUGGEST USING STEEPER SIDE SLOPES (UPTO 4:1) FOR
 DETENTION AREA TO BETTER DEFINE THE STORM WATER
 DETENTION AREA.
 6. LABEL VERTICAL DATUM ON CIVIL PLANS.
 7. USE LATEST CWPB DETAILS.
 8. REPLACE SIDEWALK AT NEW DRIVEWAY ENTRANCE WITH 6"
 THICK SLAB.
 9. VERIFY STORMATER OUTFALL PIPE IS FUNCTIONAL.
 10. PROVIDE SWPPP AND EROSION CONTROL PLAN WITH
 ENGINEERING PERMIT APPLICATION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120
  

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 04-18-2013 Cont ID  
Sent By vnoel Date 04-18-2013 Time 15:11 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2013-04-18 15:14:361. APPLICATION FOR UNITY OF TITLE NEEDS TO BE MADE
 THROUGH ENGINEERING SERVICES. APPLICATION IS AVAILABLE
 ON-LINE.
 2. SKETCH AND LEGAL DESCRIPTION IS NEEDED FOR SIDEWALK
 ALONG OKEECHOBEE ROAD. WHEN SKETCH APPROVED WE WILL
 FORWARD THE FORM OF SIDEWALK EASEMENT TO BE GRANTED TO
 CITY.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 03-11-2013 Cont ID  
Sent By vnoel Date 03-11-2013 Time 08:35 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2013-03-11 08:41:291. UNITY OF TITLE WILL BE REQUIRED.
 2. SIDEWALK EASEMENT WILL BE REQUIRED ALONG OKEECHOBEE
 ROAD.
 3. HOW WILL DUMPSTER BE ACCESSED? ENCLOSURE WILL NEED
 TO MEET CITY STANDARD.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 03-13-2013 Time 09:01 Sent To  
Notes
2013-03-13 09:02:44SEE COMMENTS FROM B. MOREE, V. NOEL, AND T. WARD

Review Stop Z ZONING
Rev No 2 Status P Date 04-11-2013 Cont ID  
Sent By mdekle Date 05-07-2013 Time   Rev Time 0.00
Received By mdekle Date 05-07-2013 Time 15:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 03-13-2013 Cont ID  
Sent By jroach Date 03-13-2013 Time   Rev Time 0.00
Received By mdekle Date 03-13-2013 Time 11:35 Sent To  
Notes
2013-03-13 11:35:59CITY OF WEST PALM BEACH
 PLANNING DIVISION
 PLANS AND PLATS REVIEW COMMITTEE
 MARCH 13, 2013
  
 INFORMAL SITE PLAN REVIEW; KAUFF?S
 ISPR 13-02
 A REQUEST BY HOWARD KAUFF FOR AN INFORMAL SITE PLAN
 APPROVAL FOR THE CONSTRUCTION OF A NEW ONE (1) STORY
 BUILDING CONSISTING OF 1,500 SQUARE FEET OF WAREHOUSE
 SPACE, ALONG WITH 7,245 SQUARE FEET OF OUTDOOR STORAGE
 AREA.
 P.C.N. 74-43-43-28-09-010-0140
 1141 OLD OKEECHOBEE ROAD
  
 GENERAL COMMENTS:
  
 1. WHEN RESUBMITTING:
  
 A. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 ALL DEPARTMENTS IN A WRITTEN FORMAT WHEN RESUBMITTING.
 NOTE THAT RESUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 B. TEN (10) SETS OF REVISED PLANS AND/OR DOCUMENTS
 SHALL BE PROVIDED, ALONG WITH ONE (1) REDUCED COPY
 (11IN X 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 D. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 2. THE APPLICANT SHOULD NOTIFY THE APPROPRIATE DISTRICT
 COMMISSIONER (SHANON MATERIO - DISTRICT 5;
 [email protected]) TO INFORM HER OF THE PROPOSED
 REVISIONS TO THE PREVIOUSLY APPROVED DEVELOPMENT AS
 PART OF THE REVIEW PROCESS AND NOTIFY PLANNING STAFF IF
 ANY ISSUES ARISE THAT MAY NEED TO BE ADDRESSED BY THE
 APPLICANT.
  
 SITE/LANDSCAPE PLANS, ARCHITECTURAL ELEVATIONS,
 JUSTIFICATION STATEMENTS, ETC:
  
 BOUNDARY SURVEY/SITE PLAN:
  
 1. THE APPLICANT IS REQUESTED TO ELABORATE FURTHER ON
 THE PARKING DATA THAT WAS SUBMITTED ON THE LANDSCAPE
 PLAN TO INCLUDE THE PROPOSED USES IN ACCORDANCE WITH
 SECTION 94-486 OF THE CITY?S ZLDR?S.
  
 LANDSCAPE PLAN:
  
 1. IN ACCORDANCE WITH SECTION 94-443 OF THE CITY?S
 ZLDR?S, FOR INDUSTRIAL USES AND USES IN INDUSTRIAL
 DISTRICTS, THE BUFFER STRIP SHALL BE AT LEAST TEN FEET
 WIDE ALONG THE EDGE OF PROPERTY WHEN ADJACENT TO A
 PUBLIC THOROUGHFARE AND AT LEAST FIVE FEET WIDE ALONG
 THE EDGE OF PROPERTY WHEN ADJACENT TO NONRESIDENTIAL
 ZONING DISTRICTS. THE BUFFER STRIP MAY NOT BE
 INTERRUPTED BY MORE THAN 25 PERCENT OF ITS REQUIRED
 LENGTH TO PROVIDE FOR SIGNS OR VEHICULAR INGRESS AND
 EGRESS. THE APPLICANT IS REQUESTED TO MITIGATE THE
 PERCENTAGE OF LANDSCAPING THAT WOULD OTHERWISE BE
 REQUIRED FOR THE SIDE BUFFER AND ALLOCATE TO THE
 LANDSCAPING ENHANCEMENT ALONG CHARLOTTE AVENUE AND OLD
 OKEECHOBEE ROAD. PLEASE REVISE THE PROPOSED LANDSCAPE
 PLAN TO REFLECT THE MODIFICATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 BEST REGARDS,
  
  
 MURRIAH DEKLE, MPA, PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1442
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved