Plan Review Details - Project Z12110020
Plan Review Stops For Project Z12110020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 12-11-2012 Cont ID  
Sent By lmartine Date 12-11-2012 Time 16:45 Rev Time 0.00
Received By lmartine Date 12-11-2012 Time 16:27 Sent To  
Notes
2012-12-11 16:44:42BUILDING REVIEW COMMENTS
  
  
 : PROVIDE BUILDING CODE DESIGN ANALYSIS.
  
 : A SEPARATE RACKING STORAGE PERMIT WILL BE REQUIRED.
  
 : SEE 2010 FLORIDA BUILDING CODE CHAPTER 7 FIRE AND
 SMOKE PROTECTION FOR MIXED OCCUPANCIES.
  
  
 LUIS MARTINEZ
 561-805-6710
  
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-13-2012 Cont ID  
Sent By bmoree Date 12-13-2012 Time 15:45 Rev Time 0.00
Received By bmoree Date 12-13-2012 Time 15:45 Sent To  
Notes
2012-12-13 15:45:171. CIVIL DRAWING SUBMISSION REQUIRED FOR ENGINEERING &
 PUBLIC WORKS PERMIT.
 2. STORMWATER POLLUTION PREVENTION PLAN REQUIRED.
 3. STORMWATER MANAGEMENT PLAN REQUIRED.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 12-11-2012 Cont ID  
Sent By ddaniels Date 12-11-2012 Time 08:51 Rev Time 0.00
Received By ddaniels Date 12-10-2012 Time 15:42 Sent To  
Notes
2012-12-10 15:52:2712/10/12 PLANS REVIEWED BY FIRE ***DENIED***
  
 1. SHOW SCOPE OF WORK ON PLANS.
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 5. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 12-11-2012 Time   Rev Time  
Received By   Date 12-11-2012 Time   Sent To  
Notes
2012-12-11 16:07:37WOULD LIKE TO SEE SUGGESTIONS FOR OTHER SPECIES OF TREE
 INSTEAD OF THE LIVE OAK IN THE SMALL PARKING ISLANDS.
 GREG MIHALKO
 561-822-2188
 [email protected]

Review Stop PARK PARKING
Rev No 1 Status F Date 12-12-2012 Cont ID  
Sent By ssamuels Date 12-12-2012 Time 12:09 Rev Time 0.00
Received By ssamuels Date 12-12-2012 Time 12:09 Sent To  
Notes
2012-12-12 12:11:14PLEASE PROVIDE THE SITE KEY NOTES IN DIAGRAM ACCORDANCE
 WITH
 THE CITY OF WEST PALM BEACH STANDARD

Review Stop POLICE POLICE
Rev No 1 Status F Date 12-07-2012 Cont ID  
Sent By   Date 12-07-2012 Time   Rev Time 0.00
Received By ktucker Date 12-07-2012 Time 13:53 Sent To  
Notes
2012-12-12 11:17:18DOORS
 A. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM (1) INCH
 THROW OR MECHANICAL INTERLOCK.
 B. GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 C. REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE
 PEEPHOLE/ SECURITY VIEWER.
 D. EXTERIOR ROLL-UP DOORS SHALL BE TARGET-HARDEN
 E. NO OVERNIGHT PARKING IN THAT BACK LOT WHERE THEY
 KEEP VEHICLES TO BE REPAIRED
 F. LIGHTING?
 G. PROPER SIGNAGE TO KEEP CUSTOMERS FROM DRIVING TO THE
 REAR PARKING AREA WHERE THE VEHICLE WILL BE WAITING
 REPAIR
 H. CAMERAS? SHOULD BE INSTALLED COVERING THAT BACK
 PARKING LOT, THE FRONT CUSTOMER PARKING, REGISTER AREA
 I. ALARM SYSTEM?
  
  CONSTRUCTION SITES CONDITIONS FOR APPROVAL
  
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
 QUESTIONS/COMMENTS, CONTACT KELLY CARSILLO, CRIME
 PREVENTION, AT (561) 822-1620.

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-07-2012 Cont ID  
Sent By tward Date 12-07-2012 Time 13:29 Rev Time  
Received By tward Date 12-07-2012 Time   Sent To  
Notes
2012-12-07 13:28:111. NO ENGINEERING PLANS SUBMITTED.
 2. PRELIMINARY SITE PLAN AND PRELIMINARY LANDSCAPE PLAN
 INDICATED AS NOT TO BE USED FOR REGULATORY APPROVAL,
 PERMIT OR CONSTRUCTION.
 3. COPY OF SFWMD ERP PERMIT OR PERMIT MODIFICATION TO
 BE SUBMITTED BEFORE START OF CONSTRUCTION.
 4. EROSION CONTROL PLAN AND STORM WATER POLLUTION
 PREVENTION PLAN TO BE SUBMITTED WITH THE ENGINEERING
 PERMIT APPLICATION.
 5. PROPOSED AND EXISTING UTILITIES NEED TO BE SHOWN ON
 THE LANDSCAPE PLAN.
 6. SITE DEVELOPMENT SHOULD ACCOMODATE OR MODIFY THE
 EXISTING STORM WATER DRAINAGE SYSTEM ON THE SITE.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-06-2012 Cont ID  
Sent By vnoel Date 12-06-2012 Time 08:11 Rev Time  
Received By vnoel Date 12-06-2012 Time   Sent To  
Notes
2012-12-06 10:59:101. NO PRELIMINARY ENGINEERING PLANS PROVIDED.
 2. DUMPSTER ENCLOSURE DOES NOT MEET CITY STANDARD.
 3. EXISTING DRAINAGE WILL NEED TO BE ADDRESSED.
 4. THERE APPEARS TO BE AN 8" WATER LINE ALONG THE SOUTH
 PROPERTY LINE THAT MAY REQUIRE AN EASEMENT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 12-07-2012 Time   Rev Time 0.00
Received By bcollins Date 12-07-2012 Time 15:13 Sent To  
Notes
2012-12-07 15:23:33NEED TO DEMONSTRATE ABILITY OF SANITATION TRUCKS TO
 MANUEVRE WITHIN SITE (USE AUTOTURN). NEED TO SHOW HOW
 VEHICLES TURN AROUND IF HANDICAPPED SPACES ARE IN USE
 (USE AUTOTURN) - MAY REQUIRE "T" TURN. PARKING SPACES
 ARE 16 FT DEEP - ACCOMODATE COMPACT CARS ONLY.

Review Stop Z ZONING
Rev No 4 Status F Date 01-14-2013 Cont ID  
Sent By jroach Date 01-08-2013 Time 14:42 Rev Time 0.00
Received By jroach Date 01-08-2013 Time 14:42 Sent To  
Notes
2013-01-14 14:49:54ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.08.2013
 PROJECT NO.:Z12110020
 CASE NO.: PB 1171GG
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: STEVE MEIER
 TELEPHONE NO.: 214.632.9611
 SCOPE OF REVIEW: PROPOSED FIRESTONE AUTO CARE FACILITY.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. DUMPSTER ENCLOSURE DETAIL SHALL BE PROVIDED WITH
 DIMENSIONS, AND SHALL CONFORM TO THE CITY'S MINIMUM
 REQUIREMENTS.
  
 2. THE CONFIGURATION AND RADIUS OF ONE OF THE LANDSCAPE
 ISLANDS IS SHOWN DIFFERENTLY ON THE LANDSCAPE PLAN.
  
 3. THE OPEN SPACE PROVIDED SHOULD BE 82%, NOT 83%.
  
 4. THE LANDSCAPING ON THE NORTH SIDE OF THE BUILDING
 DOES NOT MATCH THAT SHWON ON THE ELEVATION,
 SPECIFICALLY THE # OF PALM CLUSTERS.
  
 5. WHAT IS PROPOSED TO HAPPEN WITH THE UNDERGROUND PIPE
 LEADING FROM THE CATCH BASIN. IT IS SHOWN AS EXTENDING
 UNDERNEATH A PROPOSED TREE. PLEASE CLARIFY.
  
 6. THERE SHOULD BE 15 REQUIRED SHADE/FLOWERING TREES.
  
 7. IS THE CATCH BASIN TO REMAIN IN THE LANDSCAPE
 ISLAND?
  
 8. IF YOU HAVE 33 SHADE/FLOWERING TREES, AND YOU ONLY
 NEED 15, THEN NONE OF THEM ARE BEING SUBSTITUTED WITH
 PALMS.
  
 9. TREES SHALL BE A MINIMUM OF 8 FEET IN HEIGHT.
  
 10. THERE SHOULD BE 12 REQUIRED SHADE TREES.
  
 11. THERE SHOULD BE 3 REQUIRED FLOWERING TREES.
  
 12. THERE SHOULD BE 40 REQUIRED SHRUBS.
  
 13. THERE SHOULD BE 19,967.904 SQUARE FEET OF OPEN
 SPACE REQUIRED (40% OF THE LOT).
  
 14. THE DUMPSTER TRUCK SHALL NOT CROSS OVER THE
 PROPOSED CURB.
  
 15. THE DUMPSTER TRUCK SHOWN ON THE AUTO-TURN DRAWING
 NEEDS TO LINE UP WITH THE ENCLOSURE.
  
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 01-14-2013 Cont ID  
Sent By jroach Date 01-07-2013 Time 14:37 Rev Time 0.00
Received By jroach Date 01-07-2013 Time 14:36 Sent To  
Notes
2013-01-14 14:38:49ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.07.2013
 PROJECT NO.:Z12110020
 CASE NO.: PB 1171GG
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: STEVE MEIER
 TELEPHONE NO.: 214.632.9611
 SCOPE OF REVIEW: PROPOSED FIRESTONE AUTO CARE FACILITY.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. STILL AWAITING THE REVISED SITE PLAN.
  
 2. THE LANDSCAPE PLAN DOES NOT MATCH THE LATEST SITE
 PLAN THAT I HAVE SEEN.
  
 3. COMMENT #14 OF 1/2/13 PPRC COMMENTS....THE LANDSCAPE
 DATA TABLE STILL DOES NOT REFLECT THE OPEN SPACE
 LANDSCAPE REQUIREMENTS.
  
 4. COMMENT #15 OF 1/2/13 PPRC COMMENTS....A PERCENTAGE
 OF PALMS WAS INCLUDED ON THE PLANS, BUT THIS JUST SHOWS
 THE PERCENTAGE OF PALMS RELATIVE TO THE TOTAL NUMBER OF
 TREES. WHAT IS I NEED IS THE PERCENTAGE OF REQUIRED
 SHADE/FLOWERING TREES THAT ARE BEING SUBSTITUTED WITH
 PALMS. FOR EXAMPLE, IF MY SHADE TREE REQUIREMENT IS 10,
 I CAN SUBSTITUTE 3.5 OF THEM WITH PALMS. IF YOU HAVE
 THE 10 SHADE TREES, THEN NONE ARE BEING SUBSTITUTED,
 AND YOUR PERCENTAGE OF SUBSTITUTION WOULD BE 0%.
  
 5. COMMENT #16 OF 1/2/13 PPRC COMMENTS....UTILITIES ARE
 STILL NOT SHOWN ON THE PLANS.
  
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 01-02-2013 Cont ID  
Sent By jroach Date 01-02-2013 Time 11:08 Rev Time 0.00
Received By jroach Date 01-02-2013 Time 11:08 Sent To  
Notes
2013-01-02 11:08:39ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.02.2012
 PROJECT NO.:Z12110020
 CASE NO.: PB 1171GG
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: STEVE MEIER
 TELEPHONE NO.: 214.632.9611
 SCOPE OF REVIEW: PROPOSED FIRESTONE AUTO CARE FACILITY.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. WRITTEN RESPONSES SHALL BE PROVIDED TO ALL COMMENTS
 ISSUED AT THE DECEMBER 12, 2012 PLANS AND PLATS REVIEW
 COMMITTEE MEETING.
  
 2. ELECTRONIC COPIES OF ALL PLANS SHALL BE PROVIDED. I
 DID NOT RECEIVE ELECTRONIC COPIES OF THE PLAN SHOWING
 THE TURNING RADII
  
 3. REPEAT COMMENT - A CURRENT TRAFFIC CONCURRENCY
 APPROVAL LETTER SHALL BE PROVIDED FROM THE PALM BEACH
 COUNTY TRAFFIC DIVISION.
  
 4. REPEAT COMMENT - PLEASE BE SURE TO COORDINATE A
 MEETING WITH THE DISTRICT COMMISSIONER (KIMBERLY
 MITCHELL), AS WELL AS COMMUNICATE WITH THE ROOSEVELT
 ESTATES NEIGHBORHOOD ASSOCIATIONS.
  
 5. REPEAT COMMENT - A LETTER OF NO OBJECTION SHALL BE
 PROVIDED FROM THE FOLLOWING UTILITY COMPANIES:
  
 A. CITY OF WEST PALM BEACH PUBLIC UTILITIES
  
 6. IN THE SITE DATA TABLE...
  
 A. PLEASE INDICATE THE AMOUNT OF EACH ITEM REQUIRED, IN
 ADDITION TO WHAT IS PROVIDED. PLEASE SEE COMMENTS DATED
 DECEMBER 12, 2012 FOR THE REQUIRED AMOUNTS.
 B. THE PERCENTAGE OF OPEN SPACE SHALL BE A MINIMUM OF
 40%. PLEASE NOTE THAT OPEN SPACE IS THE LOT AREA MINUS
 THE BUILDING FOOTPRINT.
 C. THE TABLE SHOWS AN FAR OF 1.0. WITH A BUILDING
 COVERAGE OF 17%, THE FAR SHOWN IS INCORRECT. 1.0 IS THE
 MAXIMUM FAR ALLOWED WITHIN THE ZONING DESIGNATION.
 D. PLEASE PROVIDE ALL PERCENTAGES TO ONE (1) DECIMAL
 POINT, OR ROUND TO THE NEAREST WHOLE NUMBER. FOR
 EXAMPLE, IF ROUNDING, THE BUILDING COVERAGE SHOULD BE
 18%, ETC.
  
 7. IT APPEARS THAT THE AREA PREVIOUSLY LABELED AS
 "LANDSCAPE PAVERS" HAS BEEN CONVERTED INTO REGULAR
 ASPHALT. PLEASE EXPLAIN WHY THIS AREA IS SO LARGE IN
 SIZE. FOR SUFFICIENT BACK-OUT, A "NOTCH" OF ONLY 3-5
 FEET IS NECESSARY. WITH THE EXCESSIVE ASPHALT, THIS ARE
 MIGHT BE CONFUSED AS ADDITIONAL PARKING. PLEASE MODIFY
 THIS PORTION OF THE PARKING AREA, OR EXPLAIN THE
 NECESSITY OF THE ADDITIONAL ASPHALT AREA.
  
 8. REPEAT COMMENT - PLEASE NOTE THAT LIGHTING LEVELS
 SHALL NOT EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE
 BOUNDARY OF THE CPD. IF NO PHOTOMETRIC PLAN IS PROVIDED
 AT THIS TIME, SUCH PLANS WILL BE REVIEWED AT PERMITTING
 AT SHALL COMPLY WITH THIS PROVISION.
  
 9. REPEAT COMMENT - THE DETAIL OF THE MONUMENT SIGN
 SHOWN ON SHEET PA4 IS TOO LARGE FOR THAT AREA SHOWN ON
 THE SITE PLAN. THE DETAIL SHOWS A MONUMENT SIGN THAT IS
 15'4" IN WIDTH, WHILE THE AREA BETWEEN THE DUMPSTER
 ENCLOSURE AND THE LANDSCAPE BUFFER IS ONLY 11' IN
 WIDTH. PLEASE ADJUST ACCORDINGLY.
  
 10. REPEAT COMMENT - PLEASE PROVIDE DIMENSIONS OF THE
 DUMPSTER ENCLOSURE, AS WELL AS A DETAIL. ALL DUMPSTER
 ENCLOSURES SHALL MEET THE MINIMUM CRITERIA PROVIDED IN
 SECTION 94-444(B) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS).
  
 11. THE STRIPING FOR THE AISLE BETWEEN THE ACCESSIBLE
 PARKING SPACES AND THE FRONT ENTRANCE SHALL BE WHITE,
 NOT YELLOW (SEE PARKING STALL DETAIL).
  
 12. PLEASE INCLUDE THE BIKE RACK DETAIL ONTO THE SITE
 PLAN, OR CREATE AN ADDITIONAL SHEET THAT INCORPORATES
 ALL DETAILS, ETC.
  
 13. REPEAT COMMENT - PLEASE PROVIDE A HEIGHT AND/OR
 DETAIL OF THE PROPOSED SCREEN WALL ON THE EAST SIDE OF
 THE BUILDING.
  
 14. REPEAT COMMENT - BE SURE THE LANDSCAPE DATA TABLE
 INDICATES ALL STATISTICAL INFORMATION TO SATISFY
 ARTICLE XIV OF THE ZLDRS. FOR EXAMPLE...
  
 A. 1 SHADE TREE FOR EACH 1,600 SQ. FT. OF OPEN SPACE
 B. 1 FLOWERING TREE FOR EACH 6,400 SQ. FT. OF OPEN
 SPACE
 C. 1 SHRUB FOR EACH 500 SQ. FT. OF OPEN SPACE
  
 15. REPEAT COMMENT - PLEASE NOTE THAT ONLY A MAXIMUM OF
 35% OF THE REQUIRED SHADE OR FLOWERING TREES MAY BE
 SUBSTITUTED WITH PALMS. PLEASE PROVIDE A CALCULATION
 INDICATING COMPLIANCE WITH SUCH. IF SHADE OR FLOWERING
 TREES ARE BEING SUBSTITUTED WITH PALMS, THEY SHALL BE
 DONE AT A RATIO OF 2 PALM TREES FOR EACH
 SHADE/FLOWERING TREE, UNLESS IT IS A ROYAL PALM OR
 SUCKERING PALM SUCH AS ARECA PALM, PAUROTIS PALM, AND
 THE SENEGAL DATE PALM. IF A SUBSTITUTION IS MADE, PALMS
 ARE SUPPOSED TO BE PLANTED IN CLUSTERS OF THREE (3),
 WITH THE EXCEPTION OF THE THOSE LISTED PREVIOUSLY.
  
 16. REPEAT COMMENT - PLEASE CLARIFY WHAT IS BEING DONE
 WITH THE EXISTING CATCH BASINS, ETC. IT APPEARS THAT
 THEY WILL BE LOCATED IN AREAS OF FUTURE LANDSCAPE
 ISLANDS. IF THEY ARE TO REMAIN, PLEASE SHOW ALL
 UTILITIES ON THE SITE/LANDSCAPE PLANS TO ENSURE THERE
 ARE NO CONFLICTS.
  
 17. PURSUANT TO AN EMAIL I HAD SENT ON JULY 26, 2012,
 COMMENTING ON THE PROPOSED DEVELOPMENT...
  
 A. CANVAS AWNINGS SHALL BE PROVIDED AS OPPOSED TO METAL
 AWNINGS IN ORDER TO BE COMPATIBLE WITH THE CHARACTER OF
 THE OTHER BUILDINGS IN THE DEVELOPMENT.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-12-2012 Cont ID  
Sent By jroach Date 12-12-2012 Time 11:04 Rev Time 0.00
Received By jroach Date 12-12-2012 Time 11:04 Sent To  
Notes
2012-12-12 11:05:15ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.12.2012
 PROJECT NO.:Z12110020
 CASE NO.: PB 1171GG
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: STEVE MEIER
 TELEPHONE NO.: 214.632.9611
 SCOPE OF REVIEW: PROPOSED FIRESTONE AUTO CARE FACILITY.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. A CURRENT TRAFFIC CONCURRENCY APPROVAL LETTER SHALL
 BE PROVIDED FROM THE PALM BEACH COUNTY TRAFFIC
 DIVISION.
  
 2. PLEASE BE SURE TO COORDINATE A MEETING WITH THE
 DISTRICT COMMISSIONER (KIMBERLY MITCHELL), AS WELL AS
 COMMUNICATE WITH THE ROOSEVELT ESTATES NEIGHBORHOOD
 ASSOCIATIONS.
  
 3. A LETTER OF NO OBJECTION SHALL BE PROVIDED FROM THE
 FOLLOWING UTILITY COMPANIES:
 A. CITY OF WEST PALM BEACH PUBLIC UTILITIES
  
 4. PLEASE PROVIDE THE AFFIDAVIT REGARDING ACQUISITION
 OF THE MAILING LIST/LABELS (PAGE 19 OF THE DEVELOPMENT
 APPLICATION)
  
 5. PURSUANT TO THE SITE PLAN CHECKLIST CONTAINED WITHIN
 THE DEVELOPMENT APPLICATION, PLEASE BE SURE TO PROVIDE
 THE FOLLOWING INFORMATION IN YOUR DATA TABLE:
  
 A. EXISTING FUTURE LAND USE DESIGNATION ? COMMERCIAL
 (C)
 B. EXISTING ZONING DESIGNATION ? COMMERCIAL PLANNED
 DEVELOPMENT (CPD)
 C. PERCENTAGE OF OPEN SPACE REQUIRED & PROVIDED ?
 MINIMUM OF 40%
 D. PERCENTAGE OF LANDSCAPING/IMPERVIOUS SURFACE
 REQUIRED & PROVIDED ? MINIMUM OF 15%
 E. PERCENTAGE OF BUILDING COVERAGE REQUIRED & PROVIDED
 ? MAXIMUM OF 60%
 F. PERCENTAGE OF IMPERMEABLE SURFACE REQUIRED &
 PROVIDED ? MAXIMUM OF 85%
 G. FLOOR AREA RATIO (FAR) ? MAXIMUM OF 1.0
 H. REQUIRED # OF PARKING SPACES ? MINIMUM OF 3 PER
 SERVICE BAY AND 1 PER 500 OF ENCLOSED AREA
  
 6. PLEASE EXPLAIN THE PURPOSE OF THE ?LANDSCAPE PAVERS?
 NEAR THE FRONT ENTRANCE. PURSUANT TO ORDINANCE NO.
 3844-05, ?THE OVERNIGHT STORAGE OF MATERIALS AND THE
 DISPLAY OF GOODS OUTDOORS SHALL BE PROHIBITED?.
  
 7. PLEASE CONFIRM THAT ALL MECHANICAL EQUIPMENT WILL BE
 MOUNTED ON THE ROOF. IF SO, PLEASE PROVIDE A ROOF PLAN
 SHOWING THE LOCATION, AS WELL AS ITS LOCATION ON THE
 ELEVATIONS. ANY ROOFTOP EQUIPMENT SHALL BE SCREENED
 FROM VIEW.
  
 8. PLEASE NOTE THAT LIGHTING LEVELS SHALL NOT EXCEED
 1.0 FOOTCANDLES WHEN MEASURED AT THE BOUNDARY OF THE
 CPD. IF NO PHOTOMETRIC PLAN IS PROVIDED AT THIS TIME,
 SUCH PLANS WILL BE REVIEWED AT PERMITTING AT SHALL
 COMPLY WITH THIS PROVISION.
  
 9. PLEASE PROVIDE DIMENSIONS FOR THE LETTERS ON THE
 PROPOSED WALL-MOUNTED SIGNS. ALL SIGNS SHALL CONFORM TO
 THE REQUIREMENTS CONTAINED IN ORDINANCE NO. 3844-05,
 LETTER HEIGHT SHALL NOT EXCEED 2?6? (OVERALL SIGN
 HEIGHT CONFORMS TO THE REQUIREMENTS).
  
 10. THE DETAIL OF THE MONUMENT SIGN SHOWN ON SHEET PA4
 IS TOO LARGE FOR THAT AREA SHOWN ON THE SITE PLAN.
  
 11. THE FREESTANDING SIGN SHALL BE A MINIMUM OF 24 FEET
 FROM ANOTHER LOT.
  
 12. PLEASE PROVIDE DIMENSIONS OF THE DUMPSTER
 ENCLOSURE, AS WELL AS A DETAIL. ALL DUMPSTER ENCLOSURES
 SHALL MEET THE MINIMUM CRITERIA PROVIDED IN SECTION
 94-444(B) OF THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 13. PLEASE PROVIDE A PARKING STRIPING DETAIL (INCLUDING
 ACCESSIBLE SPACES). ALL STRIPING SHALL CONFORM TO THE
 PROVISIONS IN ARTICLE XV OF THE ZLDRS. PLEASE NOTE THAT
 STRIPING OF THE PARKING SPACES (WITH EXCEPTION TO THOSE
 AREAS ASSOCIATED WITH THE ACCESSIBLE SPACES) SHALL BE
 WHITE IN COLOR, NOT YELLOW.
  
 14. PLEASE PROVIDE A DETAIL OF THE PROPOSED BIKE RACK.
  
 15. PLEASE PROVIDE A HEIGHT AND/OR DETAIL OF THE
 PROPOSED SCREEN WALL ON THE EAST SIDE OF THE BUILDING.
  
 16. THE DRIVE AISLE FOR THE PARKING ON THE WEST SIDE OF
 THE BUILDING NEEDS TO BE A MINIMUM OF 24 FEET IN WIDTH.
  
 17. THE ACCESSIBLE PARKING SPACES ON THE WEST SIDE OF
 THE BUILDING DO NOT APPEAR TO MEET THE MINIMUM
 DIMENSIONAL REQUIREMENTS. ACCESSIBLE SPACES ARE TO BE
 12 FEET IN WIDTH WITH A 5 FOOT ACCESS AISLE.
  
 18. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 LOADING ZONE. IT IS LISTED ON THE SITE KEY NOTES, BUT
 IS NOT LABELED ON THE PLAN.
  
 19. PLEASE CLARIFY WHY THERE ARE SIGNIFICANT AREAS
 SHOWN AS BEING MULCH (IE TERMINAL ISLANDS IN THE
 PARKING ROWS, ETC.). THESE SEEM TO BE PRETTY
 SIGNIFICANT IN SIZE. PLEASE CONSIDER SOME TYPE OF
 GROUNDCOVER, ETC.
  
 20. IF THE SPACE PERMITS, ADDITIONAL TREE NEED TO BE
 PLACED AT THE SOUTH END OF EACH PARKING ROW IN THE
 ISLANDS PROVIDED.
  
 21. BE SURE THE LANDSCAPE DATA TABLE INDICATES ALL
 STATISTICAL INFORMATION TO SATISFY ARTICLE XIV OF THE
 ZLDRS. FOR EXAMPLE?
  
 A. 1 SHADE TREE FOR EACH 1,600 SQ. FT. OF OPEN SPACE
 B. 1 FLOWERING TREE FOR EACH 6,400 SQ. FT. OF OPEN
 SPACE
 C. 1 SHRUB FOR EACH 500 SQ. FT. OF OPEN SPACE
  
 22. PLEASE NOTE THAT ONLY A MAXIMUM OF 35% OF THE
 REQUIRED SHADE OR FLOWERING TREES MAY BE SUBSTITUTED
 WITH PALMS. PLEASE PROVIDE A CALCULATION INDICATING
 COMPLIANCE WITH SUCH. IF SHADE OR FLOWERING TREES ARE
 BEING SUBSTITUTED WITH PALMS, THEY SHALL BE DONE AT A
 RATIO OF 2 PALM TREES FOR EACH SHADE/FLOWERING TREE,
 UNLESS IT IS A ROYAL PALM OR SUCKERING PALM SUCH AS
 ARECA PALM, PAUROTIS PALM, AND THE SENEGAL DATE PALM.
 IF A SUBSTITUTION IS MADE, PALMS ARE SUPPOSED TO BE
 PLANTED IN CLUSTERS OF THREE (3), WITH THE EXCEPTION OF
 THE THOSE LISTED PREVIOUSLY.
  
 23. PLEASE ENSURE THAT THE PLANTING DETAIL CONFORM TO
 THAT SHOWN IN THE DEVELOPMENT APPLICATION.
  
 24. PLEASE NOTE THAT PURSUANT TO SECTION 94-443(B)(4)
 OF THE ZLDRS, A SHADE OR FLOWERING TREE SHALL BE
 PROVIDED FOR EACH 30 LINEAR FEET OF BUFFER. IT DOES NOT
 APPEAR THAT THE NORTH OR SOUTH PROPERTY LINES CONFORM
 TO THIS REQUIREMENT.
  
 25. PLEASE NOTE ON THE PLANS THAT ALL LANDSCAPE AREAS
 WILL BE FULLY IRRIGATED WITH AN AUTOMATIC IRRIGATION
 SYSTEM, AND THAT SUCH WILL BE DESIGNED TO HAVE 120%
 COVERAGE. PLEASE REFER TO SECTION 94-445(4)(G) OF THE
 ZLDRS.
  
 26. PLEASE CLARIFY WHAT IS BEING DONE WITH THE EXISTING
 CATCH BASINS, ETC. IT APPEARS THAT THEY WILL BE LOCATED
 IN AREAS OF FUTURE LANDSCAPE ISLANDS. IF THEY ARE TO
 REMAIN, PLEASE SHOW ALL UTILITIES ON THE SITE/LANDSCAPE
 PLANS TO ENSURE THERE ARE NO CONFLICTS.
  
 27. IS IT POSSIBLE TO INCORPORATE FOUNDATION PLANTING
 AROUND ANY OF THE OTHER SIDES OF THE BUILDING?
  
 28. PURSUANT TO AN EMAIL I HAD SENT ON JULY 26, 2012,
 COMMENTING ON THE PROPOSED DEVELOPMENT?
  
 A. IS THERE ANY WAY TO DO CANVAS AWNING AS OPPOSED TO
 METAL AWNINGS? THIS WOULD FIT INTO THE CHARACTER OF THE
 OTHER BUILDINGS IN THE DEVELOPMENT. ADDITIONALLY, CAN
 AWNINGS BE ADDED OVER THE DOORS ON THE EAST ELEVATION?
  
 29. IS IT POSSIBLE TO INCLUDE LANDSCAPING IN THE
 COLORED RENDERINGS TO SHOW THE RELATIONSHIP BETWEEN THE
 PROPOSED LANDSCAPE PLAN AND THE BUILDING ELEVATIONS?
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) TO BE CONSIDERED FOR THE NEXT AVAILABLE PLANNING
 BOARD HEARING, ALL RESUBMITTED ITEMS WILL NEED TO BE
 TURNED IN TO THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION NO LATER THAN 12:00PM ON DECEMBER 21,
 2012.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved