Plan Review Details - Project Z12110018
Plan Review Stops For Project Z12110018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-11-2012 Cont ID  
Sent By lmartine Date 12-11-2012 Time 17:58 Rev Time 0.00
Received By lmartine Date 12-11-2012 Time 17:54 Sent To  
Notes
2012-12-11 17:56:08BUILDING REVIEW
  
  
 THE PLANS PROVIDED ARE TO PRELIMINARY FOR COMMENTS.
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-14-2012 Cont ID  
Sent By bmoree Date 12-14-2012 Time 11:33 Rev Time 0.00
Received By bmoree Date 12-14-2012 Time 11:33 Sent To  
Notes
2012-12-14 11:33:321. A SEPARATE FORMAL SUBMITTAL OF COMPLETED CIVIL
 DRAWINGS SHALL BE MADE TO THE ENGINEERING & PUBLIC
 WORKS DEPARTMENT FOR PERMTTING.
 2. UTILITIES SHALL BE PRIVATELY OWNED.
 3. ROADWAYS SHALL BE PRIVATELY OWNED.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-11-2012 Cont ID  
Sent By ddaniels Date 12-11-2012 Time 08:56 Rev Time 0.00
Received By ddaniels Date 12-11-2012 Time 08:56 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status   Date 12-11-2012 Cont ID  
Sent By gmihalko Date 12-11-2012 Time 16:03 Rev Time 0.00
Received By gmihalko Date 12-11-2012 Time 15:52 Sent To  
Notes
2012-12-11 16:02:19LANDSCAPING LOOKS GOOD FOR THE MOST PART. I WOULD LIKE
 TO SEE A BETTER SUGGESTION FOR THE PARKING ISLANDS
 OTHER THAN LIVE OAKS IN SUCH A SMALL SPACE.
  
 GREG MIHALKO
 561-822-2188
 [email protected]

Review Stop PARK PARKING
Rev No 1 Status F Date 12-11-2012 Cont ID  
Sent By ssamuels Date 12-11-2012 Time 12:39 Rev Time 0.00
Received By ssamuels Date 12-11-2012 Time 12:39 Sent To  
Notes
2012-12-11 12:41:47PLEASE SHOW DATA OF BICYCLE RACK PER CITY OF WEST PALM
 BEACH STANDARD.
  
 DOUBLE CHECK ON ON - STREET PARKING ON TAM AVE.

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ktucker Date 12-12-2012 Time 09:54 Sent To  
Notes
2012-12-12 09:59:15CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL, OFC
 CARSILLO (561) 578-3529
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
 PLEASE KEEP IN MIND, WE WILL BE PAYING ATTENTION TO
 LIGHTING, LANDSCAPING, SECURITY DETAIL. THIS IS AN
 EARLY PLAN, BUT THESE COMMENTS ARE WHAT I WILL BE
 LOOKING FOR IN THE FUTURE. THERE WILL BE CRIME/TRESPASS
 ISSUES ON THE PROPERTY. SAFETY OF RESIDENTS / VISITORS
 IS PRIORITY
 DESIGN FOR POCKET PARK/WALKING PATHS
 A. BENCHES/SEATING AREA SHALL HAVE ADEQUATE LIGHTING
 AND BE LOCATED IN OPEN VIEW TO ELIMINATE CONCEALMENT
 AREAS.
 B. BENCHES WILL BE DIVIDED STYLE SEATING.
 C. SHALL BE DESIGNED TO MAXIMIZE NATURAL SURVEILLANCE
 OF THE PEDESTRIAN USERS THROUGH SELECTIVE VEGETATIVE
 MANAGEMENT PRACTICES.
 D. GROUND COVER SHALL BE NO HIGHER THAN 24 INCHES, WITH
 TREES HAVING A MINIMUM 7-FOOT CLEAR TRUNK SPACE FOR A
 NATURAL SURVEILLANCE WINDOW.
 E. INSTALL 10-15 FOOT PEDESTRIAN-SCALE LIGHTING. AS A
 GENERAL RULE, THE MINIMUM LIGHTING INTENSITY AT ANY
 POINT ALONG THE PATH SHALL BE AT 0.6 FOOT-CANDLES.
 F. SIGHT LINES SHALL HAVE A 12-FOOT CLEAR DISTANCE
 SPACE AT ENTRY POINTS, CURVES, MERGERS, INTERSECTIONS,
 ETC. LANDSCAPING SHALL NOT CONFLICT WITH LIGHTING (TO
 INCLUDE LONG-TERM TREE CANOPY GROWTH).
 G. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 DUSK TO DAWN OPERATION FOR ALL PEDESTRIAN SIDEWALKS.
 H. LIGHTING FOR ENTRANCE SIGN TO PATHWAYS SHALL BE
 PROVIDED TO ALLOW NIGHTTIME USE OF PEDESTRIAN WALKWAYS
  
  LIGHTING
  
 A. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 B. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 C. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO RESIDENCES PROVIDE FOR DUSK
 TO DAWN OPERATION.
 D. ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING.
 E. BUILDING LIGHTING (NON GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDES.
 NUMERICAL ADDRESS
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 ADDRESS SHOULD BE PLACED UNDER A LIGHT FIXTURE OR BE
 BACK LIT.
 B. ADDRESS NUMERALS SHALL BE OF A CONTRASTING COLOR TO
 THE BUILDING COLOR
 C. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 D. ADDRESS NUMBERS ON DOORS OF MULTI-UNITS AND SINGLE
 FAMILY HOMES NEED TO BE A MINIMUM OF 6 INCHES HIGH.
 E. BUILDING NUMBERS FOR MULTI-UNIT BUILDINGS SHALL BE A
 MINIMUM OF 12 INCHES HIGH AND PLACED IN A CONSPICUOUS
 LOCATION ON ALL SIDES WITH PUBLIC ACCESS, AWAY FROM
 LANDSCAPING. NUMBERS SHOULD BE OF A CONTRASTING
 BACKGROUND.
 DOORS
 A. DOOR LEADING INTO A RESIDENTIAL UNIT, SHALL BE SOLID
 CORE.
 B. EXTERIOR DOORS SHALL BE EQUIPPED WITH A 180-DEGREE
 PEEPHOLE AND NON-REMOVABLE SECURITY HINGES.
 LOCKS
 A. ANTI-LIFTING AUXILIARY LOCKS SHALL BE INSTALLED ON
 SLIDING DOORS AND WINDOWS.
 B. ALL DOORS SHALL BE EQUIPPED WITH SINGLE CYLINDER
 DEAD BOLT LOCK WITH A MINIMUM THROW OF ONE INCH AND AN
 EMBEDMENT OF NOT LESS 5/8 INCH INTO THE HOLDING DEVICE.
 PICK PLATES SHOULD ALSO BE PLACED ALL EXTERIOR DOORS.
 C. CONTROLLED ACCESS INTO THE RESIDENTIAL BUILDINGS/
 DAY CARE CENTER. (CARD ACCESS, KEY FOB, CODE ACCESS OR
 HUMAN)
 ELEVATORS
 A. ELEVATORS SHALL BE EQUIPPED WITH EMERGENCY TWO-WAY
 COMMUNICATION.
 B. ELEVATORS SHALL HAVE NO STOP BUTTON.
 ELEVATORS SHALL BE LOCATED CLOSE TO THE MAIN ENTRANCE,
 CONSTRUCTED TO AVOID HIDDEN SPACES AND UTILIZE CCTV
 SURVEILLANCE
 CAMERAS
 A. CCTV CAMERAS LOCATED ON EACH FLOOR (AS WELL AS
 MONITORING ACCESS POINTS, STAIRWELLS, LOBBY, ETC.).ALL
 BUILDINGS SHALL BE PRE-WIRED FOR CLOSED-CIRCUIT
 TELEVISION (CCTV) AND ALARM SYSTEMS
 B. THE MONITORING AND CONTROL OF THE CCTV CAMERAS SHALL
 BE AT A CENTRAL MONITORING OFFICE.
 C. A HIGH-RESOLUTION COLOR DIGITAL VIDEO CAMERA SYSTEM
 WITH MONITORING AND PHOTO PROCESSING PRINTOUT
 CAPABILITIES SHALL BE USED.
  
  MISCELLANEOUS
 A. STAIRWAYS (TO INCLUDE RISERS/BANISTERS) AND
 BALCONIES SHALL PROVIDE OPEN VIEWS.
 B. ADULT DAY CARE CENTER SHALL BE PRE-WIRED TO ALARM
 CENTER. (INCLUDES ANY FUTURE CLUBHOUSE, RECREATIONAL
 BUILDINGS)
 C. BICYCLE SPACES SHALL BE LOCATED IN CLOSE PROXIMITY
 TO THE FRONT OF BUILDINGS AND NOT IN PARKING LOTS.
 D. IF CENTRALIZED, MAILBOX LOCATIONS SHALL BE IN A WELL
 LIT, HIGH TRAFFIC LOCATION.
 E. CONVEX MIRRORS SHALL BE INSTALLED IN STAIRWELL
 ENABLING VIEWS OF UPPER AND LOWER STAIRWAYS
  
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-10-2012 Cont ID  
Sent By tward Date 12-10-2012 Time 16:04 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2012-12-10 16:33:491. SFWMD ERP REQUIRED BEFORE START OF
 CONSTRUCTION/DEMOLITION.
 2. EROSION CONTROL PLAN AND STORM WATER POLLUTION
 PREVENTION PLAN REQUIRED WITH ENGINEERING PERMIT
 APPLICATION.
 3. NO DRAINAGE CALCULATIONS PROVIDED. CALCULATIONS WILL
 BE NEEDED WITH THE ENGINEERING PERMIT APPLICATION.
 4. NO ENGINEERING PLANS PROVIDED OTHER THAN ENGINEERING
 SITE PLAN.
 5. AVOID LOCATING TREES ADJACENT TO UNDERGROUND UTILITY
 LINES.
 6. OAK TREES NEAR YARD DRAINS WILL RESULT IN
 LEAVES/ACORNS ACCUMULATING IN/ON YARD DRAIN.
 7. EXISTING CURB INLET ON TAMARIND AVE, POINT OF
 PROPOSED DRAINAGE CONNECTION, MAY HAVE TO BE REPLACED
 DEPENDING ON CURRENT CONDITION OF THE INLET.
 8. CONSIDER MOVING FIRE LINES TO BUILDINGS A1 AND A2
 FURTHER NORTH AND CLOSER TO INLET TO AVOID THE BREAK IN
 THE EXFILTRATION TRENCH SOUTH OF THE INLET.
 9. NOTE ON ENGINEERING SITE PLAN INDICATES EXISTING ROW
 TO BE ABANDONED. SURVEY INDICATES DOUGLAS AVE ROW QUIT
 CLAIMED TO PALM BEACH HOUSING AUTHORITY.
 10. NO SIDEWALK PROPOSED ALONG THE SOUTH SIDE OF GRANT
 STREET ALONG THE NORTH PROPERTY LINE?
 11. HOW WILL DRAINAGE IN 50' EASEMENT ACCOMMODATE
 FUTURE ROAD IN THIS EASEMENT?
 12. LEGAL DESCRIPTION OF PROPERTY - PLAT OF DUNBAR
 VILLAGE RECORDED ON PAGE 77 (NOT 177) OF PLAT BOOK 18.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 02-12-2013 Cont ID  
Sent By vnoel Date 02-12-2013 Time 10:45 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2013-02-12 10:49:00PASSED, BUT 30" FM ALONG NORTH LINE STILL HAS "WATER"
 IN THE LINE TEXT.
 IF THE 30" FM IS "NOT LOCATED", HOW IS IT BEING SHOWN?
 IF FROM CITY AS-BUILTS, THEN LABEL AS SUCH.

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-12-10 09:14:141. PROPERTY WILL NEED TO BE REPLATTED.
 2. 30" FM ALONG NORTH LINE IS CALLED OUT AS "WATER".
 LANDSCAPING WILL NEED TO BE REMOVED FROM THIS AREA.
 3. WHO WILL BE THE RECIPIENT OF THE 50 FOOT EASEMENT?
 4. ARE ON-SITE UTILITIES TO BE PRIVATE OR PUBLIC? IF
 PROPOSED PUBLIC, WILL NEED APPROVAL FROM UTILITIES
 DEPT.
 5. HOW ARE THE MULTIPLE BUILDING ENCROACHMENTS TO BE
 HANDLED?
 6. LABEL LOCATIONS OF TRASH RECEPTACLES.
 7. SOUTH END OF PROPOSED BUILDINGS ENCROACH INTO
 PROPOSED 10' UTILITY EASEMENT ADJACENT TO 50' EASEMENT.
 8. 10' UTILITY EASEMENT SHOWN IN DIFFERENT LOCATION ON
 LANDSCAPE PLANS AND NOT LABELED ON SITE PLAN.
 9. EXISTING GAS/TELEPHONE LINES WILL NEED TO BE
 ADDRESSED.
 10. DEDICATED FPL EASEMENTS SHOULD BE GRANTED TO
 REPLACE BLANKET EASEMENT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 12-11-2012 Time 10:00 Sent To  
Notes
2012-12-11 10:01:23PLEASE DESCIBE ACCESS/EGRESS TO SOUTH.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 12-10-2012 Time   Sent To  
Notes
2012-12-10 15:00:58ZONING COMMENTS
  
 ZONING COMMENTS
  
 1. WHEN RESUBMITTING:
  
 A. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 ALL DEPARTMENTS IN A WRITTEN FORMAT.
 B. 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11X17) AND
 AN ELECTRONIC COPY OF ALL PLANS.
 C. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 D. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 E. IN ORDER TO BE CONSIDERED FOR THE JANUARY PLANNING
 BOARD MEETING PLANS MUST BE RESUBMITTED BY DECEMBER 21,
 2012.
  
 SITE PLAN COMMENTS:
 2. WHAT SETBACK STANDARDS ARE YOU USING RESIDENTIAL
 PLANNED DEVELOPMENT OR MF32? THE SITE PLAN SHOWS A 25
 FOOT SETBACK ALONG GRANT AND 20 AROUND THE OTHER
 PROPERTY LINES. STAFF WOULD LIKE TO SEE THE BUILDING
 PUSHED UP AT CLOSE TO THE STREETS AS POSSIBLE.
  
 3. WILL THERE BE AN ENTRANCE OFF OF TAMARIND?
 RESIDENTIAL DEVELOPMENT SIGNS ARE ONLY PERMITTED AT
 ENTRANCES INTO THE DEVELOPMENT 94-407(2).
  
 4. WILL THIS SITE BE ENCLOSED WITH A FENCE?
  
 5. DO YOU CURRENTLY HAVE ANY ILLUSTRATION OF WHAT THE
 SIGN WILL LOOK LIKE?
  
 6. THERE IS ON-STREET PARKING ALONG TAMARIND THAT COULD
 COUNT TOWARDS REQUIRED PARKING. THIS WILL HELP REDUCE
 THE PARKING WAIVER.
  
 7. THE BUILDINGS LOCATED ALONG THE SOUTH PROPERTY LINE
 ENCROACH INTO THE REQUIRED 10 FOOT LANDSCAPE BUFFER.
  
 8. PROVIDE BICYCLE PARKING DETAILS.
  
 LANDSCAPE PLAN COMMENTS:
  
 9. THE LANDSCAPE PLAN INDICATED THAT A VARIANCE IS
 NEEDED FOR THE MULTIFAMILY TREE REPLACEMENT. NO
 REQUIRES IS SHOWN ON THE WAIVER SHEET OR IN THE
 JUSTIFICATION LETTER.
  
 10. NO MORE THAN 20% OF THE LANDSCAPE BUFFER CAN BE
 INTERRUPTED FOR DRIVEWAYS. THE BUFFER ALONG GRANT DOES
 NOT COMPLY WITH THIS REQUIREMENT.
  
 ELEVATIONS/ARCHITECTURAL PLANS:
  
 11. PROVIDE A PERSPECTIVE OF THE VIEW ALONG THE
 TAMARIND CORRIDOR.
  
 12. PLEASE PROVIDE IN WRITING THAT YOU COMPLY WITH THE
 ARCHITECTURAL STANDARDS SHOWN BELOW AND FOUND IN
 ORDINANCE NO. 4402-12, SECTION 94-222(H), IF
 APPLICABLE:
  
  
 (H) ARCHITECTURAL STANDARDS: ARCHITECTURAL STANDARDS
 FOR COLEMAN PARK SHALL BE AS FOLLOWS:
 (1) EXTERIOR FINISH MATERIAL MAY INCLUDE STONE, BRICK,
 STUCCO, EXPOSED CONCRETE, CERAMIC TILE,
 ANY STONE CLADDING MATERIAL, LIMESTONE, PRECAST
 CONCRETE, CLAPBOARD SIDING, FIBER CEMENT
 SIDING AND WOOD SHINGLES. WALLS SHALL COMBINE NO MORE
 THAN TWO MATERIALS AND SHALL
 CHANGE MATERIAL ALONG A HORIZONTAL LINE, WITH THE
 VISUALLY HEAVIER MATERIAL BELOW THE
 LIGHTER MATERIAL. VINYL AND ALUMINUM SIDING SHALL BE
 PROHIBITED.
 (2) FRONT FACING GARDEN WALLS AND FENCES SHALL BE 48
 INCHES IN HEIGHT.
 LANGUAGE UNDERLINED ADDED, AND LANGUAGE STRICKEN
 DELETED.
 (3) REAR GARDEN WALLS AND FENCES NOT FACING STREETS
 SHALL BE 48 TO 72 INCHES IN HEIGHT. GARDEN
 WALLS AND FENCES SHALL CONSIST OF PAINTED, STAINED, OR
 PRESSURE TREATED WOOD PICKETS, PLASTIC
 COATED CHAIN LINK, DECORATIVE METAL, INDIGENOUS ROCK,
 OR BLOCK AND STUCCO.
 (4) ALL BUILDINGS SHALL HAVE THEIR PRINCIPAL PEDESTRIAN
 ENTRANCE(S), INCLUSIVE OF FLAT, STEPPED OR
 SLOPED WALKWAYS, ON THE FRONTAGE LINE, CONNECTING THE
 FRONT ENTRANCE OF THE PRIMARY
 STRUCTURES WITH THE STREET.
 (5) WINDOWS SHALL BE VERTICAL OR SQUARE IN PROPORTION.
 (6) WINDOWS SHALL BE RECESSED A MINIMUM OF TWO INCHES
 FROM THE EXTERIOR FACE OF THE FACADE.
 (7) ALL WINDOWS SHALL BE OPERABLE.
 (8) MULTIPLE WINDOWS IN THE SAME ROUGH OPENING SHALL BE
 SEPARATED BY A FOUR-INCH WIDE POST
 AND SIT ON ONE CONTINUOUS SILL.
 (9) IF SHUTTERS ARE USED, THEY MUST BE OPERABLE, SIZED
 TO MATCH THE OPENING, AND PROVIDED FOR
 ALL WINDOWS ON A GIVEN WALL.
 (10) SLIDING DOOR SHALL ONLY BE ALLOWED ON REAR
 FACADES. ALL OTHER EXTERIOR DOORS SHALL BE
 HINGED, EXCEPT GARAGE DOORS.
 (11) GARAGES SHALL BE SETBACK A MINIMUM OF FIVE (5)
 FEET BEHIND THE FRONT FACADE FOR FRONT
 FACING GARAGE DOORS.
  
 OTHER ISSUES:
  
 13. AMEND THE JUSTIFICATION LETTER TO REQUEST THAT
 ADULT DAY CARE FACILITIES BE ADDED TO THE PERMITTED
 USES ALLOW IN THE RPD.
  
 14. PRIOR TO SCHEDULING THIS APPLICATION BEFORE THE
 PLANNING BOARD, THE APPLICANT SHALL HAVE AN
 INFORMATIONAL MEETING WITH THE COLEMAN PARK
 NEIGHBORHOOD ASSOCIATION.
  
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  

  Print