| 2012-12-11 13:43:31 | CONDITIONS FOR APPROVAL |
| | PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE |
| | APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY |
| | AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST |
| | PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL, OFC. KELLY |
| | CARSILLO (561) 822-1620. |
| | A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION |
| | TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE |
| | SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES |
| | FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT |
| | BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, |
| | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, |
| | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE |
| | SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF |
| | WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER |
| | MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE |
| | WORKING ENVIRONMENT. |
| | B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED |
| | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. |
| | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A |
| | STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT |
| | DEVELOPMENT. |
| | C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY |
| | 500 FEET AROUND THE PERIMETER OF THE SITE. |
| | |
| | * THE FRONT DESK COUNTER HAS A SPLIT IN THE DESIGN; |
| | PLACE A SWING DOOR TO LIMIT ACCESS TO THE PUBLIC |
| | * IF THE HOTEL SHOP AREA IS THE ROOM NEXT TO THE FRONT |
| | DESK, PLACE A WINDOW AT THE FRONT DESK FOR MORE |
| | SURVEILLANCE OF THE SHOP. |
| | * GLASS WINDOWS SHOULD FRONT THE EXERCISE ROOM. |
| | EMERGENCY PHONE SHOULD BE IN THIS ROOM. |
| | * EMPLOYEE AREAS NEED TO BE CONTROLLED ACCESS |
| | * THE PARKING LOT, TRESS NEED TO BE CUT BACK, I WANT |
| | TO SEE THE LIGHTING FIXTURES TO BE USED, THE LOCATION |
| | OF THE POLES IN CONJUNCTION WITH THE TREES/LANDSCAPING. |
| | FENCE IN THIS LOT. |
| | THE MAJORITY OF THE BELOW COMMENTS IS WHAT I WOULD BE |
| | LOOKING FOR AS THIS PROJECT PROGRESSES: |
| | LIGHTING |
| | A. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES. |
| | B. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS, |
| | BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS. |
| | C. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR |
| | ABOVE OR NEAR ENTRYWAYS AND ALL PEDESTRIAN SIDEWALKS |
| | SHALL BE PROVIDED. |
| | D. LIGHTING FOR ENTRANCE SIGN SHALL BE PROVIDED. |
| | E. LIGHTING ON BUILDINGS SHALL BE AROUND PERIMETER OF |
| | ALL SIDES AND ON PEDESTRIAN WALKWAY SURROUNDING THE |
| | BUILDINGS. |
| | NUMERICAL ADDRESS |
| | A. ILLUMINATED FOR NIGHTTIME VISIBILITY IS REQUIRED. |
| | B. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS |
| | REQUIRED. |
| | C. ADDRESS NUMBERS ON DOORS NEED TO BE A MINIMUM OF 6 |
| | INCHES HIGH. |
| | GUESTROOMS |
| | A. GUESTROOMS ALL NEED TO HAVE ELECTRONIC CARD ACCESS. |
| | B. DOORS SHALL BE SOLID-CORE WOOD OR METAL, AND BE |
| | SELF-CLOSING AND SELF-LOCKING. THE DOOR LOCK MUST |
| | CONSIST OF A HIGH QUALITY DEADBOLT WITH AT LEAST A |
| | ONE-INCH BOLT. THE LOCK STRIKE-PLATE MUST BE BOLTED |
| | SECURELY TO THE METAL DOORFRAME OR BY USING THREE-INCH |
| | SCREWS WHEN ATTACHED TO A WOOD DOORJAMB. ACCESSIBLE |
| | SLIDING WINDOWS MUST HAVE SECONDARY SECURITY DEVICES |
| | ATTACHED TO PREVENT FORCED ENTRY OR LIFTING OUT OF THE |
| | FRAME. |
| | C. EACH GUESTROOM SHALL BE PROVIDED WITH IN-ROOM |
| | ELECTRONIC SAFES. (NOTE: MUST BE PREPLANNED BY |
| | ELECTRICAL ENGINEER FOR ELECTRICAL HOOK-UP.) |
| | D. GUESTROOMS SHALL NOT BE ACCESSIBLE FROM OUTSIDE |
| | UNLESS BY ELECTRONIC ACCESS. |
| | EXTERIOR |
| | A. EXTERIOR BUILDING LIGHTING SHALL BE REQUIRED FOR ALL |
| | EXIT WAY, EMERGENCY ACCESS, STAIRWAY AND UTILITY ROOM |
| | DOORS. |
| | B. SECONDARY ACCESS, OTHER THAN MAIN LOBBY, SHALL BE |
| | AVAILABLE BY CONTROLLED ACCESS. |
| | C. POOL AREA RESTRICTED ACCESS HELPS PREVENT |
| | UNAUTHORIZED USE, CURBS POTENTIAL VANDALISM AND |
| | PROVIDES GREATER SECURITY AND PROTECTION TO POOL USERS, |
| | ESPECIALLY CHILDREN. |
| | D. MAIN ENTRANCE SHALL LEAD DIRECTLY TO THE FRONT LOBBY |
| | AREA WITH VISIBLE SIGNAGE INDICATING SO. |
| | E. TRAFFIC LEADING TO LOBBY OVERHANG AND/OR CIRCULAR |
| | DRIVE SHALL BE ONE WAY WITH SIGNAGE STATING SAME. |
| | STAFF |
| | A. EMPLOYEES SHALL BE INSTRUCTED TO GREET GUESTS TO |
| | REDUCE THE FEAR OF CRIME AND PROVIDE A SENSE OF |
| | SECURITY. THEY SHOULD BE TRAINED TO RECOGNIZE |
| | SUSPICIOUS PERSONS, BE AN EXTRA SET OF SECURITY EYES |
| | AND EARS FOR THE PARKING LOT AREAS, TEACH GUESTS HOW TO |
| | SECURE THEIR POSSESSIONS AND COMMUNICATE SAFE AREAS AND |
| | ROUTES TO VISIT. |
| | B. UNIFORMED OR NON-UNIFORMED PERSONNEL, WHOSE PRIMARY |
| | FUNCTION IS SECURITY, SHOULD BE EMPLOYED. |
| | C. GUESTS SHALL HAVE 24-HOUR ACCESS TO AN ON-PREMISES |
| | GUEST CONTACT STAFF MEMBER. |
| | D. APPLICATION FORMS SHALL CONTAIN LANGUAGE ALLOWING |
| | THE EMPLOYER TO CONDUCT CRIMINAL BACKGROUND CHECKS ON |
| | ALL EMPLOYEES. |
| | E. WRITTEN EMPLOYEE POLICIES AND PROCEDURES FOR LOST |
| | AND FOUND PROPERTIES SHALL BE ESTABLISHED. |
| | F. FRONT DESK CLERK SHALL BE ON DUTY AT ALL TIMES. |
| | 1.1 MISCELLANEOUS |
| | A. BEVERAGE MACHINES SHALL BE KEPT IN OPEN AREAS. |
| | B. PUBLIC PHONES SHALL BE KEPT IN OPEN AREAS, |
| | PREFERABLY WITHIN VIEW OF THE FRONT DESK. |
| | C. LEGENDS, MARQUIS MAPS, ETC., SHALL BE USED |
| | INDICATING LOCATIONS OF CONFERENCE ROOMS, ELEVATORS, |
| | STAIRS, LOBBY AREAS, RESTAURANTS, POOL, WORKOUT ROOM, |
| | ETC. |
| | D. GIFT SHOP WINDOWS SHALL BE CLEAR TO INCREASE NATURAL |
| | SURVEILLANCE |
| | E. ATM INSTALLATION SHALL MEET FSS REQUIREMENTS |
| | F. STAIRWELLS SHALL HAVE CONVEX MIRRORS INSTALLED AT |
| | LANDINGS FOR EACH LEVEL. |
| | G. INTERIOR OF ELEVATORS SHALL UTILIZE MIRRORS AND CCTV |
| | H. INSTALL CCTV FOR SURVEILLANCE OF LOBBY, STAIRWELLS, |
| | PARKING LOTS, POOL AREA AND SERVICE AREAS OF |
| | BANQUET/MEETING ROOMS. |
| | |
| | |
| | |