Plan Review Details - Project Z12070019
Plan Review Stops For Project Z12070019
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-07-2012 Cont ID  
Sent By lmartine Date 08-07-2012 Time 16:45 Rev Time 0.00
Received By lmartine Date 08-07-2012 Time 16:45 Sent To  
Notes
2012-08-07 16:46:57LOOKS GOOD.
  
 NO BUILDING COMMENTS AT THIS TIME.
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-07-2012 Cont ID  
Sent By aaponte Date 08-07-2012 Time 11:27 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 09-08-2012 Cont ID  
Sent By ddaniels Date 09-08-2012 Time 14:30 Rev Time 0.00
Received By ddaniels Date 09-08-2012 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 07-30-2012 Cont ID  
Sent By ddaniels Date 07-30-2012 Time 23:32 Rev Time 0.00
Received By ddaniels Date 07-30-2012 Time 23:32 Sent To  
Notes
2012-07-30 23:56:187/30/12 PLANS REVIEWED BY FIRE **DENIED**
  
 1. SHOW SCOPE OF WORK ON PLANS.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 6. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 7. PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 8. PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2
 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1).
  
 9. STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 10. PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 11. STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE
 LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101
 FLORIDA 2010 EDITION.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  

Review Stop PARK PARKING
Rev No 1 Status F Date 08-08-2012 Cont ID  
Sent By ssamuels Date 08-08-2012 Time 10:00 Rev Time 0.00
Received By ssamuels Date 08-08-2012 Time 10:00 Sent To  
Notes
2012-08-08 10:03:05PLEASE PROVIDE PARKING DETAIL SPECIFICATION
 HANDICAP LOGO
 HANDICAP SIGN

Review Stop POLICE POLICE
Rev No 2 Status P Date 09-20-2012 Cont ID  
Sent By   Date 09-20-2012 Time   Rev Time 0.00
Received By ktucker Date 09-20-2012 Time 15:07 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-02-2012 Time   Rev Time 0.00
Received By ktucker Date 08-02-2012 Time 11:02 Sent To  
Notes
2012-08-02 13:02:58CAMERA BOTH ENTRY VESTIBULES WITH MONITORS BEHIND
 TELLER LINES
 ARE THE RESTROOMS PUBLIC? IF SO THE DOORS LEADING TO
 THE DATA ROOM AND BREAKROOM NEED TO BE CARD ACCESS.
 CONSIDER A CAMERA MONITOR IN THE BREAKROOM
  
  
 A.ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 ADDRESS SHOULD BE PLACED UNDER A LIGHT FIXTURE OR BE
 BACK LIT.
 B.BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 C.ADDRESS SHOULD BE PLACED ON THE REAR OF THE BUILDING
 FOR POLICE
 D.ADDRESS NUMBERS ON DOORS SHALL BE A MINIMUM OF 6
 INCHES HIGH.
 E.ALL ENTRY DOORS (NON-GLASS SINGLE/DOUBLE) SHALL BE
 EQUIPPED WITH AN ASTRAGAL OVER THE THRESHOLD OF THE
 LOCKING MECHANISM AND CASE HARDENED DEADBOLT LOCKS
 SHALL BE PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM
 ONE (1) INCH THROW OR MECHANICAL INTERLOCK. DOORS
 SECURED BY ELECTRICAL OPERATION SHALL HAVE A KEYED
 SWITCH OR SIGNAL LOCKING DEVICE TO OPEN THE DOOR WHEN
 IN LOCKED POSITION. GLASS EXTERIOR DOORS SHOULD HAVE A
 HOLDING FORCE OF AT LEAST 1000LBS. DOOR HINGES SHALL
 EMPLOY NON-REMOVABLE HINGES, AND THE MAIN ENTRIES TO
 THE BANK BUILDING SHALL BE WIRED FOR CLOSED CIRCUIT
 DIGITAL CAMERA SURVEILLANCE SYSTEM.
 F.INTERIOR DOORS TO OFFICES/MEETING ROOMS SHALL HAVE
 180 DEGREE PEEPHOLE OR VISION PANEL.
 G.EXTERIOR/INTERIOR PEDESTRIAN DOORS WHICH PROVIDE
 ACCESS INTO PARKING LOTS SHALL BE SOLID CORE AND WHERE
 APPLICABLE EMERGENCY DOORS SHALL HAVE NO EXTERIOR
 HANDLES. PANIC HARDWARE SHALL HAVE SELF LOCKING
 MECHANISM, MAY HAVE ONE LOCKING POINT BETWEEN THE DOORS
 AND FRAME, IT SHOULD EXTEND ONE INCH BEYOND EDGE OF THE
 DOOR TO WHICH IT IS ATTACHED.
 H TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO BUILDINGS FOR DUSK TO DAWN
 OPERATION SHALL BE PROVIDED.
 I.BUILDING LIGHTING (NON-GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDES.
 J.MAIN EXIT DOORS SHALL HAVE HEIGHT MARKERS.
 K.ALARM SYSTEMS SHALL BE INSTALLED.
 L. HIGH-RESOLUTION COLOR DIGITAL VIDEO CAMERA SYSTEM
 WITH MONITORING AND PHOTO PROCESSING CAPABILITIES SHALL
 BE INSTALLED ABOVE EXIT DOORS, TELLER COUNTERS AND
 DRIVE-THRU LANES.
 M. MONEY LEVER SWITCHES WITHIN TELLER CASH DRAWERS THAT
 WILL ACTIVATE SYSTEM IN EMERGENCY SITUATIONS SHALL BE
 INSTALLED.
 N. DRIVE-THRU AREAS SHALL BE PROVIDED WITH ONE WAY
 DIRECTIONAL SIGNAGE.
 O. NIGHT DEPOSIT SHOULD BE LOCATED IN THE DRIVE- THRU
 LANE CLOSEST TO THE BUILDING WITH A COLOR DIGITAL VIDEO
 CAMERA TO CAPTURE TRANSACTIONS.
  
 AUTOMATED TELLER MACHINES
  
  ATM LOCATIONS SHALL BE IN AREAS WITH THE GREATEST
 NATURAL SURVEILLANCE AND INDEPENDENT FROM THE
 BUILDING.
 A. AUTOMATED TELLER MACHINES (ATM?S) SHALL COMPLY WITH
 FSS 655-966.
 B. ATM?S SHALL BE LOCATED ON MAIN ROADS IF APPLICABLE
 AND BE VISIBLE FROM THE ROADWAY.
 C. ATM?S SHALL NOT BE HIDDEN BY ANY LANDSCAPING OR
 OTHER FIXED OBJECT THAT WOULD PREVENT CLEAR VISIBILITY.
 D. ATM?S SHALL HAVE HIGH-RESOLUTION COLOR DIGITAL VIDEO
 CAMERA SYSTEM INSTALLED.
 E. ATM?S SHALL HAVE HIGH ILLUMINATION OF WALKWAYS
 LEADING TO AND FROM IT.
 F. LIGHTING SHALL BE POSITIONED SO AS NOT TO CAUSE
 GLARE ON VIDEO RECORDING.
 G. CONVEX MIRROR SHALL BE INSTALLED AND STRATEGICALLY
 PLACED TO ALLOW ATM OPERATOR TO IDENTIFY ANY
 APPROACHING PERSON(S) AND/OR POTENTIAL SUSPECT(S).
 H. ATM?S SHALL HAVE AN ALARM SYSTEM COMPONENTS, SHOCK
 AND SEISMIC SENSORS, SUFFICIENT WEIGHT AND TENSILE
 STRENGTH, HEAT DETECTORS, DOOR CONTACTS AND LOCKING
 MECHANISMS, TO DETER ATTACKS TO THE MACHINE ITSELF.
 DEVICES ARE NEEDED TO PROVIDE EARLY WARNING OF AN
 IMPENDING ATTACK.
 I. ATM?S SHOULD HAVE DURESS ALARMS AND A SECURE CLOSET
 TO SERVICE THE MACHINE.
  
  
  
 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A.AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B.THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C.PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
  
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-09-11 08:59:14PREVIOUS COMMENTS TO BE ADDRESSED AT LAND DEVELOPMENT
 STAGE.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-01-2012 Cont ID  
Sent By tward Date 08-01-2012 Time 12:52 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2012-08-01 13:12:008/1/2012
 1. NO DRAINAGE CALCULATIONS PROVIDED.
 2. STORMWATER WATER QUALITY TREATMENT TO BE PROVIDED ON
 SITE.
 3. FINAL DESIGN PLANS TO INCLUDE AN EROSION AND
 SEDIMENT CONTROL PLAN.
 4. FINAL DESIGN PLANS TO INCLUDE GRADING PLAN AND
 DRAINAGE DETAILS FOR EXFILTRATION TRENCH AND CONTROL
 STRUCTURE.
 5. SFWMD ERP PERMIT (OR EXEMPTION LETTER) IS REQUIRED
 BEFORE CONSTRUCTION.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 (561) 494-1120

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 09-06-2012 Cont ID  
Sent By vnoel Date 09-06-2012 Time 08:42 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-09-06 08:42:19FORM OF SIDEWALK EASEMENT AND UNITY OF TITLE
 APPLICATION BEING SENT TO APPLICANT.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-31-2012 Cont ID  
Sent By vnoel Date 07-31-2012 Time 12:40 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-07-31 12:40:091. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH THE ENGINEERING SERVICES DEPT.
 2. SIDEWALK EASEMENT WILL BE REQUIRED OVER THE EXISTING
 SIDEWALK ALONG BANYAN BLVD.
 3. ELEVATIONS NEED TO BE IN NGVD-29 PER CITY CODE, NOT
 NAVD 88.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 08-29-2012 Cont ID  
Sent By   Date 08-29-2012 Time   Rev Time 0.00
Received By bcollins Date 08-29-2012 Time 16:15 Sent To  
Notes
2012-08-29 16:15:26COMMENTS ADDRESSED

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-07-2012 Time   Rev Time 0.00
Received By bcollins Date 08-07-2012 Time 15:42 Sent To  
Notes
2012-08-07 16:11:28THE ALLEY ON THE SOUTH SIDE OF THE ALLEY IS ONE WAY
 WESTBOUND BY CODE. THE 14 FT. ALLEY IS TOO NARROW FOR 2
 WAY TRAFFIC AND ANY ACCESS TO THE ALLEY SHOULD BE
 MODIFIED TO PROVIDE EITHER ACCESS OR EGRESS ONLY. THE
 WESTERN ACCESS POINT ON BANYAN SHOULD BE LIMITED TO
 EGRESS ONLY OR DESIGNED TO ALLOW RIGHT TURN EGRESS ONLY
 DUE TO THE LOCATION OF THE WESTBOUND LEFT TURN LANE
 FROM BANYAN ONTO DIXIE. THE CLOSED PARKING SPACE TO THE
 ALLEY ON THE EAST SIDE OF THE PROPERTY WILL REQUIRE
 VEHICLES TO BACK OUT INTO THE ALLEY. THE PUBLIC
 SIDEWALK ON BANYAN ACROSS THE SITE DRIVEWAYS SHALL BE
 MADE ADA COMPLIANT INCLUDING THE PROVISION OF TACTILE
 SURFACES TO ALERT PEDESTRIANS OF THE DRIVEWAYS.

Review Stop Z ZONING
Rev No 2 Status P Date 09-11-2012 Cont ID  
Sent By aaponte Date 09-10-2012 Time 15:02 Rev Time 0.00
Received By aaponte Date 09-10-2012 Time 15:01 Sent To  
Notes
2012-09-11 08:11:32 
 READY FOR DAC REVIEW

Review Stop Z ZONING
Rev No 1 Status F Date 08-07-2012 Cont ID  
Sent By aaponte Date 08-07-2012 Time 12:59 Rev Time 0.00
Received By aaponte Date 08-07-2012 Time 11:27 Sent To  
Notes
2012-08-07 12:58:58ZONING COMMENTS:
 1. PLEASE PROVIDE DRAWINGS FOR THE EXISTING BUILDING.
 EXISTING CONDITIONS OF ELEVATION AND EXISTING BUILDING
 FOOTPRINT. PLEASE CLEARLY INDICATE WHAT PORTIONS
 (WALLS) OF THE EXISTING BUILDING ARE MAINTAINED.
 2. PLEASE PROVIDE A SITE PLAN WITH DIMENSIONS OF STREET
 FRONTAGES TO DETERMINE EXACT DIMENSION OF BUILDING
 FRONTAGE AND COMPLIANCE WITH MINIMUM ACTIVE USE
 FRONTAGE REQUIREMENT. MINIMUM ACTIVE USE REQUIREMENT IS
 65% OF FRONTAGE ALONG BANYAN BOULEVARD. VARIANCE MAY BE
 NECESSARY.
 3. PLEASE PROVIDE A SKETCH INDICATING THE AREA USED TO
 CALCULATE THE 25% PRIVATE OPEN SPACE REQUIREMENT.
 4. PLEASE PROVIDE A TABLE INDICATING THE TOTAL AREA OF
 THE FACADE ALONG BANYAN BOULEVARD AND THE PERCENTAGE OF
 TRANSPARENCY PROVIDED.
 5. IT IS RECOMMENDED THE DRIVE THRUE PARAPET WALL IS
 MAINTAIN BELOW THE FRIEZE HEIGHT ON EXISTING BUILDING.
 6. IT IS RECOMMENDED A LOW WALL (AT WINDOW SILL HEIGHT)
 BE INSTALLED ALONG THE BUILDING PRONTAGE. LOW LANDSCAPE
 SHALL BE INSTALLED IN FRONT AND TALLER HEDGES BEHIND
 WITH A TREE OR PALM.
 7. TWO BLANK WALLS ARE PROPOSE FOR THE PROJECT (EAST
 AND WEST ELEVATIONS). FENESTRATION SHALL BE PROVIDED TO
 COVER A MINIMUM 15% OF THE FACADE AREA. COULD SOME
 WINDOWS TO THE BATHROOMS AND JANITOR ROOM BE ADDED? CAN
 VINES BE PLANTED ALONG THE WEST ELEVATION TO MINIMIZE
 THE IMPACT OF THE FACADE?
 8. PLEASE CLARIFY PLANS FOR PROJECTING OR RECESSED
 ELEMENTS.
 9. STREET TREES, PLANTED ON TREE GRATES ALONG THE
 STREET CURB, ARE REQUIRED EVERY 30 FEET OF FRONTAGE.
 10. CAN THE BY-PASS LANE FOR THE DRIVE -THRU BE REDUCED
 TO 11 FEET?
 11. LANDSCAPE BUFFER ALONG EAST PROPERTY LINE DOES NOT
 COMPLY WITH THE MINIMUM 5 FEET REQUIRED. IF ADJACENT
 TRAVEL LANE IS REDUCED, BUFFER COULD BE INCREASED.
 VARIANCE APPROVAL MAY BE NECESSARY.
 12. ARE THE TWO-WAY ACCESS POINTS ALONG THE ALLEY
 NECESSARY? IF NOT, ADDITIONAL OPEN SPACE MAY BE
 PROVIDED.
 13. PROPOSED BIKE RACK SHALL BE RELOCATED TO THE INSIDE
 OF THE PARKING LOT.
 14. PROPOSED LANDSCAPE ALONG THE ALLEY SHALL BE
 PROTECTED WITH A RAISED CURB OR SIMILAR DEVICE.
 15. CURB CUTS SHALL NOT BE WIDER THAN 25 FEET AS
 MEASURED PARALLEL TO THE STREET AT THE CURB.
  
 HISTORIC PRESERVATION COMMENTS:
 1. ARCHED WINDOWS ARE RECOMMENDED TO BE DOUBLE FAN
 WINDOWS.
 2. PLEASE PRESERVE THE EXISTING IRON GATE AT THE MAIN
 ENTRANCE.
 3. PLEASE PRESERVE EXISTING LIGHT FIXTURES ALONG BANYAN
 BOULEVARD.
 4. PLEASE CONFIRN THE DIMENSION OF THE ARCH OPENNING TO
 BE MODIFIED WITH NEW WINDOWS.
 5. PLESE CALL OUT DECORATIVE FRIEZE ELEMENT.
 6. IF APPLICANT DESIRES TO DESIGNATE THE BUILDING AS A
 HISTORIC STRUCTURE, AND UTILIZE THE BENEFITS OF THE AD
 VALOREM TAX EXEMPTION, CONSTRUCTION CAN NOT START UNTIL
 THE BUILDING HAS BEEN DESIGNATED BY THE CITY
 COMMISSION. THE PROCESS TAKES APPROXIMATELY 3 MONTHS.
  