Plan Review Details - Project Z12070018
Plan Review Stops For Project Z12070018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-07-2012 Cont ID  
Sent By lmartine Date 08-07-2012 Time 16:20 Rev Time 0.00
Received By   Date 09-20-2012 Time 15:08 Sent To  
Notes
2012-08-07 16:40:37BUILDING REVIEW COMMENTS
  
  
 PLEASE SEE 2010 FLORIDA BUILDING CODE.
  
 THE PLANS WERE REVIEWED AS ONE BUILDING.
  
 CHAPTER 3 DEFINES YOUR PROPOSED USE AS R-4.
  
 CHAPTER 5 WILL REGULATE THE ALLOWABLE HEIGHT AND AREA,
 PLEASE SEE TYPE 1B OR 3B AND 504.2 FOR ANY HEIGHT
 INCREASES.
  
 TABLE 601 WILL DETERMINE THE FIRE RESISTANCE (HOUR)
 RATINGS FOR YOUR BUILDING ELEMENTS.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 11-05-2012 Cont ID  
Sent By bmoree Date 11-05-2012 Time   Rev Time 0.00
Received By bmoree Date 11-05-2012 Time   Sent To  
Notes
2012-11-05 15:39:181. SPECIFIC COMMENTS ARE NOT AVAILABLE UNTIL CIVIL SITE
 DRAWINGS ARE SUBMITTED TO THE ENGINEERING SERVICES &
 PUBLIC WORKS DEPARTMENT FOR FORMAL REVIEW.
 2. A STORMWATER POLLUTION PREVENTION PLAN (SWPPP) WILL
 BE REQUIRED PRIOR TO COMMENCEMENT OF SITE WORK.
 3. A RIGHT-OF-WAY PERMIT WILL BE REQUIRED FOR ALL
 PROJECT RELATED WORK IN THE ADJACENT PUBLIC
 RIGHT-OF-WAY.
 4. SOLID WASTE COLLECTION TRAFFIC CIRCULATION IS
 OBSTRUCTED BY THE BUILDING FOR THE EAST PARKING EXIT.
 CURRENT DUMPSTER LOCATION REQUIRES MULTI-POINT TURN FOR
 EXITING. DUMPSTER RELOCATION AND/OR DEDICATED
 TURN-AROUND AREA REQUIRED.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-08-2012 Cont ID  
Sent By bmoree Date 08-08-2012 Time 12:52 Rev Time 0.00
Received By bmoree Date 08-08-2012 Time   Sent To  
Notes
2012-08-08 12:52:171. SPECIFIC COMMENTS ARE NOT AVAILABLE UNTIL CIVIL SITE
 DRAWINGS ARE SUBMITTED TO THE ENGINEERING SERVICES &
 PUBLIC WORKS DEPARTMENT FOR FORMAL REVIEW.
 2. A STORMWATER POLLUTION PREVENTION PLAN (SWPPP) WILL
 BE REQUIRED PRIOR TO COMMENCEMENT OF SITE WORK.
 3. A RIGHT-OF-WAY PERMIT WILL BE REQUIRED FOR ALL
 PROJECT RELATED WORK IN THE ADJACENT PUBLIC
 RIGHT-OF-WAY.
 4. DUMPSTER LOCATION NEEDS TO BE RECOFIGURE FOR ONSITE
 PICK-UP.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 10-19-2012 Cont ID  
Sent By ddaniels Date 10-19-2012 Time 13:10 Rev Time 0.00
Received By ddaniels Date 10-19-2012 Time 13:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 09-11-2012 Cont ID  
Sent By ddaniels Date 09-11-2012 Time 17:52 Rev Time 0.00
Received By ddaniels Date 09-11-2012 Time 17:52 Sent To  
Notes
2012-09-11 17:57:5109/11/2012 PLANS REVIEWED BY FIRE ***DENIED***
  
 FIRE COMMENTS HAVE NOT BEEN ADDRESSED. SECOND REVIEW
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 07-30-2012 Cont ID  
Sent By ddaniels Date 07-30-2012 Time 23:17 Rev Time 0.00
Received By   Date 08-02-2012 Time 14:13 Sent To  
Notes
2012-07-30 23:28:357/30/12 PANS REVIEWED BY FIRE **DENIED**
  
 1. SHOW SCOPE OF WORK ON PLANS.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  

Review Stop PARK PARKING
Rev No 3 Status N Date 10-23-2012 Cont ID  
Sent By ssamuels Date 10-23-2012 Time 17:58 Rev Time 0.00
Received By ssamuels Date 10-23-2012 Time 17:57 Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status F Date 08-08-2012 Cont ID  
Sent By ssamuels Date 08-08-2012 Time 11:57 Rev Time 0.00
Received By ssamuels Date 08-08-2012 Time 11:56 Sent To  
Notes
2012-08-08 11:58:40PLEASE PROVIDE PARKING DETAIL SPECIFICATION
  
 HANDICAP LOGO
 HANDICAP SIGN

Review Stop POLICE POLICE
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 2 Status P Date 09-20-2012 Cont ID  
Sent By   Date 09-20-2012 Time   Rev Time 0.00
Received By ktucker Date 09-20-2012 Time 15:08 Sent To  
Notes
2012-09-20 15:06:09ALL COMMENTS WERE ADDRESSED AS "WILL COMPLY" NOTHING
 SHOWN ON THE PLANS
 WILL BE LOOKING FORT THE CONSTRUCTION SITE SECURITY
 PLAN

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-02-2012 Time   Rev Time 0.00
Received By ktucker Date 08-02-2012 Time 14:13 Sent To  
Notes
2012-08-02 14:15:39CARD ACCESS INTO THE BUILDING SHOULD BE USED TO CONTROL
 ENTRY INTO THE BUILDING FOR RESIDENTS AND EMPLOYEES.
 VIDEO-CAMERAS SHOULD BE USED TO MONITOR THE PREMISES,
 THE LIVING ROOM AREAS, DINING ROOM, ENTRY DOORS,
 ELEVATOR AND STAIRWELL ENTRIES.
 THE ASSISTED LIVING FACILITY WILL NEED ANY AUXILIARY
 ENTRANCES LOCKED OR REQUIRE A CARD KEY OR NUMERIC CODE
 TO GAIN ACCESS.
 EMERGENCY BUTTONS IN THE APARTMENTS.
  
 RESIDENT DOORS SHOULD HAVE PEEPHOLES AND LOCKS THAT ARE
 EASY TO OPERATE, FOR PATIENTS WHO ARE WEAK OR WHO MAY
 HAVE ARTHRITIS.
  
 ALL DOORS RESIDENT DOORS SHALL BE EQUIPPED WITH SINGLE
 CYLINDER DEAD BOLT LOCK WITH A MINIMUM THROW OF ONE
 INCH AND AN EMBEDMENT OF NOT LESS 5/8 INCH INTO THE
 HOLDING DEVICE. PICK PLATES SHOULD ALSO BE PLACED ALL
 EXTERIOR DOORS. DOORS LEADING INTO A RESIDENTIAL UNIT
 SHALL BE SOLID CORE.
  
 WILL THERE BE A RECEPTIONIST?S DESK IN BOTH LIVING ROOM
 AREAS? VISITORS WILL NEED TO CHECK-IN BEFORE SEEING
 RESIDENTS
  
 EXIT DOOR ALARMS OR OTHER SYSTEM MUST BE PROVIDED FOR
 SECURITY PURPOSES AND TO ALERT STAFF WHEN RESIDENTS
 EXIT THE FACILITY
  
 CONVEX MIRRORS SHALL BE INSTALLED IN STAIRWELL ENABLING
 VIEWS OF UPPER AND LOWER STAIRWAYS.
  
 TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO RESIDENCES PROVIDE FOR DUSK
 TO DAWN OPERATION.
  
 ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING.
  
 BUILDING LIGHTING (NON GLARE) SHALL BE AROUND PERIMETER
 ON ALL SIDES.
  
 NUMERICAL ADDRESS
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 ADDRESS SHOULD BE PLACED UNDER A LIGHT FIXTURE OR BE
 BACK LIT.
 B. ADDRESS NUMERALS SHALL BE OF A CONTRASTING COLOR TO
 THE BUILDING COLOR
 C. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 D. ADDRESS NUMBERS ON DOORS OF MULTI-UNITS AND SINGLE
 FAMILY HOMES NEED TO BE A MINIMUM OF 6 INCHES HIGH.
 E. BUILDING NUMBERS FOR MULTI-UNIT BUILDINGS SHALL BE A
 MINIMUM OF 12 INCHES HIGH AND PLACED IN A CONSPICUOUS
 LOCATION ON ALL SIDES WITH PUBLIC ACCESS, AWAY FROM
 LANDSCAPING.
  
 10.1 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A.AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B.THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C.PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-10-24 07:52:001. COMPLETE DRAINAGE SYSTEM NOT SHOWN ON LANDSCAPE PLAN
 (AS-1).
 2. SITE PLAN (SHEET C-1) SHOWS CLUSTER OF TWO TREES IN
 LANDSCAPE AREA WEST OF WEST BUILDING; LANDSCAPE PLAN
 (SHEET AS-1) SHOWS CLUSTER OF 3 TREES.
 3. WILL EXISTING 18" TREE IN HEDGE LINE OF LANDSCAPE
 AREA WEST OF WEST BUILDING BE AFFECTED BY THE PROPOSED
 EXFILTRATION TRENCH? SUGGEST USING ROOT BARRIER OR
 RELOCATING THE EXFILTRATION TRENCH.
 4. COMMENTS 5 - 8 FROM FIRST STORMWATER REVIEW STILL
 VALID (SUBMITTALS WILL BE REQUIRED WITH ENGINEERING
 PERMIT APPLICATION).
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 561-494-1120

Review Stop STORM STORMWATER
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-09-11 08:50:241. DRAINAGE ON LANDSCAPE PLANS DO NOT MATCH CIVIL
 PLANS.
 2. WIL EXISTING TREES ON WEST SIDE OF WEST BUILDING BE
 AFFECTED BY THE CONSTRUCTION OF THE DRAINAGE SYSTEM?
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPARTMENT
 (561) 494-1120
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-01-2012 Cont ID  
Sent By tward Date 08-01-2012 Time 13:15 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2012-08-01 11:22:088/1/2012
 1. ARCHITECTURAL GROUND FLOOR SITE PLAN, CIVIL SITE
 PLAN AND LANDSCAPE PLAN DO NOT MATCH:
 A. SOUTH AND WEST PARKING SPACES DIFFERENT DIMENSIONS
 B. WHEEL STOPS SHOWN ON ARCHITECTURAL PLAN
 C. HANDICAP PARKING ACCESS AISLE LOCATION
 D. SIDEWALK WIDTH ALONG SOUTH SIDE OF WEST BUILDING
 E. PALM TREES VS. HEDGE ALONG SOUTH PROPERTY LINE.
  
 2. CIVIL SITE PLAN NOT SIGNED AND SEALED.
 3. EXISTING / PROPOSED DRAINAGE SYSTEM NOT SHOWN.
 4. PROPOSED GRADING PATTERNS NOT PROVIDED.
 5. STORMWATER WATER QUALITY TREATMENT VOLUME TO BE
 PROVIDED ON SITE (MINIMUM OF 1" OF RUNOFF FROM SITE OR
 2.5" RUNOFF TIMES PERCENT IMPERVIOUS).
 6. SFWMD ENVIRONMENTAL RESOURCES PERMIT WILL BE NEEDED
 BEFORE START OF CONSTRUCTION.
 7. EROSION CONTROL PLAN WILL BE REQUIRED WITH FINAL
 ENGINEERING PLANS.
 8. DRAINAGE CALCULATIONS WILL BE REQUIRED FOR
 ENGINEERING PERMITS.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 (561) 494-1120
  

Review Stop SURVEY SURVEYING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 09-11-2012 Cont ID  
Sent By vnoel Date 09-11-2012 Time 14:08 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-09-11 14:08:38PASSED, BUT WITH PROVISION THAT UNITY OF TITLE PRIOR TO
 C.O.
 APPLICATION IS TO BE MADE THROUGH AND APPROVED BY
 ENGINEERING SERVICES.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-31-2012 Cont ID  
Sent By vnoel Date 07-31-2012 Time 10:42 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-07-31 11:32:121. PROPOSED DUMPSTER SHOULD NOT OPEN INTO ALLEY.WHERE
 IS EXISTING DUMPSTER?
 2. SITE PLAN SHOWS TREES ALONG ALLEY WHICH DO NOT SHOW
 ON LANDSCAPE PLAN.
 3. PROPOSED TREES ALONG ALLEY MAY INTERFERE WITH
 OVERHEAD LINES.
 4. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH THE ENGINEERING SERVICES DEPT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 10-16-2012 Time 16:17 Sent To  
Notes
2012-10-16 16:17:43NO NOTES

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 09-17-2012 Time   Rev Time 0.00
Received By bcollins Date 09-17-2012 Time 08:20 Sent To  
Notes
2012-09-17 08:21:14PRIOR COMMENTS ADDRESSED. PASSED, HOWEVER DIRECTIONAL
 ARROWS ON SOUTH SIDE OF PARKING LOT NEED TO BE
 REVERSED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-07-2012 Time   Rev Time 0.00
Received By bcollins Date 08-07-2012 Time 15:35 Sent To  
Notes
2012-08-07 15:39:02STRIPING (CROSS HATCHING) WILL NEED TO BE REMOVED TO
 DELINEATE THE ENTRANCE AND EXIT ON PALM BEACH LAKES
 BLVD. EXISTING AND PROPOSED STRIPING NEEDS TO BE SHOWN
 ON THE PLAN. EASTERNMOST HANDICAPPED PARKING SPACE WILL
 REQUIRE VEHICLE TO BACK OUT INTO ONCOMING TRAFFIC.

Review Stop Z ZONING
Rev No 3 Status P Date 10-25-2012 Cont ID  
Sent By aaponte Date 10-25-2012 Time 10:21 Rev Time 0.00
Received By aaponte Date 10-11-2012 Time 10:20 Sent To  
Notes
2012-10-25 12:20:53PROVISO: PLEASE PROVIDE A REVISED LANDSCAPE SHEET
 ADDRESSING THE FOLLOWING COMMENT:
 1. THE REQUIRED LANDSCAPE BUFFER ALONG THE SOUTH SIDE
 OF THE PARKING LOT SHALL INCLUDE TREES. IF POWER LINES
 ABOVE, SMALL TREE SPECIES SHALL BE SELECTED (COMMENT NO
 3 ON THE 9/13/12 REVIEW).
  

Review Stop Z ZONING
Rev No 2 Status F Date 09-13-2012 Cont ID  
Sent By aaponte Date 09-13-2012 Time 13:34 Rev Time 0.00
Received By aaponte Date 09-13-2012 Time 13:33 Sent To  
Notes
2012-09-13 14:15:121. PARKING LOT STRIPING DETAIL SHALL BE INCLUDED IN THE
 SITE PLAN DRAWING. PLEASE INCLUDE DIMENSIONS FOR
 REGULAR AND HANDICAP SPACES, AND THE CITY STRIPING
 DETAIL.
 2. PLEASE CLEARLY INDICATE THE LOCATION, NAME, SIZE AND
 CALIPER OF EXISTING TREES AND PALM ON THE PROPERTY.
 SOME OF THE EXISTING TREES ALONG PALM BEACH LAKES
 BOULEVARD HAVE CONFLICT WITH THE POWER LINES. CITY
 RECOMMENDS REMOVING THEM AND REPLACE THEM WITH NEW
 SMALL TREES APPROPRIATE FOR LOCATION.
 3. SHADE TREES SHALL BE PLANTED ALONG THE ENTIRE
 PARKING LOT LANDSCAPE BUFFER (30 FEET ON CENTER). IF
 CONLICT WITH UTILITIES SMALL TREES SHALL BE SELECTED.
 4. ALL NON-PAVED AREAS SHALL BE COVERED BY GRASS OR A
 NON-DUSTING SURFACE.
 5. A HEDGE SHALL BE PLANTED AROUND THE ENTIRE SURFACE
 PARKING LOT WITHIN THE LANDSCAPE BUFFER AREA (BOUNARIES
 ADJACENT TO PROPERTY LINE OR ROW).
 6. THE REMOVAL OF ANY EXISTING TREES OR PALMS WILL
 REQUIRE A TREE/PALM RELOCATION PERMIT FROM THE CITY.
 7. PARKING LOT TERMINAL ISLANDS SHALL BE 5' MINIMUM.
 8. PLEASE CHECK THE TRAFFIC DIRECTION ARROW, THEY ARE
 NOT PLACED CORRECTLY ON THE DRIVE AISLE.
 9. EASTERN CURB CUT WIDTH SHALL BE ADJUSTED TO NEW
 DRIVEWAY DIMENSION.
 10. PLEASE PROVIDE ARCHITECTURAL DRAWINGS FOR ALL
 ELEVATIONS, IDENTIFIYING HEIGHTS AND BUILDING
 MATERIALS.
 11. ALL PARKING SPACES REQUIRE A WHEEL STOP ACCORDING
 TO CITY STANDARDS.
 FOR ADDITIONAL INFORMATION PLEASE CALL ANA MARIA APONTE
 AT 561-822-1439

Review Stop Z ZONING
Rev No 1 Status F Date 08-07-2012 Cont ID  
Sent By aaponte Date 08-07-2012 Time 17:07 Rev Time 0.00
Received By aaponte Date 08-07-2012 Time 17:07 Sent To  
Notes
2012-08-07 17:25:391. PLEASE PROVIDE DETAIL DRAWIGNS INDICATING EXISTING
 SQUARE FOOTAGE FOR EACH FLOOR AND PROPOSED CHANGES.
 2. PARKING LOT STRIPING SHALL COMPLY WITH CITY STRIPING
 DETAILS.
 3. PLEASE PROVIDE DRAWINGS INDICATING EXISTING PLANT
 MATERIAL TO BE MAINTAIN AND PROPOSED NEW PLANT
 MATERIAL.
 4. PROPOSED FENCE ALONG THE FRONTAGE LINE CANNOT EXCEED
 4 FEET IN HEIGHT AS MEASURED FROM THE SIDEWALK
 ELEVATION.
 5. SITE PLAN DRAWINGS DO NOT MATH LANDSCAPE DRAWINGS.
 6. SHADE TREES SHALL BE PLANTED ALONG THE PARKING LOT
 LANDSCAPE BUFFER (1/30 FEET ON CENTER).
 7. DUMPSTER DIMENSIONS AND ENCLOSURE SHALL MEET CITY
 STANDARDS IN SECTION 94-444(B) AND FIGURE XIV-3.
 8. PROJECT DATE SHEET C-1 INDICATED AND ADULT DAY CARE
 USE. SUCH USE IS NOT PERMITTED IN THE PPD-R-PO.
 9. PLEASE SPECIFY THE EXACT SQUARE FOOTAGE DEDICATED TO
 OFFICE/MANAGEMENT IN THE DRAWINGS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  