Plan Review Details - Project Z12060017
Plan Review Stops For Project Z12060017
Review Stop AD ADDRESSING
Rev No 1 Status P Date 07-23-2012 Cont ID  
Sent By jnguyen Date 07-23-2012 Time 07:56 Rev Time 0.00
Received By jnguyen Date 07-19-2012 Time 08:07 Sent To  
Notes
2012-07-20 09:26:46PENDING APPROVAL FROM THE ADDRESSING REVIEW PANEL, I
 WILL PROCEED WITH CORRECTING THE CURRENT & ERRONEOUS
 ODD ADDRESS OF 715 HANK AARON DR TO 800 HANK AARON DR
 ON MONDAY, JULY 23, 2012 FOR THIS VACANT PARCEL - PCN#
 74434317250020000 (PLANNED MIZNER LAKES APARTMENTS
 COMPLEX).
  
 *THE NUMERICAL ADDRESSES ARE SUPPOSE TO BE "EVEN" ON
 THE SOUTH & EAST SIDES OF THIS PARTICULAR STREET (NOTE:
 WENDY'S IS LOCATED TO THE NORTHWEST AT 951 HANK AARON
 DR.). IN RELATION, I WILL THEN UPDATE THE STATUS OF
 THIS ZONING RECORD FROM "FAILED" TO "PASSED" ON JULY
 23, 2012.
  
 THE "PRELIMINARY" PLAN FOR THESE ADDRESSES PER NEW
 APARTMENT BUILDING FOR THIS PENDING MIZNER LAKES
 APARTMENTS COMPLEX ARE AS FOLLOWS (*THESE ADDRESSES ARE
 NOT TO-BE-OFFICIALLY ISSUED UNTIL PERMITS ARE APPLIED
 FOR):
  
 CLUBHOUSE AT 800 HANK AARON DR
 BUILDING 1 AT 900 HANK AARON DR
 BUILDING 2 AT 890 HANK AARON DR
 BUILDING 3 AT 880 HANK AARON DR
 BUILDING 4 AT 720 HANK AARON DR (MAY NOT BE CONSTRUCTED
 DEPENDING ON POSSIBLE CHANGE IN PLANS)
 BUILDING 5 AT 710 HANK AARON DR
 BUILDING 6 AT 870 HANK AARON DR
 BUILDING 7 AT 860 HANK AARON DR
 BUILDING 8 AT 850 HANK AARON DR
 BUILDING 9 AT 840 HANK AARON DR
 BUILDING 10 AT 830 HANK AARON DR
 BUILDING 11 AT 820 HANK AARON DR
 BUILDING 12 AT 810 HANK AARON DR
 BUILDING 13 AT 760 HANK AARON DR (MAY BE REVISED TO 740
 HANK AARON DR DEPENDING ON POSSIBLE CHANGE IN PLANS)
 BUILDING 14 AT 750 HANK AARON DR (MAY BE REVISED TO 730
 HANK AARON DR DEPENDING ON POSSIBLE CHANGE IN PLANS)
 BUILDING 15 AT 740 HANK AARON DR (MAY BE REVISED TO 720
 HANK AARON DR DEPENDING ON POSSIBLE CHANGE IN PLANS)
 BUILDING 16 AT 730 HANK AARON DR (MAY NOT BE
 CONSTRUCTED DEPENDING ON POSSIBLE CHANGE IN PLANS)
  
 *NOTE: IT WAS ACKNOWLEDGED TO ME THAT THE PLANNED
 BUILDINGS 4 AND 16 AT 720 & 730 HANK AARON DR MAY FOLD
 DUE TO A POSSIBLE ALTERNATIVE TO SPLIT A SOUTHWEST
 PORTION OF THIS PARCEL THAT MAY BE SOLD TO THE CITY OF
 WPB. IF THIS SCENARIO OCCURS, BUILDINGS 15, 14 & 13
 WILL BE RE-ADDRESSED AS 720, 730 & 740 HANK AARON DR
 (INSTEAD OF 740, 750 & 760 HANK AARON DR).
  
  
 SECTION 1.3B OF THE CITY OF WPB ADDRESSING POLICY IS AS
 SPECIFIED (SUBMITTED DETAILS TO
 [email protected]):
  
 ONE PRIMARY NUMBER SHALL BE ASSIGNED TO EACH STRUCTURE
 WITH MULTIPLE UNITS. EACH UNIT WITHIN THE STRUCTURE
 SHALL BE ASSIGNED A UNIT DESIGNATOR SUCH AS "SUITE".
 ALLOWED UNIT DESIGNATORS INCLUDE APARTMENT (APT)
 NUMBERS FOR APARTMENTS, AND SUITE, BAY, UNIT (STE, OR
 BAY, OR UNIT) NUMBERS FOR COMMERCIAL BUILDINGS. THE
 UNIT DESIGNATOR SHALL BE NUMERIC AND SHALL NOT INCLUDE
 ALPHA CHARACTERS.
  
 IT WILL BE THE "DEVELOPER'S RESPONSIBILITY" TO ASSIGN
 UNIT (DESIGNATORS) ADDRESSES TO ALL UNITS INSIDE THE
 STRUCTURE. THE LIST OF ADDRESSES MUST BE APPROVED BY
 THE SUPPORT SERVICES DEPARTMENT IN CHARGE OF ADDRESSING
 PRIOR TO RELEASE THE CERTIFICATE OF OCCUPANCY.
  
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
  
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO 199, (100
 MAIN ST. # 101, INDICATES THE FIRST UNIT ON THE FIRST
 FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299, (100 MAIN
 ST. # 201, INDICATES THE FIRST UNIT ON THE SECOND
 FLOOR)
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-11-2012 Cont ID  
Sent By lmartine Date 07-11-2012 Time 10:11 Rev Time 0.00
Received By lmartine Date 07-11-2012 Time 10:11 Sent To  
Notes
2012-07-11 10:43:16BUILDING REVIEW COMMENTS
  
  
 A0.01
 BUILDING DATA IS INCORRECT, PLEASE SEE 2010 FLORIDA
 BUILDING CODE CHAPTERS 5 AND 6 FOR BUILDING HEIGHT AND
 AREA AND CONSTRUCTION TYPE.
  
 COMPLIANCE WITH THE FAIR HOUSING ACT WILL BE REQUIRED
 FOR ALL RESIDENTIAL UNITS. COMPLIANCE WITH THE 2010
 FLORIDA ACCESSIBILITY CODE WILL APPLY TO COMMON USE
 AREAS AND THE PUBLIC BUILDINGS ON SITE.
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 07-27-2012 Cont ID  
Sent By bmoree Date 07-27-2012 Time 15:07 Rev Time 0.00
Received By bmoree Date 07-27-2012 Time 15:06 Sent To  
Notes
2012-07-11 12:42:401. SITE CIVIL DRAWINGS ARE REQUIRED FOR COMPREHENSIVE
 INFRASTRUCTURE COMMENTS.
 2. AN ENVIRONMENTAL RESOURCE PERMIT FOR SFWMD WILL BE
 REQUIRED.
 3. AN PHASE I ENVIRONMENTAL SITE ASSESSMENT REPORT IS
 REQUIRED IN CONJUNCTION WITH FORMAL SITE DEVELOPMENT
 CIVIL INFRASTRUCTURE REVIEW.
 4. IN CONSIDERATION OF THE PREVIOUS USE OF THE SITE,
 THE CITY MAY REQUIRE ADDITIONAL ENVIRONMENTAL SITE
 ASSESSMENT AND CONTROL, WHICH MAY INCLUDE, BUT NOT BE
 LIMITED TO, ENVIRONMENT SAMPLING AND TESTING,
 DEWATERING CONTROL, CONSTRUCTION STORMAWATER CONVEYANCE
 MANAGEMENT, PARTICULATE ABATEMENT, AND ENVIRONMENTAL
 HAZARD ABATEMENT.
 5. STORMWATER POLLUTION PREVENTION PLAN (SWPPP) AND
 STORMWATER MANAGEMENT PLAN.
 6. A SANITARY SEWER SYSTEM CAPACITY ENGINEERING
 EVALUATION WILL BE REQUIRED IN CONJUNCTION WITH FORMAL
 SITE DEVELOPMENT CIVIL INFRASTRUCTURE REVIEW.
 7. A WATER DISTRIBUTION SYS EVALUATION WILL BE REQUIRED
 IN CONJUNCTION WITH FORMAL SITE DEVELOPMENT CIVIL
 INFRASTRUCTURE REVIEW.
 8. UTILITY SYSTEM INFRASTRUCTURE IMPROVEMENTS AND/OR
 EXPANSION MAY BE REQUIRED TO SUPPORT THE PROPOSED
 DEVELOPMENT. THIS MAY INCLUDE, BUT IS NOT LIMITED TO,
 WATER DISTRIBUTION SYSTEM IMPROVEMENTS, SANITARY SEWER
 SYSTEM IMPROVEMENTS, AND STORMWATER CONVENIENCE SYSTEM
 IMPROVEMENTS.
 9. RECOMMEND INDEPENDENT UTILITY INFRASTRUCTURE MEETING
 BE SCHEDULED WITH PUBLIC UTILITIES AND ENGINEERING
 SERVICES.
  
 BRIAN R. MOREE, MPA, FCHP
 ENGINEERING CONSTRUCTION MANAGER
 CONSTRUCTION ADMINISTRATION
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET
 FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-494-1098
 MOBILE: 561-644-7270
 EMAIL: [email protected]
 WEB: WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 07-30-2012 Cont ID  
Sent By ddaniels Date 07-30-2012 Time 22:47 Rev Time 0.00
Received By ddaniels Date 07-30-2012 Time 22:47 Sent To  
Notes
2012-07-30 23:09:577/30/12 PLANS REVIEWED BY FIRE **DENIED**
  
 SECOND ATTEMPT COMMENTS NOT ADDRESSED
  
 1. SHOW SCOPE OF WORK ON PLANS.
  
 2. SHOW LIFE SAFETY PLANS.
  
 3. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 4. FIRE DEPARTMENT HAS CONCERNS WILL THERE BE ENOUGH
 PARKING IN AND OUT OF THE DEVELOPMENT.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 07-06-2012 Cont ID  
Sent By ddaniels Date 07-06-2012 Time 18:37 Rev Time 0.00
Received By ddaniels Date 07-06-2012 Time 18:37 Sent To  
Notes
2012-07-06 18:43:147/6/2012 PLANS REVIEWED BY FIRE ***DENIED***
  
 1. SHOW SCOPE OF WORK ON PLANS.
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3. SHOW LIFE SAFETY PLANS
 4. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 5. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY SECURITY
 GATES AND FENCES.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  

Review Stop POLICE POLICE
Rev No 2 Status P Date   Cont ID  
Sent By   Date 08-10-2012 Time   Rev Time 0.00
Received By ktucker Date 08-10-2012 Time 09:10 Sent To  
Notes
2012-08-10 08:49:27ADMENDMENT CHANGES NOTED.
  
 MAKE SURE THAT ALL ENTRANCES, INCLUDING THE LOBBY
 ENTRANCE, ALL CLUBOUSE GATES AND PEDESTRIAN ACCESS
 GATES ON THE TURQUOISE NECKLACE ARE KEY/FOB CONTROLLED

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 07-06-2012 Time   Rev Time 0.00
Received By ktucker Date 08-10-2012 Time 09:10 Sent To  
Notes
2012-07-06 09:15:16QUESTIONS:
  
 * HOW WILL PEDESTRIAN ACCESS GATES BE CONTROLLED?
 * CAMERA FOR VEHICLE EXITS
 * ACCESS CONTROL FOR THE POOL, CLUBHOUSE AREA, BOWLING,
 GAME ROOMS?
 * THE MAILROOM ACCESS? WILL THERE BE GLASS DOORS OR
 WILL IT BE OPEN?
 * CONSIDER MOVING THE GATES PAST THE MAIL ROOM, TO
 CONTROL ACCESS
 * GLASS DOORS SHOULD BE USED FOR THE GAME ROOM AND
 BOWLING AREA FOR EASY SURVEILLANCE
 * PRE WIRE THE CLUBHOUSE AREA FOR CCTV & ALARM
 * ALL BREEZEWAY AREAS SHOULD BE WELL LIT THROUGH OUT
 THE PROJECT
 * DID NOT SEE LIGHTING FOR THE CLUBHOUSE AREA
 * STAIRWELL ACCESS? INSTALL MIRRORS IN THE STAIRWELLS;
 FENCE OFF ANY UNDER STAIR CASE OPENINGS
 * CONSIDER A WINDOW IN THE REAR OF THE GUARDHOUSE IN
 ORDER TO SEE WHAT/WHO IS APPROACHING
 * NO SEATING UNDER THE TOWER STRUCTURE, LIGHTING?
 * IS THAT A SIDEWALK ENTRY FROM THE MAIN DRIVE INTO THE
 DEVELOPMENT (BLDG 4), IT IS UNGATED
 * WHO IS RESPONSIBLE FOR LIGHTING, LANDSCAPE MAINTAIN
 FOR THE TURQUOISE NECKLACE PATH?S
 * TOT LOT IS FENCED, BUT HEDGE NEEDS TO BE NO MORE THAT
 2' IN HEIGHT.
  
 LIGHTING
 A. PARKING LOT LIGHTING SHALL USE 20 FOOT POLES.
 B. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 C. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO RESIDENCES PROVIDE FOR DUSK
 TO DAWN OPERATION.
 D. ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING.
 E. BUILDING LIGHTING (NON GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDES.
  
  MAIL BOX LOCATION
  
 A. MAILBOX LOCATIONS SHALL BE IN A WELL LIT, HIGH
 TRAFFIC LOCATION.
  
  
  NUMERICAL ADDRESS
  
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 ADDRESS SHOULD BE PLACED UNDER A LIGHT FIXTURE OR BE
 BACK LIT.
 B. ADDRESS NUMERALS SHALL BE OF A CONTRASTING COLOR TO
 THE BUILDING COLOR
 C. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 D. ADDRESS NUMBERS ON DOORS OF MULTI-UNITS AND SINGLE
 FAMILY HOMES NEED TO BE A MINIMUM OF 6 INCHES HIGH.
 E. BUILDING NUMBERS FOR MULTI-UNIT BUILDINGS SHALL BE A
 MINIMUM OF 12 INCHES HIGH AND PLACED IN A CONSPICUOUS
 LOCATION ON ALL SIDES WITH PUBLIC ACCESS, AWAY FROM
 LANDSCAPING. NUMBERS SHOULD BE OF A CONTRASTING
 BACKGROUND.
  
 DOORS
 A. DOOR LEADING INTO A RESIDENTIAL UNIT, INCLUDING
 INTERIOR GARAGE, AND DETACHED GARAGE, SHALL BE SOLID
 CORE.
 B. FRONT DOOR SIDE PANE WINDOW SHALL BE PLACED ON THE
 OPPOSITE SIDE OF THE DOOR HANDLE AND LOCK MAKING THEM
 UNREACHABLE.
 C. EXTERIOR DOORS SHALL BE EQUIPPED WITH A 180-DEGREE
 PEEPHOLE AND NON-REMOVABLE SECURITY HINGES.
 LOCKS
 A. ANTI-LIFTING AUXILIARY LOCKS SHALL BE INSTALLED ON
 SLIDING DOORS AND WINDOWS.
 B. ALL DOORS SHALL BE EQUIPPED WITH SINGLE CYLINDER
 DEAD BOLT LOCK WITH A MINIMUM THROW OF ONE INCH AND AN
 EMBEDMENT OF NOT LESS 5/8 INCH INTO THE HOLDING DEVICE.
 PICK PLATES SHOULD ALSO BE PLACED ALL EXTERIOR DOORS.
  
 MISCELLANEOUS
 A. STAIRWAYS (TO INCLUDE RISERS/BANISTERS) AND
 BALCONIES SHALL PROVIDE OPEN VIEWS.
 B. SALES CENTER, CLUBHOUSE AND RECREATIONAL FACILITIES
 SHALL BE PRE-WIRED TO ALARM CENTER.
 C. RECREATION BUILDING AND POOL ACCESS SHALL BE
 RESTRICTED, BY KEY, KEY FOB, OR CARD ACCESS
 D. BICYCLE SPACES SHALL BE LOCATED IN CLOSE PROXIMITY
 TO THE FRONT OF BUILDINGS AND NOT IN PARKING LOTS.
 TRAILS AND PATHWAYS (TURQUOISE NECKLACE AREA)
  
 TRAILS AND PATHWAYS (TURQUOISE NECKLACE AREA)
  
 LIGHTING
 A. LIGHT POLES 10 ? 15 FOOT HIGH FOR PEDESTRIAN-SCALE
 LIGHTING SHALL BE USED FOR ALL PEDESTRIAN WALKWAYS.
 B. LANDSCAPING SHALL NOT CONFLICT WITH LIGHTING (TO
 INCLUDE LONG-TERM TREE CANOPY GROWTH).
 C. LIGHTING FOR ENTRANCE SIGN TO PATHWAYS SHALL BE
 PROVIDED TO ALLOW NIGHTTIME USE OF PEDESTRIAN WALKWAYS.
  
  DESIGN
 A. BENCHES SHALL HAVE ADEQUATE LIGHTING IF THEY ARE
 INTENDED FOR NIGHTTIME USE AND BE LOCATED IN OPEN VIEW
 TO ELIMINATE CONCEALMENT AREAS.
 B. BENCHES WILL BE DIVIDED STYLE SEATING.
 C. SHALL BE DESIGNED TO MAXIMIZE NATURAL SURVEILLANCE
 OF THE PEDESTRIAN USERS THROUGH SELECTIVE VEGETATIVE
 MANAGEMENT PRACTICES.
 D. GROUND COVER SHALL BE NO HIGHER THAN 24 INCHES, WITH
 TREES HAVING A MINIMUM 7-FOOT CLEAR TRUNK SPACE FOR A
 NATURAL SURVEILLANCE WINDOW.
 E. SIGHT LINES SHALL HAVE A 12-FOOT CLEAR DISTANCE
 SPACE AT ENTRY POINTS, CURVES, MERGERS, INTERSECTIONS,
 ETC.
  
 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
  
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 08-01-2012 Cont ID  
Sent By tward Date 08-01-2012 Time 14:19 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2012-08-01 14:26:588/1/2012
 1. BREAK IN EXFILTRATION TRENCHES NEEDED WHERE OTHER
 UTILITIES WILL PASS THROUGH THE ROCK TRENCH. THIS IS
 NOT SHOWN ON RE-SUBMITTED CIVIL PLANS. CALL OUT
 CONFLICT(S) ON FINAL ENGINEERING PLANS.
  
 TRACY L. WARD, P.E.
 ENGINEERING SERVICES DEPARTMENT
 (561) 494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-07-10 11:30:221. COORDINATE DRAINAGE DESIGN WITH PROPOSED FIRE
 STATION NO. 5 EOC DRAINAGE SYSTEM.
 2. CONSTRUCTION EASEMENT MAY BE NEEDED TO WORK ON FIRE
 STATION NO. 5 SITE.
 3. MAINTAIN PROPER CLEARANCE BETWEEN SANITARY SEWER AND
 DRAINAGE STRUCTURE WEST OF BUILDING 13.
 4. PROVIDE BREAK IN EXFILTRATION TRENCH WHERE OTHER
 UTILITIES CROSS THE STORM PIPES.
 5. INDICATE WHERE THE CONTROL WEIRS WILL BE BETWEEN THE
 EXFILTRATION TRENCHES AND "LAKES".
 6. SHEETS 5 AND 6 INCORRECTLY TITLED (W&S DETAILS VS.
 P&D DETAILS).

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-03-2012 Cont ID  
Sent By vnoel Date 07-03-2012 Time 12:01 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-07-03 12:01:481. SIDEWALK EASEMENT WILL BE REQUIRED IN FRONT OF
 BUILDING NO. 4.
 2. UTILITY EASEMENTS WILL BE REQUIRED FOR THE TWO LINES
 TO THE METER ASSEMBLIES.
 3. DISCUSSION WITH PUBLIC UTILITIES AND LAW DEPT. WILL
 BE NEEDED FOR THE FEASIBILITY OF THE TURQUOISE
 NECKLACE.
 4. PEDESTRIAN CROSSING WILL BE NEEDED ACROSS ENTRANCE
 FROM EAST SIDE OF HANK AARON TO SOUTH SIDE.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 07-31-2012 Time 08:46 Sent To  
Notes
2012-07-31 09:04:12TRAFFIC STUDY SUBMITTED AND IS ACCEPTED.
  
 SITE PLAN STILL LACKING INTERNAL SIGNAGE AND TRAFFIC
 CONTROL - STOP SIGNS. FLOW AROUND TRAFFIC CIRCLE NEEDS
 TO BE DELINEATED WITH CHEVRONS AND ONE-WAY SIGNS IN
 CENTRAL ISLAND. TRAFFIC FROM DRIVE ON NORTHWEST SIDE OF
 CIRCLE IS DIRECTLY FACING OPPOSING TRAFFIC IN CIRCLE.
 REDESIGN IS NEEDED WITH POSSIBLE SHIFT IN CENTRAL
 ISLAND LOCATION, OR INCREASING ITS DIAMETER, TO BETTER
 DELINEATE TRAFFIC FLOW.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 07-06-2012 Time   Rev Time 0.00
Received By bcollins Date 07-06-2012 Time 16:40 Sent To  
Notes
2012-07-06 17:00:45THE TRAFFIC STATEMENT PREPARED BY THE APPLICANT'S
 ENGINEER STATES THAT THE PROPOSED DEVELOPMENT WILL
 GENERATE OVER 3,900 DAILY TRIPS, OVER 270 AM AND OVER
 340 PM PEAK HOUR TRIPS. THE PROPERTY IS EXEMPT FROM
 PALM BEACH COUNTY'S TRAFFIC CONCURRENCY REQUIREMENTS.
 HOWEVER, BASED ON THE MAGNITUDE OF THE PROJECTED TRIP
 GENERATION, THE APPLICANT SHALL SUBMIT A TRAFFIC IMPACT
 STUDY TO INCLUDE THE INTERSECTIONS OF HANK AARON DRIVE
 WITH PALM BEACH LAKES BLVD. AND CONGRESS AVENUE AS WELL
 AS THE SITE DRIVEWAYS ON HANK AARON DRIVE. THE SITE
 PLAN SHALL SHOW ROADWAY SIGNING AND STRIPING, E.G.,
 CROSSWALK SIGNS, STOP SIGNS, STOP BARS, LANE LINES,
 ETC.

Review Stop Z ZONING
Rev No 2 Status F Date 08-29-2012 Cont ID  
Sent By lfranco Date 08-17-2012 Time 17:32 Rev Time 0.00
Received By lfranco Date 08-17-2012 Time 17:32 Sent To  
Notes
2012-08-17 18:57:02CITY OF WEST PALM BEACH
 PLANNING DIVISION
  
  
 PLANS AND PLATS REVIEW COMMITTEE
 JULY 11, 2012
  
 RE-SUBMITTAL (1): JULY 19, 2012
  
 MAJOR AMENDMENT TO THE MIZNER LAKES APARTMENT
 RESIDENTIAL PLANNED DEVELOPMENT
 PB 1171FF
  
 A REQUEST BY BRIAN CHEGUIS/DONALDSON HEARING, OF
 COTLEUR & HEARING, INC., ON BEHALF OF AARON DRIVE
 HOLDINGS, LLC FOR A MAJOR AMENDMENT TO THE MIZNER LAKES
 APARTMENTS RESIDENTIAL PLANNED DEVELOPMENT (?RPD?) TO
 BUILD APARTMENT BUILDINGS FOR MULTIFAMILY USE
 CONSISTING OF 548 RESIDENTIAL UNITS.
  
 P.C.N. 74-43-43-17-25-002-0000
 715 HANK AARON DRIVE
  
  
 GENERAL COMMENTS:
  
 1. WHEN RESUBMITTING:
  
 A. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 ALL DEPARTMENTS IN A WRITTEN FORMAT WHEN RESUBMITTING.
 NOTE THAT RESUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 B. 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 D. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
  TRAFFIC CONCURRENCY/ JUSTIFICATION STATEMENT/ PLANS:
  
 2. THE APPLICANT SHOULD MEET WITH THE APPROPRIATE
 NEIGHBORHOOD ASSOCIATIONS AND DISTRICT COMMISSIONER TO
 INFORM THEM OF THE PROPOSED REVISIONS TO THE APPROVED
 DEVELOPMENT AS PART OF THE REVIEW PROCESS AND NOTIFY
 PLANNING STAFF OF THE OUTCOME OF THE MEETING AND ANY
 ISSUES THAT MAY NEED TO BE ADDRESSED BY THE APPLICANT.
  
 RESUBMITTAL: THE APPLICANT INDICATED THAT THEY WOULD BE
 SENDING AN INFORMATIONAL PACKET AND WILL PROVIDE
 WRITTEN DOCUMENTATION THAT ALL NEIGHBORHOOD
 ASSOCIATIONS WITHIN THE SURROUNDING VICINITY WERE
 CONTACTED. THE APPLICANT WAS ADVISED THAT STAFF NEEDS
 FEEDBACK FROM APPLICANT OF COMMENTS OR CONCERNS THE
 ASSOCIATIONS MAY HAVE ABOUT THE PROJECT, PRIOR TO
 TAKING THE ITEM TO PLANNING BOARD AND CITY COMMISSION.
  
 3. THE ITEMS BELOW WERE REQUIRED AT TIME OF APPLICATION
 SUBMITTAL, PROVIDE ALL THE UTILITY LETTERS. THE
 APPLICATION MAY NOT MOVE FORWARD TO PLANNING BOARD
 UNTIL ALL COMMENTS ARE ADDRESSED AND THE PLANNING
 DEPARTMENT RECEIVES ALL LETTERS ACCORDINGLY.
  
  DEVELOPMENT APPLICATION: N. CITY SERVICE AND PUBLIC
 UTILITY LETTERS
  
 A PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC
 UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT
 ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE
 WITH THE PROVISIONS OF THEIR SERVICES:
  
  TELEPHONE:
 ROBERT LOWEN
 AT&T FLORIDA - ENGINEERING DEPARTMENT
 2021 SOUTH MILITARY TRAIL ? WEST PALM BEACH, FLORIDA
 33415
 PHONE: (561) 357.6615 ? FAX: (561) 964.3499 EMAIL:
 [email protected]
  
 NATURAL GAS:
 NANI SANTIAGO
 FLORIDA PUBLIC UTILITIES
 1641 WORTHINGTON RD SUITE 220 - WEST PALM BEACH, FL
 33409
 PHONE: (561) 838.1785 GENERAL PHONE: (561) 832.2461
 FAX: (561) 838.1769 (EASEMENT CONSENT FORMS CAN BE
 FAXED) EMAIL: [email protected]
  
 ELECTRIC SERVICE:
 FLORIDA POWER & LIGHT COMPANY
 810 CHARLOTTE AVENUE WEST PALM BEACH, FLORIDA 33401
  
 THE FP&L PROJECT MANAGER (INCLUDING NAME AND TELEPHONE
 NUMBER) FOR THE PROJECT'S LOCATION MAY BE FOUND BY
 VISITING THE FOLLOWING WEBSITE:
  
 HTTP://APP.FPL.COM/NAPPS/PS/SERVICEM.NSF/FPLWEB+SEARCH+
 SIMPLE-OPENFORM
  
 TELEVISION CABLE:
 WADE HAGERTY
 COMCAST CABLE COMMUNICATIONS
 10435 IRONWOOD ROAD PALM BEACH GARDENS, FLORIDA 33410
 PHONE: (561) 227-4127 FAX: (561) 640-0231 - EMAIL:
 [email protected]
 SITE PLAN:
  
 RESUBMITTAL: COMMENT IS STILL OUTSTANDING
  
 4. SHEET A0.01 AND A1.01 PARKING CALCULATIONS:
  
 A. PURSUANT TO SECTION THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-486, TABLE XV-6,
 RESIDENTIAL MULTIFAMILY, ONE (1) PARKING SPACE IS
 REQUIRED PER EVERY 10 UNITS FOR GUESTS. THEREFORE, FOR
 548 UNITS, 55 GUEST PARKING SPACES ARE REQUIRED. 1,058
 REGULAR PARKING + 55 GUEST SPACES = 1113 PARKING
 REQUIRED.
  
 RESUBMITTAL: DOES NOT COMPLY, HOWEVER, APPLICANT
 RE-SUBMITTED ON AUGUST 6, 2012 AND AUGUST 17, 2012 A
 PARKING WAIVER JUSTIFICATION AND PEDESTRIAN PROXIMITY
 PLAN. STAFF HAS INDICATED SOME ITEMS THAT WILL NEED TO
 BE ADDRESSED IN THE PLANS TO JUSTIFY WAIVER OF THE
 PARKING REQUIREMENTS.
  
  NOTE, THE JUSTIFICATION STATEMENT STATES 1,077 PARKING
 HAVE BEEN PROVIDED INCLUDING 32 ON-STREET PARKING
 SPACES, SEE COMMENT (B) BELOW AND REVISE ALL
 DOCUMENTATION TO MATCH ACCORDINGLY.
 B. ADDITIONALLY, PURSUANT TO SECTION 94-485 (O), 20 HC
 SPACES ARE REQUIRED FOR UP TO 1,000 REGULAR SPACES,
 PLUS ONE (1) HC SPACE FOR EACH 100 OVER 1,000.
 THEREFORE, 21 HC ARE REQUIRED NOT 20. THE SITE PLAN
 SHOWS 30 HC PROVIDED ON THE SITE DATA, BUT THE PLANS
 SHOW ONLY 26 HC? PLEASE CLARIFY. ALSO, SUGGEST
 RELOCATING AND/OR ADDING HC SPACE(S) AT THE SOUTHWEST
 CORNER OF THE PROJECT, SINCE THERE ARE NO HC SPACES
 PROPOSED IN THAT AREA TO SERVE BUILDING 4, TYPE A OR
 BUILDING 16, TYPE E.
  
  THE JUSTIFICATION STATEMENT STATES THAT AN ADDITIONAL
 32 ON-STREET PARKING SPACES ARE PROVIDED THAT ARE
 LOCATED ON THE WEST AND EAST SIDE OF HANK AARON, THE
 ONLY PARKING AVAILABLE THAT CAN BE COUNTED TOWARDS THE
 PROJECT'S REQUIREMENTS IS THE ON-STREET PARKING ON THE
 EAST SIDE OF HANK AARON, WHICH IS ADJACENT TO THE
 FRONTAGE OF THE PROJECT. THE SITE PLAN SHOWS 16 PARKING
 SPACES VS. JUSTIFICATION STATEMENT NOTED AS 32 PARKING
 SPACES. REVISE ALL DOCUMENTATION TO CORRELATE.
  
 5. SHEET A1.01 - SITE PLAN, INCLUDES THE SITE DATA WITH
 10 BICYCLE PARKING SPACES PROVIDED AND NO REQUIREMENT
 FOR BICYCLE PARKING, WHICH IS INCORRECT; SHEET A0.01,
 PROJECT DATA DOES NOT DENOTE ANY BICYCLE PARKING. ALSO,
 ON SHEET A1.01, THE SITE PLAN DOES NOT SHOW ANY BICYCLE
 PARKING. PURSUANT TO SECTION 94-485(Q), ONE (1) BICYCLE
 PARKING SPACE SHALL BE PROVIDED FOR EVERY 20 AUTOMOBILE
 PARKING SPACES, OR FRACTION THEREOF, REQUIRED FOR THE
 USE. THE BICYCLE PARKING SPACES SHALL BE SPREAD
 THROUGHOUT THE SHOPPING PLAZA. SHOW A DETAIL OF
 PROPOSED AREAS. THE BICYCLE RACK(S) SHALL COMPLY WITH
 THE DESIGN STANDARDS SET FORTH. A LINK OF ACCEPTABLE
 BICYCLE RACKS WITH DETAILS AND MINIMUM DIMENSIONS WILL
 BE PROVIDED VIA EMAIL FOR YOUR REFERENCE.
  
 RESUBMITTAL: BIKE DETAILS DO NOT COMPLY WITH ACCEPTIBLE
 BICYCLE STANDARDS AS DISCUSSED AND PROVIDED BY STAFF ON
 8/21/12. REVISE PLANS ACCORDINGLY. INCLUDE BICYCLE
 PARKING/RACKS PAD DETAIL AND DIMENSIONS AND COORDINATE
 WITH ARCHITECT/ENGINEER THE LOCATIONS WITH CLOSE
 PROXIMITY TO BUILDINGS TO MAKE SURE THERE IS ADEQUATE
 CLEARANCE FOR THE BICYCLES TO PARK.
 COORDINATE AMOUNT OF BICYCLE PARKING AND RACKS BETWEEN
 ALL PLANS. THE LANDSCAPE PLAN SHOW 7 BICYCLE PARKING
 SPACES PER RACK VS. SHEET A5.03 WHICH SHOWS A DIFFERENT
 NUMBER.
  
 6. SHOW DIMENSION OF RESIDENTIAL DEVELOPMENT
 IDENTIFICATION SIGN THAT MEETS ALL REQUIREMENTS OF
 SECTION 94-407 (2):
  
 B.2. THE MAXIMUM SQUARE FEET PER FACE OF A SIGN IS 48
 SQUARE FEET, SHALL BE SETBACK A MINIMUM OF 20 FEET FROM
 THE PROPERTY LINE;
 F. MAXIMUM HEIGHT IS FOUR (4) FEET; THE SIGN PROPOSED
 IS AT 9 FEET. IS A WAIVER REQUESTED FOR THE ADDITIONAL
 HEIGHT?
  
 7. SHEET 3 "PAVING AND DRAINAGE" LOWER THE HC PAINTED
 LOGO TO LEAVE 2 FEET FROM BOTTOM OF LOGO TO THE BOTTOM
 OF PARKING STALL STRIPPING. THE DETAIL SHOWS 16 INCHES
 BETWEEN CENTER PARKING STALL PAINTING DETAIL, AND
 STALLS BEING 9 FEET WIDE. APPLICANT MAY CONSIDER
 REDUCING TO THE MINIMUM ZLDR DIMENSIONS OF 12 INCHES
 BETWEEN CENTER OF STRIPING AND 8'-6" WIDE TO
 ACCOMMODATE MORE PARKING SPACES, SINCE THE PROPOSED
 SITE PLAN DOES NOT MEET THE MINIMUM PARKING SPACES
 REQUIRED.
  
 8. THE ARCHITECTURAL PLANS SHOW A SIDE PRIVACY WALL,
 BUT THE CIVIL DENOTES A FENCE? PLEASE CLARIFY. ALSO,
 THE DETAIL PLAN FOR THE PEDESTRIAN ACCESS FEATURES
 SHOWS A CURVED GATE, THE PLANS SHOW A STRAIGHT LINE,
 DEPICT ON SITE PLAN, THE CURVATURE TO ASSURE IT IS
 WITHIN THE APPLICANT'S PROPERTY.
  
 LANDSCAPE PLAN:
  
 10. PRIOR TO THE FINAL APPROVAL OF THE ALTERATION AND
 BUILDING PERMIT, PROVIDE LANDSCAPE PLANS TO THE
 PLANNING DIVISION WITH A REVISED PLAN OF THE EXISTING
 TREES TO REMAIN OR BE RELOCATED, SINCE THE
 JUSTIFICATION STATEMENT AND LANDSCAPE PLANS NOTE THAT A
 TREE SURVEY OF EXISTING TREES COULD NOT BE PERFORMED
 UNTIL THE LAND IS CLEARED OF EXCESSIVE OVERGROWTH OF
 VEGETATION.
  
  
 RESUBMITTAL (1): OUTSTANDING COMMENT TO BE ADDRESSED
 PRIOR TO FINAL APPROVAL OF BUILDING (LANDSCAPE) PERMIT.
 APPLICANT INDICATED THAT THE FINAL DESTINATION OF
 RELOCATED TREES SHALL BE DETERMINED ONCE OVERGROWTH IS
 REMOVED AND THE EXACT DEMEANOR OF THE NATIVE TREE CAN
 BE MORE ACCURATELY DETERMINED.
  
 11. SHEET LP-1, LANDSCAPE DATA, SHOW WHAT LANDSCAPING
 IS "PROVIDED" ON THE TABLE. THE "REQUIRED" PART IS THE
 ONLY ITEMS SHOWN. THE LANDSCAPING REQUIRED AND PROVIDED
 IS FOR THE LANDSCAPING WITHIN THE PROPERTY, THE
 ADDITIONAL LANDSCAPING ON THE LAKE PATH CANNOT BE
 COUNTED TOWARDS THE LANDSCAPE REQUIREMENTS. A SEPARATE
 TABULATION FOR THAT AREA SHOULD BE INCLUDED ON PLANS.
  
 RESUBMITTAL: PER MEETING DISCUSSION , PROVIDE DETAILS,
 INCLUDING CROSS SECTION OF PROPOSED IMPROVEMENTS ON
 CITY PROPERTY (AKA TURQUOISE NECKLACE) FOR STAFF REVIEW
 (SIDEWALK, WALL, LANDSCAPING, BENCHES, ETC.). FINAL
 APPROVAL OF LANDSCAPING AND DESIGN IS CONTINGENT ON
 APPROVAL BY THE PUBLIC UTILITIES DEPARTMENT AND
 PERTINENT DEPARTMENTS REGARDING USAGE OF CITY PROPERTY.
  
 12. THE "TABULAR TREE LIST", IS THAT WHAT IS EXISTING?
 UNDER STATUS, IS "TBD" (TO BE DETERMINED), WHETHER TO
 REMAIN OR RELOCATE? PLEASE CLARIFY AND NOTE COMMENT
 NUMBER 8 ABOVE.
  
 RESUBMITTAL (1): OUTSTANDING COMMENT TO BE ADDRESSED
 PRIOR TO FINAL APPROVAL OF BUILDING (LANDSCAPE) PERMIT.
 APPLICANT INDICATED THAT THE FINAL DESTINATION OF
 RELOCATED TREES SHALL BE DETERMINED ONCE OVERGROWTH IS
 REMOVED AND THE EXACT DEMEANOR OF THE NATIVE TREE CAN
 BE MORE ACCURATELY DETERMINED.
  
 13. SHEET LD-6 OF 6 - SHOW A DETAIL PROVIDING A ROOT
 BARRIER SYSTEM FOR THE CANOPY TREES, FOR INSTANCE, THE
 LIVE OAKS (QV) PROPOSED THROUGHOUT THE PARKING LOTS,
 ETC. DUE TO THE NATURE OF THEIR ROOT SYSTEM, IT IS
 STRONGLY RECOMMENDED TO AVOID FUTURE ISSUES WITH THE
 TREE'S ROOT SYSTEM.
  
 RESUBMITTAL (1): THERE ARE SOME AREAS WITHIN THE PLANS
 THAT MAY REQUIRE ADDITIONAL REVIEW DUE TO CLOSE
 PROXIMITY TO A STRUCTURE/INFRASTRUCTURE, I.E. DUMPSTER
 ENCLOSURES, ETC. STAFF HAS DISCUSSED SOME AREAS DURING
 MEETINGS WITH APPLICANT (BRIAN CHEGUIS).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1443
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 07-06-2012 Cont ID  
Sent By lfranco Date 07-06-2012 Time 17:44 Rev Time 0.00
Received By lfranco Date 07-06-2012 Time 17:42 Sent To  
Notes
2012-07-06 17:42:55CITY OF WEST PALM BEACH
 PLANNING DIVISION
  
  
 PLANS AND PLATS REVIEW COMMITTEE
 JULY 11, 2012
 MAJOR AMENDMENT TO THE MIZNER LAKES APARTMENT
 RESIDENTIAL PLANNED DEVELOPMENT
 PB 1171FF
  
 A REQUEST BY BRIAN CHEGUIS/DONALDSON HEARING, OF
 COTLEUR & HEARING, INC., ON BEHALF OF AARON DRIVE
 HOLDINGS, LLC FOR A MAJOR AMENDMENT TO THE MIZNER LAKES
 APARTMENTS RESIDENTIAL PLANNED DEVELOPMENT (?RPD?) TO
 BUILD APARTMENT BUILDINGS FOR MULTIFAMILY USE
 CONSISTING OF 548 RESIDENTIAL UNITS.
  
 P.C.N. 74-43-43-17-25-002-0000
 715 HANK AARON DRIVE
  
  
 GENERAL COMMENTS:
  
 1. WHEN RESUBMITTING:
  
 A. PROVIDE WRITTEN RESPONSES TO REVIEW COMMENTS MADE BY
 ALL DEPARTMENTS IN A WRITTEN FORMAT WHEN RESUBMITTING.
 NOTE THAT RESUBMITTALS MAY BE SUBJECT TO ADDITIONAL
 COMMENTS.
  
 B. 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 D. PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
  TRAFFIC CONCURRENCY/ JUSTIFICATION STATEMENT/ PLANS:
  
 2. THE APPLICANT SHOULD MEET WITH THE APPROPRIATE
 NEIGHBORHOOD ASSOCIATIONS TO INFORM THEM OF THE
 PROPOSED REVISIONS TO THE APPROVED DEVELOPMENT AS PART
 OF THE REVIEW PROCESS AND NOTIFY PLANNING STAFF OF THE
 OUTCOME OF THE MEETING AND ANY ISSUES THAT MAY NEED TO
 BE ADDRESSED BY THE APPLICANT.
  
  
 3. THE ITEMS BELOW WERE REQUIRED AT TIME OF APPLICATION
 SUBMITTAL, PROVIDE ALL THE UTILITY LETTERS. THE
 APPLICATION MAY NOT MOVE FORWARD TO PLANNING BOARD
 UNTIL ALL COMMENTS ARE ADDRESSED AND THE PLANNING
 DEPARTMENT RECEIVES ALL LETTERS ACCORDINGLY.
  
  DEVELOPMENT APPLICATION: N. CITY SERVICE AND PUBLIC
 UTILITY LETTERS
  
 A PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC
 UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT
 ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE
 WITH THE PROVISIONS OF THEIR SERVICES:
  
  TELEPHONE:
 ROBERT LOWEN
 AT&T FLORIDA ? ENGINEERING DEPARTMENT
 2021 SOUTH MILITARY TRAIL ? WEST PALM BEACH, FLORIDA
 33415
 PHONE: (561) 357.6615 ? FAX: (561) 964.3499 EMAIL:
 [email protected]
  
 NATURAL GAS:
 NANI SANTIAGO
 FLORIDA PUBLIC UTILITIES
 1641 WORTHINGTON RD SUITE 220 - WEST PALM BEACH, FL
 33409
 PHONE: (561) 838.1785 GENERAL PHONE: (561) 832.2461
 FAX: (561) 838.1769 (EASEMENT CONSENT FORMS CAN BE
 FAXED) EMAIL: [email protected]
  
 ELECTRIC SERVICE:
 FLORIDA POWER & LIGHT COMPANY
 810 CHARLOTTE AVENUE WEST PALM BEACH, FLORIDA 33401
  
 THE FP&L PROJECT MANAGER (INCLUDING NAME AND TELEPHONE
 NUMBER) FOR THE PROJECT'S LOCATION MAY BE FOUND BY
 VISITING THE FOLLOWING WEBSITE:
  
 HTTP://APP.FPL.COM/NAPPS/PS/SERVICEM.NSF/FPLWEB+SEARCH+
 SIMPLE-OPENFORM
  
 TELEVISION CABLE:
 WADE HAGERTY
 COMCAST CABLE COMMUNICATIONS
 10435 IRONWOOD ROAD PALM BEACH GARDENS, FLORIDA 33410
 PHONE: (561) 227-4127 FAX: (561) 640-0231 - EMAIL:
 [email protected]
  
 SITE PLAN:
  
 4. SHEET A0.01 AND A1.01 PARKING CALCULATIONS:
 A. PURSUANT TO SECTION THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-486, TABLE XV-6,
 RESIDENTIAL MULTIFAMILY, ONE (1) PARKING SPACE IS
 REQUIRED PER EVERY 10 UNITS FOR GUESTS. THEREFORE, FOR
 548 UNITS, 55 GUEST PARKING SPACES ARE REQUIRED. 1,058
 REGULAR PARKING + 55 GUEST SPACES = 1113 PARKING
 REQUIRED.
  
  NOTE, THE JUSTIFICATION STATEMENT STATES 1,077 PARKING
 HAVE BEEN PROVIDED INCLUDING 32 ON-STREET PARKING
 SPACES, SEE COMMENT (B) BELOW AND REVISE ALL
 DOCUMENTATION TO MATCH ACCORDINGLY.
 B. ADDITIONALLY, PURSUANT TO SECTION 94-485 (O), 20 HC
 SPACES ARE REQUIRED FOR UP TO 1,000 REGULAR SPACES,
 PLUS ONE (1) HC SPACE FOR EACH 100 OVER 1,000.
 THEREFORE, 21 HC ARE REQUIRED NOT 20. THE SITE PLAN
 SHOWS 30 HC PROVIDED ON THE SITE DATA, BUT THE PLANS
 SHOW ONLY 26 HC? PLEASE CLARIFY. ALSO, SUGGEST
 RELOCATING AND/OR ADDING HC SPACE(S) AT THE SOUTHWEST
 CORNER OF THE PROJECT, SINCE THERE ARE NO HC SPACES
 PROPOSED IN THAT AREA TO SERVE BUILDING 4, TYPE A OR
 BUILDING 16, TYPE E.
  
  THE JUSTIFICATION STATEMENT STATES THAT AN ADDITIONAL
 32 ON-STREET PARKING SPACES ARE PROVIDED THAT ARE
 LOCATED ON THE WEST AND EAST SIDE OF HANK AARON, THE
 ONLY PARKING AVAILABLE THAT CAN BE COUNTED TOWARDS THE
 PROJECT'S REQUIREMENTS IS THE ON-STREET PARKING ON THE
 EAST SIDE OF HANK AARON, WHICH IS ADJACENT TO THE
 FRONTAGE OF THE PROJECT. THE SITE PLAN SHOWS 16 PARKING
 SPACES VS. JUSTIFICATION STATEMENT NOTED AS 32 PARKING
 SPACES. REVISE ALL DOCUMENTATION TO CORRELATE.
  
 5. SHEET A1.01 - SITE PLAN, INCLUDES THE SITE DATA WITH
 10 BICYCLE PARKING SPACES PROVIDED AND NO REQUIREMENT
 FOR BICYCLE PARKING, WHICH IS INCORRECT; SHEET A0.01,
 PROJECT DATA DOES NOT DENOTE ANY BICYCLE PARKING. ALSO,
 ON SHEET A1.01, THE SITE PLAN DOES NOT SHOW ANY BICYCLE
 PARKING. PURSUANT TO SECTION 94-485(Q), ONE (1) BICYCLE
 PARKING SPACE SHALL BE PROVIDED FOR EVERY 20 AUTOMOBILE
 PARKING SPACES, OR FRACTION THEREOF, REQUIRED FOR THE
 USE. THE BICYCLE PARKING SPACES SHALL BE SPREAD
 THROUGHOUT THE SHOPPING PLAZA. SHOW A DETAIL OF
 PROPOSED AREAS. THE BICYCLE RACK(S) SHALL COMPLY WITH
 THE DESIGN STANDARDS SET FORTH. A LINK OF ACCEPTABLE
 BICYCLE RACKS WITH DETAILS AND MINIMUM DIMENSIONS WILL
 BE PROVIDED VIA EMAIL FOR YOUR REFERENCE.
  
 6. SHOW DIMENSION OF RESIDENTIAL DEVELOPMENT
 IDENTIFICATION SIGN THAT MEETS ALL REQUIREMENTS OF
 SECTION 94-407 (2):
  
 B.2. THE MAXIMUM SQUARE FEET PER FACE OF A SIGN IS 48
 SQUARE FEET, SHALL BE SETBACK A MINIMUM OF 20 FEET FROM
 THE PROPERTY LINE;
 F. MAXIMUM HEIGHT IS FOUR (4) FEET; THE SIGN PROPOSED
 IS AT 9 FEET. IS A WAIVER REQUESTED FOR THE ADDITIONAL
 HEIGHT?
  
 7. SHEET 3 "PAVING AND DRAINAGE" LOWER THE HC PAINTED
 LOGO TO LEAVE 2 FEET FROM BOTTOM OF LOGO TO THE BOTTOM
 OF PARKING STALL STRIPPING. THE DETAIL SHOWS 16 INCHES
 BETWEEN CENTER PARKING STALL PAINTING DETAIL, AND
 STALLS BEING 9 FEET WIDE. APPLICANT MAY CONSIDER
 REDUCING TO THE MINIMUM ZLDR DIMENSIONS OF 12 INCHES
 BETWEEN CENTER OF STRIPING AND 8'-6" WIDE TO
 ACCOMMODATE MORE PARKING SPACES, SINCE THE PROPOSED
 SITE PLAN DOES NOT MEET THE MINIMUM PARKING SPACES
 REQUIRED.
  
 8. THE ARCHITECTURAL PLANS SHOW A SIDE PRIVACY WALL,
 BUT THE CIVIL DENOTES A FENCE? PLEASE CLARIFY. ALSO,
 THE DETAIL PLAN FOR THE PEDESTRIAN ACCESS FEATURES
 SHOWS A CURVED GATE, THE PLANS SHOW A STRAIGHT LINE,
 DEPICT ON SITE PLAN, THE CURVATURE TO ASSURE IT IS
 WITHIN THE APPLICANT'S PROPERTY.
  
 9. SHEET PH.01, PHOTOMETRIC PLAN - EXTEND FOOT
 CANDLE/LUMENS CALCULATIONS TO THE EDGE OF ALL PROPERTY
 LINES.
  
  
 LANDSCAPE PLAN:
  
 10. PRIOR TO THE FINAL APPROVAL OF THE ALTERATION AND
 BUILDING PERMIT, PROVIDE LANDSCAPE PLANS TO THE
 PLANNING DIVISION WITH A REVISED PLAN OF THE EXISTING
 TREES TO REMAIN OR BE RELOCATED, SINCE THE
 JUSTIFICATION STATEMENT AND LANDSCAPE PLANS NOTE THAT A
 TREE SURVEY OF EXISTING TREES COULD NOT BE PERFORMED
 UNTIL THE LAND IS CLEARED OF EXCESSIVE OVERGROWTH OF
 VEGETATION.
  
 11. SHEET LP-1, LANDSCAPE DATA, SHOW WHAT LANDSCAPING
 IS "PROVIDED" ON THE TABLE. THE "REQUIRED" PART IS THE
 ONLY ITEMS SHOWN. THE LANDSCAPING REQUIRED AND PROVIDED
 IS FOR THE LANDSCAPING WITHIN THE PROPERTY, THE
 ADDITIONAL LANDSCAPING ON THE LAKE PATH CANNOT BE
 COUNTED TOWARDS THE LANDSCAPE REQUIREMENTS. A SEPARATE
 TABULATION FOR THAT AREA SHOULD BE INCLUDED ON PLANS.
  
 A. IN THE GENERAL NOTES, ITEM 4, DENOTES MXD CODE, IS
 THAT A TYPO? REVISE ACCORDINGLY.
  
 12. THE "TABULAR TREE LIST", IS THAT WHAT IS EXISTING?
 UNDER STATUS, IS "TBD" (TO BE DETERMINED), WHETHER TO
 REMAIN OR RELOCATE? PLEASE CLARIFY AND NOTE COMMENT
 NUMBER 8 ABOVE.
  
 13. SHEET LD-6 OF 6 - SHOW A DETAIL PROVIDING A ROOT
 BARRIER SYSTEM FOR THE CANOPY TREES, FOR INSTANCE, THE
 LIVE OAKS (QV) PROPOSED THROUGHOUT THE PARKING LOTS,
 ETC. DUE TO THE NATURE OF THEIR ROOT SYSTEM, IT IS
 STRONGLY RECOMMENDED TO AVOID FUTURE ISSUES WITH THE
 TREE'S ROOT SYSTEM.
  
  A. SHOW "PROVIDED" INFORMATION ON THE XERISCAPE DATA.
  
 14. SHOW LIGHT POLES ON SITE PLAN AND LANDSCAPE PLANS
 TO AVOID UTILITY CONFLICTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP, SENIOR PLANNER
 CITY OF WEST PALM BEACH