Plan Review Details - Project Z12050010
Plan Review Stops For Project Z12050010
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 06-12-2012 Cont ID  
Sent By lmartine Date 06-12-2012 Time 17:08 Rev Time 0.00
Received By lmartine Date 06-12-2012 Time 17:08 Sent To  
Notes
2012-06-12 17:11:10BUILDING REVIEW COMMENTS
  
  
 NO CONSTRUCTION DRAWINGS WERE PROVIDED.
  
 FLOOR PLAN LOOKS FINE.
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop PARK PARKING
Rev No 1 Status F Date 06-12-2012 Cont ID  
Sent By ssamuels Date 06-12-2012 Time 19:26 Rev Time 0.00
Received By ssamuels Date 06-12-2012 Time 19:26 Sent To  
Notes
2012-06-12 19:28:09PARKING SHEET DATA IS NEEDED TO SHOW ALL SPECIFICATION
 OF PARKING STALL, HANDICAP SYMBOLS, STRIPING
 AND SIGNS.

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-06-12 08:42:07 CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL.
 A.AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B.THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C.PROPERTY SHALL BE POST ?NO TRESPASSING? SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
  
  
 A. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM (1) INCH
 THROW OR MECHANICAL INTERLOCK.
 B. GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 C. REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE
 PEEPHOLE/ SECURITY VIEWER.
 D. ALL BUILDINGS SHALL BE PRE-WIRED FOR CLOSED-CIRCUIT
 TELEVISION (CCTV) AND ALARM SYSTEMS
 E. SIGNS SHALL CLEARLY IDENTIFY PUBLIC ENTRANCES.
  
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-06-11 17:28:581. NO ENGINEERING PLANS OR STORM WATER CALCULATIONS
 PROVIDED.
 2. SFWMD ERP PERMIT TO BE MODIFIED/OBTAINED.
 3. STORM WATER POLLUTION PREVENTION PLAN TO BE PREPARED
 BEFORE START OF CONSTRUCTION.
  
 TRACY L. WARD, P.E.
 SENIOR STORM WATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-08-2012 Cont ID  
Sent By vnoel Date 06-08-2012 Time 08:49 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2012-06-08 08:49:121. ALTHOUGH STATED IN JUSTIFICATION THAT COPIES WERE
 PROVIDED, NO SURVEY WAS INCLUDED IN PACKAGE. ONLY COPY
 OF RECORD PLAT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 06-12-2012 Time 13:46 Sent To  
Notes
2012-06-12 13:46:50NO COMMENTS

Review Stop Z ZONING
Rev No 1 Status F Date 06-12-2012 Cont ID  
Sent By eschneid Date 06-12-2012 Time 16:09 Rev Time 0.00
Received By eschneid Date 06-12-2012 Time 16:08 Sent To  
Notes
2012-06-12 16:09:11PB 1248Q
 MORSELIFE PACE PROGRAM MAJOR AMENDMENT
 4847 FRED GLADSTONE DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TEN
 (10) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 JUNE 22, 2012, TO BE SCHEDULED FOR THE JULY 17, 2012
 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING
 (AUGUST 22, 2012), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF ORDINANCE NO.
 4357-11.
  
 1) PLEASE PROVIDE A COPY OF THE PALM BEACH COUNTY
 TRAFFIC CONCURRENCY LETTER APPROVING THE NEW VEHICLE
 TRIPS.
  
 2) THE 7,000 SQUARE FOOT ADDITION WILL BE PROCESSED
 THROUGH THE FORMAL SITE PLAN REVIEW PROCESS. DETAILED
 SITE AND LANDSCAPE PLANS AND ELEVATIONS WILL BE
 REQUIRED WITH THE APPLICATION AND A DETAILED SITE
 REVIEW WILL BE PERFORMED AT THAT TIME. NOT IF TREES ARE
 TO BE REMOVED OR RELOCATED, A TREE ALTERATION PERMIT IS
 REQUIRED.
  
 3) THE PARKING CALCULATIONS FOR THE MORSE GERIATRIC
 CENTER SHALL BE BROKEN OUT INTO EACH ELEMENT. IT
 APPEARS THAT THE PARKING "REQUIRED" IS UNDERSTATED AS
 IT DOES NOT FACTOR IN THE ENTIRE OFFICE SQUARE FOOTAGE.
 THERE STILL APPEARS TO BE EXCESS IN THE TOTAL PROVIDED
 PARKING.
  
 4) THE DAYCARE FACILITIES, ADULT, PARKING REQUIREMENT
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS SHALL BE
 USED. THE REQUIRED 5 VISITOR SPACES ARE NOT INCLUDED ON
 THE PARKING TABLE.
  
 5) THE MASTER PLAN SHALL DESIGNATE THE LOCATION OF THE
 VAN PARKING. IT SHALL BE SCREENED FROM THE ADJACENT
 RESIDENTIAL.
  
 6) PLEASE PROVIDE THE DIMENSIONS OF THE VANS, SO THAT
 STAFF CAN VERIFY THE VANS WILL FIT IN THEIR INTENDED
 PARKING SPACES.
  
 7) THE LATEST PROPERTY APPRAISER AERIAL SHOWS THE
 MORSELIFE PARKING LOT FULL. THERE DO NOT APPEAR TO BE
 ENOUGH OPEN PARKING SPACES TO PARK AN ADDITIONAL 60
 EMPLOYEES, 5 GUESTS AND 15 VANS. PLEASE EXPLAIN.
  
 8) STAFF ONLY COUNTS 299 PARKING SPACES DRAWN ON THE
 PLAN, NOT 306 SPACES AS LISTED PARKING TABLE. THE
 LATEST AERIAL SHOWS THAT THE 299 SPACES AS SHOWN ON THE
 PLAN ARE INCORRECT. THE AERIAL SHOWS A NUMBER OF ACCESS
 AISLES IN THE PARKING LOT WHICH ARE NOT REFLECTED ON
 PLAN. THIS WOULD REDUCE THE PARKING COUNT FURTHER.
 PARKING LOT INTERIOR AND TERMINAL ISLANDS ALSO APPEAR
 TO BE INCORRECTLY SHOWN. PLEASE CORRECT THE PARKING
 LAYOUT AND THE PARKING NUMBERS.
  
 9) WHERE IS THE OUTDOOR RECREATION AREA FOR THE PROGRAM
 PARTICIPANTS?
  