| 2011-12-16 10:07:23 | PB 1399N |
| | SEDONA COMMONS CPD CONNECT BUILDINGS 5 & 6 |
| | 8120 OKEECHOBEE BLVD |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN OFRMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE |
| | (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT |
| | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE |
| | RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING AND ZONING |
| | DEPARTMENT HAS NOT RECEIVED A RESPONSE TO THE PPRC |
| | COMMENTS WITHIN 60 DAYS FROM THE DATE OF THESE COMMENTS |
| | (FEBRUARY 16, 2012), THE CASE SHALL BE CONSIDERED |
| | WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW |
| | DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE ADDITIONAL |
| | (1) RESUBMITTAL AT NO ADDITIONAL COST. IF |
| | PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE |
| | SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED |
| | A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL |
| | APPLICATION FEE ($60). |
| | |
| | 1) CONDITION FOR APPROVAL - THERE IS A 10 FOOT FPL |
| | EASEMENT WHICH CURRENTLY EXISTS BETWEEN BUILDINGS 5 & |
| | 6. THE NEW BUILDING MAY NOT BE CONSTRUCTED OVER THE |
| | EASEMENT WITHOUT A RELEASE OF THE EASEMENT FROM FPL OR |
| | CONSENT FROM FPL THAT A BUILDING MAY BE CONSTRUCTED |
| | OVER THEIR EASEMENT. |
| | |
| | 2) THE PLANS SHALL BE CHANGED TO REFLECT THAT A UNITY |
| | OF TITLE IS REQUIRED TO JOIN TRACTS D AND E. THE SURVEY |
| | COMMENTS INCLUDED A TYPO THAT THE UNITY OF TITLE WAS |
| | FOR TRACTS E AND F. |
| | |
| | 3) PLEASE VERIFY YOUR SETBACK DIMENSIONS LISTED ON THE |
| | DATA TABLE FOR UNIFIED TRACTS D & E WITH THE ACTUAL |
| | PLAN CONDITIONS, ESPECIALLY THE REAR SETBACK |
| | |
| | 4) THE BUILDING REVIEWER, LUIS MARTINEZ, REQUIRES |
| | ADDITIONAL CLARIFICATION OF THE RESPONSE TO HIS |
| | COMMENTS: |
| | |
| | A. EAST ELEVATION, CHECK YOUR ALLOWABLE OPENINGS PER |
| | TABLE 704.8, FLORIDA BUILDING CODE (FBC). - THE |
| | RESPONSE STATES THAT THERE ARE HUNDREDS OF FEET FROM |
| | THE EAST FACADE TO THE PROPERTY LINE. THIS IS INCORRECT |
| | AS THE BOUNDARY OF TRACT D IS 10 FEET FROM THE FACE OF |
| | THE BUILDING. PLEASE PROVIDE THE FACADE CALCULATIONS |
| | THAT THE ALLOWABLE OPENINGS MEET TABLE 704.8, FLORIDA |
| | BUILDING CODE (FBC) AT THIS PORTION OF THE BUILDING. |
| | THE SOUTHERN PART FO THE BUILDING (ADJACENT TO TRACT E) |
| | IS ONLY FIVE (5) FEET, NOT TEN (10) FEET FROM THE |
| | PROPERTY LINE. THE FACADE CALCULATIONS THAT THE |
| | ALLOWABLE OPENINGS MEET TABLE 704.8, FLORIDA BUILDING |
| | CODE (FBC) AT THIS PORTION OF THE BUILDING SHALL BE |
| | PROVIDED AS WELL. THE ALLOWED PERCENTAGE OF OPENINGS |
| | MAY AFFECT THE DESIGN OF THE EAST FACADE OF THE |
| | BUILDING. |
| | |
| | B. VERIFY YOUR TRAVEL DISTANCES AND EXITING |
| | REQUIREMENTS ARE COMPLIANT PER FBC CHAPTER 10. PLEASE |
| | SHOW ON THE PLANS THE PATH OF TRAVEL FOR THE NEW SUITE |
| | #8 TO SHOW THAT THE PROPOSED DOOR LOCATIONS ON THE EAST |
| | FACADE OF THE BUILDING COMPLY WITH FBC CHAPTER 10 (75 |
| | FOOT TRAVEL DISTANCT). IF THE DOOR THAT EXITS GENERALLY |
| | TO THE WEST OF THE BUILDING IS REQUIRED TO BE AN EXIT |
| | DOOR, THEN THE SITE AND LANDSCAPE PLANS SHALL BE |
| | AMENDED TO SHOW A SIDEWALK FROM THE DOOR TO THE INTENAL |
| | SIDEWALK NETWORK WHICH THEN LEADS TO THE PUBLIC |
| | RIGHT-OF-WAY. |
| | |
| | |
| | |
| | |
| | |