Plan Review Details - Project Z11070007
Plan Review Stops For Project Z11070007
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-13-2011 Cont ID  
Sent By lmartine Date 09-13-2011 Time 14:56 Rev Time 0.00
Received By lmartine Date 09-13-2011 Time 14:56 Sent To  
Notes
2011-09-13 15:37:54BUILDING REVIEW COMMENTS
  
  
  
 TYPE II A CONSTRUCTION REQUIRES NON COMBUSTIBLE FLOOR
 AND ROOF SYSTEMS, PLEASE VERIFY.
  
 SEE EXISTING BUILDING CODE CHAPTER 9, CHANGE OF
 OCCUPANCY FOR ADDITIONAL REQUIREMENTS.
  
 VERTICAL ACCESSABILITY WILL BE REQUIRED, SEE CHAPTER 11
 FLORIDA BUILDING CODE. ALSO SEE 11-9 FOR THE NUMBER OF
 ACCESSIBLE SLEEPING ROOMS REQUIRED.
  
 SEE FLORIDA BUILDING CODE SECTION 1030 FOR SPECIFIC
 ADDITIONAL INSTITUTIONAL REQUIREMENTS.
  
 SEE SECTION 1026 FOR EMERGENCY ESCAPE AND RESCUE
 OPENING REQUIREMENTS
  
 A LIFE SAFETY PLAN WILL BE REQUIRED TO DETERMINE EGRESS
 AND EXITING.
  
 A GREASE TRAP WILL BE REQUIRED FOR THE KITCHEN
 OPERATION.
  
 EAST AND WEST EXIT STAIRS SHALL BE ENCLOSED AND FIRE
 RATED.
  
 THIS REVIEW IS PRELIMINARY BASED ON THE DRAWINGS
 PROVIDED.
  
  
  
 LUIS MARTINEZ
 561-805-6710
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 09-13-2011 Cont ID  
Sent By bmoree Date 09-13-2011 Time 14:39 Rev Time 0.00
Received By bmoree Date 09-13-2011 Time 14:29 Sent To  
Notes
2011-09-13 14:39:431. INCOMPLETE SITE CIVIL DRAWINGS. TO EFFECTIVELY
 PROVIDE COMMENT IN REFERENCE TO ANY PROPOSED
 CONSTRUCTION IN THE RIGHT-OF-WAY (ALLEY), ENGINEERING
 SERVICE MUST RECEIVE A COMPLETE PLAN SET REPRESENTING
 THE ALL PROPOSED CONSTRUCTION WITH SUPPORTING TECHNICAL
 SPECIFICATIONS AND DETAILS.
 2. UTILITY SERVICE DEMAND CALCULATIONS ARE NOT
 CONTAINED WITHIN THE PLANS. WILL THE PROJECT UTILITY
 SERVICE DEMAND FOR WATER AND SANITARY DIFFER FROM
 PREVIOUS USE?
 3. STORMWATER CALCULATIONS ARE REQUIRED FOR ONSITE
 MODIFICATIONS. THIS SHALL INCLUDE BOTH A STORMWATER
 POLLUTION PREVENTION PLAN (SWPPP) DETAILING HOW SOIL
 AND DEBRIS WILL BE CONTAINED ON SITE DURING
 CONSTRUCTION ACTIVITY AND A MASTER STORMWATER
 MANAGEMENT PLAN FOR POST-CONSTRUCTION.
  
 FOR FURTHER INFORMATION, PLEASE CONTACT ENGINEERING
 SERVICES.
  
 BRIAN R. MOREE
 CONSTRUCTION MANAGER
 ENGINEERING SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-494-1098 OFFICE
 561-644-7270 MOBILE
 [email protected]

Review Stop PARK PARKING
Rev No 1 Status F Date 09-14-2011 Cont ID  
Sent By ssamuels Date 09-14-2011 Time 10:24 Rev Time 0.00
Received By ssamuels Date 09-14-2011 Time 10:24 Sent To  
Notes
2011-09-14 10:27:29NEED TO PROVIDE DETAIL SITE SHEET SHOWING ALL
 SPECIFICATION
 ADA PARKING STALL
 SYMBOLS
 SIGNS
 LOGO ON PAVEMENT.

Review Stop STORM STORMWATER
Rev No 1 Status F Date 09-14-2011 Cont ID  
Sent By tward Date 09-14-2011 Time 12:27 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2011-09-14 12:27:18NO CIVIL PLANS OR DRAINAGE CALCULATIONS SUBMITTED.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-29-2011 Cont ID  
Sent By vnoel Date 08-29-2011 Time 08:37 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2011-08-29 08:45:021. PACKAGE INCOMPLETE - NO SURVEY PROVIDED.
 2. IT APPEARS THAT THE ALLEY TO THE SOUTH IS INCLUDED
 IN THE SITE PLAN. APPLICATION WILL NEED TO BE MADE FOR
 ABANDONMENT OR REVOCABLE PERMIT.
 3. SCALE IS WRONG ON SITE PLAN, SHOULD BE 1" = 20'.

Review Stop Z ZONING
Rev No 1 Status F Date 09-18-2011 Cont ID  
Sent By astelly Date 09-14-2011 Time 17:18 Rev Time 0.00
Received By astelly Date 09-14-2011 Time 17:18 Sent To  
Notes
2011-09-18 18:39:12AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE SCALE ON THE SITE PLAN IS INCORRECT.
 A LANDSCAPE PLAN IS REQUIRED TO SATISFY ALL COMMENTS
 BELOW. A SIGNED AND SEALED LANDSCAPE PLAN MUST BE
 PRESENTED UPON APPROVAL OF THE CLASS B SPECIAL USE
 PREMIT.
  
 ALL TREES MUST BE A MINIMUM OF 8' WITH 5' OF CLEAR
 TRUNK.
 PLANT MATERIALS MUST BE #1 GRADE OR BETTER.
 SHRUBS MUST BE A MINIMUM OF 2 GALLONS.
 HEDGES MUST BE A MINIMUM OF 24" IN HEIGHT.
 PALM TREES MAY BE SUBSTITUTED FOR A MAXIMUM OF 35% OF
 THE REQUIRED SHADE TREES. HOWEVER, WHEN PALMS ARE
 SUBSTITUTED, TWO (2) SHALL BE PROVIDED FOR EACH
 REQUIRED SHADE OR FLOWERING TREE. ROYAL PALMS, SRECAS,
 PAUROTIS AND SENEGAL DATE PALMS ARE EXCLUDED FROM THIS
 REQUIREMENT.
 AN IRRIGATION SYSTEM IS REQUIRED.
  
 THE FOLLOWING COMMENTS PERTAIN TO THE SURFACE PARKING
 LOT AT WEBSTER AND BUNKER:
  
 THE SURVEY INDICATES THAT THERE ARE MONITORING WELLS IN
 THE PROPOSED PARKING AREA. PLEASE PROVIDE A WRITTEN
 EXPLANATION REGARDING THE ACTIVITY FOR THE WELLS AND
 THE IMPACT UPON THE PROPOSED PARKING.
 ALL PARKING ROWS MUST TERMINATE WITH A LANDSCAPED
 TERMINAL ISLAND.
 ALL INTERIOR AND TERMINAL ISLANDS MUST BE AT LEAST 5'
 IN WIDTH WITH A RADIUS OF 2.5'.
 THE INTERIOR AND TERMINAL ISLANDS MUST BE LANDSCAPED
 WITH AT LEAST ONE (1) SHADE OR FLOWERING TREE.
 PLEASE LIST THE PLANTINGS IN THE EXISTING LDIVIDER
 MEDIAN (LANDSCAPE STRIP). SHADE OR FLOWERING TREES MUST
 BE PLANTED AT 30' INTERVALS.
 SHADE TREES MUST BE PLANTED AT 30' INTERVALS WITHIN THE
 LANDSCAPE BUFFER ALONG BUNKER ROAD.
 A 5' WIDE LANDSCAPE BUFFER IS REQUIRED ALONG THE REAR
 OF THE PARKING LOT SINCE THE PROPERTY IS ADJACENT TO A
 RESIDENTIAL ZONING DISTRICT. THE BUFFER MUST BE PLANTED
 WITH SHADE TREES AT 30' INTERVALS.
 SHRUBS, GRASS OR GROUND COVER MUST BE PLANTED OVER THE
 ENTIRE LENGTH OF ALL BUFFER STRIPS AND PARKING ISLANDS.
  
 THE FOLLOWING COMMENTS PERTAIN TO THE PARCEL CONTAINING
 THE PRIMARY STRUCTURE:
  
 A PROTECTIVE SCREEN WALL AT LEAST 5' IN HEIGHT AND A 5'
 (MIN.) LANDSCAPE BUFFER IS REQUIRED ALONG THE ENTIRE
 LENGTH OF THE PROPERTY ADJACENT TO THE RESIDENTIAL
 ZONING DISTRICT AT THE REAR OF THE PROPERTY. THE BUFFER
 MUST BE PLANTED WITH SHADE OR FLOWERING TREES AT 30'
 INTERVALS.
 ONE (1) SHADE TREE MUST BE PLANTED FOR EVERY 900 S.F.
 OF PLAZA - THE MEDITATION GARDEN - AT THE FRONT OF THE
 PROPERTY.
 THE FLOOR OF THE PLAZA SHALL BE MADE OF CONCRETE,
 PAVERS OR OTHER DURABLE MATERIAL.
 AT LEAST ONE (1) FLOWERING TREE IS REQUIRED FOR EVERY
 6400 S.F. OF OPEN SPACE IN THE GARDEN.
 AT LEAST ONE SHURB MUST BE PLANTED FOR EVERY 500S.F. OF
 OPEN SPACE IN THE GARDEN. SHRUBS MAY BE PLANTED AT 3'
 INTERVALS OR CLUSTERED FOR EFFECTIVENESS.
 ONE TREE MAY BE SUBSTITUTED FOR FIVE (5) SHRUBS.
 HOWEVER, SHRUBS MAY NOT BE SUBSTITUTED FOR REQUIRED
 TREES.
 LANDSCAPING IS REQUIRED ADJACENT TO THE HANDICAP
 PARKING SPACES.
 PLANTING AREAS ADJACENT TO THE HANDICAP PARKING SPACES
 MUST BE PROTECTED WITH NON-MOUNTABLE CONCRETE CURBING.
 THE WALLS OF THE DUMPSTER ENCLOSURE MUST BE PLANTED
 WITH SHRUBS OR HEDGES AT 2' INTERVALS.
 ** PLEASE FIND AN ALTERNATE LOCATION FOR THE DUMPSTER
 DUE TO COMPLAINTS FROM NEIGHBORING PROPERTY OWNERS
 PLEASE INDICATE THE LOCATION OF THE CURB RAMP OR CURB
 CUT FOR THE HANDICSP PARKING.
 PLEASE PROVIDE A STRIPED QUEUING AREA RATHER THAN AN
 ISLAND BETWEEN THE HANDICAP PARKING SPACES.
  
 ONE BICYCLE PARKING SPACE MUST BE PROVIDED FOR EVERY 20
 REQUIRES PARKING SPACES. PLEASE INDICATE THE LOCATION
 OF THE BIKE RACK.
  
  
  
  