Plan Review Details - Project Z11070002
Plan Review Stops For Project Z11070002
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-10-2011 Cont ID  
Sent By lmartine Date 08-10-2011 Time 08:39 Rev Time 0.00
Received By lmartine Date 08-10-2011 Time 08:39 Sent To  
Notes
2011-08-10 08:46:43BUILDING REVIEW COMMENTS
  
  
  
 SEE FLOOD ZONE REQUIREMENTS FOR ZONE A-5, ELEVATION
 MINIMUM AT 7.5'.
  
 PROVIDE ACCESSIBLE ROUTE FROM THE PARKING TO AND
 THROUGH-OUT THE TRAILER COMPLEX.
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 10-13-2011 Cont ID  
Sent By eschneid Date 10-13-2011 Time 12:24 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-10-2011 Cont ID  
Sent By   Date 08-10-2011 Time   Rev Time 0.00
Received By bmoree Date 08-10-2011 Time 12:20 Sent To  
Notes
2011-08-10 12:39:201. RECOMMEND RELOCATING ON-SITE WATER AND SEWER
 CONNECTION OUT OF TREE PLANTING AREA.
 2. SITE CIVIL CONSTRUCTION TO BE PERMITTED THROUGH
 ENGINEEIRNG SERVICES. (INCLUDING SWPPP, STORMWATER
 MANAGEMENT PLAN, UTILITIES, )
  
  
 BRIAN R. MOREE
 ENGINEERING SERIVCE CONSTRUCTION MANAGER
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 561-644-7270 CELLULAR
 561-494-1098 OFFICE
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 10-13-2011 Cont ID  
Sent By eschneid Date 10-13-2011 Time 12:24 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-10-2011 Cont ID  
Sent By tward Date 08-10-2011 Time 09:52 Rev Time 0.00
Received By tward Date 08-10-2011 Time 09:52 Sent To  
Notes
2011-08-10 09:53:01PRIOR TO BUILDING PERMIT BEING ISSUED, PROVIDE
 ENGINEERING CALCULATIONS (S&S) SHOWING THAT WATER
 QUALITY IS BEING PROVIDED AND THAT THE POST-DEVELOPMENT
 OFFSITE DISCHARGE DOES NOT EXCEED THE PRE-DEVELOPMENT
 OFFSITE DISCHARGE.

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 10-13-2011 Cont ID  
Sent By eschneid Date 10-13-2011 Time 12:25 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-08-2011 Cont ID  
Sent By vnoel Date 08-08-2011 Time 09:25 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2011-08-08 09:56:401. EXISTING EASEMENTS IN DEED BOOK 1080/244 NEED TO BE
 SHOWN.
 2. ABOVE EASEMENT NEEDS TO BE TERMINATED AND NEW 25'
 DRAINAGE EASEMENT GRANTED TO CITY.
 3. PER CITY CODE, VERTICAL DATUM SHALL BE NGVD -29.
 4. SURVEY IS REQUIRED TO BE DATED WITHIN ONE YEAR.
 5. 2 ON-SITE BENCHMARKS ARE REQUIRED FOR TOPOGRAPHIC
 SURVEYS.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-09-2011 Time   Rev Time 0.00
Received By bcollins Date 08-09-2011 Time 09:41 Sent To  
Notes
2011-08-09 09:49:44TRAFFIC PLAN DID NOT ADDRESS ALL CWPB CONDITIONS:
  
 NO INFORMATION ON HOW CONSTRUCTION TRAFFIC WOULDBE
 PREVENTED FROM PARKING AND DRIVING ON CITY STREETS
 NO UPDATED TRAFFIC STUDY WAS PROVIDED TO INDENTIFY
 CONSTRUCTION TRAFFIC IMPACTS
 TRAFFIC PLAN INDICATES NEW YIELD SIGN AT 59TH ST. AND
 FLAGLER (DIXIE HWY). EXISTING STOP SIGN SHOULD NOT BE
 REPLACED
 FLAGLER DRIVE IS NOT DIXIE HIGHWAY.

Review Stop Z ZONING
Rev No 3 Status P Date 12-07-2011 Cont ID  
Sent By eschneid Date 11-17-2011 Time 10:27 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 10-13-2011 Cont ID  
Sent By eschneid Date 10-13-2011 Time 12:25 Rev Time 5.00
Received By eschneid Date   Time   Sent To  
Notes
2011-10-13 12:27:54CASE NO. PB 1609
 FPL CONSTRUCTION SUPPORT AREA
 5904 NORTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF
 FORMAT OF ALL REVISED PLANS. PLEASE NOTE THAT CHANGES
 ON THE RESUBMITTED PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT YOU PREVIOUS COMMENTS WERE NOT
 SUFFICIENTLY ADDRESSED; THEREFORE, THE NEXT RESUBMITTAL
 WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE IS 20% OF
 THE ORIGINAL APPLICATION FEE ($200).
  
 1) THE PPRC RESPONSE MENTIONS THAT THE CONSTRUCTION
 TRAFFIC MANAGEMENT PLAN WAS CORRECTED BASED ON THE PPRC
 COMMENTS. PLEASE PROVIDE ONE HARD COPY OF THE REVISED
 PLAN AS WELL AS THE PLAN ELECTRONICALLY IN .PDF FORMAT.
  
 2) PLEASE PROVIDE A REVISED SITE PLAN WHICH CLEARLY
 SHOWS THE FOLLOWING OUTSTANDING COMMENTS FROM THE
 AUGUST 10, 2011 PPRC MEETING ADDRESSED.
  
 A. PPRC COMMENT #1(SITE CERTIFICATION CONDITION L) -
 THE SITE PLAN SHALL SHOW THE LOCATION OF THE HEDGE AND
 CALL OUT THE PLANT MATERIAL, THE HEIGHT AT INSTALLATION
 AND THE PLANT SPACING. THE MINIMUM REQUIREMENTS OF THE
 CITY'S LANDSCAPE REGULATIONS SHALL BE FOLLOWED (SEE
 ARTICLE XIV OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS).
  
 B. PPRC COMMENT #2 - THE SITE PLAN SHALL SHOW THE
 HEIGHT OF THE PERIMETER FENCE AT 6 FEET HIGH.
  
 C. PPRC COMMENT #3 - THE FENCE SHOWN ON THE WESTERN
 SIDE OF THE PROPERTY ON THE SITE PLAN DOES NOT MATCH
 THE LOCATION OF THE FENCE SHOWN ON THE SURVEY. IF THE
 FENCE IS TO REMAIN AT ITS EXISTING LOCATION THEN THE
 SITE PLAN SHALL ACCURATELY SHOW THE FENCE LOCATION, IF
 THE FENCE IS TO BE INSTALLED AS SHOWN ON THE SITE PLAN,
 THEN THE FENCE ON THE SITE PLAN SHALL CLEARLY BE
 LABELED AS A NEW FENCE.
  
 D. PPRC COMMENT #8 - THE SITE PLAN SHALL STATE THAT THE
 PARKING AREA WILL BE A PAVED OR CONCRETE SURFACE.
  
 E. PPRC COMMENT #9 - THE ENTRY DRIVE AND THE WEST SIDE
 OF THE PARKING AREA SHALL BE CURBED OR HAVE OTHER
 BARRIER ON THE GROUND TO PREVENT VEHICULAR ENCROACHMENT
 INTO THE LANDSCAPED AREAS WITH THE PROTECTED TREES
 [SECTION 94-485(G) ZONING AND LAND DEVELOPMENT
 REGULATIONS].
  
 F. PPRC COMMENT #10 - THE SITE PLAN SHALL INCLUDE
 PARKING DETAILS MEETING CITY STANDARDS (DOUBLE STRIPED,
 WHITE FOR NON-ADA SPACES) [SECTION 94-485(G) ZONING AND
 LAND DEVELOPMENT REGULATIONS].
  
 3) PLEASE NOTE THAT IN ORDER TO COMPLY WITH PPRC
 COMMENT #1 (SITE CERTIFICATION CONDITION R) A CONDITION
 WILL BE INCLUDED WITH THE APPROVAL LETTER THAT THE 4
 TREES, TOTALING APPROXIMATELY 15 DBH, SHALL BE INCLUDED
 (AND CLEARLY IDENTIFIED ON) AS PART OF THE LANDSCAPE
 PLAN FOR THE MANATEE VIEWING CENTER.
  
 4) IN ORDER TO FULLY COMPLY WITH PPRC COMMENT #2 A
 CONDITION WILL BE INCLUDED WITH THE APPROVAL LETTER
 REQUIRING A PERMIT FOR ALL OF THE FENCING AND GATES
 ON-SITE.
  
 5) IT HAS COME TO THE STAFF'S ATTENTION THAT A HISTORIC
 STRUCTURE HAS BEEN MOVED TO THE SITE. IT IS UNCLEAR AT
 THIS POINT WHAT THE FINAL DISPOSITION OF THIS STRUCTURE
 IS. IF THE STRUCTURE IS TO REMAIN ON THE SITE, IT SHALL
 BE CLEARLY INCLUDED ON THE REVISED SITE PLAN. ALL
 SETBACK DIMENSIONS AND INFORMATION ABOUT THE STRUCTURE
 SHALL BE INCLUDED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-05-2011 Cont ID  
Sent By eschneid Date 08-05-2011 Time 16:19 Rev Time 2.00
Received By eschneid Date 08-05-2011 Time 16:19 Sent To  
Notes
2011-08-05 16:20:21CASE NO. PB 1609
 FPL RIVIERA BEACH MODERNIZATION CONSTRUCTION SUPPORT
 AREA
 5904 NORTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING AND ZONING
 DEPARTMENT HAS NOT RECEIVED A RESPONSE TO THE PPRC
 COMMENTS WITHIN 60 DAYS FROM THE DATE OF THE PPRC
 MEETING (10/10/2011), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($200).
  
 1) NO LANDSCAPE PLAN WAS SUBMITTED TO DEMONSTRATE
 COMPLIANCE WITH CONDITIONS OF CERTIFICATION L AND R AND
 TO SHOW WHAT WILL BE CONTAINED IN THE "VEGETATED
 BUFFER" SHOWN ON THE EROSION CONTROL PLAN.
  
 2) CONDITION OF CERTIFICATION M REQUIRES A SIX (6) FOOT
 HIGH PERIMETER FENCE FOR THE SITE. THE PLANS DO NOT
 INDICATE THE HEIGHT OF THE "EXISTING" FENCE. PLEASE
 NOTE THAT THE CITY RECORDS DO NOT INDICATE THAT A
 PERMIT WAS ISSUED FOR THE FENCE INSTALLATION. FPL WILL
 NEED TO RECTIFY THE LACK OF A FENCE PERMIT.
  
 3) THE SURVEY SHOWS THE EXISTING FENCE ALONG THE
 PROPERTY LINE, YET THE SITE PLAN SHOWS THE MAJORITY OF
 THE FENCE WEST OF THE PROPERTY LINE WITHIN THE NORTH
 FLAGLER DRIVE RIGHT-OF-WAY. IF THE SITE PLAN IS
 INCORRECT IT SHALL BE DRAWN ACCURATELY. IF THE FENCE IS
 IN THE RIGHT-OF-WAY, IT SHALL BE REMOVED AND INSTALLED
 ON FPL PROPERTY IN COMPLIANCE WITH THE CONDITIONS OF
 CERTIFICATION.
  
 4) THE SITE PLAN SEEMS TO INDICATE THE LOCATION OF THE
 STORMWATER PIPE WHICH TRAVERSES THE SITE AS A DASHED
 DOUBLE LINE. IF THIS IS THE CASE, THEN THE PIPE SHALL
 BE DESIGNATED AS SUCH ON THE PLANS. IN ACCORDANCE WITH
 CONDITION OF CERTIFICATION V, PLEASE PROVIDE
 VERIFICATION FROM THE CITY'S ENGINEERING SERVICES
 DEPARTMENT AS TO WHAT MAY BE CONSTRUCTED OVER THE PIPE.
 ADDITIONALLY, VERIFY THAT THE WEIGHT OF THE TRAILERS
 BEING MOVED TO THE PROPOSED LOCATION WILL NOT
 NEGATIVELY AFFECT THE PIPE.
  
 5) PLEASE PROVIDE A LETTER FROM BELL SOUTH TO ALLOW THE
 PLACEMENT OF THE TRAILERS AND THE ROAD PAVEMENT WITHIN
 THEIR EASEMENT.
  
 6) THE QUIT CLAIM DEED PROVIDED WITH THE APPLICATION
 LISTS A NUMBER OF RESERVATIONS AND EASEMENTS NOT SHOWN
 ON THE SURVEY (THEY ARE LISTED IN THE TABLE). PLEASE
 PROVIDE COPIES OF THE DOCUMENTS AND STATE HOW THE
 LOCATION OF THE TRAILERS AND THE PAVING DOES NOT
 INTERFERE WITH THE EASEMENTS. IF THE TRAILERS OR
 PAVEMENT ENCROACH THE EASEMENTS, PROVIDE LETTERS OF NO
 OBJECTION FROM THE EASEMENT HOLDERS.
  
 7) THE LIGHTING PLAN INDICATES THAT THERE WILL BE NO
 REAR OR DIRECT SIDE LIGHT EMISSION FROM THE TEMPORARY
 LIGHTS. PLEASE EITHER VERIFY THAT THIS IS THE CASE OR
 VERIFY THAT THE LIGHT LEVELS AT THE SOUTH AND WEST
 PROPERTY LINES WILL NOT EXCEED 0.5 FOOT CANDLES AS
 REQUIRED BY CONDITION OF CERTIFICATION C.
  
 8) PROVIDE DETAILS FOR THE PARKING LOT/ENTRY DRIVE
 SURFACE AND CONSTRUCTION AND THE SURFACE MATERIAL
 AROUND THE CONSTRUCTION TRAILERS.
  
 9) HOW WILL THE VEGETATED BUFFER AREAS AND ANY OTHER
 LANDSCAPE ON SITE BE PROTECTED FROM VEHICULAR
 ENCROACHMENT?
  
 10) PROVIDE PARKING STALL DETAILS. THE PARKING SPACES
 SCALE AT APPROXIMATELY 16 FEET DEEP, WHICH DOES NOT
 MEET CODE REQUIRED MINIMUMS. THE ADA SPACES MEASURE AT
 APPROXIMATELY 9 FEET WIDE, WHICH DO NOT MEET CODE
 REQUIRED MINIMUMS.
  
 11) THE PARKING COUNT FOR THE SOUTHERNMOST PARKING ROW
 IS 21 NOT 22 AS STATED. NOTE: PROVIDE ACCURATE PARKING
 COUNTS ONCE THE ADA SPACE WIDTH IS CORRECTED.
  
 12) PROVIDE DETAILS ON THE ADA ROUTE FROM THE ADA
 PARKING SPACES TO THE TRAILER RAMPS.
  
 13) PROVIDE VERIFICATION FROM THE CONSTRUCTION SERVICES
 DEPARTMENT THAT THE PEDESTRIAN ROUTE FROM NORTH FLAGLER
 DRIVE TO THE CONSTRUCTION TRAILERS MAY SHARE THE ENTRY
 DRIVEWAY.
  
 14) PLEASE DO NOT FORGET THE FOLLOWING ADDITIONAL
 CONDITIONS OF CERTIFICATION J (SIGN AT BROADWAY AND
 59TH), N (CONSTRUCTION SECURITY PLAN), P (POSTING "NO
 TRESPASSING" SIGNS), U (CORRECT DRAINAGE EASEMENT FOR
 STORMWATER PIPE), Z (WATER AND SEWER FROM WEST PALM
 BEACH), HH (SUBMITTAL OF CONSTRUCTION DOCUMENTS) AND JJ
 (INSPECTIONS) WHICH RELATE TO THE CONSTRUCTION SUPPORT
 AREA.
  
 15) PLEASE PROVIDE A STATUS UPDATE OF THE COUNTY'S USE
 OF THE SITE AS PART OF THE ARTIFICIAL REEF PROGRAM.
  