Plan Review Details - Project Z10110006
Plan Review Stops For Project Z10110006
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-08-2010 Cont ID  
Sent By lmartine Date 12-08-2010 Time 11:07 Rev Time 0.00
Received By lmartine Date 12-08-2010 Time 11:07 Sent To  
Notes
2010-12-08 11:18:26BUILDING REVIEW COMMENTS
  
  
 FLOOD ZONE A-8 WILL REQUIRE ANY MECHANICAL EQUIPMENT
 AND THE FINISH FLOOR TO BE A MINIMUM 15.5' A.S.L.
  
 PLEASE PROVIDE AN EGRESS PLAN TO DETERMINE IF
 ADDITIONAL EXITING WILL BE REQUIRED.
  
 PALM BEACH COUNTY IMPACT FEES MAY BE ASSESSED,
 561-233-5019.
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-08-2010 Cont ID  
Sent By bmoree Date 12-08-2010 Time   Rev Time 0.00
Received By bmoree Date 12-08-2010 Time 09:57 Sent To  
Notes
2010-12-08 09:57:101. PROVIDE EASEMENT IN FORMATION FOR UTILITY METER
 LOCATIONS.
 2. ADA ACCESSIBLE ROUTE FOR SIDEWALK ADJACENT PARKING
 AREA IS INCOMPLETE.
 3. SITE CIVIL INFORMATION SHALL INCLUDE UTILITY
 CALCULATION, STORMWATER MANAGEMENT PLAN, AND POLLUTION
 PREVENTION PLAN.
 4. ALL TRAFFIC AND PEDESTRIAN CONTROLS SHALL BE STRIPED
 WITH THERMOPLASTIC.
  
 BRIAN R. MOREE
 ENGINEERING CONSTRUCTION SUPERVISOR
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 561-494-1098 OFFICE
 561-644-7270 MOBILE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 11-22-2010 Cont ID  
Sent By mcarsill Date 11-22-2010 Time 12:05 Rev Time 0.00
Received By mcarsill Date 11-22-2010 Time 10:41 Sent To  
Notes
2010-11-22 12:05:33INFORMAL SITE PLAN REVIEW
 4215 UP THE GROVE LANE
 FLORIDA POWER AND LIGHT OFFICES AND EMERGENCY
 OPERATIONS CENTER
  
 1. PROVISIONS ARE TO BE MADE FOR FIRE AND PARAMEDICAL
 ACCESS THROUGH THE ROLLING GATE.
  
 2. THE FIRE HYDRANT NEAR THE BUILDING SHOULD BE
 RELOCATED AT LEAST 40 FEET AWAY FROM THE BUILDING.
  
 3. THE FIRE LINE BACKFLOW PREVENTION DEVICE SHALL BE
 EQUIPPED WITH TAMPER SWITCHES, CHAIN AND LOCK.
  
 4. A KNOX BOX WILL BE REQUIRED FOR THE BUILDING. KNOX
 LOCKING CAPS ARE REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION. THESE DEVICES CAN BE ORDERED AT
 WWW.KNOXBOX.COM.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 GENERATOR INSTALLATION.
  
 6. PLEASE CLASSIFY THE BUILDING AS AN ASSEMBLY
 OCCUPANCY NOT OFFICES AS DESCRIBED ON SHEET A-101.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEM.
  
 8. PLEASE DECLARE ON DRAWINGS ALL EXIT FACILITIES.
  
 9. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS.
  
 10. THE FIRE LINE INSTALLATION SHALL COMPLY WITH NFPA
 24. THE FIRE LINE HAS A FIRE HYDRANT INSTALLED ON THE
 SAME LINE AS THE FIRE SPRINKLER SYSTEM. ALSO ON SHEET
 C1.0 A SIGNIFICANT AMOUNT OF PIPE IS SHOWN FOR THE FDC.
 IT IS NOT NECESSARY TO INSTALL THIS AMOUNT OF PIPE. THE
 FDC CAN BE INSTALLED NEARER THE BUILDING. ALSO PLEASE
 EXPLAIN THE 200 PSI ABOVE GROUND CHECK VALVE ON THE
 FIRE LINE ON C1.0. THIS ARRANGEMENT DOES NOT APPEAR TO
 BE NORMAL.
  
 11. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
 [email protected]

Review Stop L LANDSCAPING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status F Date 03-02-2011 Cont ID  
Sent By rkussner Date 03-02-2011 Time 13:34 Rev Time 0.00
Received By rkussner Date 03-02-2011 Time 13:34 Sent To  
Notes
2011-03-02 14:46:18***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE DEMONSTRATE HOW YOU ARRIVED AT THE 44,625
 SQUARE FEET OF OPEN SPACE. THIS PARCEL IS FENCED OFF
 FROM UP THE GROVE LANE TO BEYOND THE EXISTING RETENTION
 AREA ALONG THE NORTH PERIMETER OF THE SITE. THE
 ORIGINAL SUBMITTAL ENCOMPASSED THE ENTIRE PARCEL, AS IT
 SHOULD. THE NEW SUBMITTAL SPLITS THE SITE WITH A
 PORTION OF THE IMPROVEMENTS IN THE NORTHERN PORTION OF
 THE SITE WHICH IS BEYOND THE LIMIT OF WORK. OPEN SPACE
 IS DETERMINED BY TAKING THE TOTAL LOT AREA AND
 DEDUCTING THE FOOTPRINT OF THE STRUCTURE. THE
 DIFFERENCE IS THE OPEN SPACE. THE OPEN SPACE SHOULD BE
 CALCULATED BASED UPON THE ENTIRE FENCED AREA. THE
 REQUIRED TREES AND SHRUBS SHOULD BE BASED UPON THAT
 FIGURE.
  
 2. PURSUANT TO SECTION 94-443 (B) (1), FOR INDUSTRIAL
 USES AND USES IN INDUSTRIAL DISTRICTS, THE LANDSCAPE
 BUFFER STRIP SHALL BE AT LEAST TEN FEET SIDE ALONG THE
 EDGE OF PROPERTY WHEN ADJACENT TO A PUBLIC THOROUGHFARE
 AND OTHER NONRESIDENTIAL ZONING DISTRICTS. FOR ALL
 OTHER NONRESIDENTIAL USES, THE BUFFER STRIP SHALL BE AT
 LEAST FIVE FEET SIDE ALONG THE ENTIRE EDGE OF PROPERTY
 WHEN ADJACENT TO A PUBLIC THOROUGHFARE, AND WHEN
 ADJACENT TO NONRESIDENTIAL ZONING DISTRICTS. A FIVE
 FOOT BUFFER IS REQUIRED ALONG THE FULL LENGTH OF THE
 PARCEL ON THE EAST AND WEST SIDE AND ALONG THE NORTH
 PERIMETER.
  
 3. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER STRIP FOR EACH 30 LINEAR FEET OR PORTION ,
 THEREOF. THIS APPLIES TO THE EAST, WEST AND NORTH SIDES
 OF THE SITE.
  
 4. BASED UPON AN AGREEMENT MADE BETWEEN THE APPLICANT
 AND THE REVIEWER, THE ORIGINAL APPROVED LANDSCAPE PLAN
 HAD THE FOLLOWING NOTE THAT DOES NOT APPEAR ON THIS
 MOST RECENT PLAN: "A SIMPSON STOPPER HEDGE (MYRCIANTHES
 FRAGRANS) WILL BE PROVIDED ALONG MILITARY IN LIEU OF
 CONTINUOUS HEDGE ALONG WEST PERIMETER. PLANS WILL BE
 PROVIDED WHEN THE SURVEY IS AVAILABLE".
  
 5. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPE OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED. THIS SHALL ALSO APPLY TO THE NORTH
 HALF OF THE PARCEL. THE EXISTING ASPHALT PAVING WHICH
 SERVES NO PURPOSE SHALL BE REMOVED AND THAT AREA SHALL
 BE SODDED, AS WELL.
  
 6. A NOTE ON THE PLAN INDICATES THAT ALL LANDSCAPE
 AREAS SHALL BE PROVIDED WITH A FULLY AUTOMATIC
 IRRIGATION SYSTEM. THE NORTH PORTION OF THE SITE SHALL
 BE FULLY IRRIGATED.
  
 7. PURSUANT TO SECTION 94-444 (B), OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES AND OTHER
 MECHANICAL EQUIPMENT SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING HAS BEEN PROVIDED. THERE APPEARS
 TO BE GROUND LEVEL AIR CONDITIONING UNITS AND A
 TRANSFORMER ON THE NORTH SIDE OF THE PROPOSED BUILDING.
 THESE ITEMS SHALL BE SCREENED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 01-14-2011 Cont ID  
Sent By rkussner Date 01-14-2011 Time 16:45 Rev Time 0.00
Received By rkussner Date 01-14-2011 Time 16:45 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-08-2010 Cont ID  
Sent By rkussner Date 12-08-2010 Time 11:30 Rev Time 0.00
Received By rkussner Date 12-08-2010 Time 11:30 Sent To  
Notes
2010-12-08 12:11:46***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-443 (C) (3) (A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH AND NOT
 LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL. THE
 LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE. THIS COMMENT APPLIES TOT THE SOUTH END
 OF THE HANDICAP PARKING ROW ON THE EAST SIDE OF THE
 BUILDING.
  
 2. THE FENCE ADJACENT TO UP THE GROVE LANE SHALL , AT A
 MINIMUM, BE INSTALLED ALONG THE INTERIOR PERIMETER OF
 THE LANDSCAPE SETBACK WITH THE HEDGE TO BE PLANTED ON
 THE STREET SIDE OF THE FENCE. T
  
 3. THERE ARE SOME CONFLICTS BETWEEN PROPOSED STREET
 LIGHTS AND TREES. THERE IS ALSO A CONFLICT BETWEEN A
 PROPOSED TREE AND THE FIRE AND WATER LINES TOWARD THE
 SOUTHWEST CORNER OF THE SITE. THE TREES ADJACENT TO UP
 THE GROVE LANE SHALL BE EQUALLY SPACED.
  
 4. PURSUANT TO SECTION 94-443 (B) (1), FOR INDUSTRIAL
 USES AND USES IN INDUSTRIAL DISTRICTS, THE BUFFER STRIP
 SHALL BE AT LEAST TEN FEET WIDE ALONG THE EDGE OF
 PROPERTY WHEN ADJACENT TO A PUBLIC THOROUGHFARE AND AT
 LEAST FIVE FEET WIDE ALONG THE EDGE OF PROPERTY WHEN
 ADJACENT TO NONRESIDENTIAL ZONING DISTRICTS. PURSUANT
 TO SECTION 94-443 (B) (4), AT LEAST ONE SHADE OR
 FLOWERING TREE SHALL BE PLANTED IN A REQUIRED STRIP FOR
 EACH 30 LINEAR FEET OR FRACTION THEREOF. HEDGES SHALL
 BE PLANTED AT TWO-FOOT INTERVALS FOR EACH LANDSCAPE
 BUFFER. THESE REQUIREMENTS HAVE NOT BEEN MET ALONG THE
 EAST OR WEST SIDES OF THIS TRACT OR PARCEL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2010-12-07 13:49:37ONLY SEEING 4 LIGHT POLES?
 CCTV OR ALARM SYSTEM?
 GATE ACCESS FOR PD?
 DOORS/LOCKS?
  
 A. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 B. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO BUILDINGS FOR DUSK TO DAWN
 OPERATION SHALL BE PROVIDED.
 C. ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING
 D. BUILDING LIGHTING (NON-GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDE.
  DOORS
 E. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL
 EXTERIOR DOORS WITH A MINIMUM (1) INCH THROW OR
 MECHANICAL INTERLOCK.
 F GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 G. REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE
 PEEPHOLE/ SECURITY VIEWER.
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-07-2010 Cont ID  
Sent By vnoel Date 12-07-2010 Time 06:47 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2010-12-07 06:47:39WHEN CONSTRUCTION DOCUMENTS ARE SUBMITTED FOR
 PERMITTING , THE APPLICANT SHOULD INCLUDE COPIES OF THE
 FOLLOWING :
 1) SFWMD ERP ( OR PERMIT MOD )
 2) DRAINAGE REPORT , CALCULATIONS & GEOTECHNICAL
 RESULTS
 3) ALL COMPLETE STORMWATER MANAGEMENT PLAN FOR USE
 DURING CONSTRUCTION
 4) APPLICATION SHOULD REVIEW FLOOD PLAIN MAPS AND
 CONDITIONS TO DETERMINE IF FINISHED FLOOR ELEVATION
 SHOULD BE INCREASED OR OTHERWISE

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-03-2010 Cont ID  
Sent By vnoel Date 12-03-2010 Time 08:00 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2010-12-03 08:00:251. PER CITY CODE, THE VERTICAL DATUM IS TO BE NGVD-29.
 2. EASEMENT MAY BE REQUIRED DEPENDING ON FINAL METER
 LOCATION.
 3. SHOW EXISTING CB SOUTH OF COVERED WORK AREA.
 4. UNITY OF TITLE MAY ALSO BE REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 12-06-2010 Time   Rev Time 0.00
Received By bcollins Date 12-06-2010 Time 08:51 Sent To  
Notes
2010-12-06 08:51:04NO COMMENTS

Review Stop Z ZONING
Rev No 2 Status P Date 03-21-2011 Cont ID  
Sent By ajones Date 03-21-2011 Time 14:29 Rev Time 0.00
Received By ajones Date 03-21-2011 Time 14:29 Sent To  
Notes
2011-03-21 14:32:50PASSED WITH THE PROVISO THAT WHEN THE BUILDING PERMIT
 IS SUBMITTED THE BICYCLE RACKS MUST BE CHANGED TO A
 TYPE ON THE CITY'S APPROVED LIST.

Review Stop Z ZONING
Rev No 1 Status F Date 12-06-2010 Cont ID  
Sent By ajones Date 12-06-2010 Time 10:30 Rev Time 0.00
Received By ajones Date 12-06-2010 Time 10:29 Sent To  
Notes
2010-12-06 11:02:40PLANNING AND ZONING:
  
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
  
  
 PLANS AND PLATS REVIEW COMMITTEE
 DECEMBER 8, 2010
 INFORMAL SITE PLAN REVIEW CASE NO. 10-03
 4215 UP THE GROVE LANE
 FPL GENERAL OFFICES COMMAND CENTER
  
 THE FOLLOWING ITEMS MUST BE PROVIDED PRIOR TO ZONING
 APPROVING THE ISPR:
  
 - A TRAFFIC CONCURRENCY LETTER FROM PALM BEACH COUNTY;
 AND
 - PUBLIC UTILITY LETTER (FPL, BELLSOUTH, COMCAST AND
 FLORIDA PUBLIC UTILITIES); AND
 - PROVIDE THE PLANNING DEPARTMENT WITH A RECORDED COPY
 OF THE UNITY OF TITLE.
  
 THE SITE PLAN SHALL BE REVISED AND RESUBMITTED
 ADDRESSING THE FOLLOWING COMMENTS:
  
 1. PROVIDE A DETAIL OF THE DUMPSTER ENCLOSURE. ALL
 DUMPSTER ENCLOSURES MUST COMPLY WITH SECTION 94-444 (B)
 AND FIGURE XIV-3 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 2. PROVIDE A DETAIL OF THE SCREENING FOR THE GENERATOR.
 3. PROVIDE A PARKING STALL DETAIL. ALL PARKING STALL
 MUST COMPLY FIGURE XV-2 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 4. REVISED PLANS TO PROVIDE ONE (1) BICYCLE PARKING
 SPACE.
  
 GENERAL COMMENTS
  
 1. IS THERE ANY PROPOSED SIGNAGE?
 2. THE TWO (2) LIVE OAK TREES LOCATED IN THE WEST
 LANDSCAPE PARKING ISLANDS MAY CONFLICT WITH THE
 PROPOSED LOCATION OF THE LIGHT POLES.
 3. PROVIDE RESPONSES TO REVIEW COMMENTS IN A WRITTEN
 FORMAT. PLEASE NOTE, IF THE PLANNING AND ZONING
 DEPARTMENT HAS NOT RECEIVED A RESPONSE TO THE PPRC
 COMMENTS WITHIN SIXTY (60) DAYS FROM THE PPRC MEETING,
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE RE-SUBMITTAL OF A NEW DEVELOPMENT
 APPLICATION.
  