Plan Review Details - Project Z10090014
Plan Review Stops For Project Z10090014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By bmoree Date   Time   Rev Time 0.00
Received By bmoree Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 10-13-2010 Cont ID  
Sent By lmartine Date 10-13-2010 Time 08:59 Rev Time 0.00
Received By lmartine Date 10-13-2010 Time 08:59 Sent To  
Notes
2010-10-13 09:23:14BUILDING REVIEW COMMENTS
  
  
 SHEET A-1.1 CALLS OUT TWO DIFFERENT CONSTRUCTION TYPES
 AND BOTH ARE INCORRECT ACCORDING TO TABLE 503, 2007
 FBC.
  
 PLEASE INDICATE WHETHER THE DESIGN IS FOR 1 COMPLETE
 BUILDING OR 2 BUILDINGS SEPARATED BY A 4 HOUR FIRE
 WALL.
  
 PALM BEACH COUNTY IMPACT FEES WILL BE REQUIRED.
  
  
  
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 10-29-2010 Cont ID  
Sent By bmoree Date 10-29-2010 Time 14:50 Rev Time 0.00
Received By bmoree Date 10-29-2010 Time 14:50 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date   Cont ID  
Sent By   Date 10-12-2010 Time   Rev Time 0.00
Received By bmoree Date 10-12-2010 Time 10:06 Sent To  
Notes
2010-10-12 10:05:141. (SHEET C1) FINISHED FLOOR ELEVATION (FFE) IS LOWER
 THAN NEARBY EXISTING SEWER MANHOLE. FFE SHOULD BE A
 MINIMUM 12??? ABOVE ADJACENT ROADWAY / PARKING AREA
 ELEVATION.
 2. (SHEET A1.2) HANDICAPPED RAMPS AND ACCESS ROUTES
 SHALL HAVE DETECTABLE WARNING THAT COMPLIES WITH FBC
 11-4.29. PREFABRICATED ANSI A117.1-1986 TRUNCATED DOMES
 ARE PREFERRED.
 3. (SHEET LA-2) LANDSCAPE MATERIAL PLANTING LOCATION
 CONFLICTS WITH EXISTING BACKFLOW PREVENTER.
 4. (SHEET LA-2) PROPOSED DUMPSTER LOCATION CONFLICTS
 WITH EXISTING SEWER MANHOLE.
 5. PRIVATE FIRE LINE / FDC IN SOUTHEAST CORNER OF
 PROPERTY IS IN CONFLICT WITH PROPOSED DRIVEWAY
 ENTRANCE. ONE OF THE TWO ELEMENTS WILL NEED TO BE
 RELOCATED.
 6. UNITY OF TITLE APPLICATION REQUIRED. ( BUILDING
 CONNECTION AND SHARED INFRASTRUCTURE.)
 7. PERVIOUS AND IMPERVIOUS CALCULATIONS REQUIRED.
 8. WATER/ SEWER / FIRE SYSTEM DESIGN CALCULATIONS
 REQUIRED.
 9. SHOW ALL FDC AND HYDRANT LOCATIONS.
  
 BRIAN R. MOREE
 ENGINEERING SERVICES DEPARTMENT
 561-644-7270
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 09-30-2010 Cont ID  
Sent By mcarsill Date 09-30-2010 Time 09:05 Rev Time 0.00
Received By mcarsill Date 09-30-2010 Time 08:41 Sent To  
Notes
2010-09-30 09:05:06PLANNING BOARD CASE NO. 1603 (Z10090014)
 2101 PALM BEACH LAKES BOULEVARD
  
 1. NEW BUILDING SHALL MEET THE REQUIREMENTS FOR A CLASS
 A MERCANTILE OCCUPANCY.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS.
  
 3. WHAT FIRE RATING DOES THE DOORS HAVE LOCATED WITHIN
 THE 4 HOUR FIRE WALL.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. PROPER EXITS ARE TO BE PROVIDED FROM THIS CLASS A
 MERCANTILE OCCUPANCY.
  
 6. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD
 PARTY CERTIFICATED APPROVED MONITORING COMPANY FOR
 CENTRAL STATION SERVICE.
  
 7. KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.
  
 8. THE FIRE DEPARTMENT CONNECTION SHALL BE LOCATED NO
 FATHER THAN 150 FEET FROM A FIRE HYDRANT.
  
 9. BUILDING ADDRESS IS REQUIRED. THE MINIMUM HEIGHT OF
 THESE NUMBERS ARE TO BE 6" AND AT LEAST 1" WIDE.
  
 10. SINCE THIS BUILDING IS SEPARATE FROM THE OTHER ONE,
 SEPARATE UTILITIES AND INFRASTRUCTURE IS EXPECTED.
  
 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 13. PLEASE ILLUSTRATE THE LOCATIONS OF ALL EMERGENCY
 LIGHTS AND EXIT SIGNS.
  
 14. PLEASE ILLUSTRATE THE LOCATIONS OF ALL PORTABLE
 FIRE EXTINGUISHERS.
  
 15. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 16. PLEASE ILLUSTRATE ON THE PLANS THE 60" AISLE THAT
 IS REQUIRED TO REACH AN EXIT.
  
 17. PLEASE SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, PLUMBING, FIRE SPRINKLER AND FIRE ALARM
 PLANS TO THE CONSTRUCTION SERVICES DEPARTMENT.
  
 18. PLEASE SUBMIT A LIFE SAFETY PLAN.
  
 19. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING,
 AND AFTER CONSTRUCTION.
  
 20. KNOX-BOX MATERIALS CAN BE ORDERED AT
 WWW.KNOX-BOX.COM.
  
 21. AN EMERGENCY PLAN AND STAFF TRAINING FOR EMERGENCY
 EGRESS AND THE USE OF PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 22. FIRE DRILLS ARE REQUIRED IN CLASS A AND B
 MERCANTILE OCCUPANCIES.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop L LANDSCAPING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 10-26-2010 Cont ID  
Sent By rkussner Date 10-26-2010 Time 10:38 Rev Time 0.00
Received By rkussner Date 10-26-2010 Time 10:38 Sent To  
Notes
2010-10-26 11:13:18***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1 REPEAT COMMENT: FIVE POINTS WERE TAKEN ON THE
 XERISCAPE DESIGN OPTIONS FOR THE USE OF A MOISTURE
 SENSING CONTROLLER OTHER THAN A RAIN SWITCH BUT A RAIN
 SWITCH WAS PROPOSED. PLEASE CLARIFY BY INDICATING THE
 TYPE OF EQUIPMENT TO BE USED. YOU CANNOT TAKE CREDIT
 FOR A RAIN SWITCH.
  
 2. REPEAT COMMENT: PURSUANT TO SECTION 94-443 (B) (4),
 AT LEAST ONE SHADE OR FLOWERING TREE SHALL BE PLANTED
 IN THE REQUIRED LANDSCAPE STRIP FOR EACH 30 LINEAR FEET
 OR PORTION THEREOF. THIS LANDSCAPE STRIP IS REQUIRED TO
 BUFFER NONRESIDENTIAL USES ADJACENT TO A PUBLIC
 THOROUGHFARE AND NONRESIDENTIAL ZONING DISTRICT AND
 APPLIES TO THE NORTH, SOUTH AND EAST PERIMETER OF THE
 SITE. NO TREES ARE SHOWN ALONG THE SOUTHWEST SIDE OF
 THE SITE, ADJACENT TO THE PARKING LOT. THE EXISTING
 HEDGE SHOULD BE MAINTAINED AT A HEIGHT NOT EXCEEDING
 SIX (6) FEET. IF BETWEEN FOUR (4) AND EIGHT (8)
 EXISTING SHRUBS WERE REMOVED, THERE WOULD BE ROOM TO
 PLANT THE TREES AT THE CORRECT SPACING.
  
 3. REPEAT COMMENT: PURSUANT TO SECTION 94-443 (C) (3)
 (A), EACH ROW OF PARKING SPACES SHALL BE TERMINATED BY
 LANDSCAPED ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH
 AND NOT LESS THAN THE LENGTH OF THE ADJACENT PARKING
 STALL. THE LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE
 SHADE OR FLOWERING TREE. THERE ARE TWO (2) MISSING
 TERMINAL LANDSCAPE ISLANDS ON THE NORTHWEST SIDE OF THE
 BUILDING (REAR).
  
 4. REPEAT COMMENT: THERE ARE AT LEAST TWO (2) CONFLICTS
 BETWEEN PROPOSED STREET LIGHTS AND TREES.
  
 5. REPEAT COMMENT: PLEASE SUBMIT TWO (2) REVISED SETS
 OF SIGNED AND SEALED PLANS FOR THE TREE ALTERATION
 PERMIT, ONCE THE LANDSCAPE PLANS HAVE BEEN APPROVED.
 PLEASE PROVIDE THE TREE MITIGATION DETAILS. SHOW THE
 CALIPER INCHES OF TREES BEING REMOVED AND THE CALIPER
 INCHES OF TREES THAT WILL BE INSTALLED WITH THE NEW
 LANDSCAPING. IF THERE IS A SHORTAGE, ADDITIONAL TREES
 WILL NEED TO BE PLANTED ON SITE OR ELSEWHERE WITHIN THE
 CITY LIMITS.
  
 6. PLEASE IDENTIFY THE "EXISTING PLANT MATERIAL "
 LOCATED ALONG THE FRONT OF THE BUILDING.
  
 7. IF EXISTING TREE AND PLANT MATERIAL WILL REMAIN, IT
 MUST BE IN A HEALTHY CONDITION AND MEET ALL MINIMUM
 GRADE STANDARDS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 10-13-2010 Cont ID  
Sent By rkussner Date 10-13-2010 Time 10:15 Rev Time 0.00
Received By rkussner Date 10-13-2010 Time 10:14 Sent To  
Notes
2010-10-13 11:59:30***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FOERMAT.
  
 1. THE LANDSCAPE CALCULATIONS ARE INCORRECT. THE
 REQUIRED TREES AND SHRUBS ARE BASED UPON OPEN
 SPACE--NOT PERVIOUS LANDSCAPE AREA. OPEN SPACE IS
 DETERMINED BY TAKING THE TOTAL SQUARE FOOTAGE OF THE
 SITE AND DEDUCTING THE BUILDING FOOTPRINT. OPEN SPACE
 IS THE DIFFERENCE. THERE IS A DEFICIENCY IN THE NUMBER
 OF TREES AND SHRUBS REQUIRED. PLEASE REVISE THE
 CALCULATIONS AND MODIFY THE PLAN TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENTS.
  
 2. .PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE
 ITEMS ENUMERATED IN THIS SECTION ARE REQUIRED TO BE
 PART OF THE LANDSCAPE PLAN, WHICH WILL INCLUDE THE
 LOCATION OF ALL EASEMENTS AND UTILITIES TO BE SHOWN ON
 THE PLAN. ALL EXISTING SHRUBS AND TREES SHALL BE
 IDENTIFIED.
  
 3. FIVE POINTS WERE TAKEN ON THE XERISCAPE DESIGN
 OPTIONS FOR THE USE OF A MOISTURE SENSING CONTROLLER
 OTHER THAN A RAIN SWITCH, BUT A RAIN SWITCH WAS
 PROPOSED. PLEASE CLARIFY BY INDICATING THE TYPE OF
 EQUIPMENT TO BE USED.
  
 4. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR
 SIDEWALK-SURFACES AND REQUIRED BUFFER STRIPS AND
 LANDSCAPED OPEN SPACE AREAS SHALL BE PLANTED WITH
 GRASS. GRASS AREAS SHALL BE SODDED. PLEASE SHOW SOD IN
 THE RIGHTS-OF-WAY.
  
 5. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL
 AREAS TO BE PLANTED IN A CULTIVATED LANDSCAPE,
 IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE. THIS INCLUDES ALL RIGHTS-OF-WAY.
 ALSO, A NOTE ON THE LANDSCAPE PLAN INDICATES THAT 100%
 COVERAGE WILL BE PROVIDED.
  
 6. PURSUANT TO SECTION 94-442 (C), PALM TREES MAY BE
 SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE
 OR FLOWERING TREES REQUIRED BY THIS ARTICLE. WHEN PALM
 TREES ARE SUBSTITUTED FOR SHADE TREES, TWO PALM TREES
 SHALL BE PROVIDED FOR EACH REQUIRED SHADE TREE. THIS
 2:1 SUBSTITUTION SHALL NOT BE REQUIRED FOR ROYAL PALMS
 BUT WILL BE REQUIRED FOR THE FOXTAIL PALMS. IN ANY
 CASE, THE
 35 PERCENT CANNOT BE EXCEEDED. PLEASE PROVIDE THE
 CALCULATIONS.
  
 7. THE PROPOSED HEDGE ALONG THE EAST PROPERTY LINE
 SHALL BE PLANTED ALONG THE INTERIOR PERIMETER OF THE
 LANDSCAPE BUFFER WITH SOD OR PREFERABLY GROUND COVER
 BETWEEN THE HEDGE AND SIDEWALK. THE HEDGES ALONG THE
 NORTH AND SOUTH SIDES OF THE SITE SHALL BE PLANTED 18
 INCHES IN FROM THE PROPERTY LINE.
  
 8. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN THE
 REQUIRED LANDSCAPE STRIP FOR EACH 30 LINEAR FEET OR
 PORTION THEREOF. THIS LANDSCAPE STRIP IS REQUIRED TO
 BUFFER NONRESIDENTIAL USES ADJACENT TO A PUBLIC
 THOROUGHFARE AND NONRESIDENTIAL ZONING DISTRICT AND
 APPLIES TO THE NORTH, SOUTH AND EAST PERIMETER OF THE
 SITE. THE SPACING BETWEEN TREES EXCEEDS THIRTY (30)
 FEET ALONG THE EAST SIDE AND NO TREES ARE SHOWN ALONG
 THE SOUTH SIDE OF THE SITE.
  
 9. PURSUANT TO SECTION 94-443 (C) (3) (A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH AND NOT
 LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL. THE
 LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE. THERE IS AT LEAST ONE (1) MISSING
 ISLAND ON THE EAST SIDE OF THE BUILDING AND TWO (2) ON
 THE WEST SIDE.
  
 10. THERE ARE SOME CONFLICTS BETWEEN PROPOSED STREET
 LIGHTS AND TREES.
  
 11. STAFF RECOMMENDS THAT IN ALL AREAS WHERE PARKING
 ROWS ARE ADJACENT TO LANDSCAPE AREAS, CURBING BE USED
 INSTEAD OF CAR STOPS. PARKED VEHICLES SHALL NOT EXTEND
 INTO A LANDSCAPED AREA THAT IS FIVE OR LESS FEET WIDE
 UNLESS TWO ADDITIONAL FEET ARE ADDED TO THE BUFFER. THE
 TWO ADDITIONAL FEET OF LANDSCAPING SHALL CONTAIN NO
 PLANT, IRRIGATION DEVICE, OR OTHER OBJECT HIGHER THAN
 SIX INCHES ABOVE THE TOP OF THE CURB. IN ADDITION, THE
 PROPOSED 26 FOOT DRIVE AISLE ON THE EAST SIDE OF THE
 BUILDING COULD BE REDUCED TO 24 FEET WITH THE
 ADDITIONAL AREA CONVERTED INTO GREEN SPACE. THIS WILL
 CONVERT PAVED AREA INTO GREEN SPACE AND ALLOW THE TREES
 MORE ROOM FOR THEIR ROOT SYSTEM FO DEVELOP.
  
 12. PLEASE SUBMIT A TREE ALTERATION PERMIT APPLICATION
 WITH SETS OF SIGNED AND SEALED PLANS TO THE PLANNING
 AND ZONING DEPARTMENT.
  
 13. PLEASE PROVIDE SOD AND IRRIGATION ON THE OUTPARCEL
 SITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop PARK PARKING
Rev No 1 Status P Date 10-09-2010 Cont ID  
Sent By ssamuels Date 10-09-2010 Time 18:11 Rev Time 0.00
Received By ssamuels Date 10-09-2010 Time 18:11 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date 10-11-2010 Cont ID  
Sent By kcarsill Date 10-12-2010 Time   Rev Time 0.00
Received By   Date 10-12-2010 Time   Sent To  
Notes
2010-10-13 07:18:37CONDITIONS FOR APPROVAL
 PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY OF WEST
 PALM BEACH POLICE DEPARTMENT CPTED OFFICIAL. OFC.
 CARSILLO 822-1620, [email protected]
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST ???NO TRESPASSING??? SIGNS
 EVERY 500 FEET AROUND THE PERIMETER OF THE SITE.
 LIGHTING
 A. PARKING LOT AND PEDESTRIAN LIGHTING SHALL BE:
 A) HIGH EFFICACY OF GREATER THAN 70 LUMENS PER WATT
 B) A KELVIN TEMPERATURE OF 3,500 K OR GREATER THAN
 KELVIN TEMPERATURE
 C) COLOR RENDERING INDEX (CRI) OF 70 OR GREATER
 D) LAMP LIFE OF 20 THOUSAND HOURS OR GREATER.
 B. LIGHT POLES 10 ??? 15 FOOT HIGH FOR PEDESTRIAN-SCALE
 LIGHTING SHALL BE USED FOR ALL PEDESTRIAN WALKWAYS.
 C. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 D. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 E. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO BUILDINGS FOR DUSK TO DAWN
 OPERATION SHALL BE PROVIDED.
 F. ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING
 G. BUILDING LIGHTING (NON-GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDE.
  DOORS
 A. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM (1) INCH
 THROW OR MECHANICAL INTERLOCK.
 B. GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE PEEPHOLE/
 SECURITY VIEWER
  
 BOTH BUILDINGS SHALL BE PRE-WIRED FOR CLOSED-CIRCUIT
 TELEVISION (CCTV) AND ALARM SYSTEMS. VIDEO SURVEILLANCE
 EQUIPMENT AND CCTV TO DETER ROBBERIES/THEFT SHALL BE
 INSTALLED, THEREBY INCREASING THE RISK OF
 IDENTIFICATION. CCTV SHOULD BE INSTALLED TO OBSERVE AND
 RECORD ACTIVITIES AND TRANSACTIONS, FRONT, REAR AND
 SIDE DOOR, REAR OF THE BUILDING AND ALLEY.
 BIKE RACKS SHOULD BE AT THE FRONT OF THE BUILDING OR
 COMPLEX, NOT IN THE PARKING LOT FOR EASY SURVEILLANCE
 AND SAFETY.
  
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 10-13-2010 Cont ID  
Sent By vnoel Date 10-13-2010 Time 12:45 Rev Time 0.00
Received By vnoel Date 10-13-2010 Time   Sent To  
Notes
2010-10-13 12:48:34WHEN CONSTRUCTION DOCUMENTS ARE SUBMITTED FOR
 PERMITTING, THE APPLICANT SHOULD INCLUDE COPIES OF THE
 FOLLOWING:
  
 1) SFWMD ERP ( OR MOD )
 2) DRAINAGE REPORT, CALCULATIONS & GEOTECHNICAL
 RESULTS.
 3) ALL COMPLETE STORMWATER MANAGEMENT PLAN FOR USE
 DURING CONSTRUCTION.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2010-11-01 07:11:181) APPLICANT STATES THAT AMENDMENT TO PROTECTIVE
 COVENANT HAS BEEN RELEASED, BUT IS NOT MENTIONED IN
 EITHER OF THE OFFICIAL RECORD BOOKS STATED. HAS BEEN
 SENT TO LAW FOR THEIR REVIEW.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 09-29-2010 Cont ID  
Sent By vnoel Date 09-29-2010 Time 11:11 Rev Time 0.00
Received By VNOEL Date 10-13-2010 Time 12:40 Sent To  
Notes
2010-09-29 10:47:181. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING SERVICES.
 2. PROTECTIVE COVENANT IN ORB 2979, PG 1493 WILL NEED
 TO BE RELEASED.
 3. THE FUTURE DUMPSTER ENCLOSURE WILL NEED TO BE
 APPROVED BY SANITATION AS IT DOES NOT APPEAR TO BE
 READILY ACCESSIBLE.
 4. PROVIDE SCHEMATIC WATER & SEWER PLANS FOR ANY
 POTENTIAL CONFLICT WITH FUTURE BUILDING PAD.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 10-25-2010 Cont ID  
Sent By jroach Date 10-25-2010 Time 15:03 Rev Time 0.00
Received By jroach Date 10-25-2010 Time 15:03 Sent To  
Notes
2010-10-25 15:04:13PER DISCUSSION ON OCTOBER 25, 2010, NO COMMENTS ON
 RESUBMITTED PLANS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 10-13-2010 Cont ID  
Sent By   Date 10-13-2010 Time   Rev Time 0.00
Received By bcollins Date 10-13-2010 Time 12:39 Sent To  
Notes
2010-10-13 12:39:42NO COMMENTS

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 10-13-2010 Cont ID  
Sent By jroach Date 10-13-2010 Time 14:40 Rev Time 0.00
Received By jroach Date 10-13-2010 Time 14:40 Sent To  
Notes
2010-10-13 14:40:59ZONING PLANS AND PLATS REVIEW COMMITTEE (PPRC) REVIEW
  
 DATE OF REVIEW: 10/12/2010
 CASE NO.: PLANNING BOARD CASE NO. 1603
 ADDRESS: 2101 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: JAMES BRINDELL AND JOSH LONG,
 GUNSTER
 TELEPHONE NO.: 561.650.0511
 SCOPE OF APPLICATION: CONSTRUCTION OF A 35,000 SQUARE
 FOOT ADDITION AND A 4,500 SQUARE FOOT OUTPARCEL TO AN
 EXISTING FURNITURE STORE.
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE UPDATED LETTERS FROM THE FOLLOWING
 PUBLIC UTILITY COMPANIES:
  
 A. FLORIDA POWER & LIGHT (FPL) ??? LETTER INDICATES
 THAT THEY HAVE SUFFICIENT CAPACITY, BUT DOES NOT
 INDICATE WHETHER OR NOT THE PROPOSED PROJECT ENCROACHES
 INTO ANY OF THEIR SERVICES.
  
 B. AT&T ??? LETTER INDICATES THAT THEY HAVE SUFFICIENT
 AVAILABILITY AND THAT THE PROJECT IS LOCATED IN AN AREA
 SERVED BY AT&T; IT DOES NOT INDICATE WHETHER OR NOT THE
 PROPOSED PROJECT ENCROACHES INTO ANY OF THEIR SERVICES.
  
 C. FLORIDA PUBLIC UTILITIES ??? LETTER INDICATES THAT
 GAS SERVICE IS AVAILABLE AND LOCATED ON THE PROPERTY,
 BUT REQUESTS FURTHER INFORMATION AS TO WHETHER THESE
 SERVICES WILL BE DEACTIVATED OR RELOCATED AS PART OF
 THE PROPOSED DEVELOPMENT.
  
 2. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT, A
 UNITY OF TITLE WILL BE REQUIRED TO BE RECORDED IN THE
 PUBLIC RECORDS OF PALM BEACH COUNTY.
  
 3. PLEASE PROVIDE ONE (1) COPY OF THE TITLE POLICY FOR
 EACH OF THE PROPERTIES.
  
 4. THE SITE DATA TABLE SHALL INDICATE THE AMOUNT OF
 OPEN SPACE (OPEN SPACE = LOT AREA ??? BUILDING
 COVERAGE).
  
 5. THE CALCULATIONS SHOWN ON THE LANDSCAPE PLAN ARE
 INCORRECT. THE SITE PLAN INDICATES 228,000 SQUARE FEET
 OF LANDSCAPE AREA, WHILE THE LANDSCAPE PLAN INDICATES
 288,000 SQUARE FEET. PLEASE ADJUST THE LANDSCAPE PLAN
 ACCORDINGLY. ADDITIONALLY, PER SECTION 94-442 OF THE
 ZLDRS, THE AMOUNT OF LANDSCAPE MATERIAL (I.E. SHADE
 TREES, SHRUBS, ETC.) SHALL BE BASED UPON OPEN SPACE,
 NOT LANDSCAPE AREA. ALL CALCULATIONS WILL NEED TO BE
 ADJUSTED ACCORDINGLY.
  
 6. THE SITE DATA TABLE SHALL INDICATE THE AMOUNT OF
 IMPERVIOUS SURFACE (IMPERVIOUS SURFACE = LOT AREA ???
 BUILDING COVERAGE, SIDEWALKS, PARKING LOT, ETC.), WHICH
 SHALL NOT EXCEED 85%.
  
 7. THE SITE DATA TABLE INDICATES 130 PROPOSED PARKING
 SPACES ON THE CITY FURNITURE PROPERTY???ONLY 129 SPACES
 ARE SHOWN ON THE SITE PLAN. SIX (6) SPACES ARE
 INDICATED ON EITHER SIDE OF THE EXISTING PYLON SIGN,
 BUT ONLY FIVE (5) SPACES ARE PROVIDED. PLEASE ADJUST
 PLANS ACCORDINGLY.
  
 8. THE SITE DATA TABLE INDICATES 88 SPACES ON THE
 ASHLEY FURNITURE/RETAIL PROPERTY???ONLY 87 SPACES ARE
 PROVIDED. TEN (10) SPACES ARE INDICATED IN THE
 NORTHWEST PORTION OF THE PROPERTY (ALONG ALLEY), BUT
 ONLY NINE (9) SPACES ARE PROVIDED. PLEASE ADJUST PLANS
 ACCORDINGLY.
  
 9. THE SITE DATA TABLE AND SITE PLAN INDICATE THE CITY
 FURNITURE BUILDING AS BEING 70,000 SQUARE FEET, WHILE
 THE SURVEY INDICATES 71,577 SQUARE FEET. PLEASE CLARIFY
 AND ADJUST PLANS AND ALL CALCULATIONS ACCORDINGLY.
  
 10. THE SITE PLAN INDICATES FOUR (4) ON-STREET PARKING
 SPACES IN FRONT OF THE FUTURE BUILDING PAD???THE SURVEY
 ONLY INDICATES THREE (3) SPACES. PLEASE CLARIFY AND
 ADJUST PLANS ACCORDINGLY.
  
 11. THERE IS ONE (1) PARKING SPACE LOCATED IN THE
 EXTREME SOUTH CORNER OF THE CITY FURNITURE PROPERTY
 THAT DOES NOT MEET THE MINIMUM DIMENSIONAL REQUIREMENTS
 FOR A REGULAR PARKING SPACE???THIS SPACE WILL NEED TO
 BE LABELED AS A SMALL-CAR SPACE OR THE DIMENSIONS SHALL
 BE ADJUSTED ACCORDINGLY. IF THE SPACE IS TO REMAIN AS A
 SMALL-CAR SPACE, PLEASE INCLUDE THIS IN THE SITE DATA
 TABLE CALCULATIONS AND PROVIDE A DETAIL INDICATING HOW
 THIS WILL BE SIGNED/LABELED ON-SITE.
  
 12. THE PARKING SPACES ALONG THE ALLEY DO NOT MEET THE
 MINIMUM DIMENSIONS FOR A REGULAR SPACE. THESE SPACES
 SHALL BE IDENTIFIED AS SMALL-CAR SPACES. PLEASE NOTE
 SUCH ON THE PLANS, AND PROVIDE A DETAIL INDICATING HOW
 THESE SPACES WILL BE SIGNED/LABELED ON-SITE. THESE
 SPACES SHALL ALSO BE CALCULATED IN THE SITE DATA TABLE.
 PLEASE NOTE THAT PER SECTION 94-485(N)(1) OF THE ZLDRS,
 NOT MORE THAN 30% OF THE SPACES MAY BE DESIGNATED FOR
 SMALL-CAR USE.
  
 13. THERE IS ONE (1) PARKING SPACE ADJACENT TO THE
 FUTURE BUILDING PAD THAT DOES NOT SHOW A WHEEL STOP.
 PLEASE ADJUST PLANS ACCORDINGLY.
  
 14. THERE IS ONE (1) PARKING SPACE LOCATED TO THE RIGHT
 OF THE CITY FURNITURE BUILDING ENTRY THAT IS INDICATED
 AS BEING 12 FEET WIDE, BUT DOES NOT HAVE A HANDICAP
 ACCESSIBLE LOGO. THIS BUILDING IS REQUIRED TO HAVE FIVE
 (5) ACCESSIBLE SPACES, BUT ONLY FOUR (4) ARE LABELED.
 PLEASE LABEL THIS ADDITIONAL SPACE AS BEING AN
 ACCESSIBLE SPACE.
  
 15. PLEASE INDICATE WHAT WILL BE PROVIDED IN THE AREA
 OF THE FUTURE BUILDING PAD UNTIL SUCH TIME THAT THIS
 STRUCTURE IS BUILT (I.E. SOD, ETC.). PLEASE PROVIDE A
 PHASING PLAN FOR THE SITE PLAN AND LANDSCAPE PLANS
 INDICATING WHAT WILL BE INSTALLED WITH EACH PHASE OF
 THE PROJECT.
  
 16. PER SECTION 94-145(5)(B) OF THE CITY???S ZLDRS, THE
 MINIMUM LANDSCAPE AREA (PERVIOUS SURFACE) SHALL BE 15%.
 AS PER OUR DISCUSSION, THIS IS DUE TO THE EXISTING CITY
 FURNITURE PROPERTY. IT IS STAFF???S RECOMMENDATION THAT
 THE PROJECT BE REVIEWED AS A COMMERCIAL PLANNED
 DEVELOPMENT (CPD), AND THAT A WAIVER BE REQUESTED FOR
 THIS PROVISION.
  
 17. PLEASE PROVIDE THE PHOTOMETRIC LEVELS ALONG THE
 SOUTH PROPERTY LINE, ALONG THE ADJACENT PROPERTY. SUCH
 LEVELS SHALL NOT EXCEED 1.0 FOOTCANDLES.
  
 18. PLEASE PROVIDE A DETAIL INDICATING THE DESIGN AND
 SIZE OF THE PROPOSED MONUMENT SIGN. ALL SIGNS WILL BE
 GOVERNED BY THE GENERAL COMMERCIAL (GC) ZONING
 REGULATIONS.
  
 19. AT THE PROPOSED OUT-PARCEL, LANDSCAPE MATERIAL
 SHALL BE PROVIDED ON ALL SIDES OF THE DUMPSTER
 ENCLOSURE, WITH THE EXCEPTION OF GATE OPENINGS. PLEASE
 PROVIDE SHRUBS/HEDGES ON THE SOUTH SIDE OF THE
 ENCLOSURE AND LOADING SPACE. IT IS UNCLEAR AS TO THE
 PURPOSE OF THE CONCRETE WALK, AS THIS DOES NOT CONNECT
 TO ANY OTHER WALKWAY.
  
 20. PLEASE PROVIDE A DETAIL OF THE PROPOSED DUMPSTER
 ENCLOSURE ASSOCIATED WITH THE FUTURE OUT-PARCEL.
  
 21. A TERMINAL LANDSCAPE ISLAND IS REQUIRED AT THE
 SOUTH END OF THE PARKING ROW LOCATED IMMEDIATELY WEST
 OF THE OUT-PARCEL.
  
 22. PLEASE NOTE ON THE PLANS THAT THE EXISTING CURB
 OPENING WILL NEED TO BE CLOSED AS PART OF THE NEW CURB
 OPENING IN THE NORTHEAST CORNER OF THE PROPERTY.
  
 23. PLEASE REVISE THE BIKE RACK DETAIL TO BE IN
 CONFORMANCE WITH THE ATTACHED GUIDELINES.
  
 24. THERE SHALL BE A MINIMUM OF 12 BICYCLE PARKING
 SPACES, AND SUCH FACILITIES SHALL BE PROVIDED FOR EACH
 OF THE BUILDINGS/BUSINESSES (NO BIKE RACKS ARE SHOWN
 ADJACENT TO THE OUT-PARCEL).
  
 25. THE PARKING STRIPING DETAILS SHALL BE REVISED TO
 CONFORM TO THE ATTACHED REQUIREMENTS.
  
 A. PLEASE LABEL THE ONE DETAIL AS SMALL-CAR. BE SURE TO
 INDICATE HOW THESE SPACES WILL BE SIGNED/LABELED
 ON-SITE. YOU MAY ALSO WANT TO NOTE ???SEE SITE PLAN???
 REGARDING THE LENGTH OF THE SMALL-CAR PARKING STALL AS
 THIS VARIES.
  
 B. THE WHEEL STOP SHOULD BE 2 FEET AS MEASURED FROM THE
 BACK OF THE WHEEL STOP (ADJUST ON ALL PARKING DETAILS).
  
 C. NO DIMENSIONS ARE SHOW FOR THE SPACING BETWEEN THE
 DOUBLE-STRIPING (REFER TO SMALL-CAR AND REGULAR STALL
 DETAILS).
  
 D. THE DIMENSIONS BETWEEN THE DOUBLE-STRIPING AS SHOWN
 ON THE HANDICAPPED STALL DETAIL ARE INCORRECT; IT
 SHOULD BE 12 INCHES.
  
 E. NO DIMENSION IS SHOWN REGARDING THE PLACEMENT OF THE
 HANDICAP SYMBOL.
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  