Plan Review Details - Project Z10040024
Plan Review Stops For Project Z10040024
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 05-12-2010 Cont ID  
Sent By lmartine Date 05-12-2010 Time 09:44 Rev Time 0.00
Received By lmartine Date 05-12-2010 Time 09:44 Sent To  
Notes
2010-05-12 09:58:36PLEASE PROVIDE THE FOLLOWING INFORMATION WITH YOUR
 FORMAL BUILDING PERMIT APPLICATION.
  
  
 1)
 COMPLETE LIFE SAFETY PLAN.
  
 2)
 FBC 2007, TABLE 503 REGULATES CONSTRUCTION TYPE VS.
 ALLOWABLE SQUARE FOOT AREA PER FLOOR.
  
 3)
 FBC 2007, 11-4.3.1 REQUIRES AN ACCESSIBLE ROUTE WITHIN
 THE STRUCTURE AS WELL AS THE SITE.
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date 05-07-2010 Cont ID  
Sent By efabian Date 05-07-2010 Time 12:15 Rev Time 1.50
Received By efabian Date 05-07-2010 Time 12:15 Sent To  
Notes
2010-05-07 12:19:17DENIED
  
 ADDITIONAL DATA IS NEEDED BEFORE A PASSED STATUS CAN BE
 ACHIEVED AS NOTED BELOW:
  
 PRELIMINARY RECORDS THUS FAR REVIEWED INDICATE THAT THE
 POST FLOWS OR USAGE DEMANDS OF THE CRA'S NEW BUILDING
 ADDITION PROPOSED DESIGN ARE VERY SIMILAR IN BOTH SIZE
 AND SCOPE TO THAT OF THE PRE-EXISTING ABANDONED
 BUILDING'S SIZE AND FLOWS/USAGE DEMANDS. CONSEQUENTLY,
 THE PROPOSED CRA BUILDING ADDITION WOULD BE OF MINIMAL
 IMPACT TO CITY???S EXISTING UTILITIES INFRASTRUCTURE.
  
 WHAT CAN BE FURTHER EXPLORED IS THE LIKELIHOOD TO
 UTILIZE THE EXISTING WATER SERVICES TO THE PAL BUILDING
 AS ALSO ADEQUATE TO SERVE THE PROPOSED CRA ADDITION,
 WHICH IT WILL BECOME UNIFIED WITH. TO ASCERTAIN THE
 POSSIBILITY AND FEASIBILITY OF THIS APPROACH WILL
 REQUIRE SOME ADDITIONAL RESEARCH.
  
 BUILDING PLANS OF THE EXISTING PAL PROJECT SHALL BE
 RETRIEVED FOR REVIEW FROM RECORDS RETENTION. SINCE THE
 NEW 1450 SQ. FT. ADDITION WILL CONSIST OF A KITCHEN
 AREA, A GREASE TRAP INTERCEPTOR WILL PROBABLY HAVE TO
 BE INSTALLED. THIS TOO WILL HAVE TO BE ASCERTAINED.
  
 IF I MAY BE OF FURTHER ASSISTANCE:
  
 EMERY P. FABIAN
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-822-1200
 FAX: 561-494-1116
 MOBILE: 561-662-2269
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 04-28-2010 Cont ID  
Sent By mcarsill Date 04-28-2010 Time 16:01 Rev Time 0.00
Received By mcarsill Date 04-28-2010 Time 15:50 Sent To  
Notes
2010-04-28 16:00:54PAL EXTENSION
 922-7TH STREET
 FORMAL SITE PLAN REVIEW NO. 10-03 (Z10040024)
  
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. PLEASE DECLARE CONSTRUCTION TYPE FOR ADDITION.
  
 4. PLEASE DECLARE ON THE PLANS THE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 5. PLEASE ILLUSTRATE ALL ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTS.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 7. PLEASE INDICATE THE TYPES OF COOKING THAT IS PLANNED
 FOR THE BREAKROOM.
  
 8. PLEASE INDICATE ALL APPROPRIATE CODES FOR THE
 PROJECT.
  
 9. PLEASE SUBMIT COMPLETE STRUCTURAL, MECHANICAL,
 ELECTRICAL, AND PLUMBING PLANS FOR REVIEW.
  
 10. PLEASE SUBMIT A LIFE SAFETY PLAN FOR REVIEW.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-07-2010 Cont ID  
Sent By rkussner Date 05-07-2010 Time 16:39 Rev Time 0.00
Received By rkussner Date 05-07-2010 Time 16:39 Sent To  
Notes
2010-05-07 17:02:17***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE SUBMIT A LANDSCAPE PLAN SIGNED AND SEALED BY
 A REGISTERED LANDSCAPE ARCHITECT. THE LANDSCAPE PLAN
 SHALL INCLUDE ALL OF THE ITEMS ENUMERATED IN SECTION
 94-448 (D) (2).
  
 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 3. A TREE ALTERATION PERMIT WILL BE REQUIRED IF ANY
 EXISTING TREES WILL BE REMOVED. THE APPLICATION IS
 AVAILABLE AT THE FRONT DESK OF THE PLANNING AND ZONING
 DEPARTMENT.
  
 4. THE STRIPING AND CAR-STOP DETAILS WERE INCORRECT AND
 DO NOT MEET CITY STANDARDS. DOUBLE STRIPING IS
 REQUIRED---NOT SINGLE STRIPING. A COPY OF THE APPROVED
 DETAIL CAN BE OBTAINED AT THE FRONT DESK OF THE
 PLANNING AND ZONING DEPARTMENT.
  
 5. ADDITIONAL COMMENTS WILL BE FORTHCOMING AFTER WE
 RECEIVE A DETAILED LANDSCAPE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop PARK PARKING
Rev No 1 Status N Date 05-11-2010 Cont ID  
Sent By ssamuels Date 05-11-2010 Time 18:57 Rev Time 0.00
Received By ssamuels Date 05-11-2010 Time 18:57 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2010-05-11 13:33:02* LIGHTING FOR THE EXTERIOR OF THE BLDG, OR FOR THE
 PARKING AREA NOT SHOWN
 * WILL THE BLDG BE ALARMED, CCTV EQUIPPED?
 * WILL IMPACT RESISTANT GLASS BE USED ON WINDOWS?
 * WHAT ACCESS CONTROLS WILL BE USED TO ENTER THE
 BUILDING?
 * HOW WILL THE ENTRY ACESS FROM THE REAR PARKING AREA
 THAT LEADS TO THE PROPSED PLAY AREA BE CONTROLLED?
 * WHAT TYPE OF HARDWARE FOR THE DOORS WILL BE USED?
  
  
 COMMERCIAL SECURITY
 1.1 LIGHTING
 A. PARKING LOT AND PEDESTRIAN LIGHTING SHALL BE:
 A) HIGH EFFICACY OF GREATER THAN 70 LUMENS PER WATT
 B) A KELVIN TEMPERATURE OF 3,500 K OR GREATER THAN
 KELVIN TEMPERATURE
 C) COLOR RENDERING INDEX (CRI) OF 70 OR GREATER
 D) LAMP LIFE OF 20 THOUSAND HOURS OR GREATER.
 B. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 C. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 D. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO BUILDINGS FOR DUSK TO DAWN
 OPERATION SHALL BE PROVIDED.
 E. BUILDING LIGHTING (NON-GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDE.
 1.2 DOORS
 A. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM (1) INCH
 THROW OR MECHANICAL INTERLOCK.
 B. GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 C. REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE
 PEEPHOLE/ SECURITY VIEWER.
 1.3 DESIGN
 A. BUILDING ARCHITECTURE SHALL ALLOW FOR ENHANCED
 NATURAL SURVEILLANCE OF ALL PARKING LOTS AND PROVIDE A
 SENSE OF SECURITY TO PATRONS AND VISITORS.
 B. LANDSCAPING SHALL NOT OBSTRUCT VIEW FROM WINDOWS OR
 WALKWAYS.
 C. ALL BUILDINGS SHALL BE PRE-WIRED FOR CLOSED-CIRCUIT
 TELEVISION (CCTV) AND ALARM SYSTEMS.
 D. DUMPSTERS SHALL NOT ALLOW FOR EASY CONCEALMENT,
 CREATE BLIND SPOTS OR HIDING AREAS AND SHOULD BE ABLE
 TO BE LOCKED.
 E. SIGNS SHALL CLEARLY IDENTIFY PUBLIC ENTRANCES.
 F. LANDSCAPING SHALL BE MAINTAINED AT 3 FEET OR LESS.
 TREES SHALL BE INSTALLED SO AS NOT TO CONFLICT WITH THE
 LIGHTING SYSTEM. LOWER CANOPY LIMBS ON TREES SHALL BE
 MAINTAINED AT 8 FEET OR HIGHER
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2010-05-06 10:50:121. UNITY OF TITLE WILL BE REQUIRED.
 2. REAR "NON-ALLEY" ACCESS WILL NEED TO BE COMPLETED
 PRIOR TO FINAL APPROVAL.
 3. LEGAL DESCRIPTION AND SURVEY SHOULD BE FOR BOTH
 PROPERTIES.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bcollins Date 05-11-2010 Time 11:48 Sent To  
Notes
2010-05-11 11:47:59NO COMMENTS

Review Stop Z ZONING
Rev No 1 Status F Date 05-11-2010 Cont ID  
Sent By aaponte Date 05-11-2010 Time 08:24 Rev Time 0.00
Received By aaponte Date 05-11-2010 Time 08:24 Sent To  
Notes
2010-05-11 09:21:221. PLEASE PROVIDE A SURVEY OF THE ENTIRE PROPERTY
 (EXISTING PAL + ADDITIONAL SITE). PLEASE INCLUDE
 UNDERGROUNG AND ABOVE GROUND UTILITY INFORMATION ON
 SURVEY.
 2. A UNITY OF TITLE WILL BE REQUIRED.
 3. A TREE ALTERATION FORM WAS FILLED OUT WITH THE SITE
 PLAN SUBMITTAL, BUT NO LANDSCAPE DRAWINGS WERE
 PROVIDED. ALL TREES EXISTING ON SITE SHALL BE
 IDENTIFIED ALSO.
 4. THE NEW ADDITION REQUIRES 3 PARKING SPACES. PLEASE
 PROVIDE INFORMATION REGARDING EXISTING PARKING SPACES
 ON SITE TO DETERMINE HOW MANY SPACES SHALL BE REPLACED
 FOR THE EXISTING PAL BUILDING.
 5. COMMUNITY CENTERS HAVE SPECIAL SETBACK REQUIREMENTS.
 FRONT SETBACK IS 10 FEET FROM THE LOT LINE, PORCH MAY
 ENCROACH INTO FRONT SETBACK. SIDE SETBACK IS 10 FEET
 FROM LOT LINE.
 6. PLEASE INDICATE THE PROPERTY LINE ON ALL THE
 DRAWINGS.
 7. PLEASE PROVIDE INFORMATION REGARDING THE LEGAL RIGHT
 TO USE THE NEIGHBORING PROPERTY TO ACCESS PARKING AREA.
 8. 90 DEGREE ANGLE PARKING REQUIRES 24 FEET BACK UP
 AREA. SPACE PROVIDED IS ONLY 14' (10' OUTSIDE
 PROPERTY).
 9. PLEASE PROVIDE INFORMATION TO CONFIRM FACADES HAVE A
 MINIMUM OF 15% FENESTRATION AREA. 30% TRANSPARENCY IS
 REQUIRED.
 10. PARKING AREA SHALL BE SCREENED BY A 5 FOOT
 LANDSCAPE BUFFER. A HEDGE SHALL BE PLANTED AROUND THE
 PARKING AREA, AND SHADE TREES SHALL BE PROVIDED EVERY
 30 FEET. EACH ROW OF PARKING SHALL BE TERMINATED BY
 LANDSCAPE ISLAND NO LESS THAN 5 FEET IN WIDTH, AND
 CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE.
 11. A PROTECTIVE SCREEN WALL AND A LANDSCAPE BUFFER
 SHALL BE PROVIDED ADJACENT TO THE EAST PROPERTY LINE.
 12. PLEASE INDICATE LOCATION OF GARBAGE DISPOSAL AND
 PROPOSED SCREENING.
 13. PARKING DETAIL AND WHEEL STOP SHALL MATCH CITY'S
 STANDARD.
 14. EXTERIOR LIGHTING SHALL BE PROVIDED WITH A MINIMUM
 OF 0.6 FOOTCANDLES MEASURED AT THE BACK EDGE OF CURB
 ONE FOOT ABOVE GROUND.
 15. STREETSCAPE SHALL BE PROPOSED.
 16. PLEASE CONFIRM COMPLIANCE WITH HISTORIC
 PRESERVATION APPROVALS.