| 2010-01-07 16:04:46 | PLANNING BOARD CASE NO. 1223E |
| | COLUMBIA HOSPITAL - ABOVE GROUND FUEL TANK |
| | ZONING COMMENTS - 1/7/10 |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX |
| | (6) COPIES, ONE (1) REDUCED COPY (11 INCHES X 17 |
| | INCHES), AND AN ELECTRONIC COPY IN .PNG FORMAT OF ALL |
| | PLANS. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO |
| | ADDITIONAL COMMENTS. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING AND ZONING |
| | DEPARTMENT HAS NOT RECEIVED A RESPONSE TO THE PPRC |
| | COMMENTS WITHIN 60 DAYS FROM THE DATE OF THESE COMMENTS |
| | (3/7/10), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY |
| | FURTHER ACTION SHALL REQUIRE RESUBMITTAL OF A NEW |
| | DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED |
| | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE |
| | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE |
| | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. |
| | |
| | 1) STAFF VISITED THE SITE AND NOTED THAT THE PLANS |
| | SUBMITTED DO NOT MATCH ACTUAL SITE CONDITIONS: |
| | |
| | A. THERE IS AN EXISTING FIRE HYDRANT, STAND PIPE, AND |
| | TWO UNDERGROUND ACCESS COVERS THAT ARE NOT SHOWN WEST |
| | OF THE PROPOSED FUEL TANK ENCLOSURE. |
| | B. THE PARKING AREA SOUTH OF THE PROPOSED FUEL TANK |
| | ENCLOSURE HAS FIVE PARKING SPACES, NOT THREE AS SHOWN. |
| | C. THE TREE, INCLUDING SPECIES, IN THE TERMINAL ISLAND |
| | SOUTHWEST OF THE PROPOSED FUEL TANK ENCLOSURE IS NOT |
| | SHOWN. |
| | |
| | 2) DUE TO THE DISCREPANCIES IN THE SUBMITTED PLAN AND |
| | ACTUAL SITE CONDITIONS, A SURVEY OF THE AREA OF WORK IS |
| | REQUIRED. THE PLANS SHALL MATCH THE SURVEY. |
| | |
| | 3) THE FIRE HYDRANT REQUIRES A CLEAR AREA OF FOUR FEET |
| | TO THE REAR. ROUGH FIELD MEASUREMENTS INDICATE THAT THE |
| | HEDGE AND POSSIBLY THE ENCLOSURE WILL ENCROACH INTO THE |
| | CLEAR AREA. |
| | |
| | 4) THE PODOCARPUS HEDGE SHALL BE INSTALLED AT FOUR FEET |
| | IN HEIGHT AND TWO AND A HALF FEET ON CENTER. THE PLANS |
| | SHALL BE REVISED TO STATE THIS. |
| | |
| | 5) THE HEDGE SHALL BE SHOWN ON THE SITE PLAN. |
| | |
| | 6) THE SITE PLAN SHALL INDICATE WHERE THE GATE TO THE |
| | ENCLOSURE IS LOCATED. |
| | |
| | |
| | |
| | |