Plan Review Details - Project Z09080021
Plan Review Stops For Project Z09080021
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-09-2009 Cont ID  
Sent By lmartine Date 09-09-2009 Time 09:37 Rev Time 0.00
Received By lmartine Date 09-09-2009 Time 09:37 Sent To  
Notes
2009-09-09 09:41:13PRELIMINARY PLANS LOOK GOOD. NO COMMENTS.
  
  
  
 LUIS MARTINEZ
 561-805-6710
  
  
  
  
 .
  
  
  

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date 08-25-2009 Cont ID  
Sent By efabian Date 08-25-2009 Time 10:00 Rev Time 0.00
Received By jrenault Date 09-08-2009 Time 09:36 Sent To  
Notes
2009-08-25 10:00:01FAILED - NO CIVIL ENGINEERING PLANS HAVE YET BEEN
 SUBMITTED. HOWEVER, BOTH THE OWNER/DEVELOPER AND THE
 PROJECT MANAGER MET WITH OUR DEPARTMENT JUST LAST
 FRIDAY, 08-14-09, TO DISCUSS THE SANITARY CONNECTION
 THEY ARE CHALLENGED WITH: THE NEAREST CONNECTION IS
 OVER 300 FEET AWAY. THEIR ENGINEER IS DUE TO MEET WITH
 ME TOMORROW (08-26-09) TO FURTHER DISCUSS THEIR
 UTILTIES PLANS.
  
 08-26-09 PLANS WILL HAVE TO BE REDESIGNED DUE TO THE
 IMPACT TO THE SITE OF A PROPOSED LIFT STATION ADDITION
 AT THE N.W. CORNER OF THE PROPERTY, THE DUMPSTER
 ENCLOSURE IS UNDERSIZED AND MAY HAVE TO BE RECONFIGURED
 TO BE SERVICED OR ROLLED OUT TO A STAGING AREA IF AN
 ALTERNATIVE PLAN CAN NOT BE ACHIEVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 08-25-2009 Cont ID  
Sent By mcarsill Date 08-25-2009 Time 16:21 Rev Time 0.00
Received By mcarsill Date 08-25-2009 Time 16:12 Sent To  
Notes
2009-08-25 16:21:09FORMAL SITE PLAN REVIEW NO. 09-04
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE PLAN DOES NOT ILLUSTRATE ANY NEW OR EXISTING
 FIRE HYDRANTS.
  
 3. ONE WAY INGRESS/EGRESS PROVIDES FOR ONLY FOURTEEN
 FEET OF OPENING. POSSIBLE OVERHANGS NEAR CORNERS MAY
 OBTRUDE INTO THIS WIDTH.
  
 4. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE IS REQUIRED TO BE PLACED ON
 THE BUILDING.
  
 5. TENANT SEPARATION WALL REQUIRED BETWEEN MEDICAL
 SUITE AND MERCANTILE SUITE.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 7. WRONG FIRE CODE INFORMATION LISTED ON PAGE A-1.
  
 8. PLEASE REVIEW 1017.1 OF THE FLORIDA BUILDING CODE
 AGAIN.
  
 9. PLEASE PROVIDE MORE DETAILS ON GENERATOR, GENERATOR
 ROOM, AND FUEL SUPPLIES.
  
 10. PLEASE PROVIDE COMPLETE STRUCTURAL, MECHANICAL,
 ELECTRICAL, AND PLUMBING PLANS TO THE CONSTRUCTION
 SERVICES DEPARTMENT.
  
 11. PLEASE ILLUSTRATE ALL SAFETY EQUIPMENT TO INCLUDE
 ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS, AND PORTABLE
 FIRE EXTINGUISHERS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop L LANDSCAPING
Rev No 1 Status F Date 09-03-2009 Cont ID  
Sent By rkussner Date 09-03-2009 Time 15:05 Rev Time 0.00
Received By rkussner Date 09-03-2009 Time 15:05 Sent To  
Notes
2009-09-03 16:43:38***WALK-IN URGENT CARE LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-443 (B)(1), FOR ALL
 NONRESIEDENTIAL USES, THE BUFFER STRIIP SHALL BE AT
 LEAST FIVE FEET WIDE ALONG THE ENTIRE DEDGE OF PROPERTY
 WHEN ADHJACENT TO NONRESIDENTIAL ZONING DISTRICTS. AT
 LEAST ONE SHADE OR FLROWERING TREE SHALL BE PLANTED IN
 A REQUIRED BUFFER STRIP FOR EACH 30 LINEAR FEET OR
 PORTION THEREOF. SHRUBS, GRASS, GROUND COVER OR OTHER
 SUITABLE LIVE PLANT MATERIAL SHALL BE PLANTED ALONG THE
 ENTIRE BUFFER STRIP AREA. NO LANDSCAPE BUFFER WAS
 PROVIDED ALONG THE WEST SIDE OF THE BUILDING. THE
 LANDSCAPING SHOWN IS OFF-SITE.
  
 2. PURSUANT TO SECTION 94-443 (C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH (EXCLUDING
 THE REQUIRED CURB) AND NOT LESS THAN THE LENGTY OF THE
 ADJACENT PARKING STALL. NO LANDSCAPE ISLAND WAS
 PROVIDED IN THE LOCATION OF THE LOADING BAY OR THE
 HANDICAP MANEUVERING AREA. THE OTHER TERMINAL ISLANDS
 DO NOT MEET THE WIDTH REQUIREMENT WHEN THE CURBING IS
 INSTALLED.
  
 3. PURSUANT TO SECTION 94-443 (C)(3)(B), ONE INTERIOR
 LANDSCAPE ISLAND SHALL BE PROVIDED FOR EVERY TEN
 PAKRING SPACES OR FRACTION THEREOF. INTERIOR LANDSCAPE
 ISLANDS SHALL BE AT LEAST FIVE FEET WIDE , EXCLUDING
 THE REQUIRED CURB, AND SHALL CONTAIN AT LEAST ONE SHADE
 OR FLOWERING TREE. THE ISLAND ADJACENT TO THE DUMPSTER
 DOES NOT MEET THIS REQUIREMENT. THE ISLAND WILL NEED TO
 BE ADDED TO ONE SIDE BUT THE OTHER SIDE CAN BE TWO TO
 THREE FEET IN WIDTH TO ACCOMMODATE THE REQUIRED
 SCREENING HEDGE.
  
 4. THE DUMPSTER DOES NOT MEET MINIMUM CITY OF WEST PALM
 BEACH STANDARDS AND IS NOT ACCSSIBLE. PLEASE PROVIDE
 THE STANDARD CITY DUMPSTER DETAIL. PURSUANT TO SECTION
 94-444 (B), OUTDOOR GARBAGE OR TRASH RECEPTACLES AND
 OTHER MECHANICAL EQUIPMENT SHALL BE SCREENED. THE
 DUMPSTER ENCLOSURE SHALL HAVE A HEDGE PLANTED ON THREE
 SIDES. THE GENERATOR ROOM SHOWN ON THE SITE PLAN DOES
 NOT APPEAR ON THE LANDSCAPE PLAN. IT WILL NEED TO BE
 SCREENED, AS WELL.
  
 5. STAFF RECOMMENDS THAT VERTICAL LANDSCAPE ELEMENTS
 SUCH AS ALEXANDER PALMS BE PLANTED ALONG THE FOUNDATION
 OF THE BUILDING (EAST SIDE) TO ACCENTUATE THE
 ARCHITECTURE AND CREATE SOME INTEREST. THE SIX FOOT
 WALKWAY COULD BE REDUCED TO FIVE FEET WITH THE
 ADDTIONAL SPACE ADDED ONTO THE LANDSCAPE STRIP TO
 ACCOMMONDATE THE PALMS.
  
 6. THERE ARE ROYAL PALM STREET TREES ALONG PALM BEACH
 LAKES BOULEVARD. THIS PROPERTY SHALL BE REQUIRED TO
 PLANT ROYAL PALMS IN THE RIGHT-OF-WAY TO BE CONSISTENT
 WITH THE OTHER PROPERTIES ON THE STREET.
  
 7. THE RIGHT-OF-WAY SHOWN ON THE SURVEY IS 4O FEET WIDE
 BUT IS SHOWN AT NINE FEET ON THE SITE AND LANDSCAPE
 PLANS.
  
 8. PURSUANT TO SECTION 94-443 (C)(5)(A), LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS 'TYPE D'. NO CURBING WAS CALLED OUT ON
 THE SITE PLAN AND NONE WAS SHOWN ON THE LANDSCAPE PLAN.
  
 9. THERE ARE CONFLICTS BETWEEN PROPOSED STREET LIGHTS
 AND TREES. LIGHTS SHALL BE CENTERED BETWEEN THE TREES.
 ON THE LANDSCAPE PLAN, PLEASE SHOW ALL UTILITIES,
 STREET LIGHTS, EASEMENTS AND ANY OTHER ITEM THAT MAY
 INTERFERE WITH THE PROPOSED LANDSCAPING.
  
 10. PURSUANT TO SECTION 94-442 (D), PRIVATE LANT AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED STRIPS AND LANDSCAPED OPEN SPACE
 AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS SHALL BE
 SODDED. THIS INCLUDES THE RIGHT-OF-WAY ADJACENT TO PALM
 BEACH LAKES BOULEVARD. A NOTE ON THE LANDSCAPE PLAN
 INDICATES THAT ALL LANDSCAPED AREAS SHALL BE IRRIGATED.
 THE IRRIGATION SHALL BE PROVIDED IN THE RIGHTS-OF-WAY.
  
 11. PROVIDE THE SPACING FOR ALL PROPOSED PLANT
 MATERIAL.
  
 12. HEDGES ADJACENT TO RIGHTS-OF-WAY SHALL BE PLANTED
 ALONG THE INTERIOR PERIMETER OF THE LANDSCAPE BUFFER
 WITH GROUND COVER OR SOD PLANTED ON THE STREET SIDE OF
 THE HEDGE.
  
 13. PLEASE PROVIDE THE CITY OF WEST PALM BEACH STRIPING
 DETAIL.
  
 14. LAUREL OAK TREES ARE NOT AS DURABLE AS LIVE OAK.
 UNLESS THE AREA WHERE THE OAK TREES WILL BE PLANTED IS
 A WET AREA, THE LIVE OAK WOULD BE A BETTER CHOICE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop PARK PARKING
Rev No 1 Status F Date 09-02-2009 Cont ID  
Sent By ssamuels Date 09-02-2009 Time 22:09 Rev Time 0.00
Received By ssamuels Date   Time   Sent To  
Notes
2009-09-02 22:07:27SUGGESTIVE RECOMMENDED FOR OUTPATIENT FACILITY IS 10%
 OF THE TOTAL PARKING FOR ACCESSIBLE ADA PARKING.
 DUMPSTER LOCATION IS DIFFICULT TO TRAVEL AROUND BEING
 19'-2" AND DRIVEWAY IS 12'-4''
 ADA SIGN DETAIL NEED TO BE SHOW. WITH $AMOUNT
 HANDICAP ACCESSIBLE SYMBOL NEED TO BE 2' FROM THE
 BOTTOM OF PARKING STALL FOR ENFORCEMENT PURPOSES

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2009-09-03 11:27:08NOT ENOUGH INFORMATION PROVIDED AT THIS TIME
 ALL DOORS LEADING FROM THE WAITING ROOM TO THE REAR
 EXAM ROOMS SHOULD BE LOCK CONTROLLED (BUZZER TYPE)
 DOOPRS LEADING TO PATIENT AREA...GLASS?
 SHATTER RESISTANT WINDOWS?
 ALARM, CAMERA SYSTEM?
 LOCKS USED?
 CUT OFF LIGHT FIXTURES FOR THE PARKING LOT?
 HOW ARE YOU GOING TO SECURE NARCOTICS OR PAIN
 MEDICATION?
  
  
 COMMERCIAL SECURITY
  LIGHTING
  
 A. PARKING LOT AND PEDESTRIAN LIGHTING SHALL BE:
 A) HIGH EFFICACY OF GREATER THAN 70 LUMENS PER WATT
 B) A KELVIN TEMPERATURE OF 3,500 K OR GREATER THAN
 KELVIN TEMPERATURE
 C) COLOR RENDERING INDEX (CRI) OF 70 OR GREATER
 D) LAMP LIFE OF 20 THOUSAND HOURS OR GREATER.
 B. LIGHT POLES 10 ??? 15 FOOT HIGH FOR PEDESTRIAN-SCALE
 LIGHTING SHALL BE USED FOR ALL PEDESTRIAN WALKWAYS.
 C. PARKING LOT LIGHTING SHALL USE 20 -25 FOOT POLES.
 D. LANDSCAPING SHALL NOT OBSTRUCT VIEW OF WINDOWS,
 BUILDING ADDRESS NUMBERS, LIGHTING AND WALKWAYS.
 E. TIMER CLOCK OR PHOTOCELL SENSOR-ENGAGED LIGHTING FOR
 ABOVE OR NEAR ENTRYWAYS TO BUILDINGS FOR DUSK TO DAWN
 OPERATION SHALL BE PROVIDED.
 F. ENTRANCE SIGN LIGHTING SHALL BE PROVIDED. DIRECTORY
 SHOULD BE AT ALL ENTRANCES WITH LIGHTING
 G. BUILDING LIGHTING (NON-GLARE) SHALL BE AROUND
 PERIMETER ON ALL SIDE.
  
  NUMERICAL ADDRESS
 A. ILLUMINATION FOR NIGHTTIME VISIBILITY IS REQUIRED.
 ADDRESS SHOULD BE PLACED UNDER A LIGHT FIXTURE OR BE
 BACK LIT.
 B. BI-DIRECTIONAL VISIBILITY FROM THE ROADWAY IS
 REQUIRED.
 C. ADDRESS NUMBERS ON SUITES/OFFICES WITHIN
 MULTI-TENANT BUILDINGS SHALL BE A MINIMUM OF 6 INCHES
 HIGH.
 D. BUILDING NUMBERS SHALL BE A MINIMUM OF 12 INCHES
 HIGH AND PLACED IN A CONSPICUOUS LOCATION AWAY FROM
 LANDSCAPING. MULTIPLE LOCATIONS MAY BE REQUIRED.
 NUMBERS OF CONTRASTING COLORS SHOULD BE USED.
  
  DOORS
 A. EXTERIOR DOORS SHALL ALL BE EQUIPPED WITH SECURITY
 HINGES AND SHALL BE REINFORCED WITH CASE HARDENED
 STRIKE PLATES. CASE HARDENED DEADBOLT LOCKS SHALL BE
 PROVIDED ON ALL EXTERIOR DOORS WITH A MINIMUM (1) INCH
 THROW OR MECHANICAL INTERLOCK.
 B. GLASS PERIMETER DOORS SHALL BE EQUIPPED WITH CASE
 HARDENED GUARD RINGS TO PROTECT THE MORTISE LOCK
 CYLINDER.
 C. REAR DOORS SHALL BE EQUIPPED WITH 180-DEGREE
 PEEPHOLE/ SECURITY VIEWER.
  
  MAILBOXES
 A. MAILBOX LOCATIONS SHALL BE IN A WELL LIT, HIGH
 TRAFFIC LOCATION.
  
  DESIGN
 A. BUILDING ARCHITECTURE SHALL ALLOW FOR ENHANCED
 NATURAL SURVEILLANCE OF ALL PARKING LOTS AND PROVIDE A
 SENSE OF SECURITY TO PATRONS AND VISITORS.
 B. LANDSCAPING SHALL NOT OBSTRUCT VIEW FROM WINDOWS OR
 WALKWAYS.
 C. CROSSWALKS SHALL BE RAISED AND DELINEATED BY USING
 CONTRASTING PAVER BLOCKS AS OPPOSED TO SURFACE
 STRIPING.
 D. ALL BUILDINGS SHALL BE PRE-WIRED FOR CLOSED-CIRCUIT
 TELEVISION (CCTV) AND ALARM SYSTEMS.
 E. DUMPSTERS SHALL NOT ALLOW FOR EASY CONCEALMENT,
 CREATE BLIND SPOTS OR HIDING AREAS AND SHOULD BE ABLE
 TO BE LOCKED.
 F. SIGNS SHALL CLEARLY IDENTIFY PUBLIC ENTRANCES.
 G. LANDSCAPING SHALL BE MAINTAINED AT 3 FEET OR LESS.
 TREES SHALL BE INSTALLED SO AS NOT TO CONFLICT WITH THE
 LIGHTING SYSTEM. LOWER CANOPY LIMBS ON TREES SHALL BE
 MAINTAINED AT 8 FEET OR HIGHER.
 H. BIKE RACKS SHOULD BE AT THE FRONT OF THE BUILDING OR
 COMPLEX, NOT IN THE PARKING LOT FOR EASY SURVEILLANCE
 AND SAFETY.
  

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jrenault Date 09-08-2009 Time 09:41 Sent To  
Notes
2009-09-08 09:44:18PROVIDE DRAINAGE CALCULATIONS TO DEMONSTRATE THAT WATER
 QUALITY IS BEING PROVIDED AND ALSO THAT THE POST
 DEVELOPMENT SITE DISCHARGE DOES NOT EXCEED THE PRE
 DEVELOPMENT SITE DISCHARGE

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By vnoel Date 09-08-2009 Time 08:36 Sent To  
Notes
2009-09-08 08:46:151. THERE ARE EXISTING ADJOINING FEATURES SHOWN ON THE
 LANDSCAPE PLAN THAT ARE NOT SHOWN ON SURVEY.
 2. SHOW THE 6' U.E.'S AS ABANDONED BY RESOLUTION NO.
 99-72.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-25-2009 Cont ID  
Sent By bcollins Date 08-25-2009 Time 11:20 Rev Time 0.00
Received By bcollins Date 08-25-2009 Time 11:19 Sent To  
Notes
2009-08-25 11:18:58COUNTY NEEDS TO APPROVE ACCESS ON PBL. STANDARD PARKING
 SPACES ARE 22' - COMPACT ARE 20' (SEE EAST END OF
 PROPERTY). DRIVE AISLE APPEARS TO BE LESS THAN 12' AT
 ENTRANCES - DIFFICULT TO TELL IF IT IS COLUMNS OR JUST
 ROOF OVERHANG. TRAVEL AROUND DUMPSTER IS AWKWARD DUE TO
 OFFSET IN DRIVEWAY.TO OPTIMIZE DRIVEWAY SPACING ON 13TH
 ST., DRIVEWAY SHOULD BE PUSHED TO THE EAST. NEEDS
 SIGNING AND MARKING PLAN. MAY NEED CONCURRENCY LETTER
 FROM COUNTY.

Review Stop Z ZONING
Rev No 1 Status F Date 09-04-2009 Cont ID  
Sent By kdfreema Date 09-04-2009 Time 16:56 Rev Time 0.00
Received By kdfreema Date 09-04-2009 Time 16:56 Sent To  
Notes
2009-09-04 16:57:331. SIGNAGE WILL BE REVIEWED AT THE TIME OF PERMIT,
 HOWEVER, PLEASE KNOW THAT THE MAXIMUM PERMISSIBLE SIGN
 HEIGHT IN THE NEIGHBORHOOD COMMERCIAL ZONING DISTRICT
 IS 10 FEET. SEE SECTION 94-408(A) FOR THE FULL LISTING
 OF REQUIREMENTS.
 2. THE LOADING ZONE IS UNDERSIZED. THE MINIMUM SIZE IS
 10 FEET BY 25 FEET. SEE SECTION 94-485, TABLE XV-4.
 3. PLEASE CLARIFY WHAT IS MEANT BY THE NOTE BILL BOARD
 ON THE ELEVATIONS. IS THERE ANY EXISTING SIGNAGE
 PROPOSED TO BE INSTALLED THERE? IF SO, PLEASE PROVIDE
 DETAILS AND NOTE THAT IT MUST COMPLY WITH SECTION
 94-408(A) AS REFERENCED ABOVE.
 4. THE LANDSCAPE PLAN DOES NOT SHOW THE GENERATOR WHICH
 APPEARS ON THE SITE PLAN. PLEASE REVISE THE LANDSCAPE
 PLAN ACCORDINGLY AND PROVIDE THE REQUIRED SCREENING.
 5. PLEASE PROVIDE DETAILS OF THE GENERATOR ENCLOSURE.
 IS THIS AN UNROOFED OR ROOFED STRUCTURE? THE PLANS
 AREN???T CLEAR ON THIS.
 6. PLEASE PROVIDE DETAILS ON THE BICYCLE PARKING,
 INCLUDING THE BRAND AND MODEL OF RACK TO BE USED.
 PLEASE CONTACT ALEX HANSEN, SENIOR PLANNER, AT
 561-822-1463 FOR THE SPECIFICS ON WHAT TYPES OF BICYCLE
 RACKS WILL WORK BEST FOR YOUR APPLICATION. PLEASE NOTE
 THAT HE WILL BE OUT OF THE OFFICE UNTIL SEPT. 11TH.
 7. PLEASE INCLUDE THE CORRECT CITY-DETAIL FOR THE
 PARKING LOT STRIPING. THIS CAN BE PROVIDED TO YOU AFTER
 THE PPRC MEETING IF YOU DO NOT ALREADY HAVE IT.
 8. THE SURVEY SHOWS TWO 6 FOOT WIDE UTILITY EASEMENTS
 RUNNING EAST AND WEST THROUGH THE MIDDLE OF THE
 PROPERTY. PLEASE CONFIRM THAT THESE EASEMENTS STILL
 EXIST, IF SO, THEY WILL NEED TO BE ABANDONED.
 9. THE IMPERMEABLE SQUARE FOOTAGE SHOULD INCLUDE PAVING
 AND BUILDING AREA. WHEN ADDED TO THE PERMEABLE (IE
 LANDSCAPED) AREA, THAT FIGURE SHOULD EQUAL THE TOTAL
 SQUARE FOOTAGE OF THE LOT.
 10. THERE IS AN EXISTING CATCH BASIN WITHIN THE RIGHT
 OF WAY ON PALM BEACH LAKES BLVD. PLEASE ADD THIS BASIN
 TO THE SITE PLAN. IT APPEARS THAT IT MAY INTERFERE WITH
 THE LOCATION OF THE DRIVEWAY.
 11. PLEASE CLARIFY WHAT IS AND IS NOT CURBED ON THE
 SITE PLAN. IT APPEARS THAT THERE IS A CURB BETWEEN THE
 HANDICAP SPACE AND THE DRIVE AISLE. ALSO, IT APPEARS
 THAT SIDEWALK USERS WILL HAVE TO CROSS OVER A CURB WHEN
 TRAVERSING THE DRIVE AISLES ON BOTH SIDES OF THE
 PROPERTY. THESE ARE BOTH CONDITIONS WHICH MAY NOT
 EXIST. PLEASE CLEARLY SHOW ON THE PLAN WHERE CURBING IS
 PROPOSED TO BE INSTALLED.
 12. PLEASE PROVIDE AN ACCESSIBLE ROUTE FROM THE
 SIDEWALK TO THE BUILDING ENTRY.
 13. PLEASE INCLUDE A NOTE ON THE PLANS THAT ALL CURBING
 SHALL BE FDOT D TYPE CURB.
  

  Print