Plan Review Details - Project Z08050015
Plan Review Stops For Project Z08050015
Review Stop L LANDSCAPING
Rev No 1 Status   Date 05-14-2008 Cont ID  
Sent By adavila Date 05-14-2008 Time 15:51 Rev Time 0.00
Received By RKUSSNER Date 05-14-2008 Time 15:52 Sent To  
Notes
2008-05-14 15:52:17PLANS AND PLATS REVIEW COMMITTEE
 MAY 14, 2008
 PLANNING BOARD CASE NO. 1564A
 HANLEY CENTER MAIN CAMPUS ? PLANNED DEVELOPMENT
  
  
 PLANNING AND ZONING DEPARTMENT
  
 LANDSCAPE COMMENTS
  
 1. PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 2. PURSUANT TO ARTICLE XIV, SECTION 94-443(C)(3)(B),
 ONE INTERIOR LANDSCAPE ISLAND SHALL BE PROVIDED FOR
 EVERY TEN PARKING SPACES OR FRACTION THEREOF.INTERIOR
 LANDSCAPE ISLANDS SHALL BE AT LEAST FIVE FEET WIDE
 (INSIDE DIMENSION) AND SHALL CONTAIN AT LEAST ONE SHADE
 OR FLOWERING TREE.ADDITIONAL LANDSCAPE ISLANDS WILL
 NEED TO BE ADDED TO COMPLY WITH THIS REQUIREMENT.SOME
 OF THE EXISTING ISLANDS ARE NOT MEETING THE WIDTH
 REQUIREMENT.
  
 3. PURSUANT TO SECTION 94-443(C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS.THE LANDSCAPED ISLAND SHALL CONTAIN AT LEAST
 ONE SHADE OR FLOWERING TREE.THERE IS AT LEAST ONE
 AREA OF THE SITE WHERE TWO PARKING ROWS ARE TERMINATED
 BY A LARGE LANDSCAPE ISLAND AND ONLY ONE TREE HAS BEEN
 PROVIDED, INSTEAD OF THE TWO TREES REQUIRED.
  
 4. MUCH OF THE PROPOSED LANDSCAPING IS WITHIN UTILITY
 EASEMENTS.PLEASE OBTAIN WRITTEN PERMISSION FROM THE
 EASEMENT HOLDER TO ALLOW THE PLANTING WITHIN THEIR
 EASEMENTS.
  
 5. THERE ARE NUMEROUS CONFLICTS BETWEEN PROPOSED
 LANDSCAPING AND UTILITIES.ALL EASEMENTS AND UTILITIES
 SUCH AS OVERHEAD LINES, METERS, CLEAN-OUTS, TELEPHONE
 LINES, WATER AND SEWER LINES, ELECTRIC TRANSFORMERS AND
 ANYTHING ELSE THAT MAY INTERFERE WITH THE LANDSCAPING
 SHALL BE SHOWN ON THE LANDSCAPE PLANS.ALL STREET
 LIGHTS SHALL ALSO BE SHOWN ON THE LANDSCAPE PLAN.
  
 6. A NEW TREE ALTERATION PERMIT APPLICATION NEEDS TO BE
 SUBMITTED WITH THIS CURRENT PROJECT. ALL EXISTING AND
 PROPOSED TREES MUST BE ACCURATELY IDENTIFIED. PLEASE
 PROVIDE THE TOTAL LOSS OF TREE CANOPY MEASURED IN
 SQUARE FEET OR BY CALIPER INCH OF TRUNK DIAMETER FOR
 THE 104 TREES PROPOSED TO BE REMOVED.DETERMINE THE
 AMOUNT OF NEW CANOPY THAT WILL BE ADDED BASED UPON THE
 SPECIFICATIONS ON THE PLANT LIST.YOU WILL BE
 RESPONSIBLE TO MITIGATE THE DIFFERENCE (NET LOSS) OF
 TREE CANOPY ON SITE OR ON CITY PROPERTY.
  
 7. INSTALL LANDSCAPING ON THE INSIDE OF THE PROPOSED 26
 FOOT WALL TO CREATE A VISTA AS VIEWED FROM THE DINING
 ROOM.PERHAPS FICUS REPENS COULD BE ATTACHED TO BOTH
 SIDES OF THE WALL TO SOFTEN THE IMPACT OF AN EIGHT FOOT
 WALL IN CONJUNCTION WITH ADDITIONAL LANDSCAPING BEING
 INSTALLED BETWEEN THE WALL AND THE DINING ROOM.
  
 8. PURSUANT TO SECTION 94-445(4)(B), WHENEVER THE
 CLUSTERING OF PALM TREES IS UTILIZED, A MINIMUM OF
 THREE PALM TREES PER CLUSTER SHALL BE REQUIRED.THE
 PROPOSED PALMS IN THE LANDSCAPE ISLANDS (TERMINAL AND
 INTERIOR) SHALL BE GROUPED IN CLUSTERS OF THREE TO
 SERVE AS A SUBSTITUTION FOR REQUIRED SHADE TREES.
  
 9. PURSUANT TO SECTION 94-443(B)(4), AT LEAST ONE SHADE
 OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED BUFFER
 STRIP FOR EACH 30 LINEAR FEET OR FRACTION THEREOF ALONG
 THE NORTH PERIMETER OF THE SITE TO FILL THE GAPS.TREE
 SPECIES THROUGHOUT THE SITE SHALL BE SELECTED BASED
 UPON FPL?S ?PLANT THE RIGHT TREE IN THE RIGHT PLACE?
 THAT REGULATES WHAT TREES CAN BE PLANTED NEAR OR UNDER
 POWER LINES.
  
 10. BASED UPON THE INFORMATION PROVIDED ON THE
 XERISCAPE DESIGN OPTION CHART, FIVE POINTS HAVE BEEN
 CREDITED FOR UTILIZATION OF A MOISTURE SENSING
 CONTROLLER OTHER THAN A RAINSWITCH.IN ORDER TO TAKE
 ADVANTAGE OF THIS, YOU MUST SPECIFY THE EQUIPMENT THAT
 WILL BE INSTALLED.
  
 11. IN ORDER TO FOLLOW XERISCAPE PRINCIPLES AND REDUCE
 MAINTENANCE, THE USE OF GROUND COVER INSTEAD OF SOD
 SHOULD BE UTILIZED IN SMALL AREAS SUCH AS LANDSCAPE
 ISLANDS.
  
 12. MUCH OF THE EXISTING LANDSCAPING IS TO REMAIN.ALL
 EXISTING TREES AND PLANT MATERIAL SHALL BE IN GOOD
 CONDITION.A CERTIFIED ARBORIST SHALL BE HIRED TO
 PRUNE ALL TREES IN NEED OF CORRECTIVE PRUNING. ALL
 TREES AND PLANTS THAT DONOT MEET THE FLORIDA NUMBER 1
 GRADES AND STANDARDS SHALL BE REPLACED.

Review Stop Z ZONING
Rev No 1 Status   Date 05-14-2008 Cont ID  
Sent By adavila Date 05-14-2008 Time 14:23 Rev Time 0.00
Received By adavila Date 05-14-2008 Time 15:21 Sent To  
Notes
2008-05-09 14:24:16PLANS AND PLATS REVIEW COMMITTEE
 MAY 14, 2008
 PLANNING BOARD CASE NO. 1564A
 HANLEY CENTER MAIN CAMPUS - PLANNED DEVELOPMENT
  
  
 PLANNING AND ZONING DEPARTMENT
  
 ZONING COMMENTS
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TEN
 (10) COPIES OF ALL REVISED SHEETS, ONE (1) REDUCED COPY
 (8 ? BY 11), AND AN ELECTRONIC COPY IN .PNG FORMAT OF
 ALL PLANS.PLEASE NOTE THAT RE-SUBMITTALS MAY BE
 SUBJECT TO ADDITIONAL COMMENTS.
  
 * PLEASE SUPPLY THE LEGAL DESCRIPTION OF THE PROPERTY
 IN WORD FORMAT.
  
 * THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING AND ZONING DEPARTMENT BY NOON
 ON THURSDAY, MAY 22, 2008, TO BE SCHEDULED FOR THE JUNE
 17, 2008 PLANNING BOARD MEETING.
  
 * PLEASE NOTE THAT IF THE PLANNING AND ZONING
 DEPARTMENT HAS NOT RECEIVED A RESPONSE TO THE PPRC
 COMMENTS WITHIN 60 DAYS FROM THE PPRC MEETING, THE CASE
 SHALL BE CONSIDERED WITHDRAWN.ANY FURTHER ACTION
 SHALL REQUIRE RESUBMITTAL OF A NEW DEVELOPMENT
 APPLICATION.
  
 * PLEASE NOTE THAT IF PREVIOUSLY-ISSUED COMMENTS
 CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE.SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 GENERAL COMMENTS
  
 1. PURSUANT TO SECTION 94-207(A)(1), THE INTENT OF THE
 PLANNED DEVELOPMENT DISTRICTS IS TO ENCOURAGE THROUGH
 INCENTIVES THE USE OF INNOVATIVE LAND PLANNING AND
 DEVELOPMENT TECHNIQUES TO CREATE MORE DESIRABLE AND
 ATTRACTIVE DEVELOPMENT IN THE CITY.PLEASE NOTE THAT
 ADDITIONAL DESIGN AND ARCHITECTURAL STANDARDS MAY BE
 REQUESTED AS PART OF THIS PD APPLICATION.THESE
 STANDARDS ARE REFLECTED IN THESE PPRC COMMENTS.
  
 2. PROVIDE WRITTEN DOCUMENTATION SHOWING COMPLIANCE
 WITH SECTIONS 94-207(B) AND 94-273(D)(28) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 3. PROVIDE THE ARCHITECTURAL STANDARDS AND/OR DESIGN
 GUIDELINES THAT WILL BE PART OF THIS PD APPLICATION.
  
 4. PLEASE NOTE THAT ALL OVERHEAD LINES SHALL BE BURIED
 WITHIN THE PROPERTY LINES.
  
 5. PLEASE NOTE THAT ALL SIGNS SHALL COMPLY WITH SECTION
 94-408(F) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.FOR THIS PD APPLICATION, POLE SIGNS SHALL
 NOT BE PERMITTED.IN ADDITION, PARKING AREA
 IDENTIFICATION SIGNS AND PARKING AREA INSTRUCTIONAL AND
 RELATED SIGNS SHALL COMPLY WITH SECTIONS 94-407(5) AND
 (6), RESPECTIVELY.PLEASE NOTE THAT STAFF RECOMMENDS
 THAT A MASTER SIGN PROGRAM BE CREATED AS PART OF THIS
 PD APPLICATION.
  
 6. PER THE JUSTIFICATION STATEMENT, THE ACCESS EASEMENT
 FROM 45TH STREET WILL BE UTILIZED BY HANLEY CENTER AS
 THE MAIN ENTRANCE TO THE CAMPUS.PROVIDE A NOTARIZED
 LETTER OF NO OBJECTION FROM ST. MARY?S HOSPITAL
 REGARDING THE LOCATION AND THE USE OF THE ACCESS
 EASEMENT AS THE MAIN ENTRANCE.PLEASE NOTE THAT ST.
 MARY?S HAS APPLIED FOR A FENCE PERMIT TO GATE THIS
 ROADWAY.ADDITIONALLY, PROVIDE DETAILS OF THIS
 ROADWAY, TO INCLUDE THE ENTRANCE TO THE HANLEY CENTER
 MAIN CAMPUS.
  
 7. PROVIDE LETTER(S) OF NO OBJECTION FROM THE EASEMENT
 OWNERS STATING THAT ALL AFFECTED EASEMENTS WILL BE
 ABANDONED, TERMINATED, RESCINDED AND/OR RELOCATED.ALL
 AFFECTED EASEMENTS SHALL BE ABANDONED, TERMINATED,
 RESCINDED AND/OR RELOCATED AT THE TIME THE NEW PLAT
 WILL BE RECORDED.
  
 8. PER THE JUSTIFICATION STATEMENT, THE APPLICANT IS
 REQUESTING A TOTAL OF FIVE (5) WAIVERS: TWO (2) SETBACK
 WAIVERS, ONE (1) SETBACK ENCROACHMENT WAIVER, AND TWO
 (2) FENCE HEIGHT WAIVERS.PROVIDE DOCUMENTATION
 SHOWING COMPLIANCE WITH SECTION 94-273(A)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.IN ADDITION,
 PLEASE STATE WHAT IS BEING PROPOSED TO MITIGATE THE
 WAIVERS REQUESTED.
  
 9. PURSUANT TO SECTION 94-203(B)(3), MINIMUM SETBACKS
 MAY BE WAIVED BY THE CITY COMMISSION WHEN ONE OR MORE
 SIDES OF A PARCEL ABUT A ZONING DISTRICT WHICH PERMITS
 A LESSER SETBACK.MORE THAN ONE SIDE OF THE PROPERTY
 ABUTS A COMMUNITY SERVICE (CS) ZONING DISTRICT, WHICH
 DOES NOT ALLOW A LESSER SETBACK THAN THE SETBACKS
 REQUIRED IN A COMMUNITY SERVICES PLANNED DEVELOPMENT
 (CSPD) ZONING DISTRICT.THEREFORE THE POOL EQUIPMENT
 BUILDING AND THE GENERATOR SHALL BE RELOCATED SO THAT
 IT NO LONGER ENCROACHES INTO THE REQUIRED SIDE SETBACK.
 PLEASE NOTE THAT THE APPLICANT HAS THE OPTION TO APPLY
 FOR A TEXT AMENDMENT IN ORDER TO CHANGE THIS PROVISION
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 SURVEY
  
 10. PROVIDE AN ALTA/ACSM LAND TITLE SURVEY THAT IS
 WITHIN ONE (1) YEAR OLD.
  
 SITE PLAN (SHEETS SP-0 TO SP-4)
  
 11. PROVIDE SETBACKS AND BUILDING SEPARATIONS FOR ALL
 EXISTING AND PROPOSED BUILDINGS.IF ANY OF THE
 EXISTING OR NEW BUILDINGS DO NOT COMPLY WITH THE
 SETBACK OR BUILDING SEPARATION DISTANCE REQUIREMENTS
 PER SECTION 94-203(B)(2), A WAIVER FROM THIS SECTION IS
 REQUIRED.PLEASE NOTE THAT PER SECTION
 94-203(B)(2)(E), MINIMUM BUILDING SEPARATION SHALL BE
 15 FEET.ADDITIONALLY, PLEASE VERIFY THAT ALL
 BUILDINGS MEET THE FLORIDA BUILDING CODE BUILDING
 SEPARATION REQUIREMENTS.
  
 12. NUMBER ALL PARKING SPACES, OR PROVIDE THE TOTAL
 NUMBER OF PARKING SPACES IN EACH PARKING ROW.PARKING
 SPACES SHALL BE IDENTIFIED PER PHASE.
  
 13. PROVIDE WIDTH DIMENSION OF ALL DRIVE AISLES.
 PLEASE NOTE THAT PER SECTION 94-485(J), 90 DEGREE ANGLE
 PARKING AND TWO-WAY TRAFFIC REQUIRES A DRIVE AISLE OF
 24 FEET MINIMUM.
  
 14. PROVIDE DETAILS OF THE ?ASPHAULT PARKING AREA?
 LOCATED BETWEEN THE MAINTENANCE BUILDINGS (BUILDINGS
 ?P?) SHOWING COMPLIANCE WITH SECTION 94-485(J) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.PLEASE NOTE
 THAT THE SURVEY SHOWS THIS AREA TO BE ?ROCK PARKING
 AREA.?PER SECTION 94-485(E), ALL PARKING AND LOADING
 SPACES, ACCESS DRIVES, AND MANEUVERING LANES SHALL BE
 PAVED WITH A NONDUSTING SURFACE IN COMPLIANCE WITH
 STANDARDS SPECIFIED BY THE CITY.
  
 15. PURSUANT TO SECTION 94-485(P), 1,001 TO 99,999
 SQUARE FEET OF OFFICE USE REQUIRES ONE (1) 10 FEET BY
 25 FEET LOADING SPACE.PROVIDE LOCATION OF THE LOADING
 AREA.
  
 16. PURSUANT TO SECTION 94-485(Q), ONE (1) BICYCLE
 PARKING SPACE SHALL BE PROVIDED FOR EVERY 20 AUTOMOBILE
 PARKING SPACES, OR FRACTION THEREOF.PROVIDE BICYCLE
 PARKING SPACES.CALCULATIONS FOR BICYCLE PARKING SHALL
 BE INCLUDED IN THE SITE DATA TABLE.
  
 17. PROVIDE BICYCLE PARKING DETAILS SHOWING COMPLIANCE
 WITH SECTION 94-485(Q)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.PLEASE NOTE THAT BICYCLE
 PARKING LOCATION AND DETAILS SHALL BE APPROVED BY ALEX
 HANSEN, TRANSPORTATION PLANNER, PRIOR TO SCHEDULING FOR
 THE PLANNING BOARD MEETING.MR. HANSEN MAY BE REACHED
 AT (561) 822-1463.
  
 18. THERE IS A DISCREPANCY IN THE SITE DATA TABLE WHEN
 CALCULATING AND COMPARING THE PARKING COUNT FOR EACH
 USE/BUILDING.THE SITE DATA TABLE SHOULD CLEARLY SHOW
 THE NUMBER OF BEDS, AREA AND PARKING SPACES OF WHAT IS
 EXISTING, WHAT IS REQUIRED AND WHAT IS PROPOSED FOR
 EACH USE/BUILDING, AND THE TOTAL FOR THE SITE.PLEASE
 REVIEW.
  
 19. THE ?TOTAL? COLUMN ONLY SHOWS TOTAL NUMBER OF BEDS
 AND AREA.AN ADDITIONAL COLUMN SHALL BE ADDED TO SHOW
 TOTAL NUMBER OF PARKING SPACES.
  
 20. PROVIDE TOTAL NUMBER OF EXISTING, REQUIRED, AND
 PROPOSED HANDICAP PARKING SPACES.PLEASE NOTE THAT THE
 TOTAL NUMBER OF PARKING SPACES LISTED ON THE SITE DATA
 TABLE SHOULD EITHER INDICATE ?TOTAL REGULAR PARKING
 SPACES PROVIDED? (187 PARKING SPACES), OR PROVIDE A
 GRAND TOTAL PARKING COUNT TO INCLUDE HANDICAP PARKING
 SPACES (193 PARKING SPACES).
  
 21. PLEASE CLARIFY IF THE BOOKSTORE, WELLNESS CENTER,
 KITCHEN/DINING BUILDING, MEETING ROOM, AND ANY OTHER
 COMMON USE AREA/BUILDING WILL BE USED ONLY BY THE
 RESIDENTS AND EMPLOYEES, OR WILL BE OPEN TO THE PUBLIC.
 IF THE LATTER, PLEASE NOTE THAT EACH OF THESE
 BUILDINGS/USES SHALL COMPLY WITH THE PARKING
 REQUIREMENTS SET FORTH IN SECTION 94-486 OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 22. ACCORDING TO THE SURVEY, THERE ARE 126 EXISTING
 PARKING SPACES ON THE SITE; HOWEVER, THE SITE DATA
 TABLE STATES THERE ARE 150 EXISTING PARKING SPACES.
 PLEASE REVIEW.
  
 23. ACCORDING TO THE SURVEY, THERE ARE 12 PARKING
 SPACES ON THE PARKING LOT BETWEEN BUILDINGS ?N? AND
 ?F;? HOWEVER, THE SITE PLAN SHOWS 11 PARKING SPACES.
 PLEASE REVIEW.
  
 24. INDENTIFY THE LOCATION OF ALL DUMPSTER ENCLOSURES,
 GENERATORS AND ANY OTHER ON-GROUND MECHANICAL
 EQUIPMENTS (EXISTING AND PROPOSED) ON SITE, WITH
 SETBACK DIMENSIONS.
  
 25. PROVIDE THE LOCATION AND DETAILS OF ALL MECHANICAL
 EQUIPMENTS FOR EACH BUILDING.PLEASE NOTE THAT ALL
 GROUND AND ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE PRINCIPAL STRUCTURE AND
 EQUIVALENT LANDSCAPE MATERIAL.
  
 26. PROVIDE DETAILS OF THE PERIMETER WALLS.ALL FENCES
 AND WALLS SHALL BE CONSISTENT WITH THE ARCHITECTURAL
 DESIGN OF THE BUILDINGS.PLEASE NOTE THAT PER SECTION
 94-302(C)(1), WALLS AND FENCES SHALL NOT EXCEED EIGHT
 (8) FEET IN HEIGHT WITHIN THE REQUIRED SIDE AND REAR
 SETBACKS, AND 48 INCHES WITHIN THE FRONT SETBACK.
  
 27. IDENTIFY AND PROVIDE DETAILS OF THE OBJECTS WITHIN
 THE 15 FOOT FP&L EASEMENT, ON THE WEST SIDE OF THE
 PROPOSED POOL EQUIPMENT BUILDING (BUILDING M).
  
 28. PROVIDE SWIMMING POOL DETAILS SHOWING COMPLIANCE
 WITH SECTION 94-304(D) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 FLOOR PLANS
  
 29. PLEASE ENSURE THAT ALL FLOOR PLANS ARE PROPERLY
 LABELED.THERE ARE SOME OCCASIONS WHERE THE FLOOR
 PLANS ARE MISLABELED (I.E. WELLNESS CENTER FIRST FLOOR
 PLAN IS LABELED AS WOMEN?S RESIDENCE FLOOR PLAN).
  
 30. PLEASE ENSURE TO INDENTIFY ALL NECESSARY DETAILS
 AND INFORMATION THAT PERTAIN TO A SPECIFIC BUILDING
 (I.E. SETBACK DIMENSIONS, BUILDING DISTANCE SEPARATION,
 MECHANICAL EQUIPMENTS, SCREENING WALLS, ROOF OVERHANG,
 AWNINGS PROJECTION, ETC.)
  
 ELEVATIONS
  
 31. PROVIDE OVERALL BUILDING HEIGHT (AS DEFINED BY THE
 ZONING AND LAND DEVELOPMENT REGULATIONS), AND BUILDING
 HEIGHT TO THE HIGHEST POINT FROM GRADE OF EACH
 BUILDING.
  
 32. PROVIDE ROOF OVERHANG AND AWNING PROJECTION
 DIMENSIONS.
  
 33. PROVIDE HEIGHT DIMENSIONS OF ALL SCREEN WALLS
 (EXISTING AND PROPOSED).
  
 34. PROPERLY LABEL ALL BUILDING ELEVATIONS.FOR
 EXAMPLE, THE ELEVATIONS FOR THE MAINTENANCE BUILDINGS
 DO NOT IDENTIFY WHICH ELEVATIONS PERTAIN TO EACH
 MAINTENANCE BUILDING.PLEASE REVIEW.
  
 35. NEW BUILDINGS SHALL BE CONSISTENT WITH THE
 ARCHITECTURAL DESIGN OF THE EXISTING BUILDINGS.
  
 36. ADDITIONAL ARCHITECTURAL DESIGN FEATURES SHALL BE
 PROVIDED TO THE MAINTENANCE BUILDINGS.
  
 LANDSCAPE PLANS
  
 37. PROVIDE LETTERS OF NO OBJECTION FROM EACH EASEMENT
 OWNER WHEREVER LANDSCAPE PLANT MATERIALS ARE BEING
 PROPOSED WITHIN THE EASEMENTS.
  
 38. LANDSCAPE REQUIREMENT TABLE SHALL INCLUDE THE
 PERCENTAGE REQUIRED AND PROPOSED OF LANDSCAPING AROUND
 THE BUILDINGS, FOR EACH BUILDING.PLEASE NOTE THAT PER
 SECTION 94-443(E)(1), AT LEAST 30 PERCENT OF THE LINEAR
 FEET AROUND THE EXTERIOR OF ALL COMMERCIAL STRUCTURES
 SHALL BE PLANTED WITH TREES, SHRUBS OR HEDGES.
  
 39. PURSUANT TO SECTION 94-443(B), A LANDSCAPE BUFFER
 OF A MINIMUM OF FIVE (5) FEET IN WIDTH SHALL BE
 PROVIDED ALONG THE ENTIRE EDGE OF THE PROPERTY.ONE
 (1) SHADE OR FLOWERING TREE SHALL BE PLANTED AT EVERY
 30 FEET INTERVAL.SHADE OR FLOWERING TREES SHALL BE
 PROVIDED ALONG THE SOUTH PROPERTY LINE, WEST OF THE
 POND.
  
 40. PROVIDE WITH AND DEPTH DIMENSIONS OF ALL TERMINAL
 AND INTERIOR LANDSCAPE ISLANDS.PLEASE NOTE THAT PER
 SECTIONS 94-443(C)(3)(A) AND (B), LANDSCAPED ISLANDS
 SHALL BE A MINIMUM OF FIVE (5) FEET IN WIDTH.
  
 41. PURSUANT TO SECTIONS 94-443(C)(3)(A) AND (B), ONE
 (1) SHADE OR FLOWERING TREE SHALL BE PLANTED AT EACH
 TERMINAL AND INTERIOR LANDSCAPE ISLAND.THERE ARE A
 NUMBER OF TERMINAL AND INTERIOR LANDSCAPE ISLANDS
 WITHOUT A SHADE OR FLOWERING TREE.PLEASE REVISE.
  
 42. PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS ?TYPE D? OR CURBING OF COMPARABLE
 DURABILITY.IDENTIFY THE TYPE OF CURBING WHEREVER
 APPLICABLE.PLEASE NOTE THAT CURBING IS NOT REQUIRED
 WHERE A WHEEL STOP IS PROVIDED.
  
 PRELIMINARY ENGINEERING PLANS (SHEETS C-1 TO C-10)
  
 43. PLEASE NOTE THAT PER SECTION 94-444(B), GARBAGE AND
 TRASH RECEPTACLES SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED.WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.IN ADDITION, DUMPSTER ENCLOSURE(S) SHALL BE
 CONSISTENT WITH THE ARCHITECTURAL DESIGN OF THE
 BUILDINGS.PROVIDE DUMPSTER ENCLOSURE DETAILS SHOWING
 THE ARCHITECTURAL DESIGN OF THE ENCLOSURE, TO INCLUDE
 LANDSCAPING.PLEASE NOTE THAT ALL DUMPSTER ENCLOSURES
 (EXISTING AND PROPOSED) SHALL HAVE THE SAME DESIGN AND
 MATERIALS.
  
 44. PROVIDE PLANS STAMPED APPROVED BY EMERY FABIAN,
 UTILITIES ENGINEERING PROJECT COORDINATOR, FOR DUMPSTER
 ENCLOSURE SIZE AND LOCATION.
  
 45. PROVIDE PARKING STALL DETAILS SHOWING COMPLIANCE
 WITH SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.PARKING STALL DETAILS
 PROVIDED DO NOT SHOW WIDTH AND DEPTH DIMENSIONS,
 STRIPING WIDTH AND SPACING DIMENSIONS, ETC.PLEASE
 REVISE.
 A. PLEASE NOTE THAT HANDICAP PARKING SYMBOL SHALL BE
 TWO (2) FEET FROM THE OPEN END OF THE PARKING SPACE.
 B. PLEASE NOTE THAT WHEEL STOPS SHALL BE TWO (2) FEET
 FROM THE CURB TO THE BACK OF THE WHEEL STOP.
  
 OTHER COMMENTS
  
 46. THE PRICE OF POSTAGE HAS INCREASED.THE STAMPS
 PROVIDED ARE $0.41 AND THE CURRENT POSTAGE IS $0.42.
 YOU ARE REQUIRED TO AFFIX A $0.01 STAMP ON EACH OF THE
 ENVELOPES.
  
 47. PLEASE CONTACT LACRAMIOARA URSU, GIS SUPPORT
 SPECIALIST, FOR ADDRESSING STANDARDS AND FURTHER
 INFORMATION FOR THE NEW BUILDINGS.