Plan Review Details - Project E23040008
Plan Review Stops For Project E23040008
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 05-01-2023 Cont ID  
Sent By lquinone Date 05-01-2023 Time 13:35 Rev Time 0.00
Received By lquinone Date 05-01-2023 Time 13:35 Sent To  
Notes
2023-05-01 13:35:44E-23040008??? INITIAL SUBMITTAL REVIEW COMMENTS 3/30
 (4/7SITE PLAN APPROVAL LETTER SUBMITTED)
  
 COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 4. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 5. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -HISTORIC PICTURES OF AREA SHOW UTILITY LOCATES NEAR
 WORK AREA ON OKEECHOBEE. SHOW AND LABEL FRANCHISE
 UTILITIES NEAR WORK AREAS.
  
 -CANNOT HAVE TWO FIRELINE DETECTOR METERS FOR ONE MAIN
 FIRELINE ACCOUNT. (A DETECTOR METER HAS TO GO ON EACH
 CONTAINMENT FIRELINE BACKFLOW ASSEMBLY)
  
 -VERIFY PRIVATE FIRE SYSTEM DOES NOT HAVE ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLY SUCH AS A WELL.
  
 -SHEET 11: PLEASE REMOVE STANDARD DETAILS FOR LARGE
 WATER METERS IF NO LARGE WATER METERS ARE BEING
 PROPOSED. (3, 4, 4.1)
  
 -ADD FLOW CALCULATIONS TO SHEET C09 AS DIRECTED IN
 STANDARD DETAIL WS5 NOTE 9.
  
 -REMOVE WPB WATER SERVICE STANDARD DETAIL WS7 FROM PLAN
 SET IF WILL NOT BE USED.
  
 -ON LABELS FOR METERS AND BACKFLOWS, ADD REFERENCE TO
 THE ASSOCIATED WPB STANDARD DETAIL.
  
 -ADD WPB WATER SERVICE STANDARD DETAIL WS2 TO PLAN SET.
  
 -ADD MARKUP NOTE TO WS1 THAT DUAL CHECK VALVE NOT USED
 WHEN A BACKFLOW ASSEMBLY IS BEING INSTALLED.
  
 -CALLOUT MINIMUM CLEARANCE DISTANCE BETWEEN BACKFLOW
 ASSEMBLY AND FIRE HYDRANT PER STANDARD DETAIL P-8.
  
 -SHEET C09: LEGEND AND ABBREVIATION LIST NOT READABLE
 (BLURRY).
  
 -UPDATE SHEET INDEX ON C01. IT NOT SEEM ACCURATE.
  
 -IN RESUBMITTAL PACKAGE, PROVIDE UPDATED LANDSCAPING
 PLANS.
  
 -WILL EXISTING METERED WATER SERVICE CONTINUE TO BE
 USED BY PROPERTY IN THE FUTURE?
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
  
 1. DRAINAGE CALCULATIONS
 A. PROPOSED LAND USE SUMMARY ??? ROOF PARKING AREA
 COUNTED TWICE? (TOTAL AREA = 8.27 ACRES VS. 7.40 ACRES)
 B. PROPOSED SOIL STORAGE LAND USE SUMMARY TABLE ???
 ROOF PARKING LISTED AS LAKE AREA?
 C. THE INVERT ELEVATION OF THE BLEEDER WILL NEED TO BE
 SET AT OR ABOVE ELEVATION 12.8 FT NAVD INSTEAD OF 12.5
 FT NAVD SO THAT ALL OF THE TREATMENT VOLUME IS RETAINED
 BEHIND THE CONTROL STRUCTURE. THE ALTERNATE
 EXFILTRATION TRENCH EQUATION MAY HAVE TO BE CONSIDERED
 BECAUSE IN THIS SCENARIO THE TRENCH WIDTH OF 10 FEET IS
 MORE THAN TWICE THE EFFECTIVE TRENCH HEIGHT (DU + DS)
 OF 4.3 FEET.
 D. PROVIDE THE BASIN RESULTS (SHOWING TOTAL RUNOFF
 VOLUMES) FOR THE ICPR MODEL RUNS.
  
 2. SHEET C-04 DEMOLITION PLAN
 A. PROVIDE A LEGEND FOR THE VARIOUS HATCH SYMBOLS ON
 THE PLAN.
 B. PROVIDE HATCH LINE OVER THE UTILITY LINES TO BE
 REMOVED.
 C. THE DRAINAGE SYSTEM NORTH OF THE EXISTING CAR
 DELIVERY AREA (AS LABELED ON SHEET C-05) IS LABELED TO
 REMAIN BUT DOES NOT APPEAR ON SHEET C-05 (PGD PLAN).
 D. THE DRAINAGE SYSTEM THAT WOULD BE WEST OF STRUCTURE
 DBI NO. 12 (AS LABELED ON SHEET C-05) IS LABELED TO
 REMAIN BUT DOES NOT APPEAR ON SHEET C-05 (PGD PLAN).
 E. CALLOUT SIDEWALK AND CURB AND GUTTER REPLACEMENT
 WITHIN OKEECHOBEE BLVD R/W. THESE ARE SHOWN ON SHEET
 C-02 (SITE PLAN).
  
 3. SHEET C-05 PGD PLAN
 A. PROVIDE GRADES FOR THE ACCESSIBILITY ROUTE AND
 HANDICAP PARKING SPACES TO ENSURE THE SLOPES MEET ADA
 CRITERIA.
 B. OVERFLOW WEIR ELEVATION AT STRUCTURE NO. 20 IS 16.11
 FT NAVD. SEVERAL CATCH BASINS AND PARKING SPACES
 (PREDOMINANTLY IF NOT ENTIRELY) OUTSIDE THE PUBLIC
 VEHICULAR ACCESSIBLE AREAS ARE LOWER THAN THE OVERFLOW
 WEIR ELEVATION. LOWEST CATCH BASIN GRATE ELEVATION
 APPEARS TO BE 13.5 FT NAVD.
 C. ADD THE SEIR ELEVATION TO THE CONTROL STRUCTURE NO.
 20 INFORMATION.
 D. STRUCTURE NO. 13 WILL NEED A PRB.
 E. CROSS SECTION A-A SHOULD POINT IN THE OPPOSITE
 DIRECTION.
 F. PROVIDE A DETAIL FOR THE FLUMES DRAINING TO THE
 SWALE AREA WHERE STRUCTURE NO. 12 IS LOCATED.
 G. SUGGEST SLOPING THE SWALE AREA TO DRAIN BETTER.
 H. IT APPEARS THE SWALE WILL HAVE SIDE SLOPES OF NEARLY
 2:1 BETWEEN STRUCTURE NO. 12 AND THE TOP OF CURB
 ELEVATION 17.95 AT THE CORNER OF SOUTH PARKING AREA.
  
 4. SHEET C-08 CROSS SECTIONS
 A. PROVIDE VERTICAL DATUM REFERENCE AND CONVERSION
 EQUATION TO NGVD1929.
 B. LABEL THE PUBLIC R/W???S ON THE CROSS SECTIONS
 (ALLEY FOR SECTIONS A-A AND B-B, OKEECHOBEE BLVD FOR
 SECTIONS D-D AND F-F, CONGRESS AVE FOR SECTION E-E).
 C. SECTION A-A ??? ARE THE 20-FT AISLE WIDTHS WIDE
 ENOUGH TO BACK OUT OF THE PARKING SPACES?
 D. SECTION C-C ???
 I. 2-FT PARKING OVERHANG AREA SHOULD NOT BE HIGHER THAN
 THE CURB.
 II. ARE THE 20-FT AISLE WIDTHS WIDE ENOUGH TO BACK OUT
 OF THE PARKING SPACES?
 E. SECTION D-D ??? CALLOUT THE 2-FT PARKING OVERHANG
 NEAR THE PROPERTY BOUNDARY
 F. SECTION E-E ???
 I. LABEL THE MINIMUM ELEVATION (16.15 FT NAVD) ON THE
 DRIVEWAY.
 II. SECTION IS AT THE EXISTING DRIVEWAY. SHOW DROP CURB
 AND SIDEWALK SLOPE INSTEAD OF EXISTING TYPE F CURB AND
 GUTTER.
  
 5. SHEET C-17 PMS PLAN
 A. ARE THE STOP BAR AND STOP SIGN NEEDED AT THE
 SOUTHEAST CORNER OF THE SITE IN FRONT OF THE BOLLARDS?
 B. 9??? PARKING SPACE WIDTH SHIFTED FOR THE EAST
 PARKING SPACES ALONG OKEESHOBEE BLVD.
 C. WHAT DO THE NUMBERS IN THE TRIANGLES REPRESENT?
  
 6. SHEET C-18 EROSION CONTROL PLAN
 A. ADD FLOATING TURBIDITY BARRIER FOR THE OUTFALL INTO
 THE CANAL NORTH OF THE ALLEY.
  
 7. SHEET L-2.0 LANDSCAPE PLAN
 A. SHOW ROOT BARRIER BETWEEN TREES AND PROPOSED
 EXFILTRATION TRENCHES.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 -PLEASE ENSURE SHEETS ARE TO SCALE WHEN PRINTED ON
 11X17 PAPER
 -SHOW ALL DRY UTILITIES WITHIN THE PROJECT SCOPE
 -CALL OUT ALL EXISTING AND PROPOSED VALVES AND
 APPURTENANCES FOR BOTH WATER AND SEWER
 -TAP CANNOT BE MADE OFF OF FIRE HYDRANT PER DETAIL P-8
 -BACKFLOW FOR METER TO BE PLACED OUTSIDE OF EASEMENT
 PER WS-1
 -RECORDS SHOW EXISTING METER ON OKEECHOBEE, PLEASE
 VERIFY AND DENOTE WHAT WILL HAPPEN TO IT (POTENTIAL USE
 FOR SERVICE INSTEAD OF HYDRANT TAP?)
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***