Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 04-26-2023 Cont ID  
Sent By lquinone Date 04-26-2023 Time 14:30 Rev Time 0.00
Received By lquinone Date 04-26-2023 Time 14:30 Sent To  
Notes
2023-04-26 14:31:23E23030045 TAKE 5 OIL CHANGE, 1122 PB LAKES BLVD. -
 INITIAL REVIEW 3.24.23
  
 COMMENTS FROM LINDA QUINONES, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER CONNECTIONS ARE REQUIRED.
 3. PLEASE PROVIDE STORMWATER CALCULATIONS.
 4. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE SHOW
 SLOPE % ON ALL SANITARY LINES AND CALL OUT MATERIAL.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 5. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 6. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 7. PLEASE CLEARLY SHOW ROAD RIGHT OF WAY.
 8. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 9. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -1122 PALM BEACH LAKES HAS A 1 INCH WATER METER PER
 UTILITY BILLING SYSTEM, BUT SHEET 6 TALKS ABOUT A 2
 INCH WATER METER. PLEASE UPDATE AND VERIFY 1 INCH METER
 SUFFICIENT.
  
 -THERE ARE SEVERAL REFERENCES TO A METER CAGE. WATER
 METERS ARE NOT ALLOWED TO BE CAGED. THE CAGE MIGHT BE
 AROUND THE BACKFLOW ASSEMBLY.
  
 -PLEASE ADD WPB STANDARD DETAILS WS1 AND WS6 IN CASE
 BACKFLOW ASSEMBLY NEEDS TO BE REPLACED.
  
 -METERED WATER SERVICE DOES NOT CURRENTLY HAVE AN
 ACTIVE USAGE BILLING ACCOUNT. ONE WOULD NEED TO BE
 SETUP BEFORE WATER COULD BE USED. BACKFLOW TESTING MUST
 BE COMPLETED SHORTLY AFTER WATER IS TURNED ON AND WILL
 BE A CONDITION OF WATER SERVICE.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 1. SHEET 2 SPECIFICATIONS AND NOTES
 A. SITEWORK NOTE #20 ??? THE CITY REQUIRES SUPERPAVE
 ASPHALT WITHIN THE RIGHT OF WAY.
 B. UPDATE FDOT STANDARD INDEX NUMBERS TO FDOT STANDARD
 PLAN NUMBERS.
 2. SHEET 3 SITE DEMOLITION AND SWPPP PREPARATION
 A. EROSION CONTROL NOTE #1 ??? SHEET SWP INSTEAD OF
 SHEET 8?
 3. SHEET 6 UTILITY PLAN
 A. LIST THE VERTICAL DATUM AND CONVERSION EQUATION TO
 NGVD1929.
 4. SHEET 7 SIGN, PARKING, EROSION CONTROL DETAILS
 A. STABILIZED CONSTRUCTION ENTRANCE IS TO BE WHOLLY
 WITHIN THE PROJECT SITE AND NOT PROJECT INTO THE R/W.
 B. UPDATE FDOT STANDARD INDEX NUMBERS TO FDOT STANDARD
 PLAN NUMBERS.
 C. PROVIDE AN ALTERNATIVE TO STRAW BALES FOR INLET
 PROTECTION.
 D. ADA PARKING STALL DETAIL ??? STRIPING LAYOUT TO
 MATCH CITY CODE SECTION 94-485 (PARALLEL 4??? STRIPES
 WITH 12-INCH SPACE BETWEEN THE STRIPES [16??? CENTER TO
 CENTER] AND 4-INCH STRIPE CONNECTING THE ENDS OF THE
 PARALLEL STRIPES).
 E. STANDARD PARKING SPACES ARE 18 FEET DEEP BY 8.5 FEET
 WIDE. SMALL PARKING SPACES ARE 16 FEET DEEP BY 8 FEET
 WIDE.
 F. WHAT IS THE 4??? YELLOW STRIPE FOR AS SHOWN ON THE
 ADA PARKING STALL DETAIL.
 G. STOP BAR DETAIL WITH SIGNAGE SHOULD ALSO MENTION
 BACK OF SIDEWALK OR EDGE OF TRAVEL WAY.
 5. SHEET SWP SWPPP & NPDES POLLUTION PREVENTION
 6. THIS AREA SURROUNDING THE SITE DRAINS TO THE CARVER
 CANAL TO THE WEST OF THE SITE. THE CARVER CANAL DRAINS
 TO THE C-17 CANAL (NOT THE C-51 CANAL).
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 -SHOW ALL DRY UTILITIES
 -PRINT SHEETS SO THEY ARE TO SCALE ON 11X17
 -EXISTING LATERALS/SERVICES NOT TO BE USED MUST BE CUT
 AND CAP AT MAIN
 -PROVIDE DATUM CONVERSION
 -PROVIDE WATER/SEWER DEMAND TABLE
 -PROPERLY LABEL ALL EXISTING UTILITY LINES WITHIN
 PROJECT SCOPE
 -AH AND LABEL ALL VALVES/APPURTENANCES FOR EXISTING
 UTILITIES IN A LEGIBLE MANNER
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***