Plan Review Details - Project E23020014
Plan Review Stops For Project E23020014
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 05-01-2023 Cont ID  
Sent By lquinone Date 05-01-2023 Time 14:25 Rev Time 0.00
Received By lquinone Date 05-01-2023 Time 13:23 Sent To  
Notes
2023-04-26 14:26:24 
  
 E23020014 ??? TRANSIT VILLAGE INIT. SUBMITTAL 2.10.2023
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 4. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE
 SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 5. PLEASE CUT AND CAP UTILITIES NOT IN USE AND REMOVE
 ANY ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM
 CITY RIGHT OF WAY. (SHEET C14 ??? CONFIRM PUBLIC
 UTILITIES APPROVED GROUTING/ABANDONING EXISTING 6 IN.
 FORCE MAIN).
 6. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 7. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?).
 8. SHEETS C-14 AND C-15: PLEASE OUTLINE AREAS OF WATER
 CONNECTION ON THE 30 SCALE PORTION OF PLAN SHEETS.
 9. BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 10. PLEASE CONFIRM PUB. UTILITIES CUSTOMER SERVICE WILL
 ALLOW METER IN SIDEWALK AS SHOWN ON SHEET C-14.
 11. SHEET C-14, PLEASE RELOCATE NOTE ???TO BE
 VACATED???, SOME TEXT IS OBSCURED.
 12. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE
 DESIGN ON ALL BACKFLOWS.
 13. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER.
 14. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 15. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY.
 16. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 17. PLEASE CLEARLY LABEL ROAD RIGHT OF WAY.
 18. IF SANITARY LINES ARE PROPOSED IN ROW PLEASE SHOW
 ADJACENT SANITARY LATERAL LOCATIONS AND SHOW ADDRESSES
 OF ADJACENT PARCELS.
 19. IF WATER LINES ARE BEING REPLACED IN ROW, SHOW
 ADJACENT PARCEL ADDRESSES.
 20. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 21. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -EXISTING BACKFLOW ASSEMBLY IS OUT OF COMPLIANCE FOR
 ANNUAL BACKFLOW TESTING. NEEDS TO HAVE PASSING TEST
 REPORT SUBMITTED TO [email protected] OR
 WATER SERVICE WILL BE LOCKED OFF.
 -SHEET C14. BACKFLOW ASSEMBLY IS LIKELY NOT LEAD-FREE
 COMPLIANT AND WOULD HAVE TO BE REPLACED WITH NEW LEAD
 FREE RP BACKFLOW ASSEMBLY.
 -SHEET C14. EITHER RELOCATE EXISTING METER BOX OUT OF
 SIDEWALK, OR HAVE IT REPLACED AND ENSURE THAT CONCRETE
 IS POURED 6 INCH THICK AROUND IT 18 INCHES OUT AND THAT
 IT IS NOT IN A SIDEWALK JOINT.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS.
 -SHEET C14 ENLARGED VIEW:
 CALLOUT SAYS 8 INCH, BUT PIPE IS LABELED 6 INCH;
 *IRRIGATION WATER SERVICE DESIGN IS NONSTANDARD TAPPED
 OFF DOMESTIC WATER SERVICE - WILL IT CREATE FLOW AND
 PRESSURE DEFICIENCIES FOR THE DOMESTIC WATER SERVICE?;
 *LABEL LIFT STATION BACKFLOW ASSEMBLY AS RP TYPE AND
 VERIFY IT WILL NOT FEED FROM FIRELINE WATER;
 *LABEL ANY PROPOSED UTILITY EASEMENTS AND ENSURE THAT
 BACKFLOW ASSEMBLIES ARE NOT INSIDE THEM.
 *ADD GRAPHIC SCALE AND SPOT ELEVATION.
 -SHEET C14:
 *LABEL 4 INCH FORCE MAIN WITH PIPE MATERIAL TYPE;
 CALLOUT HORIZONTAL CLEARANCE DISTANCE BETWEEN FORCE
 MAIN AND FIRELINE; AND CALLOUT CROSSINGS.
 *ADD FLOW CALCULATIONS FOR SIX INCH METERED WATER
 SERVICE AS DIRECTED IN NOTE 7 OF WATER SERVICE STANDARD
 DETAIL WS7.
 *ADD FLOW CALCULATIONS FOR 8 INCH FIRELINE WATER
 SERVICE AS DIRECTED IN NOTE 9 OF WATER SERVICE STANDARD
 DETAIL WS5.
 *DOES SHEET NOTE 3 APPLY?
 *ADD PROPERTY ADDRESS ACROSS THE STREET TO THE WEST.
 *IRRIGATION BACKFLOW ASSEMBLY CANNOT BE IN RIGHT OF
 WAY. MUST BE ON PRIVATE PROPERTY.
 *TWO OF THE FORCE MAIN CROSSING CALLOUTS MAY NEED SIZE
 CORRECTED.
 -SHEET C15 ENLARGED VIEW:
 *ADD GRAPHIC SCALE AND SPOT ELEVATION.
 *LABEL ANY PROPOSED UTILITY EASEMENTS AND ENSURE THAT
 BACKFLOW ASSEMBLIES ARE NOT INSIDE THEM.
 *ADD LEGEND OR CALLOUT THE DIFFERENT FRANCHISE UTILITY
 TYPES AND ENSURE THAT FIRE HYDRANT WILL NOT CONFLICT
 WITH THEM.
 *THERE ARE A BUNCH OF FRANCHISE UTILITIES NEAR THE
 METERED WATER SERVICES. PROVIDE PROFILE (LOOKING NORTH
 OR SOUTH) SHOWING ALL THE UTILITIES SO CAN ENSURE NO
 CONFLICTS.
 *IF EXISTING GATE VALVE OFF 12 INCH DIP IS CONNECTED TO
 36 INCH WATER MAIN, THEN SHOW THAT MORE CLEARLY.
 *CALL OUT AND LABELED ALL WATER PIPE AND COMPONENT
 FITTINGS BETWEEN WATER MAIN AND METERS.
 *SHOW UNDERGROUND GATE VALVE SYMBOL FOR FIRELINE.
 -SHEET C15:
 *ADD FLOW CALCULATIONS FOR 8 INCH FIRELINE WATER
 SERVICE AS DIRECTED IN NOTE 9 OF WATER SERVICE STANDARD
 DETAIL WS5.
 *ADD FLOW CALCULATIONS FOR SIX INCH METERED WATER
 SERVICE AS DIRECTED IN NOTE 7 OF WATER SERVICE STANDARD
 DETAIL WS7.
 *LABEL 4 INCH FORCE MAIN WITH PIPE MATERIAL TYPE.
 *DOMESTIC WATER SERVICE PIPING LOOKS LIKE IT IS RUNNING
 THROUGH EXFILTRATION TRENCH. IS THAT PROBLEMATIC?
 *CLEARWATER DRIVE LABEL LOOKS LIKE IT MAY BE OBSCURING
 FIRELINE WATER SERVICE PIPING.
 -SHEET C18: ADD MARKUP NOTE TO WS1 SAYING THAT DUAL
 CHECK IS NOT USED WHEN A BACKFLOW ASSEMBLY IS BEING
 INSTALLED.
 -ADD NOTE ON SHEETS C14 AND C15 TO REFER TO WPB WATER
 SERVICE STANDARD DETAILS FOR THE METERED WATER SERVICES
 AND BACKFLOW ASSEMBLIES.
 -ADD WATER SERVICE STANDARD DETAIL WS2 TO PLAN SET.
 -ON SHEET C25, SHOW EXISTING METERED WATER SERVICE AND
 ENSURE THAT FLASHING STOP SIGN IS DISTANCED FROM IT.
 -ADD MOST REVISED COPY OF LANDSCAPING PLAN IN
 RESUBMITTAL PACKAGE AND ENSURE NO LOCATION CONFLICTS
 BETWEEN TREES AND UTILITIES.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 1. REVISE THE BOUNDARY LINES (LOCATION, BEARINGS AND
 DISTANCES) ON THE AFFECTED SHEETS. PROJECT SURVEYOR
 WILL BE REVISING AT LEAST THE NORTH PROPERTY
 LINE(S)/SOUTH R/W LINE OF BANYAN BLVD.
  
 2. ADD VERTICAL DATUM REFERENCE ON EVERY SHEET WITH
 ELEVATION INFORMATION, INCLUDING THESE SHEETS: C-03,
 C-04, C-09, C-10, C-13, C-16, C-17, C-25 AND C-26.
  
 3. CONFIRM ALL EXISTING SPOT GRADES ON THE PLANS ARE IN
 REFERENCE TO NGVD1929. THE SPOT GRADE OF 16.08 NORTH OF
 THE CURB INLET ON BANYAN BLVD APPEARS SUSPECT.
  
 4. WET SEASON HIGH WATER TABLE ELEVATION CALLOUTS VARY
 THROUGHOUT THE PLANS. SEE COMMENT #1 UNDER DRAINAGE
 CALCULATIONS BELOW AS WELL.
 A. SHEET C-09: 11.00 FT NGVD AND 13.00 FT NGVD
 B. SHEET C-10: 13.00 FT NGVD AND 11.50 FT NAVD (ONLY
 USE ONE VERTICAL DATUM)
 C. DRAINAGE CALCULATIONS ??? 11.00 FT NGVD.
  
 5. PROVIDE SEPARATE SET OF PLANS FOR CLEARWATER DRIVE
 IMPROVEMENTS.
 A. PROVIDE PLAN AND PROFILE. ON THE PROFILE SHOW ALL
 EXISTING AND PROPOSED UTILITIES
 B. PROVIDE EXISTING TOPOGRAPHY OF THE R/W.
 C. INCLUDE DETAILS FOR PAVEMENT DESIGN, DRAINAGE AND
 SANITARY SEWER STRUCTURES, SIDEWALK, CURBING, ETC.
  
 6. SHEET C-03
 A. WHAT IS CONNECTED TO THE SOUTH END OF THE DRAINAGE
 PIPE LOCATED ON THE WEST SIDE OF THE EXISTING BUS
 SHELTER LOCATED APPROXIMATELY 160 FEET FROM THE SOUTH
 PROPERTY CORNER? CAN THE STORM PIPE BE
 REMOVED/ABANDONED?
 B. ADJUST THE LEADER ARROWS FOR THE REMOVAL OF THE
 EXISTING 2??? VALLEY GUTTER (ONE LEADER IS CURRENTLY
 POINTING TO CENTERLINE STRIPING NEAR THE CLEARWATER
 DRIVE LABEL [APPROX.. 120 FEET NORTH OF THE SOUTH
 PROPERTY CORNER AND 30 FEET WEST OF THE WEST PROPERTY
 LINE]; ONE LEADER IS POINTING TO 36??? WM [APPROX.. 255
 FEET NORTH OF THE SOUTH PROPERTY CORNER AND 20 FEET
 WEST OF WEST PROPERTY LINE]).
 C. IN THE NOTE ???EXIST. ASPHALT DRIVE AND CURBING TO
 BE REMOVED EAST OF PROPOSED CURB???, WHICH PROPOSED
 CURB DOES IT REFER TO. (THIS NOTE IS APPROX.. 520 FEET
 NORTH OF THE SOUTH PROPERTY CORNER AND 95 FEET WEST OF
 THE WEST PROPERTY LINE.
 D. THE EXISTING CONCRETE PLAZA WEST OF THE BUS ONLY
 PARKING SPACES IS CALLED OUT TO REMAIN BUT THE GRADES
 ON SHEET C-06 SHOW THE ADJACENT ASPHALT WILL BE LOWERED
 OVER 1.5 FEET (FOR EXAMPLE: 21.36 TO 19.75 FT NGVD;
 21.69 TO 19.90 FT NGVD).
 E. INDICATE IF ANY SIDEWALK ALONG CLEARWATER DRIVE WILL
 BE REMOVED.
  
 7. SHEET C-04
 A. CALL OUT THE REMOVAL/REPLACEMENT OF THE SANITARY
 SEWER MAIN IN CLEARWATER DRIVE.
 B. INDICATE IF ANY SIDEWALK ALONG CLEARWATER DRIVE WILL
 BE REMOVED.
  
 8. SHEET C-06
 A. PROVIDE PROPOSED SPOT GRADES AT THE BOTTOM OF THE
 FLUMES LOCATED TO THE SOUTHWEST OF STRUCTURE S-1.
 SUGGEST ALIGNING THE BOTTOM OF THE FLUMES AND HARDENING
 THE SPACE BETWEEN THE FLUME BOTTOMS TO LIMIT THE
 EROSION.
 B. IN THE STORM STRUCTURE TABLE:
 I. ADD THE NUMBER OF PRB???S TO EACH STRUCTURE.
 II. PROVIDE PROPOSED RIM ELEVATION FOR EXISTING
 DRAINAGE STRUCTURES
 III. VERIFY THE RIM/GRATE ELEVATIONS FOR ALL
 STRUCTURES.
 C. SHOW A SWALE LINE OR FLOW ARROWS ON EITHER SIDE OF
 S-1 TO INDICATE DEPRESSED AREA UP TO THE PEDESTRIAN
 CROSSOVER. WHAT IS THE EXISTING GRATE ELEVATION OF
 STRUCTURE S-1?
 D. INVERT ELEVATION OF 15.00 FT NGVD AT STRUCTURE S-3
 CREATES AN ADVERSE SLOPE ON THE PIPES FROM STRUCTURES
 S-1 AND S-2.
 E. PROVIDE EXISTING INVERT ELEVATIONS FOR THE STORM
 PIPES IN THE OPEN SPACE AREA AT THE SOUTH END OF THE
 SITE.
 F. RELOCATE EXFILTRATION TRENCHES AWAY FROM AREAS WITH
 TREES.
  
 9. SHEET C-07
 A. SECTION A-A ON SHEET C-12 SOWS THE HIGH POINT OF THE
 DRIVEWAY TO BE 8 FEET BEHIND THE SIDEWALK. THE
 RIM/GRATE ELEVATIONS FOR THE DRAINAGE STRUCTURES TO THE
 EAST OF THE ARE HIGHER THAN THE PAVEMENT ELEVATIONS OF
 18.60 AND 18.30 FT NGVD AT THE ???HIGH POINT??? OF THE
 DRIVEWAY.
 B. SECTION B-B ON SHEET C-12 SHOWS THE DRIVEWAY HIGH
 POINT AT 3.5 FEET EAST OF THE R/W. THE GRATE ELEVATION
 20.20 FT NGVD OF STRUCTURE S-23 IS HIGHER THAN THE SPOT
 GRADES OF 18.65 FT NGVD AT THE ???HIGH POINT??? OF THE
 DRIVEWAY.
 C. THE RIM ELEVATION FOR MH S-22 IS LOWER THAN THE
 GRATE ELEVATION OF THE NEARBY INLET S-23.
 D. IN THE STORM STRUCTURE TABLE:
 I. LIST THE NUMBER OF PRBS FOR EACH STRUCTURE. INCLUDE
 A PRB IN EITHER THE DOWNSTREAM SIDE OF STRUCTURE S-33,
 S-34, OR S-35 TO KEEP FLOATABLES FROM ENTERING THE
 CITY???S MS4.
 II. LABEL THE CONTROL STRUCTURES AND LIST THE CONTROL
 ELEVATION (SLOT ELEVATION) AND OVERFLOW ELEVATION (WEIR
 ELEVATION).
 III. VERIFY THE RIM/GRATE ELEVATIONS FOR ALL
 STRUCTURES.
 E. INVERT ELEVATION OF 13.00 FT NGVD AT STRUCTURE S-53
 CREATES AN ADVERSE PIPE SLOPE TO STRUCTURE S-54.
 F. INVERT ELEVATION OF 14.00 FT NGVD AT STRUCTURE S-33
 CREATES AN ADVERSE PIPE SLOPE TO STRUCTURE S-32
 G. INVERT ELEVATIONS OF 15.00 FT NGVD AT STRUCTURE S-26
 CREATES ADVERSE PIPE SLOPES TO EITHER OR BOTH PIPES TO
 STRUCTURES S-25 AND S-27.
 H. CAN THE INVERT ELEVATION OF 14.00 FT NGVD AT
 STRUCTURES S-45 AND S-45A BE LOWERED? SHEET C-15 SHOWS
 THE 6??? FM WILL HAVE A TOP OF PIPE ELEVATION OF 11.00
 FT NGVD.
 I. CONFIRM THERE IS OR WILL BE A SOUTH INVERT AT
 STRUCTURE S-43.
 J. THE SYMBOL FOR STRUCTURE S-47 IS HIDING A SPOT GRADE
 CALLOUT.
 K. SECTION E-E SHOULD POINT TO THE EAST.
 L. CALLOUT RCP PIPE WITHIN THE CLEARWATER DRIVE R/W.
 M. SHOW PAVEMENT RESTORATION ON BANYAN BLVD FOR THE
 PROPOSED UTILITY CONNECTIONS IN THE R/W.
 N. LABEL ALL EXISTING STORM PIPE SIZES AND MATERIAL ON
 CLEARWATER DRIVE AND BANYAN BLVD.
 O. RELOCATE EXFILTRATION TRENCHES AWAY FROM AREAS WITH
 TREES.
 P. JUSTIFY THE NUMBER OF OUTFALL PIPES AND THE OUTFALL
 PIPE DIAMETER(S) IF LARGER THAN 15 INCHES.
  
 10. SHEET C-09
 A. CONTROL STRUCTURE DETAIL
 I. REVISE THE STRUCTURE NUMBERS
 II. COORDINATE PIPE INVERTS AND PIPE SIZES WITH THE
 INFORMATION IN THE STORM STRUCTURE TABLE ON SHEET C-07
 III. REDUCE THE SLOT HEIGHT, RAISE THE WEIR ELEVATION
 OR REDRAW THE WEIR IN SECTION VIEW. THE CURRENT
 DIMENSIONS AND ELEVATIONS WOULD CREATE A WEIR CONDITION
 AT THE SLOT LOCATION INSTEAD OF S SLOT.
 B. PROVIDE DETAIL FOR THE CONTROL STRUCTURE FOR THE
 CLEARWATER DRIVE EXFILTRATION TRENCH.
 C. EXFILTRATION TRENCH DETAIL ???
 I. THE TRENCH HEIGHT WILL NOT BE COMPLETELY SURCHARGED
 WITH A SLOT ELEVATION OF 15.50 FEET NGVD AND TOP OF
 TRENCH ELEVATION OF 16.50 FT NGVD. CONSIDER RAISING THE
 SLOT ELEVATION TO MAXIMIZE THE ON-SITE STORAGE.
 II. IF SHWL ELEVATION IS 11.00 FT NGVD, THEN ADJUST
 LEADER ARROW TO POINT TO THE BOTTOM OF THE TRENCH
 INSTEAD OF THE PIPE ELEVATION.
 III. LIST PIPE MATERIAL AS EITHER HDPE OR RCP.
  
 IV. SHOW AND LABEL PRB???S IN BOTH STRUCTURES IN THE
 ELEVATION VIEW.
  
 D. PERVIOUS PAVERS SECTION
 I. SHOW ON THE PGD SHEETS OR SEPARATE DETAIL BLOWUPS
 WHERE THE UNDERDRAIN PIPES WILL BE LOCATED AND WHERE
 THEY WILL CONNECT TO THE DRAINAGE SYSTEM.
  
 11. SHEET C-10
 A. COORDINATE HIGH WATER TABLE ELEVATIONS AND VERTICAL
 DATUMS.
  
 12. SHEET C-12
 A. REVISE LOCATION OF BANYAN BLVD CENTERLINE AND R/W
 LINE LOCATIONS PER REVISED PROPERTY BOUNDARY.
 B. THE SECTIONS LIST COMPACTED SUBGRADE??? BUT THE
 PAVEMENT LEGEND HAS ???COMPACTED SUB-BASE???
  
 13. SHEET C-13
 A. SECTION G-G
 I. WHAT DO THE 1S AND 2S CALLOUTS REPRESENT?
 II. EXFILTRATION TRENCH SHOWN ON BOTH SIDES OF THE
 XERISCAPING ON THE SECTION BUT SHEET C-06 SHOWS NO
 EXFILTRATION PIPE AND SOLID PIPE ON THE WEST SIDE OF
 THE XERISCAPING.
 B. SECTION H-H
 I. EXFILTRATION TRENCH SHOWN ON THE SECTION BUT SHEET
 C-07 SHOWS SOLID PIPE.
 II. SHEET C-07 SHOWS PERVIOUS PAVERS ON THE RIGHT SIDE
 OF THE ITC PARCEL LINE. THE SECTION CALLOUTS
 NON-PERVIOUS BASE MATERIAL.
  
 14. SHEET C-14B
 A. NUMBER THE PROPOSED PRIVATE LIFT STATION.
 B. PROVIDE VERTICAL CLEARANCES (TOP/BOTTOM OF OUTSIDES
 OF PIPES) BETWEEN THE 4??? FM AND OTHER UTILITIES.
  
 15. SHEET C-15
 A. NUMBER THE PROPOSED PRIVATE LIFT STATION.
 B. PROVIDE VERTICAL CLEARANCES (TOP/BOTTOM OF OUTSIDES
 OF PIPES) BETWEEN THE WATER MAINS AND THE STORM PIPE
 CROSSINGS.
 C. TWO SSMH???S NUMBERED #1.
 D. CONFLICT CROSSING INFORMATION LISTS THE FM AS 6???
 ON SOME AND 4??? ON ONE.
 E. COORDINATE STORM PIPE SIZES/PIPE ELEVATIONS IN THE
 CONFLICT CROSSING INFORMATION WITH THE PIPE
 SIZES/INVERT ELEVATIONS ON THE PGD SHEETS. ELEVATIONS
 FOR THE OUTSIDE OF THE PIPES (TOP OR BOTTOM) SHOULD BE
 LISTED IN THE CONFLICT CROSSING INFORMATION.
 F. ADJUST HATCHING ON THE KEY MAP. CAN THE KEY MAP BE
 MOVED UP SO THAT THE TITLE APPEARS WITHIN THE SHEET
 BORDER?
  
 16. SHEET C-16
 A. COORDINATE STORM PIPE INFORMATION WITH THE
 INFORMATION PROVIDED ON SHEET C-07. RCP PIPE TO BE USED
 FOR STORM PIPES IN THE R/W.
  
 17. SHEET C-17
 A. COORDINATE PIPE SIZES AND ELEVATIONS WITH THE PGD
 AND W&S PLAN SHEETS.
 B. ADD THE MANHOLE NUMBERS.
 C. PROVIDE A SCALE BAR. THE SCALES APPEAR TO BE 1??? =
 40??? (H) AND 1??? = 4??? (V) WHEN PRINTED ON 24??? X
 36??? PAPER. SHEET CALLS OUT THE SCALE AS 1:30 (H) AND
 1:3 (V)
  
 18. SHEET C-25
 A. LABEL THE LIFT STATION NUMBER OR LIST AS NORTH OR
 SOUTH AND COORDINATE WITH THE W&S PLANS.
 B. PROVIDE THE VERTICAL DATUM.
 C. CONFIRM THE ELEVATIONS ARE IN REFERENCE TO NGVD.
 D. CONFIRM SIZE OF FM WITH WHAT IS SHOWN ON THE W&S
 PLANS.
 E. REVIEW ASSUMPTIONS FOR THE GROUNDWATER TABLE
 ELEVATION IN THE WETWELL FLOATATION CALCULATIONS (SEE
 COMMENT #1 BELOW FOR DRAINAGE CALCULATIONS).
  
 19. SHEET C-26
 A. LABEL THE LIFT STATION NUMBER OR LIST AS NORTH OR
 SOUTH AND COORDINATE WITH THE W&S PLANS.
 B. PROVIDE THE VERTICAL DATUM.
 C. CONFIRM THE ELEVATIONS ARE IN REFERENCE TO NGVD.
 D. CONFIRM SIZE OF FM WITH WHAT IS SHOWN ON THE W&S
 PLANS.
 E. COORDINATE THE ELEVATIONS WITH THE INFORMATION SHOWN
 ON THE W&S PLAN SHEETS.
 F. REVIEW ASSUMPTIONS FOR THE GROUNDWATER TABLE
 ELEVATION IN THE WETWELL FLOATATION CALCULATIONS (SEE
 COMMENT #1 BELOW FOR DRAINAGE CALCULATIONS).
  
 DRAINAGE CALCULATIONS
 1. HOW WAS THE WET SEASON WATER LEVEL ELEVATION OF
 11.00 FT NGVD DETERMINED? PREVIOUS PERMITS FOR THE SITE
 LIST THE WET SEASON WATER TABLE CONTROL ELEVATION AT
 14.50 FEET NGVD. THE CITY TRIES TO MAINTAIN THE WATER
 LEVEL IN CLEAR LAKE (LOCATED LESS THAN 1,000 FEET TO
 THE WEST OF THE SITE) AT 14.5 FT NGVD AND THE WATER
 LEVEL IN THE EAST LOBE OF CLEAR LAKE (LOCATED LESS THAN
 300 FEET TO THE NORTH OF THE SITE) AT THIS 14.5 FT NGVD
 STAGE OR HIGHER.
  
 2. REVISE THE EXFILTRATION TRENCH CALCULATIONS TO MATCH
 THE PROPOSED TRENCH DIMENSIONS IN THE PLANS. NOTE DU IS
 THE VERTICAL DISTANCE BETWEEN: (A) THE HIGHER OF THE
 TRENCH BOTTOM OR WET SEASON WATER LEVEL (BOTH ARE 11.00
 FT NGVD); AND (B) THE LOWER OF THE CONTROL ELEVATION
 (15.50 FEET NGVD) OR TOP OF TRENCH ELEVATION (16.50 FT
 NGVD).
  
 3. REVISE THE ICPR MODELING TO MATCH THE PROPOSED WEIR
 ELEVATION. CAN THE WEIR/SLOT ELEVATION BE RAISED? THERE
 IS PLENTY OF FREEBOARD BETWEEN THE LOWEST RIM/GRATE
 ELEVATION AND THE PEAK 25-YEAR 3-DAY STAGE.
  
 4. THE EXISTING CONDITIONS MODELING SHOULD BE AS THE
 SITE EXISTS TODAY INSTEAD OF AS IT EXISTED AS A TRAIN
 YARD AND RAIL SPUR.
  
 5. WHY TWO OUTFALL PIPES? IT WAS MENTIONED IN THE
 OPENING PARAGRAPH OF THE DRAINAGE NARRATIVE THAT THE
 SITE WAS PREVIOUSLY DESIGNED/PERMITTED WITH NO
 DISCHARGE TO OFFSITE AREAS FOR THE 25-YEAR 3-DAY EVENT.
 ONE OUTFALL PIPE SHOULD BE SUFFICIENT TO CONVEY RUNOFF
 FROM THE SITE FOR STORMS LARGER THAN THE 25-YEAR 3-DAY
 DESIGN EVENT.
  
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 PU COMMENTS SENT THRU SHARED DRIVE (MADE BY LL)
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***